Professional Documents
Culture Documents
Far East 07Bn8-F: Power Cables EN 50525-2-21
Far East 07Bn8-F: Power Cables EN 50525-2-21
Page 1/7
ADRESS: NO.8 YUANDONG ROAD GAOCHENG TOWN, YIXING CITY, JIANGSU PROVINCE, CHINA
POST CODE: 214257 TEL: +86-510-8724 9755
Technical Details
Approval VDE Marks Approval for 07BN8-F; VDE- Info Test Report
Application Far East rubber-sheathed cables 07BN8-F are intended for connection of electrical equipment in
contaminated water and for medium mechanical stresses. Specially designed for the connection of
submersible pumps to a depth of approximately 200 metres.
Owing to the various (and frequently changing) substances of which the contaminated water is made up, the
cables may be used only in easily accessible areas that can be inspected (installation depth of approximately
10 m, as customarily encountered in sewage water tanks).
These cables are also suitable for use in process water, cooling water, mine surface water, rainwater and
combined waste water. They also can be used in groundwater and seawater; it is possible to impose less
stringent specifications in terms of accessibility and inspection.
If the water concerned is aggressive or composed of special substances, the cable's resistance properties
should be examined.
These cables can be used indoors, outdoors and in explosion-hazard areas.
If they are permanently installed in protective conduits or equipment, or e.g. in well installations or are used as
rotor circuit cables for motors, the cables may be operated with an AC voltage of up to 1000 V.
The permissible AC test voltage in connection with motor tests is 3.5 kV, the maximum test duration is 5
minutes. The insulating and sheath materials used allow a maximum temperature at the conductor of 90 °C. By
virtue of this characteristic, which is verified by a VDE- Info Test Report from the VDE Test and Certification
Institute, these cables may be used according to the specifications of the Federal Testing Laboratories (PTB)
for explosion-protected pumps.
Page 2/7
ADRESS: NO.8 YUANDONG ROAD GAOCHENG TOWN, YIXING CITY, JIANGSU PROVINCE, CHINA
POST CODE: 214257 TEL: +86-510-8724 9755
Technical Details
Page 3/7
ADRESS: NO.8 YUANDONG ROAD GAOCHENG TOWN, YIXING CITY, JIANGSU PROVINCE, CHINA
POST CODE: 214257 TEL: +86-510-8724 9755
Design features
Outer jacket Synthetic thermosetting compound type EM7 in accordance with EN50363-2-1
Colour of outer jacket: black
Marking
Printing, Example:
◁ VDE-REG F398 ▷ 07BN8-F 1×1.5mm2 450/750V Far East Cable Co., Ltd. CE 90℃
The number of the outgoing code is meters (White ink marking)
Page 4/7
ADRESS: NO.8 YUANDONG ROAD GAOCHENG TOWN, YIXING CITY, JIANGSU PROVINCE, CHINA
