Professional Documents
Culture Documents
Partial Discharges: Questions For Discussion
Partial Discharges: Questions For Discussion
Authorized licensed use limited to: Auckland University of Technology. Downloaded on November 09,2020 at 07:43:57 UTC from IEEE Xplore. Restrictions apply.
ionization. Thus, the coincidence of the shape of the current
and the glow serves as further evidence electronic component
dominance in the PD current.
What is the real duration of the PD?
If we finally accept that the recorded current pulses are de-
termined by the electron current, then PD duration
corresponds to the front duration, provided that the equipment
and registration scheme as a whole are sufficient for that.
According to literary sources, it is easy to see how, as the
experimental technique developed, the duration of the PD
front “decreased” from microseconds to hundredths of a
Fig. 1b. PD form in air cavity:
nanosecond, i.e. four orders!
experiment with 1,0 mm cavity (40 mA/div, 20 ns/div) [9]. If we assume that the formation of each PD occurs when the
electric field strength is equal to the breakdown field and after
The PD current electronic component is also supported by the charge sedimentation, the field strength inside the cavity
the fact during synchronous recordings of radiation and the drops so that the PD stops, then for cavities with (0.01 - 1) mm
PD current, the waveforms coincidence of photoelectronic diameter, the electron drift time corresponding to the recorded
multipliers (PM) and current pulses shape was noted as we signal edge duration should be approximately (0.02 - 10) ns.
can see on Fig. 2. However, this assumption applies to those current pulses whose
amplitude exceeds the recording equipment sensitivity
threshold.
The question of sensitivity is also not an idle one. Firstly, the
signal size is strongly influenced by the intrinsic cavity
dimensions. The calculated curves of the formation dynamics
(by the impact ionization mechanism) and PD charge transfer
in the air cavity with 5 m diameter shown in Fig. 3 show
extremely low and unavailable for registration energy and time
characteristics of the avalanche growth process.
a)
a)
b)
Fig. 2. Current and radiation PD pulses in the air:
a) upper trace – current, lower trace – radiation [8];
b) in disc 1 mm cavity [9].
Time resolution 20 ns/div.
b)
It is known that PD radiation is associated with a neutral Fig. 3. Number of ionization events (a) and charge transfer (b) in time
air molecules excitation discharge, and only electrons can during PD in cavity with 5 μm diameter and electric field strength 270
have energy corresponding to the excitation and molecules kV/cm
Authorized licensed use limited to: Auckland University of Technology. Downloaded on November 09,2020 at 07:43:57 UTC from IEEE Xplore. Restrictions apply.
Secondly, it must be taken into consideration apparent PD reason, for example, factory PD tests of power transformers
charge can be much smaller than the true one [11] if the cavity are a good tool for testing insulation manufacturing
is in the bulk of the dielectric. There are other ”subtleties”. For technology. Some experiments have shown direct relationship
example, synchronous recording of the radiation pattern and between apparent charge and size of cavity or bubbles. So tests
the PD current in [7] showed the number of micro- discharges of the oil channel model in the oil and gas transformer
is greater than the number of current pulses. In [9], the insulation with air bubbles showed following relationships
chronography of PD radiation showed micro-discharges between size of bubbles and the PD apparent charge [15]:
starting almost simultaneously in different places of a flat
cavity form a current pulse with one or two maxima [9]. Bubble diameter, mm 2,1 3,9 5,8
Where do the initial electrons come from? What is the PD PD apparent charge
0,2…2 0,2…5 1…20
delay? range, nC
Authorized licensed use limited to: Auckland University of Technology. Downloaded on November 09,2020 at 07:43:57 UTC from IEEE Xplore. Restrictions apply.
Fig. 4. Noise signals generated by RF-communication in 220 kV SF6 bushing. RF-communication is on feeding overhead line on phase “C”.
On phase C signal is about 1 V, on phase “B” induced signal is 5 times less, on phase “A” - 20 times less.
