InRow Direct Expansion 600mm
Up to 37kW – minimum ~8kW IT load (standard), ~2kW IT load (precision)

Features and Benefits


• High density cooling
– Up to 37kW, 4000 SCFM (6796 m3/h) max airflow

– Small 600mm wide footprint

• Energy efficient
– 9.5kW rated power consumption
(35C RAT, 11.1C DP, 35C Ambient, 20.8C SAT, 100% airflow, 65Hz compressor)

– VFD scroll compressor (R-410A)

– Variable speed EC fans

• Precision control: humidification/reheat (optional)

• 4.3” touchscreen display w/ network card


(with TLS support) Front left view of the air cooled precision
600mm wide InRow DX
Additional features: EcoAisle® compatibility ∙ Active Flow Control® compatibility ∙ External brazed plate heat exchanger (App
Note 141) ∙ condensate removal ∙ supply air temp control ∙ integrated network card ∙ top or bottom piping ∙ top or bottom
electrical connections ∙ high efficiency filtration ∙ high head pressure detection

Confidential Property of Schneider Electric | Page 2


Two Control Strategies
Active Response Control actively responds to both thermal and airflow changes

1. Temperatures change entering IT Equipment 1. Pressure changes inside the contained aisle
2. InRow temperature probes Sense changes and send signal to controller 2. Active Flow Controller senses pressure change.
3. Controller adjusts cooling capacity to balance with the heat load 3. Active Flow Controller adjusts cooling fans to balance with the IT airflow
4. Active Response Controls ensures IT equipment is kept at the proper 4. Active Response Controls ensures IT equipment is kept at the proper
temperature temperature

Confidential Property of Schneider Electric | Page 3


Performance Summary
Return Air Temp Fan Speed Airflow Unit Power Condenser Fan Power Net Sensible Capacity Supply Air Temp
C (F) % l/s (SCFM) kW kW kW (BTU/hr) C (F)
30 600 (1200) 2.89 0.96 11.3 (38600) 12.9 (55.2)*
40 800 (1600) 2.93 0.98 13.1 (44700) 15.0 (59.0)*
50 900 (2000) 2.98 1.00 13.9 (47500) 17.2 (63.0)*
60 1100 (2400) 3.12 1.02 14.5 (49500) 18.8 (65.8)*
29.4C (85F)
70 1300 (2800) 3.86 1.05 17.1 (58400) 18.7 (65.7)
80 1500 (3200) 4.11 1.05 17.4 (59400) 19.9 (67.8)
90 1700 (3600) 5.01 1.05 19.7 (67300) 19.8 (67.6)
100 1900 (4000) 5.78 1.05 19.9 (67900) 20.8 (69.4)
30 600 (1200) 2.88 0.99 13.4 (45800) 15.4 (59.7)*
40 800 (1600) 2.91 1.02 14.9 (50900) 18.7 (65.7)*
50 900 (2000) 3.54 1.05 17.9 (61100) 19.3 (66.7)
60 1100 (2400) 4.29 1.05 20.9 (71400) 19.8 (67.6)
35.0C (95F)
70 1300 (2800) 5.12 1.05 23.6 (80600) 20.3 (68.5)
80 1500 (3200) 6.07 1.05 26.1 (89100) 20.8 (69.4)
90 1700 (3600) 7.09 1.05 29.2 (99700) 20.8 (69.4)
100 1900 (4000) 9.50** 1.05 32.9 (112300) 20.8 (69.4)
30 600 (1200) 2.86 1.02 14.9 (50900) 18.8 (65.8)*
40 800 (1600) 4.08 1.05 20.4 (69700) 18.3 (64.9)
50 900 (2000) 4.8 1.05 23.9 (81600) 19.7 (67.5)
60 1100 (2400) 6.36 1.05 28.7 (98000) 19.6 (67.3)
40.6C (105F)
70 1300 (2800) 7.33 1.05 31.7 (108200) 20.8 (69.4)
80 1500 (3200) 9.19 1.05 36.1 (123300) 20.8 (69.4)
90 1700 (3600) 11.57 1.05 40.7 (139000) 20.8 (69.4)
100 1900 (4000) 12.47 1.05 41.9 (143100)*** 22.5 (72.5)***
*In this case, the compressor will cycle because its speed is down to the minimum of 25 Hz. Min load condition is indoor RAT 18C, compressor 25Hz, fan @ 30%, Outdoor RA DB 46C. Capacity is 8kW.
The minimum fan speed for the InRow mode is 30%; the minimum fan speed for HACS and RACS mode is 40%.
Note: Outdoor temperature is 35°C (95°F)
Data represents performance without humidification or reheat
**Previous (ACRD5XX) unit power consumption 15kW for same capacity and supply air temperature.
***Previous (ACRD5XX) unit net sensible capacity 36.5kW and supply air temperature 26.1C
Comparison with the previous model
Electrical & Sound Data
Model Heater Humidifier Max Unit Power
kW kW kW
ACRD600
ACRD601 N/A N/A 14.6*
ACRD602
ACRD600P 2.3 – 3.3 (200-240VAC)
ACRD601P 3.0 – 3.3 (460-480VAC) 2.25 23.5*
ACRD602P 2.8 – 3.3 (380-415VAC)
*Evaluated at maximum allowable operating conditions of: 39C DB, 11.1C DP, 46C Ambient, 100% Fan Speed, 78Hz Compressor

