You are on page 1of 50

RENEW SAUR URJA PVT LTD

GURGAON,HARYANA

PROTECTION COORDINATION REPORT

00 Initial Submission 18/12/2016 RC CBR CBR


Approve
Revision Revision Particulars Date Reviewed Checked
d
CLIENT RENEW SAUR URJA PVT LTD

PROJECT 30MWp SPV PROJECT AT MALKANOOR,TELANGANA

CONTRACTOR LARSEN & TOUBRO,NAVI,MUMBAI

CONSULTANT

DOCUMENT ID REPORT NO 08/2016-17 REVISION:  00

No. of Pages (INCLUDING THIS FRONT PAGE)


Contents
Sl.No Descriptiion Page No
1 Executive Summary 3
2 Reference Documents 4
3 Device Details 5
4 Single line diagram 6
5 Short Circuit Current Details 8
6 Transformer Relay Setting Calculations 18
7 Setting Details for Line Control Panel 20
8 Setting Details for Transformer Control Panel 26
9 Setting Details for Feeder Control Panel 31
10 Setting Details for 33 kV Switch Board 38
11 Time Current Characteristic Curves 48

2
Executive Summary
Introduction
Project: 30MWp SPV Project at Malkanoor,Telangana
Owner: Renew Saur Urja Pvt Ltd
Electrical Contractor: L&T, Navi,Mumbai
ElectricalDistribution System 132kV,33 kV,0.380 kV Power Distribution System
Power System Data
Max Source Fault level (assumed) 25kA for 1 secs at 33 kV

Tools used: Paladin Design Base 5- an Electrical Design software


Protection Coordination
Selectivity of relays were worked out based on the rating of
transformers,cable size and flow of short circuit currents.
Time current characterstic curves are generated for every path and
verified .
Input Data
The SLD,Control and Relay panel drawings,Transformer Data sheets
Conclusion
Settings for each device,short circuit currents at every busbars,detailed
calculations for the settings are given in the following pages.

3
Reference Documents / Drawings
Sl.No Details File reference
1 132kV Switchyard SLD SLD_Mulkanoor.pdf
2 33kV ICOG Panel Drawing-400-29.08.16.pdf
3 33kV SwitchBoard Drawing-200-29.08.16.pdf
4 33kV Feeder -1&2 Control & Protection Panel 33KV TWIN FEEDER 1 & 2_REV-B_17.11.2016.pdf
5 132/33kV,25/30MVA Power Transformer Control & Protection Panel 132_33KV,25_30MVA TRANSFORMER CONTROL & PROTECTION PANEL_REV-
6 ACSLD ACSLD FOR FOR 30MW MULKANOOR PROJECT_TELANGANA 31 08 2016-Model.pdf
7 30 MVA,Transformer Data sheets GTP-T-05516-4.pdf
8 132kV Switchyard Single line Diagram RP-5212-DWG-ELE-AC-002-R2-132kV Switchyard SLD.DWG
9 132kV Line Control & Protection Panel 132KV LINE CONTROL & PROTECTION PANEL_REV-B_17.11.2016.pdf
10 Technical Specification of Grid Connected PhotoVoltaic Inverter PVL-L1000E_INVERTER-TECHNICAL.pdf
11 Rated Specification of the Inverter (PVL-L1000E) TMEIC INVERTER-1000KW-DATA SHEET.pdf

4
Device Details
Transformers
Details of Equipment kVA rating High Low voltage Percentage Low winding High winding Grounding Mode Vector Type of Supply Variation on Primary side
Voltage side Impedance Group Cooling
side
Main Power Transformer
Transformer 30000 132000 33000 12.49 Star Star Direct YNyn0 ONAN/ONAF -25% to +5% in 24 steps
Inverter Transformers
5 Winding Transformer 4400 33000 V 380 3.20 Delta Star Direct YND AN
3 Winding Transformer 2200 33000 V 380 3.20 Delta Star Direct YND AN

5
SINGLE LINE DIAGRAM

6
GRID APTRANSCO

LINE RELAYS
50
51

132bus_Grid

132 kV Bus

TR1_RELAYS_HV
50
51

TR_HT-132 BUS

TR1

CAB_TR1_LV

TR1_RELAYS_LV
50
51

33kV BUS-TRafo LV

33 kV Main SWBD (100)

FCP_IC1 508 511 512


50 50 50 50
51 51 51 51

363
CAB_IC1

132
86

362
OG000_SWBD1 OG000_SWBD2
50 50
51 51
icr8-33kv main board

33kV SWBD1 (200) 33kV SWBD2 (200)

IC003_SWBD2
4_TR1-BUS

IC003_SWBD1
50 icr2-33 kv bd icr3-33kv bd 50 510
51 51
497

8_TR1-BUS

9_TR1-BUS
7_TR1-BUS
CAB_IC3

506
ICR1-swbd1

33kV PNL1 33kV 33kV 33kV 33kV


50
(400) 50
PNL2(400) 50
PNL3(400) 50
PNL4(400) 50
PNL5(400)
51 51 51 51 51
IC0G0_PNL2 IC0G0_PNL4 IC0G0_PNL5
IC0G0_PNL1 91 IC0G0_PNL3
ICR4_TR ICR5_TR ICR6_TR ICR7_TR
ICR1_TR ICR2_TR 58 ICR3_TR ICR8_TR

177

319

355
180

322

358
178

320

356
179

321

357

492
400

491
399
250 251 252 253 246 247 248 249 240 241 242 243 232 233 7_TR1 7_TR2 7_TR3 7_TR4 287 292 295 298 323 328 331 334 367 372 477 480
CAB:2_INVR1
CAB_1INVR1

CAB_1INVR2

CAB:2_INVR2

CAB:2_INVR3

CAB:3_INVR1

CAB:3_INVR2

CAB:3_INVR3
CAB_1INVR4

CAB:3_INVR4
CAB_1INVR3

CAB_8INVR1

CAB_8INVR2
CAB:2_INVR4

10_INVR1-TR

10_INVR2-TR

10_INVR3-TR

10_INVR4-TR
167

171

172

173

309

313

314

315

345

349

350

351
UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS
7_INVR1 7 INV3 7 INV4
7_INVR2
4_INVR1 4_INVR2 4_INVR3 4_INVR4 5_INVR1 5_INVR2 5_INVR3 5_INVR4 6_INVR1 6_INVR2 6_INVR3 6_INVR4

10_PV4-INVR4
1_INVR1 1_INVR2 1_INVR3 1_INVR4 2_INVR1 2_INVR2 2_INVR3 2_INVR4 3_INVR1 3_INVR2 3_INVR3 3_INVR4 8_INVR1 8_INVR2

344

352

353

354

10_PV1-INVR1

10_PV2-INVR2

10_PV3-INVR3
166
182

184

186

188

190

192

194

196

198

200

202

204

206

208

174

175

176

308

316

317

318
4_PV2 4_PV3 4_PV4 5_PV2 5_PV3 5_PV4 6_PV2 6_PV3 6_PV4 7_PV2 7 PV4
1_PV1 1_PV2 1_PV3 1_PV4 2_PV1 2_PV2 2_PV3 2_PV4 3_PV1 3_PV2 3_PV3 3_PV4 8_PV11 8PV21 4_PV1 5_PV1 6_PV1 7_PV1 7 PV3

