Compensation Scheme for Power Quality Improvement

In Present Power System


Aadesh Kumar Arya, J. S. Arya Amit Kumar Manocha and Manoj Sharma

Department of Electrical Engineering


Geeta Institute of Management and Technology, Kurukshetra, India
adesh_kumararya@rediffmail.com , jsarya26@yahoo.co.in , manocha82@gmail.com, manojgarg0501@gmail.com
Abstract: The power quality (PQ) management is the main harmonic currents are injected back into power distribution
issues in power system. The industries are facing this problem.
systems which produced by nonlinear loads. These
The hybrid filter configuration with PI Controller is more
efficient scheme for the improvement of power quality in
harmonics are the origin due to the many problems and
power system. The main purpose of this work is to reduce the affect electrical equipments connected to the power supply
effects of Harmonics in a cost-effective and practical way by [6]. When the non - sinusoidal currents pass through the
mitigating both current and voltage harmonics generated in a different impedances in the power systems than voltage
power system due to the presence of non-linear loads .It also harmonics produced. Due to the propagation of voltage
shows comparative study of a simple circuit, circuit with harmonics in power systems, the power system component
hybrid filter and a circuit with hybrid filter using P-I and devices are affected. The important harmonic source is
Controller schemes. The systems are modeled by using ac/dc converters/inverters [7]. Hence, due to the serious
MATLAB/SIMULINK software and performance is observed.
issues there is need of power quality improvement
The simulation results reveal that the proposed method of
hybrid filter with PI Controller is better solution for techniques which can suppress the voltage and current
improving power quality. harmonics, improve power factor and balance the input
Index Terms— Hybrid Filter, Power Quality, PI controller, supply. A no. of circuit configurations of filters are
Total harmonic distortion (THD) available to limit harmonic current distortion. The active
power filters as well as passive power filters have been
I. INTRODUCTION studied and the developed technology to reduce the ill
impacts of harmonic load to electric power quality. Today
To develop and maintain the modern economy & society, this is an important trend in distribution system operation
the economical, social and environmental sustainability are [8]. Passive filters which act as least impedance path to the
required in the emerging future trend of energy. For the tuned harmonic frequencies were used initially to reduce
economical and social growth, the prime movers are more harmonics. This technique is simple and less expensive. But
important. The electrical energy is main prime mover for it has many drawbacks viz. resonance, fixed compensation
this. So today the electrical energy is most important characteristics, large size, high losses at no load etc. The
elements for the society and industry. The quality and technology for active power filters configuration have been
reliability of the power supply are more required for the developed for complete compensation of harmonics
health of electrical power systems [1]-[2].Both electric distortions. Active filters are very helpful to overcome the
utilities and consumers of electricity are mostly concerned a drawbacks of passive filter by using the switched mode
to the power quality of electricity. The term power quality power (SMPS) converter to eliminate the complete
has become one of the most necessary word in the power harmonic current and voltage distortion. The harmonic
industry since the late 1980s. In the power utility currents and reactive power compensation simultaneously
distribution systems, the power quality (PQ) problems are can be suppress by suitable control techniques with the
not new, but now-a-days due to the public awareness these shunt active power filters to generate a compensating
problems are popular. By invention the advances current in equal and opposite direction so that source
technology in semiconductor device have fuelled a current becomes harmonic free. However, the power rating
revolution in power electronics over the past decade, and and construction cost of active power filters is very high.
there are direction to the technocrats to continue this trend The hybrid filter configurations play a great roll to avoid
[2]. With the more application of power electronics based the limitations of active and passive filters. The power
appliances in the industry, harmonics problem is more rating of active converter, using the application of the
serious and dangerous. The power electronics based passive filters with the active filter, is reduced with respect
equipments viz. adjustable-speed motor drives, electronic to the pure active filters. This hybrid filter consists the
power supplies, Battery chargers DC motor drives, battery advantages of active filters and passive filters. So the hybrid
chargers, etc. are responsible for the enhance in power filters are cost effective and become more practical in
quality related problems [3-4]. According to characteristics industry used. The block diagram of a hybrid filter is shown
of power converters viz. nonlinear, are cause serious in fig.1 [9]. This paper presents a hybrid filter configuration
problems of poor power factor, current harmonics, non to suppress harmonic current distortion in the source
sinusoidal supply voltage, reactive power burden and low current. It is a combined system of Shunt Passive Filter
system efficiency [5].These nonlinear loads are prime (SPF) and a Series Active Filter (SAF). Many of the
sources of harmonic distortion in a power distribution important international standards define power quality as to
system. Through the point of common coupling (PCC), the maintain purely sinusoidal current waveform in phase with
purely sinusoidal voltage waveform. Therefore, a power devices in distribution systems or demand-side. The cost is
quality problem exists if any of the voltage, current or acceptable, although the performance is not that satisfactory
frequency deviation from sinusoidal nature occurs. Power to users due to dynamic characteristics of nonlinear loads.
quality problems are common in industrial, commercial and The performance of an active power filter Recent surveys
utility networks as power electronics appliances are widely clearly show that most industrial plants are more or less
used in these fields. The power electronics devices generate sensitive to voltage disturbances, and in particular voltage
harmonics and reactive power. sags are often the most concerning ones, causing frequent
protection tripping, incorrect load operation, interruption of
processes and even the whole plant shut-down. [14]. In this
paper the Simulink model is developed to reduce the effects
of Harmonics in a cost-effective and practical way by
mitigating both current and voltage harmonics generated in
a power system due to the presence of non-linear loads.
A comparative study of a simple circuit, circuit with hybrid
filter and a circuit with hybrid filter using P-I Control
strategies have been done. The systems are modeled by
using MATLAB/SIMULINK software and performance is
observed.

