You are on page 1of 7

CAMPUS FIRE SAFETY E-NEWZONE

Code Corner
SECTION 907
FIRE ALARM AND DETECTION SYSTEMS PART 2

907.2.1.1 System initia- The location from which structures is challenging


tion in Group A occupan- the live voice announce- because of the building
cies with an occupant ment originates must be area and the number and
load of 1,000 or more. constantly attended and diversity of occupants.
ABOUT CODE CORNER
Activation of the fire alarm approved by the fire code Provisions were added in
CCFS would like to in Group A occupancies official (see also com- the code to require cap-
remind you to check with an occupant load of mentary, Section tioned messages in these
with your local 1,000 or more shall initiate 907.5.2.2). In terms of buildings and grandstands
“Authority Having a signal using an emergen- the applicability of this when public address (PA)
Jurisdiction (AHJ)” cy voice/alarm communi- section, it is not as spe- systems are prescribed by
for questions and cations system in accord- cific as Section 907.2.1. the accessibility require-
opinions concerning ance with Section More specifically, the ments.
your local Fire and 907.5.2.2. concept of fire areas
does not apply. Credit is IBC Section 1108.2.7.3
Building Codes.
Exception: Where ap- not given to reduce the sets forth requirements
The information proved, the prerecorded occupant load through for audible PA systems in
contained in this ar- announcement is allowed the use of the fire area stadiums, arenas and
ticle is supplied as a to be manually deactivat- concept (see commen- grandstands. It requires
courtesy by the Inter- ed for a period of time, tary, Section 907.2). that equivalent text in-
national Code Council not to exceed 3 minutes, formation be provided to
(ICC) and is based on for the sole purpose of 907.2.1.2 Emergency the audience and that
the International Fire allowing a live voice an- voice/alarm communica- the delivery time for
and Building Codes nouncement from an ap- tion system captions. Sta- these messages be the
and their respective proved, constantly at- diums, arenas and grand- same as those broadcast
commentaries. tended location. stands required to caption from the PA system.
audible public announce- These requirements ap-
Your local codes or In order to afford au- ments shall be in accord- ply to pre-recorded and
ordinances may vary. thorized personnel the ance with Section real-time messages. Sec-
ability to selectively 907.5.2.2.4. tion 1108.2.7.3 of the
evacuate or manage oc- 2012 edition of the IBC
cupant relocation in also requires captioning
large assembly venues, Court case prompted a of messages in stadiums,
this section requires the change to the code and arenas and grandstands
fire alarm system to op- the IBC. The court ruled that have more than
erate through an emer- that persons with hearing 15,000 fixed seats.
gency voice/alarm com- impairments who attend
munications system. The events at stadiums, Because messages being
exception allows the au- grandstands and arenas broadcast can include
tomatic alarm signals to require a means of equiv- instructions to building
be overridden for live alent communications in or site occupants explain-
voice instructions if the lieu of the public address ing the actions they need
PAGE 28 live voice instructions do system. Providing occu- to take in the event of an
not exceed 3 minutes. pant notification in these emergency, the require-
CAMPUS FIRE SAFETY E-NEWZONE