REV. DATE EC O# DWN APP DES CR IPTIO N


THIS DRAWING IS PROPRIETARY INFORMA TION

Your Company Name


Address
Address
Phone and web site

Electrical One-Line Diagram for


System Study

7 DRAWN BY/DATE:
ENG. APP./DATE:
MFG. APP./DATE:
SCALE: DWG SIZE:
DWG No.:

PART No.:
REV.
SHORT CIRCUIT CURRENT DETAILS

8
GRID APTRANSCO

LINE RELAYS
50
51

132bus_Grid

132 kV Bus

TR1_RELAYS_HV
50
51

TR_HT-132 BUS

TR1

CAB_TR1_LV

TR1_RELAYS_LV
50
51

33kV BUS-TRafo LV

33 kV Main SWBD (100)

FCP_IC1 508 511 512


50 50 50 50
51 51 51 51

363
CAB_IC1

132
86

362
OG000_SWBD1 OG000_SWBD2
50 50
51 51
icr8-33kv main board
33kV SWBD1 (200) 33kV SWBD2 (200)
4_TR1-BUS

IC003_SWBD1 IC003_SWBD2
50 icr2-33 kv bd icr3-33kv bd 50 510
51 51
497

8_TR1-BUS

9_TR1-BUS
7_TR1-BUS
CAB_IC3

506
ICR1-swbd1

33kV PNL1 33kV 33kV 33kV 33kV


50
(400) 50
PNL2(400) 50
PNL3(400) 50
PNL4(400) 50
PNL5(400)
51 51 51 51 51
IC0G0_PNL2 IC0G0_PNL4 IC0G0_PNL5
IC0G0_PNL1 91 IC0G0_PNL3
ICR4_TR ICR5_TR ICR6_TR ICR7_TR
ICR1_TR ICR2_TR 58 ICR3_TR ICR8_TR

177

319

355
180

322

358
178

320

356
179

321

357

492
400

491
399
250 251 252 253 246 247 248 249 240 241 242 243 232 233 7_TR1 7_TR2 7_TR3 7_TR4 287 292 295 298 323 328 331 334 367 372 477 480
CAB:2_INVR1
CAB_1INVR1

CAB_1INVR2

CAB:2_INVR2

CAB:2_INVR3

CAB:3_INVR1

CAB:3_INVR2

CAB:3_INVR3
CAB_1INVR4

CAB:3_INVR4
CAB_1INVR3

CAB_8INVR1

CAB_8INVR2
CAB:2_INVR4

10_INVR1-TR

10_INVR2-TR

10_INVR3-TR

10_INVR4-TR
167

171

172

173

309

313

314

315

345

349

350

351
UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS UPS
7_INVR1 7 INV3 7 INV4
7_INVR2
4_INVR1 4_INVR2 4_INVR3 4_INVR4 5_INVR1 5_INVR2 5_INVR3 5_INVR4 6_INVR1 6_INVR2 6_INVR3 6_INVR4

10_PV4-INVR4
1_INVR1 1_INVR2 1_INVR3 1_INVR4 2_INVR1 2_INVR2 2_INVR3 2_INVR4 3_INVR1 3_INVR2 3_INVR3 3_INVR4 8_INVR1 8_INVR2

344

352

353

354

10_PV1-INVR1

10_PV2-INVR2

10_PV3-INVR3
166
182

184

186

188

190

192

194

196

198

200

202

204

206

208

174

175

176

308

316

317

318
4_PV2 4_PV3 4_PV4 5_PV2 5_PV3 5_PV4 6_PV2 6_PV3 6_PV4 7_PV2 7 PV4
1_PV1 1_PV2 1_PV3 1_PV4 2_PV1 2_PV2 2_PV3 2_PV4 3_PV1 3_PV2 3_PV3 3_PV4 8_PV11 8PV21 4_PV1 5_PV1 6_PV1 7_PV1 7 PV3

REV. DATE EC O# DWN APP DES CR IPTIO N


THIS DRAWING IS PROPRIETARY INFORMA TION

Your Company Name


Address
Address
Phone and web site

Flow of Short Circuit Current

9 DRAWN BY/DATE:
ENG. APP./DATE:
MFG. APP./DATE:
SCALE: DWG SIZE:
DWG No.:

PART No.:
REV.
Short Circuit Report
Bus Name : APTRANSCO
Branch Flow ( A ) IEC60909 Method
Fault At Bus: APTRANSCO
System Volt: 132000 Base Volt: 132000 V
Fault Type : Pre Fault 3-phase L-L L-G L-L-G
voltage
Bus R RMS ( A ): 132000 275 0 409 0
Bus Y RMS ( A ): 132000 275 251 0 336
Bus B RMS ( A ): 132000 275 251 0 453
Steady State flow of Current
BRANCH NAME PRE 3 PHASE LL FAULT LG FAULT LLG
FAULT FAULT FAULT
VOLTAGE

GRID - 132KV BUS 132000 275 0 409 0


275 251 0 336
275 251 0 453
132kV BUS - TR_HV SIDE 132000 275 0 409 0
275 251 0 336
275 251 0 453
TR_LV SIDE - MAIN PNL 33000 1098 0 1635 0
1098 1005 0 1344
1098 1005 0 1813
MAIN PNL - SWBD1(200) 33000 439 0 654 0
439 402 0 538
439 402 0 726
MAIN PNL - ICR8_TR 33000 73 0 109 0
73 67 0 90
73 67 0 121
MAIN PNL - SWBD2(200) 33000 439 0 654 0
439 402 0 538
439 402 0 726
MAIN PNL - ICR7_TR 33000 146 0 218 0
146 134 0 179
146 134 0 242
SWBD1(200) - ICR1_TR 33000 146 0 218 0
146 134 0 179
146 134 0 242
SWBD1(200) - ICR2_TR 33000 146 0 218 0
146 134 0 179
146 134 0 242
SWBD1(200) - ICR3_TR 33000 146 0 218 0
146 134 0 179
146 134 0 242
SWBD2(200) - ICR4_TR 33000 146 0 218 0
146 134 0 179
146 134 0 242

10
Steady State flow of Current
BRANCH NAME PRE 3 PHASE LL FAULT LG FAULT LLG
FAULT FAULT FAULT
VOLTAGE

SWBD2(200) - ICR5_TR 33000 146 0 218 0


146 134 0 179
146 134 0 242
SWBD2(200) - ICR6_TR 33000 146 0 218 0
146 134 0 179
146 134 0 242
ICR1_TR - 1_INV1 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR1_TR - 1_INV2 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR1_TR - 1_INV3 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR1_TR - 1_INV4 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR2_TR - 2_INV1 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR2_TR - 2_INV2 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR2_TR - 2_INV3 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR2_TR - 2_INV4 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR3_TR - 3_INV1 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR3_TR - 3_INV2 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR3_TR - 3_INV3 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR3_TR - 3_INV4 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR8_TR - 8_INV1 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239

11
Steady State flow of Current
BRANCH NAME PRE 3 PHASE LL FAULT LG FAULT LLG
FAULT FAULT FAULT
VOLTAGE

ICR8_TR - 8_INV2 380 3179 1679 2732 3030


3179 1679 2732 2246
3179 3358 0 3239
ICR4_TR - 4_INV1 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR4_TR - 4_INV2 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR4_TR - 4_INV3 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR4_TR - 4_INV4 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR5_TR - 5_INV1 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR5_TR - 5_INV2 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR5_TR - 5_INV3 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR5_TR - 5_INV4 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR6_TR - 6_INV1 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR6_TR - 6_INV2 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR6_TR - 6_INV3 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR6_TR - 6_INV4 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR7_TR - 7_INV1 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239

