4th Int’l Conf.

on Recent Advances in Information Technology | RAIT-2018 |

Power Quality Assessment and Improvement


of 3-Phase 3-Wire Non-Linear System Using
Instantaneous Power Theory Based
DSTATCOM
Hariom Kumar Jagannath Patra Ashiwani Yadav Nitai Pal
Dept. of Electrical Dept. of Electrical Dept. of Electrical Dept. of Electrical
Engineering Engineering Engineering Engineering
IIT(ISM) Dhanbad, India IIT(ISM) Dhanbad, India IIT(ISM) Dhanbad, India IIT(ISM) Dhanbad, India
email:hariomk28@gmail.com email:jaganath.ptr@gmail.com email:ashiwaniurgent@gmail.com email:nitai_pal@rediffmail.com

Abstract-- Harmonics is an eminent power quality issue Harmonics are predominantly because of industrial non-
confronted by the end user. It possesses several adverse linear power electronics load such as an inverter, drives,
effects in the electrical environment. It should be reduced arc furnace, rectifier, welding machines, transformers,
for the smooth and efficient operation. In the presented FACTs devices, rotating electric machines, etc [11].
study, Distribution Static Compensator (D-STATCOM) Consequently, harmonic introduced in the current ensued
is initiated to strengthen power quality in terms of reducing in a non-sinusoidal wave possessing frequencies besides
harmonics. The control strategy is contingent on fundamental frequency. Flaw of control devices,
instantaneous power theory. The harmonics annihilation is supplemental line losses (at fundamental as well as
accomplished by providing compensating current harmonic frequencies), extra noise out of motors,
accordingly that it produces the sinusoidal wave shape curtailed lifetime and enlarged losses in utility equipment
source current no matter what nonlinear load in the are some pernicious effects of harmonics.
distribution line. The harmonic current of source current is D-STATCOM is a precise effectual means for
curtailed. The switching of nonlinear load yielded in 30.30 the amelioration of power quality consequence in the
% THD (Total Harmonic Distortion) in source current. The distribution system. The Schematic diagram
DSTATCOM with instantaneous power theory has DSTATCOM incorporated in the Power system is shown
improved THD of source current by reducing to 2.31%. The in Fig. 1. Harmonic PQ consequences can be discoursed
efficacy of D-STATCOM relies too much on the control by the D-STATCOM. [3]
strategy that is employed to produce the compensating
reference current. Besides the numerous control strategy,
I s I C I L
the instantaneous power theory proves its functionality very
well. The amount of compensating current by voltage = +

source inverter (VSI) to make the source current sinusoidal


depends on the switching pattern of IGBT of VSI. I s R
L
I L

Keywords- Power quality; D-STATCOM; Instantaneous


I C
Power Theory; Clarke Transformation.

I. INTRODUCTION
In this day and age, there is augmented in the C
L V I L

anxiety of the power quality (PQ), at the power consumer


C

primarily due to the reason of more delicate loads such as


power electronics and micro-controller based load[1],[2].
There are various constraints as a result of which the PQ
in the distribution and/or transmission system figured
out. Out of them, harmonics is a prominent PQ issue
confronted by the end user. Harmonics are the voltage
and/or current waveform retaining frequency integral
multiple of power system (fundamental) frequency [11]. Fig. 1 Schematic diagram DSTATCOM
An all-inclusive utilization of non-linear load has raised incorporated in Power system
content of harmonic at point of common coupling (PCC).