Automatic transfer switches

Open Magnum ATS


Product description Commercial design highlights
Magnum姠 automatic transfer • Open enclosure
switches (ATS) can be applied
• Fixed mount only
for those applications requiring
high interrupting ratings for criti- • Magnum power case
cal standby power applications. switches or power case
For applications requiring an breakers
integrated solution with the ATS
• Fastest switching times
mounted in a larger distribution
available (<3 cycles)
lineup, the Magnum ATS can be
supplied in an open enclosure. • Source-1 and Source-2
All of the key electrical connections front accessible
components that comprise • Load connections—bus
a Magnum transfer switch connection in rear
are mounted on a vertical
chassis. This chassis can easily
be mounted inside the larger Features
distribution lineup. The ATC
• High withstand capability
controller and its associated
device panel are shipped loose • Stored energy
for mounting on the distribution switching device
lineup structure door. Optional
wire harness extenders are
• Ability to test power switching
available. The Magnum ATS devices in TEST position
option/transformer panel is • Safe to transfer manually
shipped loose for mounting under full load
beneath the vertical chassis.
• Compact design
The Source-1 and Source-2
power connections are • Multi-tap voltage selection
accessible from the front. transformer
The load connections are • Features the ATC-600 or
accessible from the rear and ATC-800 controller
are typically bussed to the
distribution lineup. • Optional service
entrance rated

Electrical ratings
• Ratings 200, 300, 400, 600,
800, 1000, 1200, 2000, 2500,
3000 and 3200 amperes
• Three- or four-pole
• Up to 600 Vac, 50/60 Hz
• UL姞 1008
• CSA姞 C22.2
• 100% rated
• 85 kA withstand
• Open or closed transition
• 30-cycle withstand rating
Source-1
Normal Source-1 Normal
Bus Connection
(front accessible)

Load Bus Mounting


ATC Connections Flanges
Controller (rear access only)
Source-2
Emergency
Source-2
Emergency Bus
Connections
Transformer
(front accessible)
Panel
Open Magnum Open Magnum Open Magnum
Front View (as shipped) Rear View Rear View

The open Magnum is shipped on a single pallet with the ATC The connections to the Source-1, Source-2 and load bus are made
controller/device panel, option/transformer panel and neutral in the back of the structure. Terminals are not supplied unless
(if ordered), all side attached to the open Magnum chassis. The ordered separately. When mounting the open Magnum chassis in
ATC controller and the device panel are mounted on a bracket for a larger distribution structure, the load connections are typically
shipping purposes only. The open Magnum chassis has two side bussed. When the load connections are bussed, then the Source-1
mounting flanges on each side used to support the chassis in the and Source-2 connections are front accessible.
distribution gear.

Option/
Transformer
Panel

Wire
Harness
Extender
(optional)
Neutral Assembly
(optional)

A neutral assembly—if ordered—is mounted on the back on the Optional 96-inch wire harness extenders are available for those
Magnum chassis only for shipping purposes. Once installed into applications where additional wire harness length is required
the larger distribution equipment, the neutral can be mounted as between the ATC controller and the main Magnum mounting
required inside the larger assembly. Typically the larger distribution chassis. The option/transformer panel is typically mounted beneath
equipment has its own neutral assembly, and the Magnum neutral the Magnum chassis. In addition to the multi-tap transformer, it will
assembly is not required. also contain additional relays, optional service entrance fused
disconnect and keyed switch.

Front View

The ATC controller and associated device panel are side mounted
for shipping purposes only. Once the open Magnum is integrated
into the distribution equipment, then both the device panel and the
controller will need to be door mounted onto the gear.

2 EATON CORPORATION
15.00
(38.1) 0.22
0.13 5.12 (5.6) 2.13
14.50
(3.3) Typ (130.0) (54.1)
(368.3)
Ø0.39
(Ø9.9) 7.50 4.45
(190.5) (113.0)
0.50 9.38 9.38
(12.7) (238.3) (238.3)
0.00
4.45
(0.0)
(113.0)
0.00 23.00
(0.0) 0.38 22.63 (584.2) Ø0.22
(9.7) 0.26 Depth Behind Door
(574.8) (5.6)
(6.6)
Option/Transformer Panel Front

Device Cutout
ATC-600/800
(Scale: 1 = 0.5)

24.50
(622.3)

Top View

59.00
(1498.6)

59.00
(1498.6)

Rear View

Front View

Three-Pole Four-Pole
A inches (mm) 26.80 (680.7) 31.64 (803.7)
B inches (mm) 23.40 (594.4) 28.24 (717.3)
Weight lbs (kg) 1900 (861.8) 2000 (907.2)
Notes:
Dimensions shown in inches (mm).
CG
Center of gravity.
Automatic, non-automatic, manual and service entrance controls provided based on customer order information.

Magnum ATS Dimensions in Inches (mm)

EATON CORPORATION 3
Withstand Table
Rating When Used with Upstream Rating When Used with Upstream
Transfer Switch Ampere Rating Circuit Breaker 3-Cycle 600V (kA) Fuse 30-Cycle 600V (kA)
200 85 85
300 85 85
400 85 85
600 85 85
800 85 85
1000 85 85
1200 85 85
2000 85 85
2500 85 85
3000 85 85
3200 85 85

Catalog Numbering System—Magnum, Automatic and Non-Automatic Transfer Switches, 200–3200 Amperes

AT V I MG A 3 3200 X K U

Type Certification
AT = Automatic U = UL listed
CT = Closed transition
NT = Non-auto
Switch Amperes Enclosure Position 14

A = Fixed mount, power case Number of Poles 0200 = 200A K = Open


Orientation
switch PCS both 3 = Three-pole 0300 = 300A
V = Vertical
B = Fixed mount, power case 4 = Four-pole 0400 = 400A
Voltage
circuit breaker PCB both 0600 = 600A
Logic C = Fixed mount, PCB normal, 0800 = 800A A = 120V, 60 Hz
I = ATC-600 (open transition) PCS emergency 1000 = 100A B = 208/120V, 60 Hz
I = ATC-800 (closed transition) D = Fixed mount, PCS normal, 1200 = 1200A E = 600V, 60 Hz or 50/60 Hz
PCB emergency 1600 = 1600A E = 600/347V, 60 Hz or 50/60 Hz
2000 = 2000A G = 220/127V, 50 Hz
Frame Size (Amperes)
2500 = 2500A H = 380/220V, 50 Hz
MG = Magnum DS 3000 = 3000A O = 415/240V, 50 Hz
3200 = 3200A W = 240V, 60 Hz
X = 480V, 60 Hz or 50/60 Hz
X = 480/277V, 60 Hz or 50/60 Hz

The catalog number ATVIMGA33200XKU The continuous current rating of this equipment
describes an ATS with the switching devices is 3200A and is applicable at 480/277 Vac, 60 Hz.
mounted vertically on a chassis in an open The transfer switch equipment is an open
enclosure. The intelligence, represented by enclosure and is listed for Underwriters
the ATC-600 is a microprocessor-based logic Laboratories UL 1008 and Canadian Standards
package. The Magnum breaker is used as the Association (CSA) applications.
switching device and is a three-pole power
case switch for each source.

Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com

© 2010 Eaton Corporation PowerChain Management is a registered


All Rights Reserved trademark of Eaton Corporation.
Printed in USA
Publication No. PA01602015E / Z9164 All other trademarks are property of their
February 2010 respective owners.

You might also like