12
Steady State flow of Current
BRANCH NAME PRE 3 PHASE LL FAULT LG FAULT LLG
FAULT FAULT FAULT
VOLTAGE

ICR7_TR - 7_INV2 380 3179 1679 2732 3030


3179 1679 2732 2246
3179 3358 0 3239
ICR7_TR - 7_INV3 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
ICR7_TR - 7_INV4 380 3179 1679 2732 3030
3179 1679 2732 2246
3179 3358 0 3239
1_INV1 - 1_PV1 380 1882 1859 1517 1884
1_INV2 - 1_PV2 380 1882 1859 1517 1884
1_INV3 - 1_PV3 380 1882 1859 1517 1884
1_INV4 - 1_PV4 380 1882 1859 1517 1884
2_INV1 - 2_PV1 380 1882 1859 1517 1884
2_INV2 - 2_PV2 380 1882 1859 1517 1884
2_INV3 - 2_PV3 380 1882 1859 1517 1884
2_INV4 - 2_PV4 380 1882 1859 1517 1884
3_INV1 - 3_PV1 380 1882 1859 1517 1884
3_INV2 - 3_PV2 380 1882 1859 1517 1884
3_INV3 - 3_PV3 380 1882 1859 1517 1884
3_INV4 - 3_PV4 380 1882 1859 1517 1884
4_INV1 - 4_PV1 380 1882 1859 1517 1884
4_INV2 - 4_PV2 380 1882 1859 1517 1884
4_INV3 - 4_PV3 380 1882 1859 1517 1884
4_INV4 - 4_PV4 380 1882 1859 1517 1884
5_INV1 - 5_PV1 380 1882 1859 1517 1884
5_INV2 - 5_PV2 380 1882 1859 1517 1884
5_INV3 - 5_PV3 380 1882 1859 1517 1884
5_INV4 - 5_PV4 380 1882 1859 1517 1884
6_INV1 - 6_PV1 380 1882 1859 1517 1884
6_INV2 - 6_PV2 380 1882 1859 1517 1884
6_INV3 - 6_PV3 380 1882 1859 1517 1884
6_INV4 - 6_PV4 380 1882 1859 1517 1884
7_INV1 - 7_PV1 380 1882 1859 1517 1884
7_INV2 - 7_PV2 380 1882 1859 1517 1884
7_INV3 - 7_PV3 380 1882 1859 1517 1884
7_INV4 - 7_PV4 380 1882 1859 1517 1884
8_INV1 - 8_PV1 380 1882 1859 1517 1884
8_INV2 - 8_PV2 380 1882 1859 1517 1884

13
Residual Voltage Summary Results: 0.5 Cycle--Symmetrical
Fault At Bus : APTRANSCO
3 Phase Fault
Bus Name Pre Fault voltage Residual voltage in
in Volts Volts
APTRANSCO 132000 0
132 kV Bus 132000 0
33 kV Main SWBD (100) 33000 4684
33kV SWBD1 (200) 33000 4685
33kV SWBD2 (200) 33000 4686
1_INVR1 380 72
1_INVR2 380 72
1_INVR3 380 72
1_INVR4 380 72
2_INVR1 380 72
2_INVR2 380 72
2_INVR3 380 72
2_INVR4 380 72
3_INVR1 380 72
3_INVR2 380 72
3_INVR3 380 72
3_INVR4 380 72
4_INVR1 380 72
4_INVR2 380 72
4_INVR3 380 72
4_INVR4 380 72
5_INVR1 380 72
5_INVR2 380 72
5_INVR3 380 72
5_INVR4 380 72
6_INVR1 380 72
6_INVR2 380 72
6_INVR3 380 72
6_INVR4 380 72
7_INVR1 380 72
7_INVR2 380 72
7_INVR3 380 72
7_INVR4 380 72
8_INVR1 380 72
8_INVR2 380 72

14
Residual Voltage Summary Results: 0.5 Cycle--Symmetrical
Fault At Bus : APTRANSCO
LL Fault
Bus Name Pre Fault voltage Residual voltage in
in Volts Volts
APTRANSCO 132000 71801
132 kV Bus 132000 71801
33 kV Main SWBD (100) 33000 17950
33kV SWBD1 (200) 33000 17950
33kV SWBD2 (200) 33000 17950
1_INVR1 380 211
1_INVR2 380 211
1_INVR3 380 211
1_INVR4 380 211
2_INVR1 380 211
2_INVR2 380 211
2_INVR3 380 211
2_INVR4 380 211
3_INVR1 380 211
3_INVR2 380 211
3_INVR3 380 211
3_INVR4 380 211
4_INVR1 380 211
4_INVR2 380 211
4_INVR3 380 211
4_INVR4 380 211
5_INVR1 380 211
5_INVR2 380 211
5_INVR3 380 211
5_INVR4 380 211
6_INVR1 380 211
6_INVR2 380 211
6_INVR3 380 211
6_INVR4 380 211
7_INVR1 380 211
7_INVR2 380 211
7_INVR3 380 211
7_INVR4 380 211
8_INVR1 380 211
8_INVR2 380 211

15
Residual Voltage Summary Results: 0.5 Cycle--Symmetrical
Fault At Bus : APTRANSCO
LGFault
Bus Name Pre Fault voltage Residual voltage in
in Volts Volts
APTRANSCO 132000 0
132 kV Bus 132000 0
33 kV Main SWBD (100) 33000 5792
33kV SWBD1 (200) 33000 5796
33kV SWBD2 (200) 33000 5798
1_INVR1 380 68
1_INVR2 380 68
1_INVR3 380 68
1_INVR4 380 68
2_INVR1 380 68
2_INVR2 380 68
2_INVR3 380 68
2_INVR4 380 68
3_INVR1 380 68
3_INVR2 380 68
3_INVR3 380 68
3_INVR4 380 68
4_INVR1 380 68
4_INVR2 380 68
4_INVR3 380 68
4_INVR4 380 68
5_INVR1 380 68
5_INVR2 380 68
5_INVR3 380 68
5_INVR4 380 68
6_INVR1 380 68
6_INVR2 380 68
6_INVR3 380 68
6_INVR4 380 68
7_INVR1 380 68
7_INVR2 380 68
7_INVR3 380 68
7_INVR4 380 68
8_INVR1 380 68
8_INVR2 380 68

16
Residual Voltage Summary Results: 0.5 Cycle--Symmetrical
Fault At Bus : APTRANSCO
LLGFault
Bus Name Pre Fault voltage Residual voltage in
in Volts Volts
APTRANSCO 132000 36974
132 kV Bus 132000 36974
33 kV Main SWBD (100) 33000 11122
33kV SWBD1 (200) 33000 11120
33kV SWBD2 (200) 33000 11120
1_INVR1 380 124
1_INVR2 380 124
1_INVR3 380 124
1_INVR4 380 124
2_INVR1 380 124
2_INVR2 380 124
2_INVR3 380 124
2_INVR4 380 124
3_INVR1 380 124
3_INVR2 380 124
3_INVR3 380 124
3_INVR4 380 124
4_INVR1 380 124
4_INVR2 380 124
4_INVR3 380 124
4_INVR4 380 124
5_INVR1 380 124
5_INVR2 380 124
5_INVR3 380 124
5_INVR4 380 124
6_INVR1 380 124
6_INVR2 380 124
6_INVR3 380 124
6_INVR4 380 124
7_INVR1 380 124
7_INVR2 380 124
7_INVR3 380 124
7_INVR4 380 124
8_INVR1 380 124
8_INVR2 380 124

