You are on page 1of 1

CLIENT M/S.

EXECUTIVE ENGINEERING, PHW DIVISION, GWSSB DOCUMENT NUMBER ANK-INST-001

AGENCY M/S. MARS PLANNING & ENGINEERING SERVICES,PVT. LTD, AHMEDABAD REFERENCE P&ID NUMBER & REV0

CONTRACTOR M/S. HYDROTECH PYRAVARAN (INDIA) PVT LTD DOCUMENT TITLE INSTRUMENT INDEX - 14.0 MLD WTP

PROJECT 14.0 MLD SEWAGE TREATMENT PLANT , ANKLESHWAR REVISION 0

RANGE TYPE OF
SL.NO TAG NUMBER SERVICE / LOCATION INSTRUMENT DESCRIPTION TYPE QUANTITY UNTS Operation
FROM TO SIGNAL

14.0 MLD - SEWAGE TREATMENT PLANT , ANKLESHWAR

1 LIT-001 MES-01-A Mechanical Fine Screen Differential Level Indicating Transmitter Ultrasonic 2 No 0 3000 mm AI Indication In SCADA

2 UFM-001 Parshall Fume Inlet Differential Level Indicating Transmitter Ultrasonic 1 No 0 3000 mm AI Indication In SCADA

3 AIT-101 SBR Tank Dissolved Oxygen Optical 2 No 0 10 mg/l AI Indication In SCADA

Indication In SCADA & Interlocking


4 LIT-101A/102A SBR Tank Level Indicating Transmitter Ultrasonic 2 No 0 6000 mm AI
with Decanter Operation

5 LS-101B/102B SBR Tank Level Switch Conductivity/Displacer 2 No 0 6000 mm AI Indication In SCADA

6 LS-001/002 PE Dosing Tank Level Switch Conductivity/Displacer 2 No 0 1000 mm DI Indication In SCADA

7 LS-003 Chlorination Tank Level Switch Conductivity/Displacer 1 No 0 3000 mm DI Indication In SCADA

8 LS-004 Plant Drain Sump Level Switch Conductivity/Displacer 1 No 0 3000 mm DI Indication In SCADA

9 LS-005 Treated Water tank Level Switch Conductivity/Displacer 1 No 0 3000 mm DI Indication In SCADA

10 PG-001/002/003 Blower Outlet Pressure Indicator Diaphragm 3 No 0 2 kg/cm2 NA NA

11 PG - 004/005 Service Water Pump Pressure Indicator Bourden 2 No 0 4 kg/cm2 NA NA

12 UFM-002 Parshall Fume Outlet Differential Level Indicating Transmitter Ultrasonic 1 No 0 3000 mm AI Indication In SCADA

pH- PotentiometricTSS- Light


pH, TSS/TOC/ COD / BOD, NH4-N / Total TOC: 0 - 200 ppmCOD: 0 - 500
ScatteringCOD/ BOD- UV
Nitrogen,Residual Chlorine Sensor with ppmBOD: 0 - 165 ppmTSS: 0 - 1500
SpectroscopyNH4-3, Total
13 AIT-001 Plant Outlet Chamber Cable & Flow Through Assembly, 4 - 20 mA 1 No ppmNO3: 0 - 100 ppmNH4: 0 - 100 RS-485/AI Indication In SCADA
Nitrogen - UV
output, RS 485 Output, Digital Display, ppm NH4+TN: 0 - 200 ppmpH: 0 - 14
SpectroscopyResidual
Panel Mounted Installation, pH
Chlorine- Ampearometric

TOC: 0 - 200 ppmCOD: 0 - 500


pH, TSS/TOC/ COD / BOD, NH4-N / Total pH- PotentiometricTSS- Light
ppmBOD: 0 - 165 ppmTSS: 0 - 1500
Nitrogen Sensor with Cable & Flow Through ScatteringCOD/ BOD- UV
14 AIT-002 Plant Outlet Chamber 1 No ppmNO3: 0 - 100 ppmNH4: 0 - 100 RS-485/AI Indication In SCADA
Assembly, 4 -20 mA output, RS 485 Output, SpectroscopyNH4-3, Total
ppm NH4+TN: 0 - 200 ppmpH: 0 - 14
Digital Display, Panel Mounted Installation, Nitrogen - UV Spectroscopy
pHCl2: 0 - 20 ppm