What repetition rate should PD have, the charge of which must bushing dismantling confirmed the initial stage of insulation
be taken into account? damage in the layers of paper adjacent to the current-
In the basic standard, it is recommended to take the appar- conducted pipe.
ent charge magnitude of repeating discharges under the PD Note that the PD data format recommended by CIGRE has
intensity, their repetition rate is not indicated. According to 23 (!) mutual distributions types of PD characteristics [20].
classical concepts, PD repletion rate should be a multiple of Recently, the most common application for the analysis of
phase-resolved PD diagrams (PRPD) has become. E. Gulsky,
network frequency. In practice, the PD sequence over time is
by the PRPD appearance, already 20 years ago created 27
most often irregular.
images (“finger prints”) of insulation defects for bushings,
In order to somehow normalize the parameter, in standard
transformers and other equipment [21]. Company ”Dimrus”
[1] repetition rate has been introduced, which can vary within
published 4 types of PRPD, corresponding to different types
Rc = 0-1. In [18], the same indicator is called “regularity, Re,” of the PD [22]. Great expectations are associated with the
and it is recommended to characterize the discharge activity analysis of the temporal characteristics of PD signals in the
by PD apparent charge, repeated at least in every second so-called TF-plane. In the new edition of the IEC 60270-
voltage period, i.e. at Re 0.5. In many publications, the 2015 standard, the sections devoted to digital methods for
intensity is expressed by q02, i.e. PD recurring with R 0.2. recording PD and, in particular, to amplitude-phase diagrams
Obviously, PD repeatability depends on many factors, for are significantly expanded.
example, on phase transitions “liquid - vapor” during PD in
liquid dielectrics. There are delays associated with the shortage How to calibrate the registration circuit when testing
of initial electrons [10, 19]. There is also PD self-extinguishing insulating structures with low capacitance between the
and, conversely, immediately before a full breakdown there are electrodes?
single powerful PD. For these reasons, we consider it In accordance with the standards requirements with a par-
advisable to provide in the measurement protocol the full allel calibration scheme, calibration capacitor must have a
characteristic of the PD discharge activity with a detailed capacity much less than the object capacity. But how to do
description discharges nature with different apparent charges. this if object capacity is a dozen or two picofarads?! All
that remains is option with sequential switching on of the
Why are there no norms for other PD characteristics? calibration capacitor, which is impossible to realize under
In our practice, there have been cases where the most field conditions. The option with the “inverted” calibration
important thing was not the maximum apparent charge, but scheme is not always convenient and it must be checked due
average current and voltage of the PD occurrence/extinction. to the uncertainty in the value of the parasitic capacitance.
In one of the diagnosed autotransformers, PD charges did not Specific problems arise when testing objects with a large
exceed 100 pC, but their quantity was very large. As it turned ratio of height to transverse dimensions and with a small
out, the isolation barriers in the autotransformer were clogged intrinsic capacity. Such structures include support and
with sawdust from the collapsing oil pump impeller. In another suspension rod insulators, surge arresters, measuring
case, when testing the autotransformer 220/110 kV, the low transformers with gas- insulated insulation, etc. The result of
value of the PD occurrence voltage, which were identified by PD measuring during their testing depends on the area of the
the oscillograms as a series in bushing insulation, was alerted. grounded electrode: the larger the area, the greater the
Despite the small charges of the PD (about 50 pC), 220 kV measured value of the apparent charge. There is dependence
Authorized licensed use limited to: Auckland University of Technology. Downloaded on November 09,2020 at 07:43:57 UTC from IEEE Xplore. Restrictions apply.
on stand height. Essence of the influence of geometry lies
in electric field heterogeneity.
The more field lines of force are closed on a grounded
plane, the greater the amount of PD induced charge is
collected on it and fixed by a registration circuit. For this
reason, norms on PD intensity in such objects should be
accompanied by detailed instructions regarding the size and
arrangement of circuit elements [25].
What should one focus on when assessing the charge of the
a) experiment sketch
PD in longitudinal isolation?
For various reasons, PD can also occur in longitudinal
insulation, for example, in coil insulation of shunt reactor
windings, power transformers and in generators stator wind-
ings. It can be attributed to PD in longitudinal insulation and
sparking in autotransformers OLTC contactors. In our
practice, the signal waveforms shown in Fig. 5 were
obtained.
