NGRM700 NGR monitor
Product description
The NGRM700 is only intended for use in high-resistance grounded systems.
In these systems, the NGRM700 monitors
• the current through the neutral-grounding resistor (NGR),
• the voltage between the star point of the transformer and earth (voltage drop across the
NGR),
• the condition of the NGR,
• line-to-line and line-to-earth voltages.
Systems with a high-resistance grounded star point can be used when an interruption
i of the power supply would involve excessive costs due to production stoppage.
LINETRAXX® NGRM700 The ground fault that occurs between a phase and earth does not lead to a failure of the
power supply in these systems. A ground fault must be detected and eliminated as quickly
Device features as possible, since the occurrence of another ground fault in a second phase would lead
• Determination of RNGR with passive and to a tripping of the overcurrent protective device.
active measurement methods In order to meet the requirements of applicable standards, the equipment must be adjusted
• Continuous monitoring of the RNGR even to local equipment and operating conditions by means of customised parameter settings.
if the installation is de-energised; Please heed the limits of the range of application indicated in the technical data.
• Alarm or trip on ground fault Any other use than that described in this manual is regarded as improper. Intended use
• Monitoring of the current INGR includes following all the instructions in this operating manual.
• Monitoring of the voltage UNGR Function
• Phase-to-ground fault indication The NGRM700 monitors NGR resistance RNGR, neutral voltage UNGR and current INGR.
(optional; up to 690 V direct coupling,
otherwise via potential transformers) NGR resistance is monitored using an active and a passive procedure:
• Communication via Ethernet/Modbus TCP active The device generates an active test pulse and measures RNGR even if the
installation is de-energised.
• Web server
passive Only for energised installations: The resistance RNGR is determined when INGR
• Language selection (German, English GB or UNGR exceeds an internal threshold. The device measures the existing current
and US, Spanish, French) and voltage and calculates RNGR.
• Test button (internal, external) with/without In the case of the “auto” method, monitoring switches automatically between “active”
tripping and “passive” when the measured value exceeds or falls below the internal threshold.
• FFT analysis of the measuring signals A short circuit or interruption of the NGR is reliably detected in an energised as well as a
• Pulser for manual ground fault location de-energised installation with the active measurement method.
• Relay for detection of ground faults and When the “passive” method is selected, no switching of the monitoring takes place. No
resistor faults monitoring of the NGR occurs while the installation is de-energised.
• Relay for shutdown of the installation The NGR relay switches from alarm state to operating state when the measured resistance
after a configurable time RNGR is within the configured thresholds.
• Can be combined with RCMS… for auto- A ground fault is signalled via the corresponding ground-fault relay when INGR or UNGR
matic shutdown of feeders exceeds the selectable thresholds. After the configurable delay time has elapsed, the
• Wide supply voltage range power system can be shut down with the trip relay. A connection to installations ranging
(24 to 240 Vac/Vdc) from 400 V…25 kV is possible via the appropriate CD-series coupling device.
• Range of use up to 5000 m AMSL INGR is measured with (universal) measuring current transformers with 5 A or 50 mA
• Fault/History memory secondary ratings. With the conversion ratio of the used measuring current transformer
the current measurement is internally set in such a way that it adjusts best to INGR.
• Analogue output of measured values
(0…10 V, 4…20 mA, etc., selectable The phase monitoring function of the NGRM can be used to indicate which phase has
parameters) the ground fault. Direct coupling is possible up to a system voltage of 690 V. For higher
voltages, the coupling is carried out via potential transformers (PT) with an adjustable
• Detachable HMI for door mounting conversion ratio.
• Password protection
• Tripping on RMS, fundamental component
signal or harmonics
• Detection of AC and DC ground faults
2 NGRM700_D00292_00_D_XXEN/09.2017
NGR monitor NGRM
FP200
7
1 ON
* MENU
8
2 ESC
<
RESET TEST
9
3 SERVICE < 10
4 <
TRIPPED
11
5 NGR FAULT INFO DATA
12
OK
6
<
GROUND FAULT
13 14 15
1 - ON Operation LED, green; on when power supply 8 - MENU Opens the device menu.
is available ESC Cancels the current process or navigates one
2- The LC display shows device and measurement step back in the device menu.
information. 9 - RESET Resets alarms.