Code Corner
ments of NFPA 72 are code change requires a rate at which the hazard
applicable for captioning one-way MNS where in- can develop;
systems. Such a system structions are broadcast
falls within the scope of by personnel authorized • The anticipated threats,
Chapter 24 of NFPA 72, to distribute messages. including natural, techno-
of “Emergency Commu- This could include fire- logical and intentional
nication Systems.” NFPA fighters during a fire events;
72 defines an emergency event; the system could • The reliability and per-
communications system be used by law enforce- formance of the MNS;
(ECS) as a system de- ment officers during a
signed for life safety domestic terrorism inci- • Security of the MNS and
that indicates the exist- dent or a weather event its components;
About the 2012 Edition
… The Center will be
ence of an emergency like a tornado warning.
and communicates the • How the building or
publishing sections of the The design of the com-
appropriate response staff implement the risk
2012 IFC for your review
and action. The ECS is pliant MNS in Chapter 24 analysis, including the use
and comparison. Please
required to be classified of NFPA 72 is not pre- of the MNS; and
note that CCFS is not
as either a one- or two- scriptive—a MNS is a per-
suggesting you adopt this • How emergency ser-
way path system. It can formance- based design.
new regulation. Any vices, such as the fire ser-
be within a building or Accordingly, fire code
regulations used in your vice and law enforcement
over a wide area or can officials should require
state/organization should agencies, can employ the
be targeted to a particu- their design to be sealed
be in accordance with the MNS.
lar group of recipients. by a registered profes-
recommendations set
The messages that will sional engineer. Section In a stadium or arena, the
forth by your
be broadcast are based 24.7 of the standard re- captioning system is re-
local Building
on an emergency re- quires the preparation
Regulations quired to be a component
sponse plan developed of a risk analysis based of the emergency voice/
Organization and State
Fire Marshal’s Office. during a risk analysis by on the nature and antici- communication alarm sys-
the project stakeholders pated risks of the facili- tem (EV/ACS). Such a sys-
and is approved by the ty. The risk analysis is
tem is required by Section
fire code official. part of the design brief, 907.2.1.1 in Group A occu-
which will serve as the pancies with an occupant
The NFPA 72 ECS re- basis of the system de- load of 1,000 or more.
quirements are based on sign and is a required
in-building or wide-area design document. NFPA The requirement in Sec-
The excerpts from The occupant notification. 72 requires the following tion 907.5.2.2.4 specifies
2009 and 2012 Interna- Wide-area systems could elements included in the the captioning system
tional Fire Code are re- include the entire area risk analysis: would be connected to
printed with the permis- of a jurisdiction. For a the EV/ ACS. The fire
sion of the International stadium, arena or grand- • The number of persons alarm control unit will
Code Council. stand captioning, NFPA within the building, ar- require a listed interface
72 defines these as mass ea, space, campus or
unit capable of displaying
All rights reserved. notification systems region; text messages. Textual
(MNS). In the context of • The character of the visible appliances are al-
PAGE 29 the NFPA 72 require- lowed by NFPA 72 when
occupancy, such as
ments, this particular unique hazards and the used in conjunction with
CAMPUS FIRE SAFETY E-NEWZONE

Code Corner
audible, visual or both height and distance from story buildings, or where
types of notification ap- the persons viewing it. a substantial number of
pliances. In the public occupants are above or
mode, textual visible 907.2.2 Group B. A manu- below the level of exit
appliances are located to al fire alarm system shall discharge, increase the
ensure readability by the be installed in Group B oc- difficulty of alerting the
building occupants. Such cupancies where one of the occupants of a fire. This
a system can display mes- following conditions exists: is especially true in non-
sages using televisions or 1. The combined Group B sprinklered buildings
light-emitting diode occupant load of all floors with given occupant load
(LED) marquee signs. is 500 or more. thresholds. Group B occu-
pancies include a specific
The design concept of 2. The Group B occupant use called ambulatory
MNS is relatively new in load is more than 100 per- care facilities which pre-
the design community. sons above or below the sent a higher level of life
Captioning systems might lowest level of exit dis- hazard than the typical
utilize components that charge. Group B occupancy. The
are not listed for fire fact that the care recipi-
alarm service so the de- 3. The fire area contains ents of such facilities
sign will be required to an ambulatory care facili- may be rendered incapa-
comply with Section ty. ble of self-preservation
24.2.2.21 of NFPA 72 for for limited periods of
textual visible notifica- Exception: Manual fire
alarm boxes are not re- time makes the need for
tion appliances. Emer- a fire alarm system criti-
gency textual messages quired where the building
cal. Section 907.2.2 re-
take precedence over any is equipped throughout
with an automatic sprin- quires a manual alarm
nonemergency text mes- system any time a fire
sages. Under NFPA 72, kler system installed in
accordance with Section area contains a ambula-
these devices require a tory care facility. See the
primary and secondary 903.3.1.1 and the occu-
pant notification appli- commentary to Section
power supply. If the de- 202, definition of
vices are not monitored ances will activate
throughout the notifica- “Ambulatory care facili-
for integrity or loss of ty” and Section
communications by an tion zones upon sprinkler
water flow. 907.2.2.1.
autonomous control or a
fire alarm control unit, Group B occupancies The exception does not
the appliance must clear- eliminate the fire alarm
generally involve individ-
ly display its status. The uals or groups of people system, but rather per-
size of characters dis- in separate office areas. mits it to be initiated
played must comply with As a result, the occu- automatically by the
the requirements in NFPA sprinkler waterflow
pants are not necessarily
72. The NFPA 72 size, aware of what is going on switch(es) instead of by
character and font re- in other parts of the the manual fire alarm
quirements are based on building. Group B build- boxes.
PAGE 30 the location of the dis- ings with large occupant
play in relation to the 907.2.2.1 Ambulatory
loads, even in single- care facilities. Fire areas
CAMPUS FIRE SAFETY E-NEWZONE

