This document refers the Basic testing of the Modbus communication of A1000 with
MODSCAN 32 software.
Required Modules:
• Drive – A1000 – CIMR-AD4A0005FMA
• PC with MODSCAN32 software
• RS232 to RS485 Converter
• USB to serial port RS232 converter
Test Setup :
• Word length can be 8, Parity is None ( H5-03) and stop bit can be 1.
• Once the above settings are done then click OK. Then MODSCAN(PC) is connected to
the drive. Still the error display on the screen then recheck the hardware cables and
settings.
• Select theMODBUS Point type is 03 : HOLDING REGISTER, These are the registers of
the Master for the control command and monitor data addressing.
Start command : Enter the value 01 in 40002 for the start command to the drive ( ex :shown in
below screen). Here 40001 is 8bit Upper register and 40002 is the lower register and hence 16bit
control word is both the addresses i.e 40001 and 40002. The Lower register 40002 is entered 01
i.e bit 0 =1.Then Drive will the start command and starts but with no frequency reference
Frequency Reference :
Enter 40003 as the Frequency reference value and check the drive parameter U4-19 for the value
gets appeared.
In the above screen shot we can see the Frequency Reference (250 = 2.5Hz) and DC bus voltage
( 580).
3 Fault Reset 0
Multifunction input
4 1 0
Multifunction input
5 2 0
Multifunction input
6 3 0
Multifunction input
7 4 0
Multifunction input
8 5 0
Multifunction input
9 6 0
Multifunction input
A 7 0
Multifunction input
B 8 0
C to F Reserved 0
Value =1 in Hex.
Status Word:
From the observations , the Modbus addresses are mentioned in the below sheet.
Drive
MODSCAN32 address(H) Description Monitor
40033 20 Drive Status
40034 21 Fault Status
Frequency
40065 23 Reference U1-01
Output
40066 24 Frequency U1-02
Output
voltage
40067 25 reference U1-06