II. P-Q THEORY


The power quality (P-Q) theory (Akagi, Kanazawa and
Therefore it is very important to compensate the dominant Nabae in1983-84) for applying to the control of APFs
harmonics and the total Harmonic Distortion (THD) below [15].This theory is based on time-domain analysis, what
5% as specified in IEEE 519 harmonic standard [10]. makes it valid for operation in steady-state or transitory
Harmonics not only influence the normal work state of regime, as well as for generic voltage and current power
electric equipments, but also interfere communication system waveforms, allowing to control the APFs in real-
equipments. At present, passive power filter (PPF), active time. This theory is very simple to apply because of the
power filter (APF) and hybrid active power filter (HAPF) calculations, which involves only algebraic calculation
are mostly used to eliminate the harmonics [11]. Harmonic (exception done to the need of separating the mean and
pollution is not a new phenomenon, issues of harmonic alternated values of the calculated power components). [15]
components of voltage and / or current curves occurred
The P-Q theory is best suited for the mathematical
early in the industrial use of electricity, the first mention
modeling of shunt APF control, hybrid filter, especially for
regarding to the use of harmonic analysis as a way of
the calculation for the reference current. It is based on
solving a practical electrical engineering problem, was
instantaneous voltage and current in three phase system (3
made in 1893 by Steinmetz. Nowadays, in modern industry,
or 4 wire). It applies an algebraic transformation (Clarke
about 50% of receivers an industrial customer are supplied
transformation) of three-phase system voltages and load
using frequency converters (AC and DC adjustable drives),
currently in the a-b-c coordinates to the – coordinates
switching mode power supply (for powering computer
by the relations [16]:
systems or process controllers) and electronic ballasts. Due
to the nonlinear characteristics of these receivers (using
diodes, thyristors or transistors to convert AC voltage in DC
voltage and DC voltage in AC voltage or DC voltage in DC
voltage), in industrial distribution systems.
Resonance phenomena can increase the harmonic
components of voltage that will lead to increase the voltage
in different parts of the electricity supply system,
overloading of transformers and, in particular capacitor.
Also, can causing losses increasing in overhead electric
lines, cable, transformers and capacitor banks, leading to The instantaneous power for the three-phase system is as
acceleration of insulation aging and reduction life [12]. The follows:
designing of the filters are more requirements for best
functioning of distribution systems. To design a filter the
size, the total investment cost and unacceptable voltage Where is the instantaneous real power and is the
profiles should be correct and harmonic must be reduced instantaneous imaginary power.
within the permissible maximal value e.g. IEEE Std. 519 By observing the formulations of P and Q, it is possible to
[13]), is keep at a minimum. Up to date, the cost of an put them in the following form
active power filter is expensive enough to postpone
practical installation. Actually, the passive power filter
using series resonant capacitors and inductors with parallel Where is DC component related to fundamental active
resistor have been widely used as harmonic improvement
current conventional and is AC component, devoid of
mean value and associated with harmonic caused by the AC
component of instantaneous real power. is DC
component related reactive power generated by
fundamental currents and voltages. is AC component and Where, is impedance of filter and is source impedance.
related to harmonic currents caused by the components of Ideally, the source harmonic currents will be null. If
AC instantaneous reactive power.
If to reduce series resonance between the
source and the filter. It avoids that the passive filter receives
the harmonic current of the rest of the system. In the
practical case simulated in this work a value K = 2 is used.