Fan Speed Airflow Sound Power Lp Sound Pressure


% m3/s (SCFM) dBA at Frequency Hz re: 10-12 W dBA, re: μPa
50 0.95 (2000) 84.1** 71.1*
75 1.43 (3000) 88.1** 75.0*
100 1.89 (4000) 96.3** 83.3*
*Weighted Sound Pressure dBA at 4.9ft (1.5m) height and 6ft (1.8m distance).
**Based on compressor operating at 65Hz rated speed.
Unit Components
Electrical Panel Inteface Panel
1. Transformers

2. User interface connectors

3. Main controller board

4. Relay board

5. Ground lug

6. Main circuit breaker

7. Compressor fuse block &


Compressor circuit breaker

8. Fan circuit breaker

9. Controller fuse

10. Heater circuit breaker (P models)

11. Humidifier circuit breaker (P models)

12. Heater contactors (P models)

13. Humidifier contactor (P models)


User Interface & Network Management Card
Network Management Card is built into the user interface

• 4.3” User friendly Touchscreen • Real-time monitoring

Status, Log, and Control Functions Accessory/Service Ports


Warning Lights
Front & Rear Door
New door: perforations for higher airflow and better placement of User Interface.
Compressor & VFD
Minimum restart time only ~48 sec (from zero to full cool)

• Energy efficient scroll compressor


• Variable frequency driven

• Refrigerant Type: R-410A

• Noise Cover - Reduces the sound pressure level 3 dB(A).

• Compressor Protection
• Low/High Suction Protection

• High Discharge Protection

• Pressure Equalization

• Oil Return

• Pump-down cycle

• Lead/lag control and heat assist mode*


* = precision models only
Electronic Expansion Valve

• EEV has independent valve control linked to main


unit controller
• Pressure & temperature measurement in one package

• Precise control of super-heat and sub-cooling


• Faster response time to temperature change
• Increased COP drives better energy efficiency
Variable Speed Fan Assembly
Two fans per cooling unit

• Variable Speed Fans


• Speed is adjusted from 30-100% for improved control and energy savings
during off peak cooling conditions.

• Backward Incline, direct drive motors


• Plug connections ensures low time to repair.
• High reliability fans with integrated EC motors.
• Power consumption < 1kW @ 100% speed – 3 Phase Power
Modes of Operation