3 - SERVICE The LED is on when there is either a device Navigates backwards (e.g. to the previous setting
fault or a connection fault, and when the device step) or selects parameter.
is in maintenance mode.
10 - TEST Starts the device self test.
4 - TRIPPED The LED is on when the trip relay has been
tripped due to an NGR fault, ground fault or a Navigates forwards (e.g. to the next setting step)
system error. or selects parameter.
5 - NGR FAULT The LED is on when an NGR fault has been 11 - INFO Shows information.
detected. Trip relay and NGR relay have tripped. Navigates down in a list or reduces a value.
6 - GROUND The LED flashes in case of a prewarning: ground 12 - DATA Indicates data and values.
FAULT fault detected, earth-fault relay has tripped, trip
OK Confirms an action or a selection.
relay has not tripped yet (ttrip elapses).
13 - X1 Interface X1
The LED is on: ground fault detected, trip relay
has tripped, installation has not been shut 14 - ETH Ethernet interface
down yet. 15 - R on/off Without function
7- Navigates up in a list or increases a value. Buzzer Active in case of alarm and/or test
Connectors CD…
N N
CD690
CD1000 G1 Rs
CD14400
CD5000
CD25000
G E
NGRM700_D00292_00_D_XXEN/09.2017 3
NGR monitor NGRM
L1
L2
L3
Ground NGR 6A 6A 6A
Trip
fault fault
CT k 50mA / 5A
11 12 14 21 22 24 31 32 34 L1 L2 L3
AC/DC
l C 24...240 V
N CD...
6A 6A
Rs (G1)
NGRM700 A1
NGR RS
A2
FP200-NGRM
E (G)
X1
E
Dig. IN/OUT Ethernet
i The “N” connection of the CD-series coupling device should be as close to the transformer star point as possible.
Circuit breaker
L1
L2
L3
Ground NGR 6A 6A 6A
Trip
fault fault
CT k 50mA / 5A
11 12 14 21 22 24 31 32 34 L1 L2 L3
AC/DC
l C 24...240 V
N CD...
6A 6A
RP
Rs (G1)
NGRM700 A1
NGR RS
A2
FP200-NGRM
E (G)
X1 X1
E
Pulser OUT Dig. IN/OUT Ethernet
RP = RPulser
The “N” connection of the CD-series coupling device should be as close to the transformer star point as possible.
i
An intermediate relay may be required between the power contactor of the pulser and the digital output at X1 of the FP200-NGRM.
4 NGRM700_D00292_00_D_XXEN/09.2017
NGR monitor NGRM
L1
L2
L3
PT *
Ground NGR
Trip
fault fault
CT k 50mA / 5A
11 12 14 21 22 24 31 32 34 L1 L2 L3
AC/DC
l C 24...240 V
N CD...
6A 6A
Rs (G1)
NGRM700 A1
NGR RS
A2
FP200-NGRM
E (G)
X1
E
Dig. IN/OUT Ethernet
Note:
* PT ratio "primary: secondary" can be adjusted in the NGRM700.
i
The “N” connection of the CD-series coupling device should be as close to the transformer star point as possible
NGRM700_D00292_00_D_XXEN/09.2017 5
NGR monitor NGRM
Circuit breaker
L1
L2
L3
Ground NGR 6A 6A 6A
Trip
fault fault
CT k 50mA / 5A
11 12 14 21 22 24 31 32 34 L1 L2 L3
AC/DC
l C 24...240 V
N CD...