Reactive Current Active Current Harmonic Current


IV. MODEL REPRESENTATION

With The main requirement of any electric power system is the


supply of electricity with a determined power quality and
Three phase distorted currents representing identified reliability to the optimum cost. For increased the quality of
currents (reference currents, ) are calculated from life of the power system, with the installation of power
inverse transformation (Clarke transform) are electronics devices with non-linear loads, with the
shown in the relation presented below. application of hybrid filter configuration. To reduce the
harmonic distortion, the hybrid filters are one of the most
effective configurations.
The three models have been simulated in MATLAB
/SIMULINK. The source current and voltage harmonics are
analyzed. The three models simulated are:
The voltage must be of good quality (sinusoidal and
 System with non-linear load without using filter.
balanced); otherwise the method of the P-Q theory does not
apply. Since the network voltage is often unbalanced and/or  System with non-linear load with hybrid filter
distorted.  System with non-linear load with hybrid filter
using P-I Controller.
III. HYBRID FILTER DESIGN
In [4], the authors described the hybrid filter design which
depends on the load to be compensated. It contains some
passive viz. inductor (L) and capacitor (C), LC branches one
for each important load current harmonic to be removed
from the source current. In the case of non-linear loads, it is
usually enough to employ one, two or three branches for the
main harmonics. By three-phase systems it is possible to
reduce or eliminate .The harmonic of 3rd order and its
multiples by choosing correct connections of the
transformers supplying the power to the load. Therefore it is
usual to include LC branches tuned for the 5th and 7th Fig. 2 Simulation model for non-linear load without filter
harmonic order.
The values of and parameter of a branch tuned for an Table1: Parameters of Active Filter
“n” order harmonic must be satisfy the equation.

Snubber Resistance 2000Ω


Where f corresponds to the fundamental frequency that was
taken as 50 Hz in this work. The active filter connected in Snubber Capacitance Infinite
series with the passive branches can be used as a controlled Internal Resistance 50Ω
voltage source.
Snubber Resistance 2000Ω
Different strategies are possible to control this compensation
voltage. In single-phase or balanced three-phase system, a
voltage proportional to source harmonic current Table 3: Gain of PI controller
permits to modify the impedance of the shunt 0.9
compensator, and the passive filter performance is Proportional Gain (Kp)
improved. The non-linear load is modeled by a current
source. From the circuit 2b, it is possible to obtain the
Integral Gain (Ki) 12
source harmonic current, equation 9.
Table4: Comparison of THD in % for using schemes

THD in %

Voltage Source Current Source


Without Filter 29.79 11.62
Hybrid Filter 5.23 2.05
Hybrid Filter using PI 1.30 1.66
Controller

V. SIMULATION RESULTS AND DISCUSSION


In this paper, three schemes are considered. In the first
scheme the model is developed without any filter using
non-linear load which shown in fig.2. After simulation, the
fig. 5 shows the waveform of voltage source without filter.
Fig.6 shows the total harmonic distortion (THD) is 29.79%.
And fig. 7 shows the waveform of current source without
filter.Fig.8 shows THD is 11.62%.
In the second scheme the Simulink model is developed
Fig. 3 Simulation model for non-linear load with hybrid using hybrid filter. The fig. 3 represents the model with
filter hybrid filter. The fig. 9 shows the waveform of voltage
source with hybrid filter. Fig.10 shows the total harmonic
distortion (THD) is 5.23%. And fig. 11 shows the
waveform of current source. Fig.12 shows THD is 2.05%.
The third scheme represents the model with hybrid filter
controlled by PI Controller which shown in fig. 4. The fig.
13 shows the waveform of voltage source with hybrid filter.
Fig.14 shows the total harmonic distortion (THD) is 1.30%.
And fig. 15 shows the waveform of current source. Fig.16
shows THD is 1.66%. In the table 1, the values of active
filter parameters are mentioned and in table 2, the values of
parameters of passive filter and table 3 represents the values
of Kp and Ki for PI-Controller. The table 4 shows the
compression of THD in each case.

Fig. 3 Simulation model for non-linear load with hybrid


filter using PI Controller

Table 2 Parameters of Passive Filter Fig.5 Waveform of voltage Source without filter
PASSIVE FILTER(L-C TYPE)
Inductance(L1) 11.24 mH
Capacitor(C1) 0.9 mF
Inductance(L2) 15.6 mH
Capacitor(C2) 0.6 mF
Inductance(L1) 11.24 mH
Fig. 10 Spectrum analysis of voltage Source with hybrid
Fig. 6 Spectrum analysis of voltage Source without filter filter

Fig.11 Waveform of current Source with hybrid filter


Fig.7 Waveform of current source without filter

Fig. 8 Spectrum analysis of current source without filter Fig.12 Spectrum analysis of current Source with hybrid
filter