17
Transformers Relay Setting Calculations
Setting Calculation for Power Transformers

132kV 33kV
CTHV:200/1 CT LV:600/1 A
30 MVA
Transformer capacity PT 30000 kVA
Primary Voltage Vp 132 kV
Secondary Voltage Vs 33 kV
Transformer HV side CT details CTHV 200/1
Turns Ratio CTR1 200
Transformer LV side CT details CTLV 600/1
Turns Ratio CTR2 600
Percentage Impedance of Transformer Z 12.50%
Fault Current at 33 kV Bus (Grid operation) 9274 A
Fault current at 132kV Bus as per report (Grid operation) 35502 A
Transformer Full Load HV side Primary Current at 0% tapping Ipfl 30000X 1000 )/ (1.732 Amps
X132x1000x1)
Transformer HV side current as per name plate 131.22 Amps
Relay drop off Ratio 0.95
HV Pick up Current 1.05 x HV Currrent/ Drop off ratio
=1.05x 131.21/0.95
145.03
Transformer HV side CT Secondary Pick up Current Isfl 0.73
IDMT setting at 132 kV side 0.7
Setting proposed on HV side Ip 0.7
Curve Normal Inverse
Transformer Full Load LV side Current at 0% tapping 30000X 1000 )/ (1.732 Amps
X33x1000x1)
Transformer LV side Primary current as per name plate 524.88 Amps
Relay drop off Ratio 0.95
LV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x 437.40/0.95
607.75
Transformer LV side CT Secondary Pick up Current Isfl 1.01
IDMT setting at 33 kV side 1
Setting proposed on LV side Ip 1
Curve Normal Inverse

18
Setting Calculation for Inverter Transformers

33kV 0.380kV
CTHV:100/1
4.4MVA
Transformer capacity PT 4400 kVA
Primary Voltage Vp 33 kV
Secondary Voltage Vs 0.38 kV
Transformer HV side CT details CTHV 80/1
Turns Ratio CTR1 80
Transformer HV side CT details CTLV 600/1
Turns Ratio CTR2 600
Percentage Impedance of Transformer Z 3.20%
Fault Current at 0.380 kV Bus (Grid operation) 9274 A
Fault current at 33 kV Bus as per report (Grid operation) 35502 A
Transformer Full Load HV side Primary Current at 0% tapping Ipfl 4400X 1000 )/ (1.732 Amps
X33x1000x1)
Transformer HV side current as per name plate 76.98 Amps
Relay drop off Ratio 0.95
HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x 76.98/0.95
89.14
Transformer HV side CT Secondary Pick up Current Isfl 1.10
IDMT setting at 33kV side 1.1
Setting proposed on HV side Ip 1.1
Curve Normal Inverse

19
SETTING DETAILS FOR LINE CONTROL PANEL

20
Setting Details for 132kV ,Line Control & Protection Panel
Line Protection
Relay settings for relays located in the Protection Panel
Relay Located in Protection Panel MiCOM P543 Multi Function Relay
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 87
Function 21
Function 99-LV
Other functions are disabled
• Power System Data 1
CT Ratio on 132 kV side 300/1:In=300
PT Ratio 132 kV/√ 3 : 110V/√ 3
Line Differential Protection 87
Parameter Function Value (Range) Set Value Set unit Primary
Value
Diff.Prot ON/OFF ON
Differential Current Monitoring I-Diff> Mon ON/OFF ON
Pick up value of differential current I-diff> 0.05..2 I/InO 0.2
T I-diff> time delay T I-diff> 0.00..60.00 s 0 sec
Pick up value of High set trip I-diff>> 0.5..35 I/InO 8
T I-diff>> time delay T I-diff>> 0.00..60.00 s 0 sec
Slope 1 of tripping charecterstic Slope 1 0.1..0.5 0.2
Base point for slope1 of charecterstic Base point 1 0.00..2 I/InO 0
Slope 2 of tripping charecterstic Slope 2 0.25..0.95 0.7
Base point for slope2 of charecterstic Base point 2 0.00..10 I/InO 4.5
Pick up for add on stablisation I Add on stab 2..15 I/InO 4
Duration for add on stablisation T Add on stab 2..250 Cycles 15

21
Distance Protection 21
Parameter Unit Parameter Range Settings
kV Unom PRIMARY in kV 1.0 .. 1200.0 kV 132
V Unom Secondary in Volts 80..125 110
A CT Primary in Amps 10~5000 300
A CT Secondary in Amps 1A/5A 1
SystemStarpoint Solid Earthed Solid
Peterson-Coil Isolated Earthed
Uph / Udelta 0.10 .. 9.99 1.73
Rated Frequency 50/60 Hz 50 Hz
Phase Seq L1 L2 L3 L1 L2 L3
L1 L3 L2
Distance Unit km/Miles km
kV Full scale volt 1.0~1200 132
A Full scale Current 10~5000 300
deg Line Angle 10~89 deg 55.45
P,Q sign Not reversed not
Reversed reversed
ohms/km R 0.168
ohms/km x1 0.0050~9.5 0.44
mfd / km c' 0.0~100 0.0081
km Line length 0.1~1000 18
ZL1 mag Ohms Line Positive Sequence impedance (mag) 5.33
ZL1 ang deg Line Positive Sequence impedance (Phase angle ) 55.45
ZL0 mag Ohms Line Zero Sequence impedance (mag) 13.719
ZL0 ang deg Line Zero Sequence impedance (Phase angle ) 70.8
KZ0 mag Ohms Default residual compensation factor (mag) 0.543
KZ0 ang deg Default residual compensation factor (Phase angle) 24.77
Z1mag Ohms Zone 1 reach impedance setting (mag) 1.06
Z1ang deg Zone 1 reach impedance setting (Phase angle) 55.45
Z2mag Ohms Zone 2 reach impedance setting (mag) 1.599
Z2ang deg Zone 2 reach impedance setting (Phase angle) 55.45
Z3mag Ohms Zone 3 reach impedance setting (mag) 2.66
Z3ang deg Zone 3 reach impedance setting (Phase angle) 55.49
Z4mag Ohms Zone 4 reach impedance setting (mag) 0.266
Z4ang deg Zone 4 reach impedance setting (Phase angle) 55.45
R1 Ph max Ohms Phase fault resistive reach value 0.7
R1 Ph min Ohms Phase fault resistive reach value 2.1
R1ph sec Time delay Zone 1 0
R2ph sec Time delay Zone 2 0.4
TZ1 sec Time delay Zone 3 0.8
TZ2 sec Time delay Zone 4 0.25
R1G Ohms Ground fault resistive reach value zone 1 4
R2G Ohms Ground fault resistive reach value zone 2 5.3
Zone 1 Z1 0.605+J0.878
Z0 0.900+j2.592
Zone 2 Z1 0.907+J1.318
Z0 1.35+j3.88
Zone 3 Z1 1.512+J2.196
Z0 2.25+j6.48
Zone 4 Z1 0.151+J0.220
Z0 0.225+j0.648