Code Corner
containing ambulatory The IBC identifies health building would not re-
care facilities shall be pro- care Group I occupancies quire smoke detection in
vided with an electronical- as including a 24-hour the individual tenant
ly supervised automatic stay. Without a 24-hour spaces but instead in the
smoke detection system stay, these surgery cen- public areas, such as lob-
installed within the ambu- ters were classified as by or lounge areas.
latory care facility and in Group B, which allowed
public use areas outside of the care providers to The exception does not
tenant spaces, including render an unlimited eliminate the fire alarm
public corridors and eleva- number of people inca- system, but rather per-
tor lobbies. pable of self- mits it to be initiated
preservation with no automatically by the
Exception: Buildings more protection than a sprinkler water flow
equipped throughout business office. Since switch(es) instead of by
with an automatic sprin- these types of facilities manual fire alarm boxes.
kler system in accord- contain distinctly differ-
ance with Section 907.2.3 Group E. A manu-
ent hazards to life safe- al fire alarm system that
903.3.1.1 provided the ty than other Group B
occupant notification initiates the occupant no-
occupancies, they are tification signal utilizing
appliances will activate now required to have a
throughout the notifica- an emergency voice/
higher level of life safe- alarm communication sys-
tion zones upon sprinkler ty and fire protection as
water flow. tem meeting the require-
evidenced by the re- ments of Section 907.5.2.2
Years ago, few surgical quirements of this sec- and installed in accord-
procedures were per- tion, as well as Section ance with Section 907.6
formed outside of a hos- 903.2.2 and the con- shall be installed in Group
pital. Today, complex struction provisions of E occupancies. When auto-
outpatient surgeries con- the code. matic sprinkler systems or
ducted outside of a hos- This section more specif- smoke detectors are in-
pital are commonplace. ically states that any stalled, such systems or
They are performed in time a fire area contains detectors shall be con-
facilities often called an ambulatory care fa- nected to the building fire
“day surgery centers” or cility, the fire area alarm system.
“ambulatory surgical should be provided with
centers” because pa- Exceptions:
a supervised smoke de-
tients are able to walk in tection system in the 1. A manual fire alarm
and walk out the same ambulatory care facility system is not required in
day. Procedures render and in public use areas Group E occupancies
care recipients tempo- outside of tenant spaces. with an occupant load of
rarily incapable of self- Therefore, in a medical 30 or less.
preservation by applica- office building, for ex-
tion of nerve blocks, se- ample, the ambulatory 2. Manual fire alarm box-
dation or anesthesia; care facility contained es are not required in
PAGE 31 however, they do typi- within would have a full Group E occupancies
cally recover quickly. coverage system. The where all of the follow-
other offices in the ing apply:
CAMPUS FIRE SAFETY E-NEWZONE