Fig. 9 Waveform of voltage Source with hybrid filter Fig 13 Source Voltage waveform with hybrid filter using PI
controller
References
[1] Aadesh Kumar Arya, Saurabh Chanana and Ashwani Kumar, “Role
of Smart Grid to Power System Planning and Operation in India”, In
Proc. of Int. Conf. on Emerging Trends in Engineering and
Technology, GIMT, Kurukshetra, DOI: 03.AETS.2013.3.258,
Association of Computer Electronics and Electrical Engineers
(ACEEE), U.S.A, p.p., 793- 802, 25th – 27th October, 2013).
[2] C. Gao, M. A. Redfern, “A Review of Voltage Control in Smart Grid
and Smart Metering Technologies on Distribution Networks”, In
Proc of International conference, Universities' Power Engineering
Conference (UPEC), Soest, Germany, p.p., 1-5 5-8, September,
2011.
[2] H. Akagi, “New Trends in Active Filters for Power Conditioning,”
IEEE Trans. on Industry Applications, vol. 32, no. 6, p.p., 1312-
1322, 1996.
[3] W.E.Kazibwe and M.H.Sendaula, “Electric Power Quality Control
Techniques”, Van Nostrand Reinhold, New York, 1993.
[4] R. C. Dugan, M. F. McGranaghan, S. Santoso and H. W. Beaty.
Electrical Power Systems Quality 2nd, ed, McGraw-Hill, 2002, USA.
Fig. 14 Spectrum analysis of voltage source with hybrid [5] Wei-Fu Su , Chin E. Lin, Ching-Lien Huang, “Hybrid filter application
filter using PI controller for power quality improvement”, Electric Power Systems Research,
vol.47, p.p., 165–171, 1998.
[6] R. Belaidi A. Haddouche and H. Guendouz , “Fuzzy Logic Controller
Based Three-Phase Shunt Active Power Filter for Compensating
Harmonics and Reactive Power under Unbalanced Mains Voltages”,
Energy Procedia, vol. 18, p.p., 560–570, 2012.
[7] Rashmi S. Phasate & Archana Bawankar, “Power Quality
Improvement in Matrix Converter Using Hybrid Filter”,
International Journal of Power System Operation and Energy
Management, vol. 2, Issue-1, 2, p.p., 2231 – 4407, 2011.
[8] G. Ahrabian, F. Shahnia, and M. T. Haque, “HYBRID Filter
Applications for Power Quality Improvement of Power Distribution
Fig.15 Waveform of current Source with hybrid filter using Networks Utilizing Renewable Energies”, IEEE International
PI controller Symposium on Industrial Electronics, Montreal, Que.vol.2, p.p.,
1161 – 1165, 9th -13th July, 2006.
[9] Laxmi Devi Sahu and Satya Prakash Dubey, “ANN based Hybrid
Active Power Filter for Harmonics Elimination with Distorted
Mains”, International Journal of Power Electronics and Drive System
(IJPEDS), vol. 2, no. 3, p.p., 241-248, September 2012.
[10] Roger C. Dugan, Mark F. Mc Granaghan, Surya Santoso and H.
Wayne Beaty, “Electrical power system quality”, Tata McGraw Hill
Education, 10th January, 2012.
[11] Wei Zhaoa, Ruimin Chena, An Luob, “Recursive Integral with Fuzzy
Control Method used in Shunt Hybrid Active Power Filter”, Energy
Procedia, vol. 16, Part C, , p.p., 1753–1759, 2012.
[12]Jarupula Somlal “Efficient Hybrid Shunt Active Power Filter for
Improvement of Power Factor and Harmonic Suppression using
MATLAB”, In proceeding of 10th WSEAS International
Conference on communications, electrical & computer
engineering, Wisconsin, USA p.p., 195-199, 2011.
[13] S Z. Shuai, A. Luo, R. Fan, “Injection branch design of injection type
Fig.16 Spectrum analysis of current Source with hybrid active power filter,” Autom. Elect. Power Syst., vol. 31, no.
5, pp. 57–60, Jun. 2007.
hybrid filter using PI controller [14] Jingrong Yu, Shiqi Ding, Yijun Wang, Weibiao Wu, Mi Dong, “The
engineering design and optimization of main circuit for hybrid active
VI. CONCLUSION power filter”, Electrical Power and Energy Systems, vol. 46, p.p.,
40–48, 2013.
[15] H. Akagi, Y. Kanazawa and A. Nabae, "Generalized Theory of
Instantaneous Reactive Power and Its Applications," Transactions
The model of different schemes viz. system for non- of the IEE-Japan, Part B, vol. 103, no.7, pp. 483-490, 1983.
linear load without filter, with hybrid filter and hybrid [16] R. Belaidi, A. Haddouche and H. Guendouz, “Fuzzy Logic
Controller Based Three-Phase Shunt Active Power Filter for
filter using PI Controller are simulated using
Compensating Harmonics and Reactive Power under Unbalanced
MATLAB/Simulink in this paper. When compared to Mains Voltages”, Energy Procedia, vol.18, p.p., 560 – 570, 2012.
these three schemes the % of THD is different. It is find
out that the system with hybrid filter is much better to
the system without filter. But the system with the hybrid
filter using PI controller is more efficient for harmonic
suppression. So the system with hybrid filter using PI
controller is more accurate for power quality
improvement.