RTS/MS/E/04 1 of 9 0
Method Statement
FOR
RTS/MS/E/04 2 of 9 0
1.0 Introduction
1.1 Purpose.
1.2 Scope
1.3 References
1.4 Definitions
1.5 Responsibilities
2.0 Requirements
2.1 Material Requirements
2.2 Tools / Equipment Requirements
2.3 Manpower Requirements
3.0 Safety
3.1 Safety Procedures
4.0 Procedures
1.0 INTRODUCTION
1.1 PURPOSE:
METHOD STATEMENT FOR
INSTALLATION OF AUDIO VISUAL AND IPTV
SYSTEM
Document No. Page Rev No.
RTS/MS/E/04 3 of 9 0
This test is to verify for compliance with the Wiring Regulation the insulation of conductor is satisfactory and that
electrical conductors or proactive conductors are not short-circuited, or show a low insulation resistance (which would
indicate defective insulation).
1.2 SCOPE:
This Method Statement refers to various work procedures which explains and covers the cable and wire insulation
testing.
1.3 REFERENCES:
Contract Specifications: Section 260519
Approved Shop Drawings:
Material Submittals: TBZ/15MAY05/BTCC/DQ/SUB/EL/006 AND TBZ/15MAY05/BTCC/DQ/SUB/EL/006-ALT
Codes & Standards: NEC, QCS 2010 (Section 21 Part 23.2.4…9)
1.4 DEFINITIONS:
RTS/MS/E/04 4 of 9 0
1.5 RESPONSIBILITIES:
2.0 REQUIREMENTS:
RTS/MS/E/04 5 of 9 0
The following list describes the Tools and/or equipment required to be abundantly available on site as applicable and
required for the pertinent works to be carried out:
Cutting Machine.
Grinder.
3. SAFETY:
Hand gloves, safety shoes, helmets, and all PPE shall be worn during the testing.
Work area should be checked and cleared from any safety hazard prior to starting the test.
Work area should be maintained clean and neat throughout all activities duration.
Any sign of hazard that would come up during activities shall be evaluated according to the attached
risk assessment.
4. PROCEDURES:
METHOD STATEMENT FOR
INSTALLATION OF AUDIO VISUAL AND IPTV
SYSTEM
Document No. Page Rev No.
RTS/MS/E/04 6 of 9 0
THIS TEST IS CARRIED OUT TO MEASURE THE INSULATION RESISTANCE OF THE CABLE UNDER TEST. INSUALTION
RESISTANCE MEASURED BETWEEN 1.) CONDUCTOR TO CONDUCTOR 2. CONDUCTOR TO EARTH.
A 500 V Insulation Tester shall be used for this test and kept at one end of the cable under test.
The first conductor for which cross insulation is being measured shall be connected to line terminal
of the instrument.
Now Press/Rotate the handle of the instrument or press push button. The reading of meter will
show the cross insulation between conductor 1 and rest of the conductors. Insulation reading shall
be recorded after applying the test voltage for about a minute till a steady reading is obtained.
Now connect next conductor to Line terminal of the instrument and connect the remaining
conductors to earth terminal of the instrument and take measurement as per procedure 11 and
111.
NOTE: 1.) Insulation resistance test shall be carried out before a completed installation is permanently
connected to the supply. Large installation may be divided into groups. A DC voltage not less than twice the
normal supply voltage (RMS value of AC system voltage) shall be applied for the measurement of the
insulation resistance. For low voltage installations, where apparatus voltage rating does not exceed 55 V, shall
be tested applying 500 V DC only.
2.) When measured with all fuse links in place, all switches (including, if possible, the main switch)
closed, the insulation resistance for whole installation resistance for whole installation shall not be less than 1
mega ohm.
3.) When measured between one phase conductor and other conductor and other conductors connected
together to earth, in turn for all phases, the insulation resistance shall be not less than 1 mega ohm.
4.) Wherever possible, so that all parts of the wiring may be tested, all lamps shall be removed, all
current using apparatus disconnected, all local switches shall be closed; where removal of lamps or
disconnection of current using apparatus is not practicable, respective control switches shall be opened.
5.) Where apparatus is disconnected for the tests, the insulation between the enclosure or frameworks
and all the live parts (phase) of the apparatus shall be measured separately and shall comply with the
METHOD STATEMENT FOR
INSTALLATION OF AUDIO VISUAL AND IPTV
SYSTEM
Document No. Page Rev No.
RTS/MS/E/04 7 of 9 0
requirements as per BS for the corresponding apparatus, where such standard is not available, the insulation
resistance shall not be less than 0.5 mega ohm.
RTS/MS/E/04 8 of 9 0
All related documents are signed-off and approved as per the instructions, quality assurance and HSE
RTS/MS/E/04 9 of 9 0
CONDUCTED BY: ____________________________________
WITNESS BY: _____________________________________
APPROVED BY: _____________________________________