AIR COOLER
T030127-37-551-2022
FEUILLE DE DONNEES PROCEDE
PROCESS DATA SHEET N° A RAPPELER / Ref. Number
REPERE / ITEM
210 - HC - 303 A/B/C/D/E 0 3/3
REV PAGE
It shall not be divulged or reproduced without
REFERENCE CLIENT :
CLIENT : BHP Billiton Petroleum-SONATRACH-AGIP ROD - D - 028
CLIENT REFERENCE :
This document is the property of BOUYGUES OFFSHORE.
LIEU : UNITE :
Berkine Basin, Algeria Central Processing Facilities (CPF)
LOCATION : PLANT :
rev
authorization.
23 PERTE DE CHARGE / PRESSURE DROP bar ALLOUEE / ALLOWED : 0.70 (2) CALCULEE / CALCULATED :
24 FACTEUR D'ENCRASSEMENT / FOULING FACTOR m².°C/W In. 0.00035 out. 0.00035
F
38 PALES VARIABLES OUI/YES VITESSE VARIABLE AUTO / AUTO VARIABLE SPEED OUI / YES NON / NO X
39 VARIABLE BLADES NON / NO X DEUX VITESSES / TWO SPEEDS OUI / YES NON / NO X
40 AUTO MANUEL / MANUAL MARCHE - ARRET / START - STOP OUI / YES X NON / NO
41 VOLETS / LOUVERS INCLIN. VARIABLE / VARIABLE PITCH OUI / YES NON / NO X AUTO MANUEL / MANUAL
autorisation.
42 REMARQUES / REMARKS
43 0 (1) The SUMMER YEAR 1 case is the design case. Design for 110 % of given duty and flows. (Heat and Material Balance T030127-31-401-2001).
44 (2) Allowable pressure drop applies to 110 % flow rates.
45 (3) Based on Material Selection Report ( T030127-92-455-2001).
46 0 (4) See details on Thermal Specification for Product Oil Cooler 210 HC 303 (T030127-39-552-2003).
47 (5) Nozzle size at inlet/outlet of each bay.
48 (6) The supplier shall consider the effects of solar radiation in the rating of air cooler, and ensure that solar radiation cannot cause over pressure of air cooler tubes.
49
50
51
52
A 5/2/2002 First issue for comments DK SL JPCH 0 9/4/2002 Issue for Construction KAMECHE LECLER JPCH