POST CODE: 214257 TEL: +86-510-8724 9755
Selection and Ordering Data
Maximum
Number of Nominal Nominal Bend Outside Weight of
Nominal Current- Current- resistance
cores and Conductor thickness thickness Radius diameter cable
overall carrying carrying of
nominal cross- diameter of of the Fixed rabge of net
diameter capacity capacity conductor
sectional area insulation sheath install cable 1000 m
at 20 ° C
1X6 3.4 1.0 1.6 8.7 34.8 8.2 ~ 9.7 138 72 65 3.30
1X10 4.4 1.2 1.8 10.5 42.0 10.0 ~ 11.5 210 101 92 1.91
1X16 5.6 1.2 1.9 11.9 47.6 11.4 ~ 12.9 288 135 123 1.21
1X25 7 1.4 2.0 13.9 55.6 13.4 ~ 14.9 410 178 162 0.780
1X35 8.7 1.4 2.2 16.4 65.6 15.9 ~ 17.4 550 220 200 0.554
1X50 10.2 1.6 2.4 18.7 74.8 18.0 ~ 20.0 750 275 250 0.386
1X70 11.8 1.6 2.6 20.7 82.8 20.1 ~ 22.1 980 340 309 0.272
1X95 13.5 1.8 2.8 23.2 92.8 22.2 ~ 24.2 1260 416 378 0.206
1X120 15.6 1.8 3.0 25.7 154.2 24.7 ~ 27.2 1560 488 444 0.161
1X150 17.2 2.0 3.2 28.1 168.6 27.1 ~ 29.6 1920 566 515 0.129
1X185 18.7 2.2 3.4 30.4 182.4 29.4 ~ 31.9 2300 644 585 0.106
1X240 21.6 2.4 3.5 33.9 203.4 32.9 ~ 35.4 2950 775 686 0.0801
1X300 24.1 2.6 3.6 37.0 222.0 36.0 ~ 38.5 3590 898 816 0.0641
1X400 27.7 2.8 3.8 41.4 248.4 40.4 ~ 42.9 4600 945 859 0.0486
1X500 31.4 3.0 4.0 45.8 274.8 44.8 ~ 47.5 5770 1080 982 0.0384
2X10 4.4 1.2 3.1 20.6 82.4 19.6 ~ 21.6 640 83 75 1.91
2X16 5.6 1.2 3.3 23.5 94.0 22.5 ~ 24.5 860 106 96 1.21
2X25 7.0 1.4 3.6 27.7 166.2 26.7 ~ 29.2 1230 142 129 0.780
Far East 07BN8-F 3G...
3G1 1.25 0.8 1.4 9.9 39.6 9.4 ~ 10.9 135 18 16 19.5
3G1,5 1.52 1.1 1.6 11.9 47.6 11.4 ~ 12.9 200 25 23 13.3
3G2,5 1.97 1.1 1.8 13.3 53.2 12.8 ~ 14.3 265 31 28 7.98
3G4 2.51 1.0 1.9 14.3 57.2 13.8 ~ 15.3 320 41 37 4.95
Page 5/7
ADRESS: NO.8 YUANDONG ROAD GAOCHENG TOWN, YIXING CITY, JIANGSU PROVINCE, CHINA
POST CODE: 214257 TEL: +86-510-8724 9755
Selection and Ordering Data
Maximum
Number of Nominal Nominal Bend Outside Weight of
Nominal Current- Current- resistance
cores and Conductor thickness thickness Radius diameter cable
overall carrying carrying of
nominal cross- diameter of of the Fixed rabge of net
diameter capacity capacity conductor
sectional area insulation sheath install cable 1000 m
at 20 ° C
3X1 1.25 0.8 1.4 9.9 39.6 9.4 ~ 10.9 135 18 16 19.5
3X1,5 1.52 1.1 1.6 11.9 47.6 11.4 ~ 12.9 200 25 23 13.3
3X2,5 1.97 1.1 1.8 13.3 53.2 12.8 ~ 14.3 265 31 28 7.98
3X4 2.51 1.0 1.9 14.3 57.2 13.8 ~ 15.3 320 41 37 4.95
3X6 3.4 1.0 2.1 16.7 66.8 16.2 ~ 17.7 445 53 48 3.30
3X10 4.4 1.2 3.3 22.1 88.4 21.1 ~ 23.1 800 74 67 1.91
3X16 5.6 1.2 3.5 24.2 96.8 23.2 ~ 25.2 1080 99 90 1.21
3X25 7 1.4 3.8 29.5 177.0 28.5 ~ 31.0 1550 131 119 0.780
3X35 8.7 1.4 4.1 34.6 207.6 33.6 ~ 36.1 2060 162 147 0.554
