ET-PW/DS-06/01-VR-

DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

PLC & HMI VALIDATION REPORT

FOR

PW/DISTRUBUTION SYSTEM-06/01
(PW/DS-06/01/HMI-01)

HETERO DRUGS LTD.


UNIT-I
BONTHAPALLY

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 1 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

Table of Contents
1 Introduction..............................................................................................................................3
2 Purpose.....................................................................................................................................3
3 Scope........................................................................................................................................3
4 References................................................................................................................................3
4.1 Glossary.............................................................................................................................3
5 Tests to Perform.......................................................................................................................4
6 Signature Log...........................................................................................................................4
7 Test Cases................................................................................................................................5
7.1 Verification of HMI and PLC Make and Model No.........................................................5
7.2 Verification of PLC Inputs and Outputs...........................................................................6
7.3 Navigation Testing..........................................................................................................11
7.4 Screen Functionality Testing...........................................................................................12
7.5 Set Parameters Screen Testing........................................................................................15
7.6 Alarm testing...................................................................................................................18
8 Deviation Reports Log...........................................................................................................20
9 Conclusion.............................................................................................................................21
10 Approval Form.......................................................................................................................21

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 2 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

1 Introduction
This document describes the PLC and HMI Validation of PW/DISTRIBUTION
SYSTEM-06/01 for Hetero Drugs Ltd Unit-1.
2 Purpose
This document details the PLC and HMI Validation is to ensure that the system software
complies with the user requirements.
3 Scope
This scope includes testing the software of the PLC and HMI software used to control the
PW/DISTRIBUTION SYSTEM-06/01 as per the user requirements.
1 References
The table below lists the documents and drawings used in the development of this document.
Table a
Description Document Number Document Date Revision

1.1 Glossary
Table b
Acronym Description
HMI Human Machine Interface
PLC Programmable Logic Controller
QA Quality Assurance
DR Deviation Report

2 Tests to Perform

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 3 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

Table c
Test ID Test Name Test Objective
Verification of
7.1 To verify the HMI and PLC Make and Model No
Hardware Components
Verification of PLC
7.2 To verify the functionality of Inputs and Outputs.
Inputs and Outputs
7.3 Navigation Testing To verify the HMI screens Navigation

7.4 Set Parameters Testing To verify the Set Parameters functionality

7.5 Alarm Testing To verify the Alarm functionality

3 Signature Log
The purpose of the signature log is to capture the names and signatures of all individuals
who executed any part of this Report. Participant should record his/her name, company
affiliation, personal signature, and personal initials in this log.

Signature Log
Name Company Signature Initials

7 Test Cases

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 4 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

Tester Name

Tester Signature

Test Date

Test Case Results

3.1 Verification of HMI and PLC Make and Model No

S. No Description / Action Result Acceptance Signature &


(Yes/No) Date

Check the PLC make and MITSUBISHI


1
model No FX3u-32M

MISTUBISHI
2 Check the PLC Analog Input
FX2N-8AD

MISTUBISHI
3 Check the PLC Analog Output
FX2N-2DA

Check the HMI make and model MISTUBISHI


4
No GT2507-WTBD

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 5 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

3.2 Verification of PLC Inputs and Outputs

S. No Description / Action Result Acceptance Signature &


(Yes/No) Date

Digital Inputs

Source the +24VDC to the input


1 ‘Feedback’ status will change
IP:0.0

Source the +24VDC to the input


2 ‘Feedback’ status will change
IP:0.1

Source the +24VDC to the input


3 ‘Feedback’ status will change
IP:0.2

Source the +24VDC to the input ‘ Mother loop Healthy’ status


4
IP:0.3 will change
Source the +24VDC to the input ‘Electric board power on ’
5
IP:0.4 status will change
Source the +24VDC to the input
6 Control on
IP:0.5

