BENSHAW INC. SPD SETTINGS SHEET - OVER LOAD RELAY - REACTOR
SurProtex Digital Protection Relay
Branch Name:
FILTER REACTOR FUNDAMENTAL CURRENT (AMPS): THIS VALUE IS BASED ON EFFECTIVE KVAR OUTPUT RATING OF
33.5 FILTER BRANCH OR BANK
FUNDAMENTAL CURRENT RATING OF BRANCH/BANK AT 10%
FILTER REACTOR FUNDAMENTAL CURRENT AT 10% OVER-VOLTAGE:
36.9 OVER-VOLTAGE)
TYPICALLY SET AT 70% OF THE REACTOR HARMONIC RSS
FILTER REACTOR OVERLOAD SETTING LEVEL RATING + THE FUNDAMENTAL CURRENT RATING OF THE
70% BRANCH/BANK AT 10% OVER-VOLTAGE.
FILTER REACTOR RECOMMENDED OVERLOAD SETTING THIS IS THE RECOMMENDED OVERLOAD RELAY SETTING
39 PROVIDING 30% OF MARGIN FOR HARMONIC RATING.
THIS IS THE MAXIMUM OVERLOAD RELAY SETTING AND
FILTER REACTOR MAXIMUM OVERLOAD SETTING PROVIDES NO MARGIN. MONITOR EQUIPMENT IF THIS SETTING
42 IS USED.
Hit the Store key to stall new The "Sto" key must be hit to store
Sto Sto Sto values settings.
Filter Bank Reactor has exceeded its current dial setting of 39.4 amps. Reference Menu 1.CHA, 2.dEF, Current Dial setting, and
O-L Thermal Overload Time Dial settings above. Increasing the Current Dial setting beyond the filter component rating should be done with extreme
caution.
Und Under Current The filter bank drew less than the undercurrent setting for 3 seconds. Reference 4.Und above.
r-P Reverse Phase Line power phasing is reversed. This setting should not be used. NEPSI recomends this setting be disabled.
One or more of the phases of the filter bank stage has been lost for more than 3 seconds. This trip could be caused by a main
P-F Phase Failure fuse operation or a stuck vacuum switch, if single phase vacuum switches are being used. Stuck open or stuck closed switches
will result in this trip.
P-f Phase Unbalance One or more phases has been unbalanced by 50% for 5 seconds. Most likely cause of this trip will be a blown fuse condition.
Long-time over-current
StL The filter bank drew more than 180% of the "current dial" setting for 5 seconds after being first energized.
trip
Short-time over-current
Loc The filter drew short-time high current for 0.5 Seconds. Reference the 7.Loc setting above.
trip
g-F Ground Fault This function is not provided.
Bar Graph, 60- Alarm Trip Load is approaching the thermal limit. This function is not typically wire and is typically disabled. Reference 5.Alt above.
110%
1000.0 00.0
1, 10
Time (Seconds)
100.0
.0 .0
2, 30 3, 30
10.0
4, 5.05, 5.0
1.0
6, 0.5 7, 0.5
0.1
0.0 50.0 100.0 Primary Amps 150.0 200.0 250.0
Reactor Harmonic Current Spectrum - Page 3
Harm # (amps) Harm # (amps) Harm # (amps) Harm # (amps)
Start Delay Time (sec) - delay The definite time pickup noted in
period after initial startup before Menu Item 1.CHA above will not
2.dEF 00-30 5
over-load trip function becomes become active for 5 second after
active. initial current is sensed by the relay.
Hit the Store key to stall new The "Sto" key must be hit to store
Sto Sto Sto values settings.
Filter Bank has exceeded its current dial setting of 12.1 amps. Reference Menu 1.CHA, 2.dEF, Current Dial setting, and Time
O-L Thermal Overload
Dial settings above. Increasing the Current Dial setting beyond the filter component rating should be done with extreme caution.
Und Under Current The filter bank drew less than the undercurrent setting for 3 seconds. Reference 4.Und above.
r-P Reverse Phase Line power phasing is reversed. This setting should not be used. NEPSI recomends this setting be disabled.
One or more of the phases of the filter bank stage has been lost for more than 3 seconds. This trip could be caused by a main
P-F Phase Failure fuse operation or a stuck vacuum switch, if single phase vacuum switches are being used. Stuck open or stuck closed switches
will result in this trip.
P-f Phase Unbalance One or more phases has been unbalanced by 50% for 5 seconds. Most likely cause of this trip will be a blown fuse condition.
Long-time over-current
StL The filter bank drew more than 180% of the "current dial" setting for 5 seconds after being first energized.
trip
Short-time over-current
Loc The filter drew short-time high current for 0.5 Seconds. Reference the 7.Loc setting above.
trip
g-F Ground Fault This function is not provided.
Bar Graph, 60-
Alarm Trip Load is approaching the thermal limit. This function is not typically wire and is typically disabled. Reference 5.Alt above.
110%
1000 00
1, 10
Time (Seconds)
100
2, 30 3, 30
10
4, 5 5, 5
6, 1 7, 0
0
0 10 20 30 40
Primary Amps 50 60 70 80