Mode of Fan control Airflow Air temperature Description


operation
without Active Flow Cool Setpoint Supply Air Setpoint The fan speed is controlled by comparing the rack
Control inlet temperature to the cooling set point. As the rack
(Sensor: Remote (Sensor: Internal Supply Air Sensor) inlet temperature deviates the fan speed adjusts to
Rack Inlet Sensor) compensate. The air temperature is controlled to the
InRow / CACS Supply Air Setpoint
with Active Flow AFC Bias Supply Air Setpoint (CACS mode only) The differential pressure reading
Control (CACS mode controls the fan speed while the air temperature is
only) (Sensor: Active Flow (Sensor: Internal Supply Air Sensor) controlled to the Supply Air Setpoint
Controller)
without Active Flow Fan Speed Supply Air Setpoint Fan speed is controlled by the fan speed preference
Control Preference Setting setting. As return air temperatures deviate from the
(Sensor: Internal Supply Air Sensor) fan speed preference setting, the fan speed adjusts
(Sensor: Return Air to bring the ∆T back to the original fan speed
Sensor – Supply Air preference. The air temperature is controlled to the
RACS / HACS Setpoint) Supply Air Setpoint
with Active Flow AFC Bias Supply Air Setpoint The differential pressure reading controls the fan
Control speed, the controller utilizes differential pressure
(Sensor: Active Flow (Sensor: Internal Supply Air Sensor) data supplied by the AFC(s) to supply the correct
Controller) amount of airflow. The air temperature is controlled
to the Supply Air Setpoint
Fan Speed Preference
This mode sets the dT setting to the cooling unit determined by the combined server dT.

• For high delta T servers the fan speed


setting of the cooling unit can be set to HACS/RACS Mode Fan Speeds
low
Speed Range Desired Temp Difference
• For lower delta T servers the fan speed
setting of the cooling unit can be set to Low 16.7C (30F)
high Med-Low 13.9C (25F)
Med 11.1C (20F)
• Fans will automatically adjust to maintain Med-High 6.3C (15F)
a constant return air temperature High 5.6C (10F)
• RAT = Supply Air Setpoint + dT

• This setting can be changed on the user


interface.
Setpoints
Target temperature values that a cooling group tries to maintain at the rack.

• Cooling Setpoint
• Controlled via Rack Inlet Temp Sensor (3 per unit)

• Controls the speed of the fans.

• Satisfies the server inlet temperature. Rack Inlet Temp Sensor


0J-0W2818A (spare)
• PID Controlled

• Uses max rack inlet temp reading as process variable

• Supply Air Setpoint


• Controlled via internal Supply Air Temp Sensor

• Controls the VFD

• Satisfies the temperature of the air expelled

• PID Controlled
Condensate Pump

• Removes condensate from the system to ensure continuous


operation
• Benefit: lower supply air temperatures
• Capacity:
• Maximum lift: 3,5 meters (11.5 ft.)

• Flowrate: 32 litres/hour (0.75 GPM)

• Maximum water temperature: 100 °C (212 °F)

• High level alarm Hartell KL-1AP-2


APC part # 491-0523A
• Integrated one way valve
Filtration
Removes particulate from the air to keep cooling coil clean

• Standard filter
• 30% filters UL 900 Class I/II (Merv 8 / G4)

• High efficiency filter (optional)


• 85% filters UL 900 Class II (Merv 13 / F7)

• Size: 470 x 418 x 96 mm


• Filters can be temporarily removed to increase cooling unit airflow
Humidity Control
Used to add or replace humidity within data center

• Internal Humidifier • Internal Humidity Sensor


• Electric immersed electrodes steam humidifier • Dew Point control is used
• Optional: feature within (P models) • Measures the humidity between 20-90%RH

• Variable Capacity Control • Connects to the unit with a RJ45 connector


• One sensor placed in supply air, and one in the
• Replaceable cylinders return air
• Setpoint range RH 25.0% - 50.0 % • Used for Humidity control of the room and for
Intellegent Water Carry Over operation
Reheat
Satisfies the humidity in the room or used for heat assist mode

• Heaters are protected against fan drop out


• Dual thermal protection on heaters manual and automatic resetteble.
• High capacity 3kW each, 6kW total
• Easy servicability
• UL and VDE approved
• Setpoint range RH 35.0% - 60.0 %,
• Internal dew point control is used :
• Fans speed in dehumidification mode : 40 %
Piping Connections
External Refrigerant and Condensate Piping Connections

 Refrigerant Liquid Line


Rotalock ¾” Piping 1 ¼” Thread

 Refrigerant Discharge Line


Rotalock ¾” Piping 1 ¼” Thread

 Humidifier Water Supply


Quick Coupling Colder

PEX tube ½” ID 5/8” OD

PEX tube 10mm ID 15mm OD

 Condensate Drain
Quick Coupling Colder

PEX tube ½” ID 5/8” OD Top Bottom

PEX tube 10mm ID 15mm OD


Top & Bottom Power Routing
Designed for underfloor power routing or overhead busway.