22
Relay settings for relays located in the Protection Panel
Bay Control Unit
Relay Located in Protection Panel MiCOM C264P Multi Function Relay
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50
Function 51
Function 50N
Function 51N
Function 67
Function 67N
Function 59
Other functions are disabled
• Power System Data 1
CT Ratio on 132 kV side 300/1:In=300
PT Ratio 132 kV/√ 3 : 110V/√ 3
• Non Directional Phase over current Protection: 51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.5 x In 450
50-2 Delay T I>> 0.00..150.00 s 0.15 s
51-1Pickup I> 0.01~8.00A 0.45 x In 135
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.05 s
IEC Curve Standard Inverse(SI) ,Very Standard Inverse
Inverse(VI) ,Extremely
Inverse(EI)
• Non Directional Ground over current Protection: 51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 1 x In 200
50N-2 Delay Te>>>> 0.00..150.00 s 0.3 s
51N-1Pickup Ie> 0.01~8.00A 0.08 x In 16
51N-1Delay TIe> 0.00..150.00 s NA s
Time dial Ie> TMS 0.02~1.5 0.07
IEC Curve Standard Inverse(SI) ,Very Standard Inverse
Inverse(VI) ,Extremely
Inverse(EI)
• Directional Phase over current Protection: 67
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.5 x In 450
50-2 Delay T I>> 0.00..150.00 s 0.15 s
51-1Pickup I> 0.1~40.00 A 0.45 x In 135
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.05 s
IEC Curve Standard Inverse(SI) ,Very Standard Inverse
Inverse(VI) ,Extremely
Inverse(EI)
• Directional Ground over current Protection: 67 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 1 x In 200
50N-2 Delay Te>>>> 0.00..150.00 s 0.3 s
51N-1Pickup Ie> 0.1~40.00 A 0.08 x In 16
51N-1Delay TIe> 0.00..150.00 s NA s
Time dial Ie> TMS 0.02~1.5 0.07
IEC Curve Standard Inverse(SI) ,Very Standard Inverse
Inverse(VI) ,Extremely
Inverse(EI)
• Over voltage Protction 59
Setting name Units Range Setting unit Prim Value
V>= Voltage set Stage 1 5-200 V 121 Volts 145.2
tV> delay Delay stage 1 0-599 2 sec
V>>= Voltage set Stage 2 5-200 V 126.5 Volts 151.8
tV>> delay Delay stage 1 0-599 0.5 sec

23
Distance Relay Setting Calculations
Name of Substation = 132 kV Mulkanoor SS S/S

Mulkanoor SS APTRANSCO SS
18 km

CTR = 300 / 1 300


PTR = 132000 / 110 1200
Protected Line parameters:
Per kilometer
Line Z1 = 0.168 + j 0.244 = 0.29624 55.45 per km

Zero seq Z0 = 0.25 + j 0.72 = 0.76217 70.85 per km


Line distance Mulkanoor SS to 18 km
APTRANSCO SS

MULKANOOR SS to APTRANSCO SS
Line parameters
Z1 18 x(0.168+j0.244)
3.024 + j 4.392 = 5.33238 55.45

Z0 18 x(0.25+j0.72)
4.5 + j 12.96 = 13.719 70.85

Zone 1 reach = 80 % of protected line


Zone 2 reach = 120 % of protected line
Zone 3 reach = 200 % of protected line
Zone 4 reach = 20 % of protected line
Ratio of Secondary to Primary Impedance =CTR/PTR = 0.250
Zone 1 Phase Reach Settings

Required Zone 1 reach = 80 % of Protected line length x Z1 x CTR/PTR


0.8 x(3.024+j4.392)x 0.250
0.605 + j 0.878 = 1.06648 55.45

Zero seq Zone 1 reach 80 % of Protected line length x Z0 x CTR/PTR


0.8 x(4.5+j12.96)x 0.250
0.900 + j 2.592 = 2.7438 70.85

Required Zone2 reach = 120 % of Protected line length x Z1 x CTR/PTR


1.2 x(3.024+j4.392)x 0.250
0.907 + j 1.318 = 1.59971 55.45

Zero seq Zone 2 reach 120 % of Protected line length x Z0 x CTR/PTR


1.2 x(4.5+j12.96)x 0.250
1.350 + j 3.8880 = 4.11571 70.85

Required Zone 3 reach = 200 % of Protected line length x Z1 x CTR/PTR


2 x(3.024+j4.392)x 0.250
1.512 + j 2.196 = 2.66619 55.45

Zero seq Zone3 reach 200 % of Protected line length x Z0 x CTR/PTR


2x(4.5+j12.96)x 0.250
2.250 + j 6.480 = 6.85951 70.85

Required Zone4 reach = 20 % of Protected line length x Z1 x CTR/PTR

24
0.2 x(3.024+j4.392)x 0.250
0.151 + j 0.220 = 0.26662 55.45

Zero seq Zone 4 reach 20 % of Protected line length x Z0 x CTR/PTR


0.2 x(4.5+j12.96)x 0.104
0.225 + j 0.648 = 0.68595 70.85

max load on line 131.22 Amps


system voltage 132 kV
Z load 580.7992 Ohms
Z load Sec 145.1998
angle 25 deg
line

Resistive Reach Calculations

All distance elements must avoid the heaviest system loading. Taking the 1 A CT
secondary rating as a guide to the maximum load current, the minimum load impedance
presented to the relay would be: Vn (phase-neutral) / In = 132 /3 1
= 76.21024

Typically, phase fault distance zones would avoid the minimum load impedance by a
margin of ≥40% if possible (bearing in mind that the power swing characteristic
surrounds the tripping zones), earth fault zones would use a ≥20% margin. This
allows maximum resistive reaches of 45.72614 for Phase faults
& 60.96819 for Earth faults
Taking a required primary resistive coverage of 7 Ω for phase faults,
and assuming a typical earth fault coverage of 20 Ω, for earth faults
the minimum secondary reaches become:
RPh (min) = 7 x 0.25 1.8 Ω (secondary);
RG (min) = 20 x 0.25 5 Ω (secondary).
RPh (max) = 46 x 0.25 11 Ω (secondary);
RG (max) = 61 x 0.25 15 Ω (secondary).
Resistive reaches could be chosen between the calculated values as shown in Table
The zone 2 elements satisfy R2Ph ≤ (R3Ph x 80%), and R2G ≤ (R3G × 80%).

25
SETTING DETAILS FOR TRANSFORMER
CONTROL PANEL

26
Setting Details for 132/33 kV ,25/30 MVA Power Transformer -Control & Protection Panel
Transformer Feeder protection for Power Transformer
Relay settings for relays located in the Protection Panel +1TR1A
Differential Protection Relay-87T/64R
Relay Located in Protection Panel +1TR1A MiCOM P643 Multi Function Relay
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 87
Function 64R
Function 99-LV
Other functions are disabled
• Power System Data 1
CT Ratio on 33 kV side 600/1:In=600
CT Ratio on 132 kV side 200/1:In=200
CT Ratio for LV NCT LV 750/1:In=750
CT Ratio for HV NCT HV 200/1:In=200
PT Ratio 33 kV/√ 3 : 110V/√ 3
Transformer Differential Protection 87
Setting name Units Range Setting unit Prim Value
DIFF: Idiff> SGx 0.10 Iref - 2.50 Iref 0.10 Iref x Iref
DIFF: Idiff>> SGx 30.0 Iref 0.1 Iref 2.5 Iref-30.0 Iref 4.0 Iref x Iref
DIFF: Idiff>>> SGx Blocked/ 2.5 Iref - 30.0 Iref 4 x Iref
DIFF: m1 SGx 0.10 - 1.50 0.30
DIFF: m2 SGx 0.10 - 1.50 0.8
DIFF: IR, m2 SGx 1.5 Iref - 10.0 Iref 4.0 Iref x Iref
DIFF: Op.del., trip sig. SGx 0.00 s -100.00 s 0.00 s sec
Is2 1 x Iref
IS-HS1 4 x Iref
IS-HS2 4 I ref
2nd harmonic Block Enabled
Ih(2)%> 10 %
5nd harmonic Block Enabled
Ih(5)%> 20 %
Restricted Earth fault Protection 64R
IREF > K1 Blocked/ 0.05 In -1.00 In 0.1 x In 20
t ref > Time delay Blocked/ 0.00 s - 10.00 s 0
Over Flux Protection LV
Setting name Units Range Setting unit Prim Value
State of the Overflux Protection ON
Pick up Value Warning Stage U/f 1.0~1.2 1.1 V/Hz
Time delay for Warning Stage U/f 0~60 sec 1 sec
V/Hz >1 Status Enabled
V/Hz >1 Trip Func IDMT
V/Hz >1 Trip Set 2.53V/Hz V/Hz
V/Hz >1 Trip TMS 0.1
V/Hz >1 tReset 0 sec
Tpre-Trip Alarm 1.0~1.4 200 sec
Time for cooldown 0~1000 sec 45
Adaption Factors 0.5~2.0 1