6A 6A
Rs (G1)
NGRM700 A1
NGR RS
A2
FP200-NGRM
E (G)
X1
E
Dig. IN/OUT Ethernet
System type AC + DC AC AC
I 1…10 A 5…25 A 5…25 A
f 0…3800 Hz 42…3800 Hz 50/60 Hz
Conversion ratio 600:1 600:1 60:5
max. 25 m (4 mm²)
Length connecting cables max. 10 m max. 40 m
max. 40 m (6 mm²)
IΔn
W20…120
W35…120AB CTB31…41
W1-S35…W5-S210
W...AB
W...
CTB
Type
W...S...
AN420
k l k l k l
6 NGRM700_D00292_00_D_XXEN/09.2017
NGR monitor NGRM
12
22
32
11
21 14
31 24
34
I1 FP200-NGRM X1 FP200-NGRM X1
I2 Reset IN
I2 +24 V, max. 100 mA +24 V, max. 100 mA
I3 I3 Test IN + +
A
B A Not in use Pull up Pull up
10 kΩ 10 kΩ
B Not in use
Q Q In
Ground max. 300 mA,
24 V
PLC
M+ Analogue output
Q2 Open Collector: Pulser OUT
M+
Q2
Open Collector: System condition
Q1
Q1 (system health) External supply. e.g.12...24 V
+ X1
Output for supply of external FP200-NGRM
+
relays (+24 V, max. 100 mA) +24 V, max. 100 mA
+
Pull up
10 kΩ
+
X1: Input I1…3 Q
The input is only detected as “activated” after the contact has max. 300 mA,
24 V
been activated for at least 150 ms. This way, short interference
pulses are ignored.
Active high Active low
X1 X1 X1 X1
I1…3 I1…3
Connection to Q1, Q2: external relay or PLC.
0…20 mA ≤ 600 Ω
Current output
X1 X1 4…20 mA ≤ 600 Ω
M+ A
0…400 μA ≤ 4 kΩ
NGRM700_D00292_00_D_XXEN/09.2017 7
NGR monitor NGRM
Technical Data
Insulation coordination according to IEC 60664-1/IEC 60664-3 Monitoring INGR
Definitions Measuring circuit 5 A
Measuring circuit 1 (IC1) (L1, L2, L3) Measuring CT nominal secondary current In DC/50/60 Hz/50…3200 Hz 5 A
Supply circuit (IC2) (A1, A2) Maximum continuous current 2 x In
Measuring circuit/Control circuit (IC3) (RS, E, CT), (X1, Ethernet) Overload capacity 10 x In for 2 s
Output circuit 1 (IC4) (11, 12, 14) Measurement accuracy ±2 % of measuring range
Output circuit 2 (IC5) (21, 22, 24) Measuring circuit 50 mA
Output circuit 3 (IC6) (31, 32, 34) Measuring CT nominal secondary current In DC/50/60 Hz/50…3200 Hz 50 mA
Rated voltage 690 V Maximum continuous current 2 x In
Overvoltage category III Overload capacity 10 x In for 2 s
Rated impulse voltage Measurement accuracy ±2 % of measuring range
IC1/(IC2…6) 8 kV
Measuring circuits 5 A and 50 mA
IC2/(IC3…6) 4 kV
Response value INGR 10…90 % INGR
IC3/(IC4…6) 4 kV
Response delay ground-fault relay ≤ 750 ms
IC4/(IC5…6) 4 kV
Response delay trip relay (configurable) 100 ms…24 h, ∞
IC5/(IC6) 4 kV
Tolerance ttrip when set to
Rated insulation voltage
RMS -20…0 ms
IC1/(IC2…6) 800 V
Fundamental 0…+150 ms (filter time)
IC2/(IC3…6) 250 V
Harmonics 0…+150 ms (filter time)
IC3/(IC4…6) 250 V
Measuring current transformer ratio primary 1…10,000
IC4/(IC5…6) 250 V
Measuring current transformer ratio secondary 1…10,000
IC5/(IC6) 250 V
Measuring range 2 x INGR
Pollution degree exterior 3