Source the +24VDC to the input


7 Hooter reset
IP:0.6
Source the +24VDC to the input
8 Spare
IP:0.7

Source the +24VDC to the input


9 Spare
IP:0.8

Source the +24VDC to the input


10 Spare
IP:0.9

Source the +24VDC to the input


11 Spare
IP:0.10

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 6 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

S. No Description / Action Result Acceptance Signature &


(Yes/No) Date

Source the +24VDC to the input


12 Spare
IP:0.11

Source the +24VDC to the input


13 Spare
IP:0.12

Source the +24VDC to the input


14 Spare
IP:0.13

Source the +24VDC to the input


15 Spare
IP:0.14

Source the +24VDC to the input


16 Spare
IP:0.15
Source the +24VDC to the input
17 Spare
IP:0.16

Source the +24VDC to the input


18 Spare
IP:0.17

Digital Outputs

+24VDC will measures in


19 Start ‘VFD’
output OP:0.0

+24VDC will measures in


20 Start ‘F201A’
output OP:0.1

+24VDC will measures in


21 Start ‘F201B’
output OP:0.2

+24VDC will measures in


22 Start ‘Tank inlet valve’
output OP:0.3

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 7 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

S. No Description / Action Result Acceptance Signature &


(Yes/No) Date

+24VDC will measures in


23 Start ‘Tank steam valve’
output OP:0.4

+24VDC will measures in


24 Start ‘Return line dumping’
output OP:0.5

+24VDC will measures in


25 Start ‘UV201 Relay’
output OP:0.6

Start ‘EH 201 vent filter heat +24VDC will measures in


26
tracer Relay’ output OP:0.7

Start ‘Water request to mother +24VDC will measures in


27
loop Relay’ output OP:10

+24VDC will measures in


28 Start ‘Hooter’
output OP:11

+24VDC will measures in


29 Start ‘Alarm lamp’
output OP:0.12

+24VDC will measures in


30 SPARE
output OP:0.13

+24VDC will measures in


31 SPARE
output OP:0.14

+24VDC will measures in


32 SPARE
output OP:0.15

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 8 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

S. No Description / Action Result Acceptance Signature &


(Yes/No) Date

+24VDC will measures in


33 SPARE
output OP:0.16

+24VDC will measures in


34 SPARE
output OP:0.16

Analog Input

‘CT201 Transmitter’ values


35 Source the 4-20mA in AI1.0
will change

‘LT201 Transmitter’ values


36 Source the 4-20mA in AI1.1
will change

‘FT201 Transmitter’ values


37 Source the 4-20mA in AI1.2
will change

‘TT201 Transmitter’ values


38 Source the 4-20mA in AI1.3
will change

‘TT202 Transmitter’ values


39 Source the 4-20mA in AI1.4
will change

‘IM201 Transmitter’ values


40 Source the 4-20mA in AI1.5
will change

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 9 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

S. No Description / Action Result Acceptance Signature &


(Yes/No) Date

41 Source the 4-20mA in AI1.6 Spare

Analog Output

1 Measure the 4-20mA in AO1.0 Spare

3.3 Navigation Testing

S. No Description / Action Result Acceptance Signature &


(Yes/No) Date

1 Click on the Main button Main screen will open

2 Click on the Login button Login screen will open

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 10 of 20


ET-PW/DS-06/01-VR-
DOCUMENT #
001
PLC & HMI VALIDATION REPORT
REVISION 00
DATE: 26-04-2021
EQUIPMENT NAME: PW/DISTRIBUTION SYSTEM-06/01
LOCATION: HETERO DRUGS LTD, BONTHAPALLY