3X50 10.2 1.6 4.5 39.5 237.0 38.5 ~ 41.0 2785 202 183 0.386
3X70 12 1.6 4.8 43.6 261.6 42.6 ~ 45.6 3590 250 227 0.272
3X95 13.5 1.8 5.3 49.2 295.2 48.2 ~ 51.2 4650 301 273 0.206
3X120 15.6 1.8 5.6 54.3 325.8 53.3 ~ 56.3 5720 352 320 0.161
3X150 17 2.0 6.0 59.4 356.4 58.4 ~ 61.4 7000 404 367 0.129
3X185 18.7 2.2 6.4 64.5 387.0 63.5 ~ 66.5 8400 446 405 0.106
3X240 21.6 2.4 7.1 72.8 436.8 71.8 ~ 74.8 10850 528 480 0.0801
4G1 1.25 0.8 1.5 10.8 43.2 10.3 11.8 166 18 16 19.5
4G1,5 1.52 1.1 2.7 14.4 57.6 13.3 15.3 315 25 23 13.3
4G2,5 1.97 1.1 1.9 14.7 58.8 14.2 15.7 340 31 28 7.98
4G4 2.51 1.0 2.3 16.1 64.4 15.3 16.8 450 41 37 4.95
4G6 3.4 1.0 2.6 19.1 76.4 18.0 20.0 620 53 48 3.30
4G10 4.4 1.2 3.9 25.1 150.6 23.8 26.3 1090 74 67 1.910
4G16 5.6 1.2 4.1 28.2 169.2 27.0 29.5 1450 99 90 1.210
4G25 7.0 1.4 4.9 33.8 202.8 32.5 35.0 2130 131 119 0.780
4G35 8.7 1.4 5.0 38.9 233.4 37.4 40.4 2790 162 147 0.554
4G50 10.2 1.6 5.7 44.4 266.4 42.9 45.9 3790 202 183 0.386
4G70 11.8 1.6 5.7 49.0 294.0 47.5 50.5 4850 250 227 0.272
4G95 13.5 1.8 6.8 55.6 333.6 54.1 57.1 6330 301 273 0.206
4G120 15.6 1.8 6.8 61.3 367.8 59.8 62.8 7770 352 320 0.161
4G150 17.2 2.0 6.5 66.0 396.0 65.0 68.0 8920 404 367 0.129
4G185 18.7 2.2 7.0 71.7 430.2 70.7 73.7 10740 446 405 0.106
4G240 21.6 2.4 7.7 81.0 486.0 80.0 83.0 13900 528 480 0.0801
4G4+2×0.75 2.51/1.08 1.1/1.0 3.1 19.5 78.0 18.5 20.5 610 41 37 4.95/26.0
Page 6/7
ADRESS: NO.8 YUANDONG ROAD GAOCHENG TOWN, YIXING CITY, JIANGSU PROVINCE, CHINA
POST CODE: 214257 TEL: +86-510-8724 9755
Selection and Ordering Data
Maximum
Number of Nominal Nominal Bend Outside Weight of
Nominal Current- Current- resistance
cores and Conductor thickness thickness Radius diameter cable
overall carrying carrying of
nominal cross- diameter of of the Fixed rabge of net
diameter capacity capacity conductor
sectional area insulation sheath install cable 1000 m
at 20 ° C
5G1.5 1.52 1.1 1.8 14.3 57.2 13.8 ~ 15.3 230 25 23 13.3
5G2,5 1.97 1.1 2.0 16.1 64.4 15.6 ~ 17.1 390 31 28 7.98
5G4 2.51 1.0 2.2 17.4 69.6 16.9 ~ 18.4 500 41 37 4.95
5G6 3.4 1.0 2.5 20.5 82.0 19.5 ~ 21.5 710 53 48 3.30
5G10 4.4 1.2 3.6 26.5 159.0 25.5 ~ 27.5 1200 74 67 1.91
5G16 5.6 1.2 3.9 30.4 182.4 29.4 ~ 31.9 1660 99 90 1.21
5G25 7.0 1.4 4.4 36.3 217.8 35.3 ~ 37.8 2430 131 119 0.780
11G1,5 1.52 1.1 2.9 22.1 88.4 21.1 ~ 23.6 620 28 23 13.3
12G1,5 1.52 1.1 3.6 22.6 90.4 21.7 ~ 23.7 760 28 23 13.3
For other ambient temperatures, the current-carrying capacities must be converted with the following factors:
℃ 20 25 30 35 40 45 50
Page 7/7
ADRESS: NO.8 YUANDONG ROAD GAOCHENG TOWN, YIXING CITY, JIANGSU PROVINCE, CHINA
POST CODE: 214257 TEL: +86-510-8724 9755