Safe isolation (reinforced insulation) between Coupling
IC1/(IC2…6) overvoltage category III, 800 V RS for Usys ≤ 4.3 kV CD690, CD1000, CD4200, CD5000 (20 kΩ)
IC2/(IC3…6) overvoltage category III, 300 V RS for Usys > 4.3 kV CD14400 (100 kΩ)
IC3/(IC4…6) overvoltage category III, 300 V Monitoring UNGR
IC4/(IC5…6) overvoltage category III, 300 V
IC5/(IC6) overvoltage category III, 300 V UNGR with RS = 20 kΩ DC/50/60 Hz/50…3200 Hz; (400/√3) … ≤ (4300/√3) V
Voltage tests (routine test) acc. to IEC 61010-1 UNGR with RS = 100 kΩ DC/50/60 Hz/50…3200 Hz; > (4.3 /√3) …(25/√3) kV
IC2/(IC3…6) AC 2.2 kV Measuring range 1.2 x UNGR
IC3/(IC4…6) AC 2.2 kV Overload capacity 2 x UNGR for 10 s
IC4/(IC5…6) AC 2.2 kV Measurement accuracy 2 % of UNGR nom with UNGR nom = (Usys (L-L)/√3)
IC5/(IC6) AC 2.2 kV Voltage response value 0…100 % UNGR
Response delay ground-fault relay ≤ 750 ms
Supply voltage Response delay trip relay (configurable) 100 ms…24 h, ∞
Nominal supply voltage Us Tolerance ttrip when set to
≤ 2000 m AC/DC, 24…240 V RMS -20…0 ms
> 2000…≤ 5000 m AC/DC, 24…120 V Fundamental 0…+150 ms (filter time)
acc. to UL AC/DC, 48…240 V Harmonics 0…+150 ms (filter time)
Tolerance±15% PT ratio primary 1…10,000
Frequency range DC, 40…70 Hz PT ratio secondary 1…10,000
Power consumption 6.5 W/13 VA DC immunity in case of active RNGR measurement
with RS = 20 kΩ DC ±12 V
Phase monitoring with RS = 100 kΩ DC ±60 V
Nominal measuring voltage Un 3 AC 100…690 V, CAT III
Digital inputs
Measuring range 1.2 x Un
Measurement accuracy ±1 % of Un Galvanic separation no
Overload capacity 2 x Un continuous Length connecting cables max. 10 m
PT ratio primary 1…10,000 Uin DC 0 V, 24 V
PT ratio secondary 1…10,000 Overload capacity -5…32 V
Measuring range with PT 100 V…25 kV Digital outputs
Monitoring NGR Galvanic separation no
Measuring input RS < 33 V RMS Length connecting cables max. 10 m
Measuring range NGR (with RS = 20 kΩ) active 0…4 kΩ Currents (sink) for each output max. 300 mA
Measurement uncertainty for T = 0…+40 °C ±20 Ω Voltage 24 V
Measuring range NGR (with RS = 100 kΩ) active 0…4 kΩ Overload capacity -5…32 V
Measurement uncertainty for T = 0…+40 °C ±30 Ω
Setting range RNGR nom15 Ω…2 kΩ
Response value RNGR nom 10…90 % RNGR
110…200 % RNGR
Response delay NGR relay and trip relay ≤ 10 s
8 NGRM700_D00292_00_D_XXEN/09.2017
NGR monitor NGRM
NGRM700_D00292_00_D_XXEN/09.2017 9
Dimension diagram NGRM700 (mm) Dimension diagram NGRM700 (inches)
63,35
61,40
55,50
2.19
2.42
2.49
0.12
3
36
6 0.2
223,50
125
150
4.92
5.91
8.80
NGRM700_D00292_00_D_XXEN / 09.2017 / pdf / © Bender GmbH & Co. KG, Germany – Subject to change! The specified standards take into account the current edition at the time of going to press.
205 8.07
211 8.31
230 9.06
245 9.65
3
5,8 0.2
13 5.3
5 ,5 3
2.83
72
65,5
2.58
14 5.6
4 7
,6 0
35 1.4