Minera
Oil-Immersed
Distribution
Transformers
Make the most of your energySM
Minera
Transformers
F - 92506 Rueil Malmaison Cedex (France)
Tél. : +33 (0)1 41 29 70 00 in this publication.
PM103041
applied in your country, a transformer should With more than 80 years of experience and over two
rolled grain oriented silicon steel. The voltages on the primary side of the choice depends on the load losses,
be best adapted to the structure of your million oil-immersed transformers installed worldwide,
stacking of the laminations is either butt transformer, or for increasing or and on the rated power. The shape
distribution network while offering the most you can be sure of investing in a proven technology,
lap or step lap type. The magnetic core decreasing the secondary voltage. of the conductor is either round, Hermetically sealed (without conservator)
cost-effective solution. With a large industrial constantly enhanced in our competence centers. Oil-immersed distribution transformers
is generally of a multi-layer, circular Tappings are provided on the primary rectangular or foil type. To obtain or with conservator
world-wide platform, we offer versatility and
cross section type, where the slitting winding and connected to an off-circuit a controlled temperature gradient, Manufacturing Standards
flexibility and are able to deliver you the Your solution in Minera ANSI, IEC, BS, AS, GOST, IS, IEEE etc.
and cutting of the magnetic core is done tap changer. The operating handle for cooling ducts are added in the coil.
oil-immersed distribution transformer Our standard range of Minera transformers is available Up to 4 MVA
by automatic machines. In order to the hand-operated, off-circuit tap The low voltage winding is built Rated power
to meet your needs. Whatever as: (others rated powers on request)
reduce the sound level of the changer is mounted outside. The around the magnetic core, and an
the transformer type you require, you will • Three phase units
transformer to a minimum, the magnetic standard tapping range is ±2x2.5%. insulating barrier is wound or Insulation level
According to IEC UM=1.1, 3.6, 7.2, 12, 17.5, 24, 36 kV
find your solution in Minera. (single phase available on request)
core and its framework are carefully However we can provide tapping range installed around the low voltage coil According to ANSI up to 36.5 kV
• With ratings up to 4 000 kVA, 36 kV, 50/60 Hz
sized to minimize the vibrations and in as per customer requirement. For in order to provide an electrical Phases 3-phase (single phase is applicable on request)
• With conservator or hermetically sealed type
particular, the magnetostriction effects adjustment operations, the transformer separation between the LV/HV coil.
• Ground, pad or pole-mounted Tappings ±2 x 2.5 % (or different range on request)
which constitute the main sources of needs to be de-energized. However, on
• Naturally cooled (ONAN), air forced (ONAF) With off-circuit tap changer
sound in distribution transformers. In request for special applications, an on Tank construction Voltage regulations
or other type of cooling upon request (regulation with on-load tap changer is available on request)
addition, in order to reduce the no load load tap changer can be provided. The corrugated tank (cooling fins)
• With normal or low noise or loss levels
losses and / or the no load current of is the most common type used for Uk=4 % for P ≤ 630kVA and UM≤24kV
PM102309
the transformer, the quality of the High voltage winding distribution transformers. The cor- Short circuit impedance Uk=4 or 4.5 % for P≤630kVA and UM=36kV
We also offer (upon request) higher ratings up to 100 The high voltage winding material is
magnetic steel and the induction rugated panels are welded onto the Uk=6 % for P > 630kVA
MVA, 170 kV and transformers for special applications
together with the design of the magnetic either copper or aluminum: the choice tank sides. Cooling radiators can also Rated frequency 50 Hz (60 Hz on request)
(rectifier, hazardous area, earthing, welding,
core are carefully chosen to meet the depends on the load losses and on be provided on request. To validate
transformers with OLTC,reactors, solar power plant, wind the rated power. The shape of the Yzn recommended up to 50kVA with UM≤24kV
requirements. the oil-tightness after complete
mill application etc.). Vector groups Yzn recommended up to 100kVA with UM=36kV
conductor is either of a round or assembly, the tank is leak tested
Surface protection rectangular type. To obtain a Dyn11 for all other rated power (any vector group according to IEC Standards)
under gas or liquid over-pressure.
One of our major quality commitment controlled temperature gradient, For hermetically sealed transform- Material thermal class insulation According to IEC 60085 class A
is to provide high-quality surface cooling ducts are added in the coil. High ers, the cooling fins are designed Mean winding temperature rise: 65K
protection. The coating (painting) type voltage coils are in long layers or of disc to compensate for excessive over Top oil temperature rise: 60 K with ambient temperature in accordance with IEC
is chosen in accordance with the pressure and to limit the effects of
PM102333
requirements: fast delivery time, improved The transformers are designed to withstand the thermal and the dynamic effects
quality and recycling capacities, reduced Short circuit withstandability
plants and in compact distribution substations resulting from a secondary short-circuit in accordance with IEC 60076-5.
size and, on request, very low noise and • For outdoor applications: ground mounted
The measurement (A-weighted sound pressure LpA) and the calculation of sound
losses values. but also pad or pole mounted
level (A-weighted sound level LwA) are done in accordance with
• Low noise level for urban or residential areas Sound level
IEC 60076-10 or NEMA - TR1.
• Normal, low, or very low level of losses
The sound level requirements are in accordance with national standards.
PM102710