27
SEF & Over Fluxing Protection -99HV/51N
Relay Located in Protection Panel +1TR1A MiCOM P642 Multi Function Relay
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 51N
Function 99-HV
Other functions are disabled
• Power System Data 1
CT Ratio for LV NCT LV 750/1:In=750
CT Ratio for HV NCT HV 200/1:In=200
PT Ratio 132 kV/√ 3 : 110V/√ 3
Standby Earth Fault Protection 51N HV
Setting name Units Range Setting unit Prim Value
IN 1 > 1 Current Set Blocked/ 0.08 In - 4.00 In 0.1 x In 20
IN 1 > 1 Function IEC Curve Definite Time IEC Definite Time
Standard Inverse IEC
Very Inverse IEC Extr.
Inverse IEC Long Time
Inv. IEEE Moderately Inv.
IEEE Very Inverse IEEE
Extr. Inverse ANSI
Normally Inv. ANSI Short
Time Inv. ANSI Long
Time Inv. RI-Type
Inverse RXIDG-Type
Inverse -
IN 1 > 1 TMS 0.025 - 1.2 1 sec
Standby Earth Fault Protection 51N LV
IN 1 > 1 Current Set Blocked/ 0.08 In - 4.00 In 0.1 x In 75
IN 1 > 1 Function IEC Curve Definite Time IEC Definite Time
Standard Inverse IEC
Very Inverse IEC Extr.
Inverse IEC Long Time
Inv. IEEE Moderately Inv.
IEEE Very Inverse IEEE
Extr. Inverse ANSI
Normally Inv. ANSI Short
Time Inv. ANSI Long
Time Inv. RI-Type
Inverse RXIDG-Type
Inverse -
IN 1 > 1 TMS 0.025 - 1.2 1 sec
Over Flux Protection HV
Setting name Units Range Setting unit Prim Value
State of the Overflux Protection ON
Pick up Value Warning Stage U/f 1.0~1.2 1.1 V/Hz
Time delay for Warning Stage U/f 0~60 sec 1 sec
V/Hz >1 Status Enabled
V/Hz >1 Trip Func IDMT
V/Hz >1 Trip Set 2.53V/Hz V/Hz
V/Hz >1 Trip TMS 0.1
V/Hz >1 tReset 0 sec
Tpre-Trip Alarm 1.0~1.4 200 sec
Time for cooldown 0~1000 sec 45
Adaption Factors 0.5~2.0 1

28
Relay settings for relays located in the Protection Panel +1TR1A
Bay Control Unit for HV -BCPU HV
Relay Located in Protection Panel +1TR1A MiCOM C264P Multi Function Relay
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50
Function 51
Function 50N
Function 51N
Function 50BF
Other functions are disabled
• Power System Data 1
CT Ratio on 132 kV side 200/1:In=200
PT Ratio 132 kV/√ 3 : 110V/√ 3
• Non Directional Phase over current Protection: 51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.5 x In 300
50-2 Delay T I>> 0.00..150.00 s 0.3 s
51-1Pickup I> 0.01~8.00A 0.7 x In 140
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.06 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Non Directional Ground over current Protection: 51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 1 x In 200
50N-2 Delay Te>>>> 0.00..150.00 s 0.3 s
51N-1Pickup Ie> 0.01~8.00A 0.1 x In 20
51N-1Delay TIe> 0.00..150.00 s NA s
Time dial Ie> TMS 0.02~1.5 0.13
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)
Breaker Failure Protectiion 50 BF
Setting name Units Range Setting unit Prim Value
CB Fail 1 Status Enabled/Disabled Enabled
CB Fail 1 Timer 0-10 0.05 sec
I< Current Set 5%
CB Fail 2 Status Enabled/Disabled Enabled
CB Fail 2 Timer 0-10 0.2 sec
I< Current Set 10 %

29
Relay settings for relays located in the Protection Panel +1TR1B
Bay Control Unit for LV -BCPU LV
Relay Located in Protection Panel +1TR1B MiCOM C264P Multi Function Relay
CT Ratio on 33kV side 600/1:In=600
33000V Outgoing to Transformer
Relay type: Schneider Electric C 264P
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 600A
CT rated secondary 1A/5A 1A
• Non Directional Phase over current Protection: 51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 2.1 x In 1260
50-2 Delay T I>> 0.00..150.00 s 0.45 s
51-1Pickup I> 0.01~8.00A 1 x In 600
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.07 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Non Directional Ground over current Protection: 51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 1 x In 600
50N-2 Delay Te>>>> 0.00..150.00 s 0.45 s
51N-1Pickup Ie> 0.01~8.00A 0.1 x In 60
51N-1Delay TIe> 0.00..150.00 s NA s
Time dial Ie> TMS 0.02~1.5 0.21
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

30
SETTING DETAILS FOR FEEDER
CONTROL PANEL

31
Setting Details for 33 kV ,Feeder 1 & 2-Control & Protection Panel
Incomer from Array Yard 1
CT Ratio on 33kV side 250/1:In=250
33000V Incomer 1 12 MW block
Relay type: Schneider Electric C 264P
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 250A
CT rated secondary 1A/5A 1A
• Non Directional Phase over current Protection: 51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.8 x In 450
50-2 Delay T I>> 0.00..150.00 s 0.6 s
51-1Pickup I> 0.1~40.00 A 0.9 x In 225
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.08 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Non Directional Ground over current Protection: 51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 0.9 x In 225
50N-2 Delay Te>>>> 0.00..150.00 s 0.6 s
51N-1Pickup Ie> 0.1~40.00 A 0.09 x In 22.5
51N-1Delay TIe> 0.00..150.00 s NA s
Time dial Ie> TMS 0.02~1.5 0.3
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)
• Directional Phase over current Protection: 67
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.8 x In 450
50-2 Delay T I>> 0.00..150.00 s 0.6 s
50-1Pickup I> 0.01~8.00A 0.9 x In 225
50-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.08 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

32
Incomer from Array Yard 2
CT Ratio on 33kV side 250/1:In=250
33000V Incomer 2 12MW block
Relay type: Schneider Electric C 264P
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 250A
CT rated secondary 1A/5A 1A
• Non Directional Phase over current Protection: 51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.8 x In 450
50-2 Delay T I>> 0.00..150.00 s 0.6 s
51-1Pickup I> 0.1~40.00 A 0.9 x In 225
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.08 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Non Directional Ground over current Protection: 51 N


Setting name Units Range Setting unit

Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 0.9 x In 225
50N-2 Delay Te>>>> 0.00..150.00 s 0.6 s
51N-1Pickup Ie> 0.1~40.00 A 0.09 x In 22.5
51N-1Delay TIe> 0.00..150.00 s NA s
Time dial Ie> TMS 0.02~1.5 0.3
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Directional Phase over current Protection: 67


Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.8 x In 450
50-2 Delay T I>> 0.00..150.00 s 0.6 s
50-1Pickup I> 0.1~40.00 A 0.9 x In 225
50-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.08 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

