A.1 GENERAL
Ambient Temperature ⁰C 35
Wet Bulb Temperature ⁰C 28
Relative Humidity % 59
Barometric Pressure
(Before Air Inlet Filter)
mbar 1,013
Power Factor Cos∅ 0.85 (lagging at Delivery Point)
O2 and NOX measurements as per ISO 8178, PM according to VDI 2066 or US EPA
method 17.
The Contractor shall ensure the compliance with the Applicable Laws including but not
limited to the requirements imposed by the relevant environmental authorities of Bangladesh
in relation to the noise measurement of the Facility and obtain all the necessary clearances,
certificates, licenses and permits on behalf of the Employer and ensure compliance of the
terms and conditions included therein.
Threshold Net Power output 100% of the Guaranteed Net Power output as