ISO performance based on natural gas with

water injection to 25 ppmvd NOx.


GE Energy
LM 6000-PC Sprint
Power Output (kWe) 43,016 49,506
Heat Rate LHV (KJ/kWe-Hr) 9,018 8,948
Exhaust Flow (kg/sec) 135 135
Exhaust Temperature (0C) 420 439
Emissions (mg/Nm3) NOx/CO
Gas or Liquid-DLE (15 ppm) 25/26, 42/6 25/32, 42/6
Gas or Liquid-DLE (25 ppm) 51/51, 274/25 51/51
Gas or Liquid-Water 51/51, 86/6 51/40, 86/6
Gas-Steam 51/27 51/51
Power Turbine Speed (rpm) 3,600 3,600
No. of Compressor Stages 19 19
LM6000 Gas Turbine (50hz) No. of Turbine Stages 7 7

TECHNOLOGY SERVICE
The LM6000 is an aeroderivative power generating gas turbine GE Energy is the world’s largest aeroderivative service
with thermal efficiencies in excess of 43.5%. provider, with a global network of field service offices and
• Baseload Power Capabilities of 43 – 50 MW ISO fully equipped Service Centers. A wide range of products
• Excellent Fast Start Capability; Able to Reach and services are offered for the LM6000 Industrial,
Maximum Power in 10 minutes Co-generation, and Oil & Gas operators including:
• Very Compact Size; Can Be Installed in Less Than 1 Acre
• Demonstrated Reliability and Availability; In Excess of • Level IV Service Centers and overhaul
99% and 98% Respectively capability in Houston, Texas and Rheden,
• Lightweight, Modular Design – the Netherlands
Easily Maintained and Transported • Conversions, Modifications and Upgrades
(CM&Us) designed to enhance the efficiency,
EXPERIENCE power output and reliability of the LM6000.
The LM6000 is based on the CF6-80C2, the predominant engine Examples include Enhanced Flow and
for Boeing™ 747 and 767 wide-body aircraft, with over Speed (EFS), Sprint Upgrade, PA-PC/PB-PD
100 million hours of operation. Conversions, Dry Low Emissions (DLE)
• Over 590 Power Generation Units Installed Worldwide Upgrades and Remote Monitoring
with More Than Nine Million Operating Hours as of Sept. 2004 and Diagnostics
• Configurations: Simple-cycle, Cogeneration • Spare or Lease Engine Options
and Combined-Cycle • Engine Exchange Programs
• Application Flexibility: • Rotable Hot Section and Module
- Electric Utilities, Municipalities and Independent Power Exchange Programs
Producers in Peaking and Combined Cycle Installations • Wide Variety of Contractual
- Industrial Users: Metallurgical Plants, Mining, Pharmaceuticals, Service Agreements
Pulp & Paper, Food Processing, Airports, Hospitals and Universities
- Oil & Gas Users: Refineries, LNG Plants and Offshore Installations This comprehensive product offering, combined with our
commitment to reduce Service Center and outage turn
INNOVATION times, may result in substantial life cycle cost savings
At GE Energy, we continue to drive innovation throughout for the plant owner/operator.
the whole gas turbine generator package.
• SPRINT®: (Spray Inter-cooling Technology) Optimal Hot Day
Power Enhancement
• 15ppm Dry Low Emissions Technology
• Fuel Flexibility
• VAR Stabilization
• Coal Feedwater Heating

www.gepower.com
LM6000 50Hz Output and Heat Rate
55,000 10,750
50,000 9,500

HEAT RATE (KJ /KWH)


45,000 9,000
OUTPUT (kW)

40,000 9,800
35,000 9,500
30,000 9,200
25,000 8,900
20,000 8,500
-20 -10 0 10 20 30 40 50 Dimensions Refer to Package Only
0
0 m, 60% RH, 101.6/152.4mm. H20 inlet/exhaust losses AMBIENT ( C)
NOx = 51mg/Nm3, LHV = 44,194 KJ/Kg LENGTH 25m x WIDTH 4.1m x HEIGHT 4.4m

STANDARD 50H Z LM6000 GENERATOR PACKAGE OPTIONAL EQUIPMENT AND SERVICES

Gas Turbine • SPRINT®


• 19 Stage Axial Compressor • Generator Options
> 5 Stages Low Pressure and 14 Stages High Pressure > TEWAC
> Horizontal Split Casing > Enclosure
> 30:1 Compression Ratio > Fault Protection
> 275 lb/s Nominal Inlet Mass Flow > Synchronous Condenser
• Annular Combustor • Fuel System
> 30 Nozzles Gas Fuel, Water Injection for NOx Control > Liquid
• Turbine Stages Water Injection or DLE
> 2 Stage High Pressure and 5 Stage Low Pressure > Dual
Power Turbine Water Injection or DLE
Generator > Gas
• 11.0 - 11.5kV, 0.8PF Continuous Duty Water or Steam Injection or DLE
• 2 Pole, 3 Phase, Brushless Exciter • Control System
• WPII Weather Protected > Black Start
• Voltage Regulator/Neutral Side Protection CT’s > Continuous Emission Monitoring
• NEMA Class F Insulation & B Temperature Rise > Remote Display
• Integrated Protective Relay Panel > Motor Control House
Package • Lube Oil System
• 24V and 125V DC Batteries > Air to Oil Coolers
• 85dBA Near Field Design > First Fill Lubricants
• Barrier Inlet Air Filters • Winterization
• 10 Minute Start Capability • Remote Monitoring and Diagnostics
• Electro-Hydraulic Start/Shutdown System • Pulse Air Filter
• Class I Div 2 Group D Class Electrical System • 80 dBA Capability
• Digital Control System with a Human Machine Interface (HMI) • Inlet Conditioning
• Lube Oil System with Duplex Shell and Tube coolers > Evaporative Cooling
• Turbine Factory Tested > Chilling
• On/Off-line Water Wash > Heating
• 1 Year Parts/Service Warranty and Remote
Monitoring and Diagnostics
• Package Familiarization Training
• Electronically Transmitted Drawings
• Start-up Technical Assistance

www.gepower.com