S. No Description / Action Result Acceptance Signature &


(Yes/No) Date

3 Click on the Mode button Mode screen will open

Click on the Set Parameters Set Parameters screen will


4
button open

5 Click on the Start/stop button Start/stop screen will open

6 Click on the Alarm button Alarm screen will open

7 Click on the Settings button Settings screen will open

Access management screen


8 Click on Access management
will open

9 Click on HMI utilities HMI utilities screen will open

10 Click on Raw value Raw value screen will open

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 11 of 20


3.4 Screen Functionality Testing

S. No Description / Action Result Acceptance Signature &


(Yes/No) Date

Main screen will open


The following go to screen
Select and Press Enter main
11 buttons are available
button in welcome screen
Home, mode, Set parameters,
login,start/stop,alarms,settings,
Mode screen will open
The following go to screen
Select and Press Enter mode
12 buttons are available
button in main screen
Auto,manual,hot water
sanitization,off
Set parameters screen will
open
The following go to screen
buttons are available
Select and Press Enter set STT201
13
parameters button in main screen parameters,TT201/202
parameter,CT/IM201
parameters,LT201
parameter,FT201
parameter,P201A/B parameter
login Screen will open
Select login button main The following go to screen
14
screen buttons are available
Login/logout, password change
Login Screen will open
Select password change button in The following go to screen
15
login screen buttons are available
Switch,logout,cancel
Start/stop Screen will open
Select start/stop button in main The following go to screen
16
Screen buttons are available
Start,stop

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 12 of 20


S. No Description / Action Result Acceptance Signature &
(Yes/No) Date

alarms Screen will open


The following go to screen
Select alarms button in main buttons are available
17
Screen Date,time message,hotter reset,
delete alarm, delete
alarms,alarm reset

Settings screen will open


The following go to screen
buttons are available
CT201-return line
Select settings button in Main conductivity, LT201-pw tank
18
screen level, FT201 return line
flow,TT201 return line
temperature,TT202 tank
temperature, STT201 vent
filter temparature.

Access management will open


The following go to screen
Select access management in buttons are available
19
settings screen Mode select, manual mode, set
parameters, analog simulation,
controller, alarm reset
HMI utilities screen will open
The following go to screen
Select HMI utilities settings
20 buttons are available add,
screen
import, export

Raw value screen will open


Select raw value screen in The following go to screen
21
settings screen buttons are exit,home, access
management, hmi utilities

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 13 of 20


3.5 Set Parameters Screen Testing

S. No Description / Action Expected Result Actual Result Signature


& Date

Alarm Set Points

Click on STT201 set point and


STT201 set point value will be STT201 Alarm
1 try to change the values
changed will indicate
TT201/202
Click on TT201/202 set point TT201/202 set point value
2 Alarm will
and try to change the values will be changed
indicate

CT/IM201
Click on CT/IM201 set point and CT/IM201 set point value will
3 Alarm will
try to change the values be changed
indicate

LT201 set point value will be


Click on LT201 set point and try LT201Alarm
4 changed
to change the values will indicate

Click on FT201 set point and try FT201 set point value will be FT201 Alarm
5
to change the values changed will indicate

P201A/B
Click on P201A/B set point and P201A/B set point value will
6 Alarm will
try to change the values be changed
indicate
Click on STT201
STT201 set point value will be STT201 Alarm
7 SanitizationTime Min set point
changed will indicate
and try to change the values
STT201
Cumulative
Click on STT201 Cumulative
STT201 Cumulative Time Min Time Min set
8 Time Min set point and try to
set point value will be changed point value
change the values
will be
changed

