Professional Documents
Culture Documents
casing impeller
Radially-split casing with center-line discharge can be left in the line while Balanced impeller designed with balancing
servicing the pump, eliminating needless disconnecting of pipes. Tapped chamber and pressure relief holes in the impeller
openings are provided for draining and gauge connections. Double volute reduce axial thrusts to a minimum, ensuring
design where radial loads demand. Center-line discharge allows self venting smooth performance and long life.
preventing possible pump failures due to vapor lock.
motor
The motor is equipped with heavy duty, grease-
lubricated ball bearings adequately rated to
accommodate impeller radial loads and residual
hydraulic thrusts.
Design Features
• Easy maintenance due to back pull-out design • Confined casing gasket
• Extensive interchangeability of parts • Drilled and tapped gauge connections are standard on suction
• Manufactured and inspected to rigid standards and discharge ports
• Quiet operation • Mount with motor feet, or motor and pump feet for convenience
• Self venting center-line discharge
Motor Mounted Centrifugal Pumps
Materials of Construction
capscrew (impeller)
flange rating (psig)
washer (impeller)
adapter bracket
gasket (casing)
seal elastomer
seal hardware
water slinger
construction
motor frame
motor shaft
shaft sleeve
seal washer
seal spring
seal seat
impeller
casing
pump
(20.00) 300
pressure psig (bar)
(17.24) 250
b
(13.79) 200 A Cast iron - ansi 125 flanges
B Ductile iron - ansi 250 flanges
(10.34) 150
(6.90) 100
a notes:
(3.45) 50 • Hydrostatic test pressure at ambient temperature is 150% maximum
working pressure
(0) 0 • All values are based on clear, clean water. Values may change with
0 50 100 150 200 250
other liquids
(-18) (10) (38) (66) (93) (121)
temperature °f(°c)
Typical Specifications
Pumps - Horizontal - Motor Mounted The casing shall be equipped with a drilled and tapped drain
connection. Suction and discharge connections shall be
1.0 Provide Armstrong single stage, single end suction, motor
provided with drilled and tapped pressure gauge connections.
mounted centrifugal pumps, with rising head characteristics to
pump shut off. 3.2 Pump impeller shall be fully enclosed type. Dynamically
balanced.
Refer to the schedule for pump flows and heads and motor
speed, efficiency, enclosure and power requirements. 3.3 Provide a shaft sleeve, extending the full length of the
mechanical seal area.
2.0 The pumps shall be Armstrong Series 4280 motor mounted
horizontal end suction pump. 3.4 Mechanical Seal shall be single spring inside type with resin
bonded carbon* face rotating against a silicone carbide seat.
3.0 Pump Construction:
epdm elastomer with stainless steel spring and hardware shall
3.1 Pump casing shall be cast iron, suitable for 175 psig working be provided.
pressure at 140°f. (Ductile iron for pressures to 250 psig). The
4.0 Motor power requirements shown on the pump schedule are
casing shall be hydrostatically tested to 150% maximum working
the minimum acceptable and have been sized for continuous
pressure.
operation without exceeding the full load nameplate rating over
The casing shall be radially split to allow removal of the rotating the entire pump curve, exclusive of service factor.
element without disturbing the pipe connections.
* For liquids above 200°f / 93°c use: antimony loaded carbon.
For glycols above 30% by weight: use silicon carbide.
Armstrong dualARM
Armstrong sg Suction Vertical In-Line Pump
Guide with Strainer
Base mounted pump with Suction Guide and Vertical In-Line with Suction Guide and Flo- dualARM Vertical In-Line incorporates two
Flo-Trex valve eliminates cost and space of: Trex valve eliminates cost and space of all pumps in a casing with single inlet and outlet
the items listed under base mounted pump, connections. Enables standby or parallel
Suction: • Y-strainer
plus the following: operation with only one set of piping. Casing
• Long radius elbow
design and port valves allow one pump to be
• Min. straight pipe run. • Inertia base with spring mounts
removed for service with the second pump
• Long radius elbow
Discharge: • Check valve still operating. When installed with a Suction
• Flexible pipe connectors
• Isolating valve Guide and Flo-Trex valve the dualARM
• Grouting
• Throttling valve represents the greatest Life Cycle Value in
• Field alignment
today’s commercial hvac market.
• Split couplings available for ease of
mechanical seal replacement