Code Corner
2.1. Interior corridors down condition, the code cation appliances and did
are protected by smoke requires a means of com- not require the added
detectors. munication between the capabilities that an EV/
established central loca- ACS provides.
2.2. Auditoriums, cafe- tion and each secured
terias, gymnasiums and area. Section 404.3.3.1 Section 907.2.3 sets
similar areas are pro- does not prescribe the forth the requirements
tected by heat detec- means of communication, for automatic fire alarm
tors or other approved which could include the and detection system
detection devices. use of text messages to requirements in Group E
cell phones/mobile devic- occupancies. Section
2.3. Shops and laborato- 907.2.3 prescribes the
ries involving dusts or es, e-mail messages or
the use of pre- installation of an EV/ACS
vapors are protected by as opposed to a tradition-
heat detectors or other established audio or visu-
al signals. The provisions al horn/strobe occupant
approved detection de- notification system.
vices. in Section 404.3.3 are not
specific to Group E occu- Exception 1 exempts
3. Manual fire alarm box- pancies—they are appli- Group E occupancies from
es shall not be required cable to all occupancies requiring a fire alarm
in Group E occupancies that develop and imple- system when the occu-
where the building is ment lockdown plans. pant load is less than 30.
equipped throughout with This would exempt small
an approved automatic Because of concerns of
school campus safety day care centers that
sprinkler system installed serve children older than
in accordance with Sec- serving kindergarten
through 12th grade stu- 21 /2 years of age or a
tion 903.3.1.1, the emer- small Sunday school
gency voice/alarm com- dents, specific require-
ments were put into the classroom at a place of
munication system will religious worship.
activate on sprinkler wa- 2012 edition of the IBC
ter flow and manual acti- and the code for en- Exception 2 exempts
vation is provided from a hanced communication manual fire alarm boxes
normally occupied loca- between the school ad- in interior corridors, la-
tion. ministrators, teachers boratories, auditoriums,
and students when a cafeterias, gymnasiums
Section 404.3.3 ad- lockdown plan is activat- and similar spaces based
dresses the development ed in Group E occupan- on the installation of
and implementation of cies. As a result, emer- heat/smoke detectors.
lockdown plans. These gency voice/alarm com- This is not an exception
requirements were devel- munication systems (EV/ from the EV/ACS but
oped to ensure that the ACS) are prescribed in simply an exemption of
level of life safety inside Group E occupancies. locations requiring manu-
of the building is not re- Previously the code al fire alarm boxes. The
duced or compromised would have permitted applicability of Exception
during a lockdown. In the manual fire alarm 2 is independent of
PAGE 32 order for a building to system to use audible whether an automatic
safely function in a lock- and visible alarm notifi- sprinkler system is in-
CAMPUS FIRE SAFETY E-NEWZONE

Code Corner
stalled. If an automatic tion 903.3.1.1 and the activates the occupant
smoke detection system occupant notification notification system in ac-
is installed, it must be appliances will activate cordance with Section
connected to the build- throughout the notifica- 907.5 shall be installed in
ing fire alarm system. tion zones upon sprinkler Group H-5 occupancies
water flow. and in occupancies used
Exception 3 allows the for the manufacture of
omission of the manual This section is intend- organic coatings. An auto-
fire alarm boxes in ed to apply to large mul- matic smoke detection
Group E occupancies tistory manufacturing system shall be installed
equipped throughout facilities. For this rea- for highly toxic gases, or-
with an automatic sprin- son, a manual fire alarm ganic peroxides and oxi-
kler system if the actua- system would be re- dizers in accordance with
tion of the sprinkler sys- quired only if the build- Chapters 60, 62 and 63,
tem will activate the ing were at least two respectively.
EV/ ACS. See Section stories in height and had
903.2.3 for sprinkler re- 500 or more occupants Because of the nature
quirements in Group E above or below the level and potential quantity of
buildings. of exit discharge. An hazardous materials in
unlimited area, two- Group H-5 occupancies, a
907.2.4 Group F. A manu- manual means of acti-
story Group F occupancy
al fire alarm system that vating an occupant noti-
complying with Section
activates the occupant fication system is essen-
507.3 of the IBC would
notification system in ac- tial for the safety of the
be indicative of an occu-
cordance with Section occupants. In accordance
pancy requiring a manual
907.5 shall be installed in with Section 2703.11,
fire alarm system.
Group F occupancies the activation of the
where both of the follow- Buildings in compliance alarm system must initi-
ing conditions exist: with Section 507.3 of the ate a local alarm and
IBC, and large manufac- transmit a signal to the
1. The Group F occupan-
turing facilities in gen- emergency control sta-
cy is two or more stories
eral, however, must be tion. The manual fire
in height; and
fully sprinklered and alarm system require-
2. The Group F occupan- would thus be eligible ment for the building is
cy has a combined occu- for the exception. The in addition to the emer-
pant load of 500 or more exception does not elim- gency alarm require-
above or below the low- inate the fire alarm sys- ments in Section 2703.12
est level of exit dis- tem but rather permits (see Section 908.2).
charge. it to be initiated auto-
matically by the sprin- Occupancies involved in
Exception: Manual fire kler system waterflow the manufacture of or-
alarm boxes are not re- switch(es) instead of by ganic coatings present
quired where the build- the manual fire alarm special hazardous condi-
ing is equipped through- boxes. tions because of the un-
PAGE 33 out with an automatic stable character of the
sprinkler system installed 907.2.5 Group H. A manu- materials, such as nitro-
in accordance with Sec- al fire alarm system that cellulose. Good house-
CAMPUS FIRE SAFETY E-NEWZONE