In one of phases in 500 kV autotransformer group, in addi-
tion to the usual PD signals, irregularly repeated oscillation b) signal transmission through capacitor to coordinated load and
packets of noticeably larger amplitude were observed. The grounding of cable shield from both ends at one point
signals had different polarity on the bushing sensors 500 and
220 kV. In this case, the signal at 220 kV bushing was ahead
of the signal at the 500 kV side by approximately 40 ns, and
its amplitude was approximately twice as large. On these
grounds, an assumption arose about sparking in the OLTC
contact system.
By acoustic method, the discharge activity in the OLTC
was confirmed. It was recommended and it performed tests
and ohmic resistances measurements with various OLTC
position. Deviations from the norm have not been
established. However, a year later, autotransformers group
crashed due to the OLTC gas protection in the suspected
phase. Opening OLTC tank showed flexible connection
c) the cable is coordinated, but the upper shield end is grounded with
burnout from the external contact of the withdrawn part copper tape
OLTC to the contactor. Similar damage was detected on the
flexible connection adjacent contact.
Thus, PD location issue was solved successfully, however,
the question remained how to calibrate PD registration scheme
in longitudinal isolation and what charge values to normalize?
What errors can occur in calibration?
The basic standard [1] introduced stringent requirements for
the errors of calibration generators. Recording equipment
producers should check them by comparing the output voltage
with a reference generator, which is stored in a separate room
with climate control, air purity, etc. And if you think about
what they transfer to the transformer input through a wire or
cable with indefinite length and indefinite location, grounding, d) signal conducted by wire
coordination, etc.? What is the signal up there? What does its Fig. 6. Changes of calibration signal waveform (upper trace).
amplitude and shape have to do with the signals that arise in
the registration scheme from real PDs? We received some Despite the inclusion of matching load resistance, the
answers in simple laboratory experiments, the scheme and presence of inductance in the ground circuit of the shield
results of which are shown in Fig. 6. affects. In some cases, practice PD measuring at existing
It can be seen front duration varies from the initial 40 ns to substations calibrating the registration scheme for various
120 ns when grounding the cable shield at the conditionally reasons was problematic. There was only one way out - to
“upper” end through a copper strip as recommended in [18]. integrate PD current to get an apparent charge. With digital
Authorized licensed use limited to: Auckland University of Technology. Downloaded on November 09,2020 at 07:43:57 UTC from IEEE Xplore. Restrictions apply.
data, this is quite simple. As a comparison result, we came to [8] C. Mayoux, M. Goldman. Partial discharges in solid dielectrics and
corona discharge phenomena // J. of Applied Physics, 1973, v. 44, no
conclusion that discrepancies in the apparent charge values 9. pp. 3940-3944.
obtained by integration and calibration do not exceed 20% [9] A. Ovsyannikov, Spatial-temporal and energy characteristics of partial
with the correct choice of integration limits over time. discharges in air cavities of solid dielectrics. Procced. NSTU, 1999.
[10] Bartnikas R., A Comment Concerning the Rise Times of Partial
What to do with PD signals attenuation data when changing Discharge Pulses // IEEE Trans. on Dielectrics and Electr. Insul., 2005,
their location? v.12, no 2. pp. 196 – 202.
When registering the PD in a transformer, calibration is [11] A. Ovsyannikov, S. Korobeinikov, D. Vagin, The relationship between
the apparent and true charges of partial discharges. Elecricity, 2014,
carried out by applying calibration charge to the winding Vol.8.
beginning via bushing. But PD can also occur in the winding [12] G. Reter, Electronic avalanches and breakdown in gases. Mir, Moscow,
bulk. If possible, then PD sensors are included in different 1968.
winding places and apparent charge value can be adjusted [13] Hummel1 R. and others, Inception time delay for internal partial
according to calibration coefficients matrix. But on this point discharges / Proc. 19th Int. Symp. on High Voltage Eng., 2015. Paper
473.
the normative documents recommendations are stopped. Is it
[14] I.V. McCalister. Electric Fields and Electric Insulation // IEEE Trans.
necessary to multiply the measured value by the attenuation on Dielectrics and Electr. Insul., 2002, v.9, no 5. pp. 672 – 694.
coefficient and compare it with the normalized value of PD [15] Niasar M.G., Edin H., Wang X., Clemence R. Рartial discharge
intensity? What to do with cables or rotating equipment? In characteristics due to air and water vapor bubbles in oil / Proc. of XVII
them, there are no intermediate points for connecting sensors Int. Symp. on High Volt. Eng., Hannover, 2011. Paper D – 067.
along the length and attenuation can be quite large. [16] A. Ovsyannikov, R. Arbuzov, S. Zhivodernikov, Estimation of the
apparent charge of partial discharges in the capacitor type insulation.