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 14 of 20


S. No Description / Action Expected Result Actual Result Signature
& Date

STT201Start
Click on STT201 Start up drain up drain min
STT201 Start up drain Min set
9 Min set point and try to change set point value
point value will be changed
the values will be
changed
TT201/202
Vent filter off
Click on TT201/202 Vent filter TT201/202 Vent filter off sp
sp min set
10 off sp Min set point and try to Min set point value will be
point value
change the values changed
will be
changed
TT201/202 -Ve
Control
Click on TT201/202 -Ve Control TT201/202 -Ve Control
hysteresis min
11 hysteresis Min set point and try hysteresis Min set point value
set point value
to change the values will be changed
will be
changed
TT201/ 202
Temparature
Click on TT201/202 Temparature TT201/202 Temparature low
low min set
12 low Min set point and try to Min set point value will be
point value
change the values changed
will be
changed
TT201/ 202
Temparature
Click on TT201/202 Temparature TT201/202 Temparature high
high min set
13 high Min set point and try to Min set point value will be
point value
change the values changed
will be
changed
CT201 H min
Click on CT201 H Min set point CT201 H Min set point value set point value
14
and try to change the values will be changed will be
changed
CT201HH min
Click on CT201 HH Min set CT201 HH Min set point set point value
15
point and try to change the values value will be changed will be
changed

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 15 of 20


S. No Description / Action Expected Result Actual Result Signature
& Date

CT201HH
Click on CT201 HH dumping dumping time
CT201 HH dumping time Min
16 time Min set point and try to min set point
set point value will be changed
change the values value will be
changed
CT201 IM201-
Click on CT201 IM201-L sp Min L sp min set
CT201 IM201-L sp Min set
17 set point and try to change the point value
point value will be changed
values will be
changed
LT201 HH sp
Click on LT201 HH sp Min set LT201 HH sp Min set point min set point
18
point and try to change the values value will be changed value will be
changed
LT201 H sp
Click on LT201 H sp Min set LT201 H sp Min set point min set point
19
point and try to change the values value will be changed value will be
changed
LT201 L sp
Click on LT201 L sp Min set LT201 L sp Min set point min set point
20
point and try to change the values value will be changed value will be
changed
LT201 LL sp
Click on LT201 LL sp Min set LT201 LL sp Min set point min set point
21
point and try to change the values value will be changed value will be
changed
P201A/B
Normal mode
Click on P201A/B Normal mode P201A/B Normal mode fixed
spees sp Min
22 fixed speed sp Min set point and speed sp Min set point value
set point value
try to change the values will be changed
will be
changed
P201A/B
Click on P201A/B Draining Draining speed
P201A/B Draining speed set
23 speed Min set point and try to Min set point
point value will be changed
change the values value will be
changed

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 16 of 20


3.6 Alarm testing

S. No Description / Action Result Acceptance Signature &


Date
(Yes/No)

Low levcl in distribution storage Alarm actuates and distribution


1
tank pump and UV system will trip

Mid-level in distribution storage Distribution pump and UV


2
tank system will trip

High levcl in distribution storage Distribution storage tank inlet


3
tank valve will open

High High level in distribution Distribution storage tank inlet


4
storage tank valve will close
Alarm actuates and VFD will
Return line flow transmitter flow increase the return line flow by
5
below set point increasing of distribution pump
speed
VFD will decrease the return
Return line flow transmitter flow
6 line flow by decreasing of
more than set point
distribution pump
Return line conductivity meter
7 Alarm actuates
conductivity more than alert limit
Return line conductivity meter
Alarm actuates and return line
8 conductivity more than action
dump valve will open
limit
Return line temperature
Steam line inlet valve will
9 transmitter temperature below set
open
point
Alarm actuate and return line
10 Hot water sanitization cycle over
dump valve will open

Hot water sanitization cycle Alarm actuates and distribution


11
aborted pump will trip

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 17 of 20


______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 18 of 20


4 Deviation Reports Log
Deviation Report Log
Report Date Date
Test ID Incident Description
# Initiated Resolved
5

Conclusion

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 19 of 20


Signature & Date

6 Approval Form
Reviewed by: Name & Department Signature& Date

Entune Labs Pvt. Ltd.


Hyderabad

Reviewed by: Name & Department Signature& Date

Hetero Drugs Ltd. (Unit-I)


Bonthapally

Approved by: Name & Department Signature& Date

Hetero Drugs Ltd. (Unit-I)


Bonthapally

______________________________________________________________________

Proprietary Information of Entune Labs Pvt. Ltd. Page 20 of 20