You are on page 1of 2

November 2019 SI-X-STYLE-19.

11
X-Style Sleeve
Page 1
Galvanized Steel Fire Damper Models: 119, D19, 319, D39
APPLICATION
The X-Style Sleeve is an integral sleeve frame. The sleeve length comes in 2 depths, 12" and 14". The integral sleeve frame comes in three
different styles. The "A" style is without any transition, and the blades are in the air stream (see also SD-117, SD-119, SD-15S, SD-17S, SD-317,
SD-319, SD-15S, SD-17S, SD-D17, SD-D19, SD-30S, SD-38S, SD-D37, SD-D39, SD-30D, SD-38D). The "B" style has a B-Pan so the blades are
out of the airstream (see also SI-BPAN). The "C" style is with a round, oval, or square transition and has 100% Free Area (see also SI-TRFD).

PANEL SIZE LIMITATIONS

Orientation Horizontal & Vertical Horizontal Vertical

Panel Minimum Panel Maximum Section Maximum Section

117X A 4"W x 4"H 48"W x 48"H 60"W x 60"H


119X
B 4"W x 3"H duct (4"W x 5"H frame) 48"W x 43"H duct (48"W x 48"H frame) 60"W x 55"H duct (60"W x 60"H frame)
15SX
17SX C 4"W x 4"H duct (6"W x 7"H frame) 46"W x 42"H duct (48"W x 48"H frame) 58"W x 54"H duct (60"W x 60"H frame)

317X A 4"W x 4"H 48"W x 48"H 36"W x 36"H


319X
B 4"W x 3"H duct (4"W x 5"H frame) 48"W x 43"H duct (48"W x 48"H frame) 36"W x 32"H duct (36"W x 36"H frame)
30SX
38SX C 4"W x 4"H duct (6"W x 7"H frame) 46"W x 42"H duct (48"W x 48"H frame) 34"W x 31"H duct (36"W x 36"H frame)
Model

D17X A 4"W x 4"H 24"W x 24"H 36"W x 36"H


D19X
B 4"W x 3"H duct (4"W x 5"H frame) 24"W x 21"H duct (24"W x 24"H frame) 36"W x 32"H duct (36"W x 36"H frame)
15DX
17DX C 4"W x 4"H duct (6"W x 7"H frame) 22"W x 20"H duct (24"W x 24"H frame) 34"W x 31"H duct (36"W x 36"H frame)

D37X A 4"W x 4"H 24"W x 24"H 36"W x 36"H


D39X
B 4"W x 3"H duct (4"W x 5"H frame) 24"W x 21"H duct (24"W x 24"H frame) 36"W x 32"H duct (36"W x 36"H frame)
30DX
38DX C 4"W x 4"H duct (6"W x 7"H frame) 22"W x 20"H duct (24"W x 24"H frame) 34"W x 31"H duct (36"W x 36"H frame)

The listed fire dampers meet the construction and


STANDARD MATERIALS AND CONSTRUCTION performance requirements of:
SLEEVE FRAME: 22 GA. one-piece roll-formed galvanized steel.
BLADE: 22 GA. galvanized steel, curtain type. • Underwriters Laboratories Inc. Standard 555
FUSIBLE LINK: UL-Listed 165°F, replaceable. • National Fire Protection Association Standard 80 and 90A
CLOSURE SPRINGS: For all Dynamic and Horizontal Static Models • ICC's International Building Code
Heat-treated Type 301 stainless steel constant force coiled • California State Fire Marshal Listing #3225-1328:100
negator type.
FINISH: Mill. • Underwriters Laboratories Inc. Approved for dual direction
FOR "C" STYLE DAMPERS airflow and static closure conditions.
TRANSITION CAPS: 20 GA. galvanized steel, riveted to sleeve frame. • Underwriters Laboratories Inc. Classified for use in fire
DUCT COLLARS: 24 GA. galvanized steel, crimped to transitions. resistive ratings of less than 3 hours.

OPTIONS
212°F replaceable fusible link
PK1202 position indicator switch
B-Pan, round, oval, or square transitions
Tab-lock retaining angles
Perimeter flange
Pull ring

NOTES
1. Nominal deductions will be made to the opening size given.

450 Riverside Rd • Wyalusing PA, 18853 • Phone 570-746-1888 • Fax 570-746-9286


MCDLG-23-01-06
November 2019 SI-X-STYLE-19.11
X-Style Sleeve
Page 2
Galvanized Steel Fire Damper Models: 119, D19, 319, D39
"A" Style
Top Blade Riveted to Frame Integral Self-Locking
Corner Joint

Integral Sleeve
Frame
Fusible
Link
Damper Centered
Height

Within Sleeve Frame

3"

¾" (Sill & Jambs)

Widt L 4")
h 1
"or
L (12
(12" or 14")

"B" Style (with B-Pan Transition for Blades Out of Airstream)


Integral Self-Locking
Top Blade Riveted Corner Joint
to Frame Integral Sleeve
See Head Frame
Sizing Chart*
1¾"

B-Pan
Fusible
Link
Frame
Height

Damper Centered
Height

Within Sleeve Frame


Duct

3"
¾" (Sill & Jambs)
Wid L 4")
1
L th
" or
(12" or 14") (12

*Head Sizing Chart on SI-BPAN.

"C" Style (with Transition for 100% Free Area)


Transition
UL-Approved Break-
away Connection when
Round or Oval
Sealant
Caulking Typ.
at Transition Collar
Frame Height†

to Sleeve (For Connection


Frame Joint to Duct)
on Interior Fra
Height

2" Fra
Duct

Damper Centered Integral Sleeve me me


Within Sleeve
UL-Listed Hi-Temp Wi
Typ. Frame Wi Pressure-Sensitive dth
Frame dth
Foil Tape (Typ.)

3"

Transition
Transition
1" Typ. on
¾" (Sill & Jambs) 3 Sides
L Collar Collar
(12" or 14")

Du
Wi ct L 4")
Du
Wi ct
dth dth
or
1 L 4")
2" r1
(1 "o
(12

Sizing Chart on SI-TRFD.

In the interest of product development, Mestek CDLG reserves the right to make changes without notice.
450 Riverside Rd • Wyalusing PA, 18853 • Phone 570-746-1888 • Fax 570-746-9286
MCDLG-23-01-06