• Hardwire connection
• On-site configurable
• Conduit routed directly through top or bottom of unit to main breaker
• Cover plates provided
Communication
Four types of standard communication provided below

• Front Display
• Each unit can be configured and operated via the display on the front door

• Network Card
• Each unit can be accessed via local network (Ethernet)

• BMS (Building Management System)


• Each unit can be monitored via MODBUS

• Group Control (A-link)


• Can be configured and communicating together in groups

• Up to 12 units

• PID fan control (based off max rack inlet temp)

• Supply Air control is handled by each unit independently of the group.


Alarms
Divided between minor alarms and critical alarms

• Thresholds • Condensate Pump (overflow)

• When the monitored input exceeds the unit threshold, an • Compressor (VFD)
alarm will occur. Temperature and Humidity
• Fan #n failure
• Communication failures : • Heater #n failure
• Internal (Network card and R2) • Filter sensor failure
• Humidifier • Humidifier alarms
• VFD
• Water detected
• Component failures :
• Temperature sensors

• Humidity sensors

• Pressure sensors
Agency Approvals and Marks

• UL/cUL Listing (ACRD600, ACRD600P, ACRD601, ACRD601P)


• According to UL 1995 and CSA 22.2 No.236

• CE (ACRD602, ACRD602P)
• EN60335-1, EN60335-2-40

• EN55022, EN55024

• IEC61000-3-2, IEC61000-3-3

• EAC (Russia) (ACRD602, ACRD602P)


• C-Tick (Australia & New Zealand) (ACRD602, ACRD602P)
Warranty and Services

• Standard Factory Warranty


• 1 Year Parts

• 1 Year Parts and Labor with Factory Start-Up Service

• Service Offers*
• Assembly

• Start-Up

• Preventive Maintenance

• On-Site Warranty Extension (parts, labor, and Prev Maint)

• Extended Compressor Warranty (parts only)

• Advantage Plans

*Refer to the Statements of Work for specific details and exclusions


Condensers & Receivers GCN-GB & EMEA-PED
A full line of condensers and receivers is provided to match your voltage and compliance needs

• Vertical/horizontal condenser placement


• All condensers have a flooded receiver with heater for low ambient
conditions – (max 200 ft equivalent length…61 meters)
• Condenser includes AC fans; indoor unit uses EC fans
• ACAC7233-C condenser uses EC fans
NAM-ASME
• ETL, CE, GB, ASME, PED certifications

Description Capacity Condition Specs Certification


ACCD75228 Condenser 38kw 95° (35°C) 208-230V/3 50/60Hz ETL
ACCD75229 Condenser 46kw 115°F(46°C) 208-230V/3 50/60Hz ETL
ACCD75230 Condenser 38kw 95°F (35°C) 460V/3 50/60Hz ETL
ACCD75231 Condenser 46kw 115°F (46°C) 460V/3 50/60Hz ETL
ACCD75232 Condenser 46kw 95°F/115°F (35°C/46°C) 230V/1 50Hz (none)*
ACCD75232-C Condenser 46kw 95°F/115°F (35°C/46°C) 230V/1 50Hz CE
ACCD75233-C Condenser 46kw 95°F/115°F (35°C/46°C) 230V/1 60Hz CE
ACAC75013 Flooded Receiver 20L down to -4°F (-20°C) 219mm dia 640mm length GB**
ACAC75014 Flooded Receiver 20L down to -4°F (-20°C) 219mm dia 640mm length ASME**
ACAC75015 Flooded Receiver 20L down to -4°F (-20°C) 219mm dia 640mm length PED**
* No major certification requirements for GCN region.
** Safety requirements: GB for GCN, ASME for NAM, PED for EMEA
Accessories
Part numbers included:

• Rope Leak Detector • EcoAisle


• AP9326 (extension) • RACS
• Spare Filters • ACCS1001

• MERV8: 0J-875-2013A • Height Adapters


• MERV13: 0J-875-2014 • ACDC2501
• Remote Temp Sensor • ACDC2506

• 0J-0W99952 (spare) • ACDC2513

• Active Flow Control • Power Trough


• ACAC22000 • AR8560

• Data Partition
• ACAC10010
Build Out Tools
Simulate your data center before you build

ISX Designer
EcoStream

Confidential Property of Schneider Electric | Page 29