1. Rating of Condenser mw MW 500
2. Elevation of Hot well Stand Pipe Connection HwSpNzEL mm -1850
3. Orientation of Hot well Stand Pipe Connection HwSpNzOa deg 0 *
4. Elevation of Side Wall Stand Pipe Connection SwSpNzEL mm 1100
5. Elevation of Low Low Low Level LLL mm -1479
6. Elevation of Low Low Level LL mm 226
7. Elevation of Normal Level NL mm 476
8. Elevation of High Level HL mm 576
9. Elevation of High High Level HHL mm 626
10. Elevation of Level Transmitter above HHL SpLtHeL mm 776
11. Elevation of Level Transmitter below LL SpLtLeL mm 176
12. Orientation of Level Transmitter(LT1) SpLt1Oa deg 180 *
13. Orientation of Level Transmitter(LT2) SpLt2Oa deg 0 *
14. Length of Level Gauge SpLgL mm 1200 *
15. Orientation of Level gauge (LG1) SpLg1Oa deg 225 *
16. Orientation of Level gauge (LG2) SpLg2Oa deg 315 *
17. Outer Diameter of Stand Pipe SpOD mm 115 *
18. Distance between Low Low Level and Level gauge LgNzD mm 75 *
Lower Connection
19. Thickness of Stand Pipe SpTk mm 5.4 *
20. Distance of Stand Pipe Nozzle from Pipe End SpNzD mm 150 *
21. Outer Diameter of Stand Pipe Nozzle SpNzOD mm 60.8 *
22. Thickness of Stand Pipe Nozzle SpNzTk mm 4.5 *
23. Length of stand pipe nozzle for site SpNzSL mm 3000 *
24. Thickness of Blind Plate of stand pipe nozzle SpNzBpTk mm 20 *
25. Outer Diameter of Level Switch Nozzle LsNzOD mm 34.2 *
26. Thickness of Level Switch Nozzle LsNzTk mm 4.05 *
27. Distance between Level Switch Nozzles LsNzD mm 350 *
28. Orientation of Level Switch(LS1) nozzle Ls1NzOa deg 180 *
29. Thickness of Blind plate for Level Switch Nozzle LsNzBpTk mm 5 *
30. Length of pipe for level switch for site LsNzSL mm 2500 *
31. Outer Diameter of Drain/Vent Nozzle DvNzOD mm 21.8 *
32. Thickness of Drain/Vent Nozzle DvNzTk mm 2.65 *
33. Length of Drain /Vent Nozzle DvNzL mm 100 *