Professional Documents
Culture Documents
ITEM NAME QTY. Manufacturer Model Type Measuring Range Target Value Medium Location
MIN Value MAX value Corrected Value
Area Identification Seq No Unit
(LL) (HH) (max : 20mA)
AERATION CASCADE
421 LS 101 LEVEL SWITCH (2WIRE) 1 ENDRESS + HAUSER ROPE TYPE 0-3 m NA 1.42 RAW WATER AERATION CASCADE
PRESSURE FILTERS
424 LS 201 LEVEL SWITCH 1 ENDRESS+HAUSER FLOAT TYPE 0 -5 m 1.7 NA FILTERED WATER CCT
LIME DOSING
430 LS 111/121 SLAKING TANK LEVEL SWITCH 2 ENDRESS+HAUSER ROD 0-5 m 0.98 1.45 LIME 5% CHEMICAL BLDG
430 LS 131/141 SLURRY TANK LEVEL SWITCH 2 ENDRESS+HAUSER ROD 0-5 m 1.4 1.5 LIME 5% CHEMICAL BLDG
COAGULANT DOSING
431 LS 111/121 COAGULANT DISSOLVING TANK LEVEL SWITCH 2 ENDRESS+HAUSER ROD 0-5 m 1.1 1.35 PACL 7.5% STORAGE TANK AREA
431 LS 211/221 COAGULANT STORAGE TANK LEVEL SWITCH 2 ENDRESS+HAUSER ROD 0-5 m 0.6 1.8 PACL 7.5% STORAGE TANK AREA
POLYMER DOSING
Page 1 of 2
INSTRUMENT LIST Gonzal, Jon:
PLEASE DOUBLE CHECK
ACTUAL FULL LEVEL
VALUE.
ITEM NAME QTY. Manufacturer Model Type Measuring Range Target Value Medium Location
MIN Value MAX value Corrected Value
Area Identification Seq No Unit
(4mA) (20mA) (max : 20mA)
AERATION CASCADE
421 FIT 101 FLOW METER 1 ENDRESS+HAUSER PROMAG W 400 ELECTROMAGNETIC 220 - 6600 383-405 m3/h 0 750 RAW WATER AERATION CASCADE
424 AIT 151 FREE CHLORINE METER 1 HACH CL 17 ANALYZER, 5440001 - 0-5 0.5-1.0 mg/L 0 2.5 TREATED WATER ANALYZER ROOM
424 AIT 152 PH/ORP METER - PH 1 HACH pH 5336T - 0-14 0-14 - 0 14 TREATED WATER ANALYZER ROOM
424 AIT 152 PH/ORP METER - ORP 1 HACH ORP 5362 - ± 2000 ? mV 0 1000 TREATED WATER ANALYZER ROOM
424 AIT 153 TURBIDITY METER 1 HACH TU5300 LXV445.99.50122 - 0-1000 0.5-3 NTU 0 3.5 TREATED WATER ANALYZER ROOM
424 FMC 001 DRINKING WATER FLOW METER 1 ENDRESS+HAUSER PROMAG L 400 ELECTROMAGNETIC 4-120 22 m3/h 0 30 TREATED WATER TREATED WATER PUMPING STATION
424 PIT 141X POTABLE WATER PRESSURE METER 1 ENDRESS + HAUSER CERABAR PMC51 CAPACITIVE 0 - 10 bar 0 10 TREATED WATER TW PUMPING STATION
424 FMC 002 SERVICE WATER FLOW METER 1 ENDRESS+HAUSER PROMAG L 400 ELECTROMAGNETIC 2-42 6 m3/h 0 12 TREATED WATER TREATED WATER PUMPING STATION
424 PIT 171X SERVICE WATER PRESSURE METER 1 ENDRESS + HAUSER CERABAR PMC51 CAPACITIVE 0 - 10 bar 0 10 TREATED WATER TW PUMPING STATION