CONCLUSION Energoexpert, 2014, Vol.6.
[17] L. Daryan, K. Zaitzev, The apparent charges of partial discharges in
For clarity in theoretical calculations, it is necessary to sectioned capacitors / Dielectric strength of the insulation of high
achieve a better understanding what we measure from of PD voltage electrical equipment. Proceed. VEI, 1989.
different types and what factors influence measurement [18] Organization Standard “FGK UES”. Method for measuring partial
results of the PD characteristics. discharges in the oil barrier insulation of power transformer equipment.
2015.
Even with all the omissions and shortcomings, diagnosis
[19] S. Korobeynikov and others. Mechanism of Partial Discharges in Free
in the PD is excellent tool for technological control in factory Helium Bubbles in Transformer Oil // IEEE Trans. on Dielectrics and
testing laboratories and therefore has the right to life. Electrical Insul., 2019, vol. 26, no. 5. С. 1605-1611.
To introduce the PD method into practice, it is necessary to [20] Lapp A., Kranz H.G. The use of the CIGRE data format for PD
diagnosis application // IEEE Trans. on Dielectrics and Electr. Insul . –
work on the listed disadvantages elimination. In particular, 2000. – v.7, no 1. – pp.102-112.
use larger number of recorded PD characteristics in order to [21] Gulsky E. Application of modern PD detection techniques to fault
produce reliable defects images that initiate them. Carry out recognition in the insulation of high voltage equipment / Proc. IX Int.
in-depth results analysis obtained in comparison with the Symp. on High Volt. Eng., Graz, 1995. Paper 4532.
other tests data, inspections, disassembly and repair. Only [22] V. Rusov, Partial discharge measurement in isolation of high voltage
equipment. Ekaterinburg, 2011.
then can we expect that the registration of the PD will become
[23] N. Kinsht and others, Methodological issues of evaluating multiple
a real tool for identifying acquired of various types partial discharges in high-voltage equipment / Methodological issues
equipment defects, including problematic ones. of studying the reliability of large energy systems. In proc. Reliability
of developing energy systems, 2018.
REFERENCES [24] A. Ovsyannikov, S. Zhivodernikov, O. Golenko, "Inverted" calibration
[1] GOST R 55191-2012 (IEC 60270:2000). High voltage test methods. scheme for the registration of partial discharges. Proc. Methods and
Partial discharge measurements. tools for assessing the state of power equipment, SPb, 2002.
[2] G. Kuchinskii, Partial discharges in high voltage structures. Energy, [25] Organization Standard “FGK UES”. Guidelines for conducting
1979. multifactor accelerated aging tests of polymeric support insulators for
voltage of 110 - 220 kV, 2014.
[3] V. Vdoviko, Partial discharges in the diagnosis of high-voltage
equipment. Novosibirsk, Nauka, 2007.
[4] R. Bartnikas. Partial Discharges, Their Mechanism, Detection and
Measurement // IEEE Trans. on Dielectrics and Electr. Insul., 2002, v.9,
no. 5. C. 763 – 808.
[5] A. Ovsyannikov, A. Kolesnikov, Investigation of the spatio-temporal
characteristics of a corona discharge in air and in oil / Methods and
means of assessment comp. energ equipment. Proceed. Production
quality and reliability of oil-filled equipment, 2002.
[6] Templeton, K Roberts, O Rudolph, P Kakeeto, M D Judd, “Partial
discharge detection and location in power transformers using the UHF
technique”, Proc. Int. Conf. on Condition Monitoring and Diagnostic
Engineering Management of Power Station and Substation Equipment
(Bangalore), Central Power Research Institute, January 2009
[7] J.H. Mason. The deterioration and breakdown of dielectrics resulting
from internal discharges // Proc. IEE - Pt. 1: General, 1951, v. 98 (109).
pp. 44-59.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on November 09,2020 at 07:43:57 UTC from IEEE Xplore. Restrictions apply.