33
Setting Details for 33 kV ,Feeder 3 & 4-Control & Protection Panel
Incomer from ICR 7
CT Ratio on 33kV side 100/1:In=100
33000V Incomer 3 4 MW block
Relay type: Schneider Electric C 264P
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 100A
CT rated secondary 1A/5A 1A
• Non Directional Phase over current Protection: 51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.6 x In 160
50-2 Delay T I>> 0.00..150.00 s 0.6 s
51-1Pickup I> 0.1~40.00 A 0.8 x In 80
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.09 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Non Directional Ground over current Protection: 51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 0.8 x In 80
50N-2 Delay Te>>>> 0.00..150.00 s 0.6 s
51N-1Pickup Ie> 0.1~40.00 A 0.08 x In 8
51N-1Delay TIe> 0.00..150.00 s NA s
Time dial Ie> TMS 0.02~1.5 0.3
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Directional Phase over current Protection: 67


Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.6 x In 160
50-2 Delay T I>> 0.00..150.00 s 0.6 s
50-1Pickup I> 0.1~40.00 A 0.8 x In 80
50-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.09 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

34
Incomer from ICR 8
CT Ratio on 33kV side 50/1:In=50
33000V Incomer 4 2 MW block
Relay type: Schneider Electric C 264P
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 50A
CT rated secondary 1A/5A 1A
• Non Directional Phase over current Protection: 51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.6 x In 80
50-2 Delay T I>> 0.00..150.00 s 0.6 s
51-1Pickup I> 0.1~40.00 A 0.8 x In 40
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.09 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Non Directional Ground over current Protection: 51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 0.8 x In 40
50N-2 Delay Te>>>> 0.00..150.00 s 0.6 s
51N-1Pickup Ie> 0.1~40.00 A 0.08 x In 4
51N-1Delay TIe> 0.00..150.00 s NA s
Time dial Ie> TMS 0.02~1.5 0.3
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Directional Phase over current Protection: 67


Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.6 x In 80
50-2 Delay T I>> 0.00..150.00 s 0.6 s
50-1Pickup I> 0.1~40.00 A 0.8 x In 40
50-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.09 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

35
Setting Details for 33 kV ,Feeder 5 & 6-Control & Protection Panel
Spare
CT Ratio on 33kV side 250/1:In=250
33000V Incomer 1 12 MW block
Relay type: Schneider Electric C 264P
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 250A
CT rated secondary 1A/5A 1A
• Non Directional Phase over current Protection: 51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.8 x In 450
50-2 Delay T I>> 0.00..150.00 s 0.6 s
51-1Pickup I> 0.1~40.00 A 0.9 x In 225
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.08 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Non Directional Ground over current Protection: 51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 0.9 x In 225
50N-2 Delay Te>>>> 0.00..150.00 s 0.6 s
51N-1Pickup Ie> 0.1~40.00 A 0.09 x In 22.5
51N-1Delay TIe> 0.00..150.00 s NA s
Time dial Ie> TMS 0.02~1.5 0.3
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Directional Phase over current Protection: 67


Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 1.8 x In 450
50-2 Delay T I>> 0.00..150.00 s 0.6 s
50-1Pickup I> 0.1~40.00 A 0.9 x In 225
50-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.08 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

36
Outgoing to Auxiliary Transformer
CT Ratio on 33kV side 30/1:In=30
33000V outgoing to 63 kVA Transformer
Relay type: Schneider Electric C 264P
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 30A
CT rated secondary 1A/5A 1A
• Non Directional Phase over current Protection: 51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.1~40.00 A 0.8 x In 24
50-2 Delay T I>> 0.00..150.00 s 0.6 s
51-1Pickup I> 0.1~40.00 A 0.04 x In 1.2
51-1Delay tI> 0.00..150.00 s NA s
Time dial I> TMS 0.02~1.5 0.07 s
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

• Non Directional Ground over current Protection: 51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.1~40.00 A 0.1 x In 3
50N-2 Delay Te>>>> 0.00..150.00 s 0.1 s
51N-1Pickup Ie> 0.1~40.00 A 0.01 x In 0.3
51N-1Delay TIe> 0.00..150.00 s 0.07 s
Time dial Ie> TMS 0.02~1.5 DT
IEC Curve Standard Inverse(SI) Standard Inverse
,Very Inverse(VI)
,Extremely Inverse(EI)

37
SETTING DETAILS FOR 33kV SWITCHBOARD

38
33kV,630 A,26.3kA /3 sec, Switch Board 1 (Item No 200)
Incomer from Inverter Transformer ICR 1
Relay Located in Switch Board Panel 1-IC003
CT Ratio on 33kV side 80/1:In=80
33000V Incomer ICR 4 MW block
Relay type: Siemens 7SR1003
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 80A
CT rated secondary 1A/5A 1A
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.005 to 5 2 x In 160
50-2 Delay T I>> 0.00..14400 s 0.9 s
51-1Pickup I> 0.05,0.06,..4 1 x In 80
51-1Delay tI> 0.00..14400 s NA s
Time dial I> TMS 0.01,0.025..1.6,1.7,..100 0.12 s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL

• Ground over current Protection: 50N/51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.005 to 5 1 x In 80
50N-2 Delay Te>>>> 0.00..14400s 0.9 s
51N-1Pickup Ie> 0.05,0.06,..4 0.1 x In 8
51N-1Delay TIe> 0.00..14400s NA s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
Time dial Ie> TMS 0.01,0.025..1.6,1.7,..100 0.44

39
Outgoing to 33 kV Switch Board
Relay Located in Switch Board Panel 2-OG000
CT Ratio on 33kV side 250/1:In=250
Relay type: Siemens 7SR1003
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 250A
CT rated secondary 1A/5A 1A
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.005 to 5 1.8 x In 450
50-2 Delay T I>> 0.00..14400s 0.75 s
51-1Pickup I> 0.05,0.06,..4 1 x In 250
51-1Delay tI> 0.00..14400s NA s
Time dial I> TMS 0.01,0.025..1.6,1.7,..100 0.08 s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL

• Ground over current Protection: 50N/51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.005 to 5 1 x In 250
50N-2 Delay Te>>>> 0.00..14400s 0.75 s
51N-1Pickup Ie> 0.05,0.06,..4 0.1 x In 25
51N-1Delay TIe> 0.00..14400s NA s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
Time dial Ie> TMS 0.01,0.025..1.6,1.7,..100 0.36

40
33kV,630 A,26.3kA /3 sec, Switch Board 2 (Item No 200)
Incomer from Inverter Transformer ICR 4
Relay Located in Switch Board Panel 1-IC003
CT Ratio on 33kV side 80/1:In=80
33000V Incomer ICR 4 MW block
Relay type: Siemens 7SR1003
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 80A
CT rated secondary 1A/5A 1A
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.005 to 5 2 x In 160
50-2 Delay T I>> 0.00..14400 s 0.9 s
51-1Pickup I> 0.05,0.06,..4 1 x In 80
51-1Delay tI> 0.00..14400 s NA s
Time dial I> TMS 0.01,0.025..1.6,1.7,..100 0.12 s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
• Ground over current Protection: 50N/51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.005 to 5 1 x In 80
50N-2 Delay Te>>>> 0.00..14400s 0.9 s
51N-1Pickup Ie> 0.05,0.06,..4 0.1 x In 8
51N-1Delay TIe> 0.00..14400s NA s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
Time dial Ie> TMS 0.01,0.025..1.6,1.7,..100 0.44