424 FIT 211 TREATED WATER TO EXISTING RESERVOIR FLOWMETER 1 ENDRESS+HAUSER PROMAG W 400 ELECTROMAGNETIC 55-1700 317 m3/h 0 500 TREATED WATER TREATED WATER PUMPING STATION
424 PIT 211 TW TO EXISTING RESERVOIR LINE PRESSURE METER 1 ENDRESS + HAUSER CERABAR PMC51 CAPACITIVE 0 - 40 8.5 bar 0 20 TREATED WATER TW PUMPING STATION
424 FIT 231 TREATED WATER TO PANSALWATTA FLOW METER 1 ENDRESS+HAUSER PROMAG W 400 ELECTROMAGNETIC 35-1100 134 m3/h 0 300 TREATED WATER TREATED WATER PUMPING STATION
424 PIT 231 TW TO PANSALWATTA RESERVOIR LINE PRESSURE METER 1 ENDRESS + HAUSER CERABAR PMC51 CAPACITIVE 0 - 40 12.3 bar 0 20 TREATED WATER TW PUMPING STATION
424 PIT 104X SURGE VESSEL PRESSURE METER (PANSALWATTA LINE) 1 0
SLUDGE THICKENER AND RECIRCULATION
426 LIT 111 THICKENER LEVEL METER 1 ENDRESS+HAUSER PROSONIC M FMU40 ULTRASONIC 0-5 4.5 m 0 ≈5.0 SLUDGE SUPERNATANT SLUDGE THICKENER
426 LIT 141/142 RECIRCULATION TANK LEVEL METER 2 ENDRESS+HAUSER FDU91 (sensor)
PROSONIC S FMU90 ULTRASONIC 0 - 10 3.5 m 0 5.0 4.55 TREATED WATER SLUDGE THICKENER
426 FIT 121 SLUDGE FLOWMETER 1 ENDRESS+HAUSER FDU91 (sensor)
PROMAG L 400 ELECTROMAGNETIC 5.4 - 180 30 m 0 45 THICKENED SLUDGE 10 g/L SLUDGE THICKENER
LIME DOSING
PROSONIC S FMU90
430 LIT 111/121 SLAKING TANK LEVEL TRANSMITTER 2 ENDRESS+HAUSER ULTRASONIC 0 - 10 1.37 m 0 2.25 2.20 LIME 5% CHEMICAL BLDG
FDU91 (sensor)
PROSONIC S FMU90
430 LIT 131/141 SLURRY TANK LEVEL TRANSMITTER 2 ENDRESS+HAUSER ULTRASONIC 0 - 10 1.75 m 0 3.15 3.10 LIME 5% CHEMICAL BLDG
FDU91 (sensor)
430 FIT 151 LIME DOSING FLOWMETER 1 ENDRESS+HAUSER PROMAG 53H ELECTROMAGNETIC 15-420 55-171 L/h 0 300 LIME 5% CHEMICAL BLDG
COAGULANT DOSING
431 LIT 111/121 COAGULANT DISSOLVING TANK LEVEL METER 2 ENDRESS+HAUSER PROSONIC S FMU90 ULTRASONIC 0 - 10 1.17 m 0 2.25 2.20 PACL 7.5% STORAGE TANK AREA
431 LIT 211/221 COAGULANT STORAGE TANK LEVEL METER 2 ENDRESS+HAUSER FDU91 (sensor)
PROSONIC S FMU90 ULTRASONIC 0 - 10 1.75 m 0 3.1 3.12 PACL 7.5% STORAGE TANK AREA
431 FIT 231 COAGULANT DOSING FLOW METER 1 ENDRESS+HAUSER FDU91
PROMAG(sensor)
53H ELECTROMAGNETIC 15-420 20-95 L/h 0 120 PACL 7.5% DOSING PUMP AREA
POLYMER DOSING
432 FIT 151/171 POLYMER DOSING FLOW METER 2 ENDRESS+HAUSER PROMAG 53H ELECTROMAGNETIC 15-420 40-61 L/h 0 120 POLYMER 0.2% DOSING PUMP AREA
Notes:
1- flow meter measuring range is the recommended flow from the manual to achieve on 0.5% error
Page 2 of 2