3 - Phase KVA/KW 50 Hertz

0.8 POWER FACTOR (LAG) AMP CHART COMMON VOLTAGE RATINGS

AMPS PER TERMINAL

KVA KW L-L 200V 208V 220V 230V 240V 380V 400V 415V
L-N 115V 120V --- --- --- 220V 230V 240V

3 2.4 8.7 8.3 7.9 7.5 7.2 4.6 4.3 4.2


6 4.9 17.3 16.7 15.8 15.1 14.5 9.1 8.7 8.4
10 8 29 28 26 25 24 15 14 14
12 9.6 35 33 32 30 29 18 17 17
15 12 43 42 39 38 36 23 22 21
18 14 52 50 47 45 43 27 26 25
20 16 58 56 53 50 48 30 29 28
26 21 75 72 68 65 63 40 38 36
30 24 87 83 79 75 72 46 43 42
39 31 113 108 102 98 94 59 56 54
45 36 130 125 118 113 108 68 65 63
52 42 150 145 137 131 125 79 75 72
60 48 173 167 158 151 145 91 87 84
75 60 217 208 197 188 181 114 108 104
90 72 260 250 236 226 217 137 130 125
120 96 347 333 315 302 289 183 173 167
125 100 361 347 328 314 301 190 181 174
150 120 434 417 394 377 361 228 217 209
200 160 578 556 525 503 482 304 289 279

Chart Notes:
L-L and L-N identifies voltage levels as measured from Line to Line or Line to Neutral respectively.
Power Factor PF = KW / KVA, and is the ratio of True Power to Apparent Power.
Power Factor Rating: Amps shown above are at 0.8PF rating. Actual load PF may differ.
Abbreviations: KVA : Kilo Volt Amperes; KW: Kilowatts; PF: Power Factor; L-L: Line to Line; L-N: Line to Neutral

Chart Instructions:
Find KVA & KW Rating
To find the KVA or KW rating (at 0.8PF) for your application, select the 50HZ three phase L-L (line to line) voltage level being utilized.
Scan down this column to the current needed for your application (select the next higher current rating for more margin). Scan the
row to the left and find the KVA and KW rating needed.

Find Current Rating


To find the phase current rating if the 50HZ load KW or KVA is known, select the known KVA or KW rating on the chart above. Scan
across the row to the right until the three phase L-L (line to line) voltage being utilized column is reached.

Useful Electrical Formulas

KVA = Volts x Amps x 1.732 KW = KVA x Power Factor (PF)


1,000

Amps (When KVA is Known) = KVA x 1,000 Amps (When KW is Known) = __________KW x 1,000_______
Volts x 1.732 Volts x Power Factor (PF) x 1.732

Disclaimer: The content herein is provided for informational purposes only. For technical assistance with your specific 50HZ needs, contact AP&C application engineers.