Code Corner
keeping and control of 1. Manual fire alarm section to require a
ignition sources is criti- boxes in sleeping units smoke detection system
cal. Chapter 29 contains of Group I-1 and I-2 oc- throughout all Group I
additional requirements cupancies shall not be occupancies. Smoke de-
for organic coating manu- required at exits if lo- tectors are only generally
facturing processes. cated at all care provid- required in the corridors
ers’ control stations or and in waiting rooms that
This section also requires other constantly attend- are open to corridors,
an automatic smoke de- ed staff locations, pro- unless noted otherwise.
tection system in certain vided such stations are IFC Committee Interpre-
occupancy conditions in- visible and continuously tation No. 36-03 makes it
volving either highly tox- accessible and that clear that the Group I
ic gases or organic perox- travel distances re- provisions only require a
ides and oxidizers. The quired in Section manual fire alarm system
need for the automatic 907.4.2.1 are not ex- with smoke detectors in
smoke detection system ceeded. selected areas.
may depend on the class
of materials and addi- 2. Occupant notification To reduce the potential
tional levels of fire pro- systems are not re- for unwanted alarms,
tection provided. This quired to be activated manual fire alarm boxes
requirement also assumes where private mode may be located at the
the quantity of materials signaling installed in care providers’ control
is in excess of the maxi- accordance with NFPA stations or another con-
mum allowable quanti- 72 is approved by the stantly attended loca-
ties shown in Tables fire code official. tion.
5003.1.1(1) and 5003.1.1
(2). Because the protection Exception 1 reduces the
and possible evacuation likelihood of accidental
of the occupants in Group or malicious false alarm
907.2.6 Group I. A manual I occupancies are most system activations by
fire alarm system that acti- often dependent on the manual means by allow-
vates the occupant notifi- response by care provid- ing the pull stations to
cation system in accord- ers, occupancies in Group be located in a more con-
ance with Section 907.5 I must be protected with trolled area. It assumes
shall be installed in Group I a manual fire alarm sys- the approved location is
occupancies. An automatic tem and in certain in- always accessible by care
smoke detection system stances, as described in providers and within 200
Next Month ...
that activates the occupant Sections 907.2.6.1, feet (60 960 mm) of trav-
907.2.6.1 Group I-1.
notification system in ac- 907.2.6.2 and 907.2.6.3, el distance. Exception 2
An automatic smoke
cordance with Section an automatic smoke de- allows the common prac-
detection system shall
907.5 shall be provided in tection system. In Group tice in Group I occupan-
be
accordance with Sections I-1, smoke alarms are cies of only notifying the
907.2.6.1, 907.2.6.2 and also required in accord- care providers instead of
907.2.6.3.3. ance with Section all building occupants in
PAGE 34 907.6.1.1. the event of a fire, sub-
Exceptions: ject to the approval of
It is not the intent of this the fire code official.

You might also like