41
Outgoing to 33 kV Switch Board
Relay Located in Switch Board Panel 2-OG000
CT Ratio on 33kV side 250/1:In=250
Relay type: Siemens 7SR1003
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 250A
CT rated secondary 1A/5A 1A
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.005 to 5 1.8 x In 450
50-2 Delay T I>> 0.00..14400s 0.75 s
51-1Pickup I> 0.05,0.06,..4 1 x In 250
51-1Delay tI> 0.00..14400s NA s
Time dial I> TMS 0.01,0.025..1.6,1.7,..100 0.08 s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
• Ground over current Protection: 50N/51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.005 to 5 1 x In 250
50N-2 Delay Te>>>> 0.00..14400s 0.75 s
51N-1Pickup Ie> 0.05,0.06,..4 0.1 x In 25
51N-1Delay TIe> 0.00..14400s NA s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
Time dial Ie> TMS 0.01,0.025..1.6,1.7,..100 0.36

42
33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR2
Incomer from Inverter Transformer
Relay Located in Switch Board Panel 1-IC0G0
CT Ratio on 33kV side 80/1:In=80
33000V Incomer ICR2 4 MW block
Relay type: Siemens 7SR1003
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 80A
CT rated secondary 1A/5A 1A
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.005 to 5 2 x In 160
50-2 Delay T I>> 0.00..14400 s 0.9 s
51-1Pickup I> 0.05,0.06,..4 1 x In 80
51-1Delay tI> 0.00..14400 s NA s
Time dial I> TMS 0.01,0.025..1.6,1.7,..100 0.12 s

IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI


MI,VI,EI, & DTL

• Ground over current Protection: 50N/51 N


Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.005 to 5 1 x In 300
50N-2 Delay Te>>>> 0.00..14400s 0.9 s
51N-1Pickup Ie> 0.05,0.06,..4 0.1 x In 30
51N-1Delay TIe> 0.00..14400s NA s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
Time dial Ie> TMS 0.01,0.025..1.6,1.7,..100 0.44

43
33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR3
Incomer from Inverter Transformer
Relay Located in Switch Board Panel 1-IC0G0
CT Ratio on 33kV side 80/1:In=80
33000V Incomer ICR3 4 MW block
Relay type: Siemens 7SR1003
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 80A
CT rated secondary 1A/5A 1A
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.005 to 5 2 x In 160
50-2 Delay T I>> 0.00..14400 s 0.9 s
51-1Pickup I> 0.05,0.06,..4 1 x In 80
51-1Delay tI> 0.00..14400 s NA s
Time dial I> TMS 0.01,0.025..1.6,1.7,..100 0.12 s

IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI


MI,VI,EI, & DTL
• Ground over current Protection: 50N/51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.005 to 5 1 x In 300
50N-2 Delay Te>>>> 0.00..14400s 0.9 s
51N-1Pickup Ie> 0.05,0.06,..4 0.1 x In 30
51N-1Delay TIe> 0.00..14400s NA s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
Time dial Ie> TMS 0.01,0.025..1.6,1.7,..100 0.44

44
33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR5
Incomer from Inverter Transformer
Relay Located in Switch Board Panel 1-IC0G0
CT Ratio on 33kV side 80/1:In=80
33000V Incomer ICR5 4 MW block
Relay type: Siemens 7SR1003
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 80A
CT rated secondary 1A/5A 1A
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.005 to 5 2 x In 160
50-2 Delay T I>> 0.00..14400 s 0.9 s
51-1Pickup I> 0.05,0.06,..4 1 x In 80
51-1Delay tI> 0.00..14400 s NA s
Time dial I> TMS 0.01,0.025..1.6,1.7,..100 0.12 s

IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI


MI,VI,EI, & DTL
• Ground over current Protection: 50N/51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.005 to 5 1 x In 300
50N-2 Delay Te>>>> 0.00..14400s 0.9 s
51N-1Pickup Ie> 0.05,0.06,..4 0.1 x In 30
51N-1Delay TIe> 0.00..14400s NA s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
Time dial Ie> TMS 0.01,0.025..1.6,1.7,..100 0.44

45
33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR6
Incomer from Inverter Transformer
Relay Located in Switch Board Panel 1-IC0G0
CT Ratio on 33kV side 80/1:In=80
33000V Incomer ICR6 4 MW block
Relay type: Siemens 7SR1003
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 80A
CT rated secondary 1A/5A 1A
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.005 to 5 2 x In 160
50-2 Delay T I>> 0.00..14400 s 0.9 s
51-1Pickup I> 0.05,0.06,..4 1 x In 80
51-1Delay tI> 0.00..14400 s NA s
Time dial I> TMS 0.01,0.025..1.6,1.7,..100 0.12 s

IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI


MI,VI,EI, & DTL
• Ground over current Protection: 50N/51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.005 to 5 1 x In 300
50N-2 Delay Te>>>> 0.00..14400s 0.9 s
51N-1Pickup Ie> 0.05,0.06,..4 0.1 x In 30
51N-1Delay TIe> 0.00..14400s NA s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
Time dial Ie> TMS 0.01,0.025..1.6,1.7,..100 0.44

46
33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR7
Incomer from Inverter Transformer
Relay Located in Switch Board Panel 1-IC0G0
CT Ratio on 33kV side 80/1:In=80
33000V Incomer ICR7 4 MW block
Relay type: Siemens 7SR1003
• SCOPE OF FUNCTION
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
• Power System Data 1
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 80A
CT rated secondary 1A/5A 1A
• Phase over current Protection: 50/51
Setting name Units Range Setting unit Prim Value
50-2 pickup I> > 0.005 to 5 2 x In 160
50-2 Delay T I>> 0.00..14400 s 0.9 s
51-1Pickup I> 0.05,0.06,..4 1 x In 80
51-1Delay tI> 0.00..14400 s NA s
Time dial I> TMS 0.01,0.025..1.6,1.7,..100 0.12 s

IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI


MI,VI,EI, & DTL
• Ground over current Protection: 50N/51 N
Setting name Units Range Setting unit Prim Value
50N-2 Pickup Ie>> >> 0.005 to 5 1 x In 80
50N-2 Delay Te>>>> 0.00..14400s 0.9 s
51N-1Pickup Ie> 0.05,0.06,..4 0.1 x In 8
51N-1Delay TIe> 0.00..14400s NA s
IEC Curve IEC NI,VI,EI,LTI,ANSI IEC NI
MI,VI,EI, & DTL
Time dial Ie> TMS 0.01,0.025..1.6,1.7,..100 0.44

47
TIME CURRENT CHARACTERSTIC CURVES

48
10000
1000
100

ITR1

FEED_CP_IC1

33kV_OG
TR1_RELAYS_HV

TR1_RELAYS_LV
10
Time in Seconds

TR1
A 30000.0 KVA
Transformer
1

LINE RELAYS

M
.1
.01

.5 1 10 100 1000 10000


Current in Amperes X 10
33000 Volt Phase Time-Current Characteristic Curves 12-18-2016
1 - Fault current Flow:ICR1-33kV SWBD-Power Trafo-Grid 19:39:55

mulk_09112016

49
10000
1000
100

IC003_SWBD1
FCP_IC1

TR1_RELAYS_LV

TR1_RELAYS_HV

LINE RELAYS
10

OG000_SWBD1
Time in Seconds
1
.1
.01

.5 1 10 100 1000 10000


Current in Amperes X 10
33000 Volt Ground Time-Current Characteristic Curves 12-18-2016
1 - Fault current Flow:ICR1-33kV SWBD-Power Trafo-Grid 19:52:39

mulk_09112016

50

You might also like