KAFD Plot 3.09 Report Revision 0


KAFD Plot 3.09
1110-3.09-DC-E
System Equipment Schedules
Job no 026794 April 2011
Revision 0
Buro Happold

Revision Description Issued by Date Checked by

0 FD issue TG April 11 AP

KAFD Plot 3.09 Report Revision 0


Buro Happold

KAFD Plot 3.09


Schedule of Electrical Accessories

Item Location Installation Manufacturer Model Finish Comment


Socket Outlets Front of house areas Recessed MK (UK) Electric Aspect White
Fused Connection Units Front of house areas Recessed MK (UK) Electric Aspect White
Data Outlets Front of house areas Recessed MK (UK) Electric Aspect White
Lighting Switches Front of house areas Recessed MK (UK) Electric Aspect White

Socket Outlets Back of house areas Recessed MK (UK) Electric Logic Plus White
Fused Connection Units Back of house areas Recessed MK (UK) Electric Logic Plus White
Data Outlets Back of house areas Recessed MK (UK) Electric Logic Plus White
Lighting Switches Back of house areas Recessed MK (UK) Electric Logic Plus White

Socket Outlets Plant and Service areas Surface MK (UK) Electric Metal Clad Plus Aluminum
Fused Connection Units Plant and Service areas Surface MK (UK) Electric Metal Clad Plus Aluminum
Data Outlets Plant and Service areas Surface MK (UK) Electric Metal Clad Plus Aluminum
Lighting Switches Plant and Service areas Surface MK (UK) Electric Metal Clad Plus Aluminum

Notes
1. Front of house areas to include all areas accessable to the public and tenants for office and residential areas.
2. Refer to specifcation for further details and descriptions.

1 of 1
Buro Happold

KAFD Plot 3.09


Schedule of Fire Alarm Equipment

Equipment Description Installation Manufacturer Model Finish Comments

Main Panels Main control panel Semi-Recessed Gent Standard


Sub Panels Sub-control panel on upper floors Surface Gent Standard

Smoke Detectors Detection device Surface Gent White


Heat Detectors Detection device Surface Gent White
Duct Detectors Detection device Gent Standard

Interface units Provides signal to various equipment Surface Gent Standar

Electronic Sounders Audiable alarm Surface Gent Red


Flashing Beacons Visual alarm Surface Gent Red

Manual Call Points Manual alarm point Semi-Recessed Gent Red

Notes
1. Refer to specifcation and drawings for further details and description

1 of 1
Buro Happold

KAFD Plot 3.09


Automatic Transfer Switch Schedule

Reference General
Location Rating (A) Manufacturer Ambient temp Frequency Mounting Voltage
B1 Tx & RMU Room 3000 ASCO Max 50°C 60Hz Floor 3 phase 380

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
1829 965 2311 2118 Refer to Architectural layouts

Notes

ATS - 1
1. Refer to specifcation for further details and descriptions
2. Unit to supply essential main switchboard EMDB-1

Notes

1 of 3
Buro Happold

KAFD Plot 3.09


Automatic Transfer Switch Schedule

Reference General
Location Rating (A) Manufacturer Ambient temp Frequency Mounting Voltage
L10 Plant Room TBC ASCO Max 50°C 60Hz Floor 3 phase 380

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
TBC TBC TBC TBC Refer to Architectural layouts

Notes

ATS - 2
1. Refer to specifcation for further details and descriptions
2. Unit to supply fire pump distribution panel

Notes

2 of 3
Buro Happold

KAFD Plot 3.09


Automatic Transfer Switch Schedule

Reference General
Location Rating (A) Manufacturer Ambient temp Frequency Mounting Voltage
L27 Plant Room TBC ASCO Max 50°C 60Hz Floor 3 phase 380

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
TBC TBC TBC TBC Refer to Architectural layouts

Notes

ATS - 3
1. Refer to specifcation for further details and descriptions
2. Unit to supply fire pump distribution panel

Notes

3 of 3
Buro Happold

KAFD Plot 3.09


Central Battery Unit Schedule

Reference General
Location Rating (A) Manufacturer Ambient temp Frequency Mounting Voltage
LB1 Plant Room 20KVA Cooper Max 50°C 60Hz Floor 3 phase 380

Physical
Depth (mm) Width (mm) Height (mm) IP Rating Room Dim.'s (m)
400mm 5600 2050 23 Refer to Architectural layouts

Notes

CBU - B1A
1. Refer to specifcation and drawings for further details and descriptions
2. Unit to have 3hour battery duration at full rated load.
3. Outstations as shown on the drawing to 13way. Dimensions 800mm (H) x 600mm (W) x 250mm (D)
4. All equipment to be contained within dedicated cabinet

Notes

1 of 2
Buro Happold

KAFD Plot 3.09


Central Battery Unit Schedule

Reference General
Location Rating (A) Manufacturer Ambient temp Frequency Mounting Voltage
LB1 Plant Room 20KVA Cooper Max 50°C 60Hz Floor 3 phase 380

Physical
Depth (mm) Width (mm) Height (mm) IP Rating Room Dim.'s (m)
400mm 5600 2050 23 Refer to Architectural layouts

Notes

CBU - 10A
1. Refer to specifcation and drawings for further details and descriptions
2. Unit to have 3hour battery duration at full rated load.
3. Outstations as shown on the drawing to 13way. Dimensions 800mm (H) x 600mm (W) x 250mm (D)
4. All equipment to be contained within dedicated cabinet

Notes

2 of 2
Buro Happold

KAFD Plot 3.09


Power Factor Correction Unit Schedule

Reference General
Location Rating (kVAr) Manufacturer Range Ambient Temp Mounting
B1 Electrical Plant Room 400 ABB APC Max 50°C Separate Floor

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
600 550 2000 500 Refer to Architectural layouts 23

Technical
Steps Control Short CCT rating Voltage Frequency
PFC 1 8No 50KVAr Maximum Automatic 42kA rms 380 60Hz

Notes
1. All equipment to be contained within purpose made steel IP23 enclosure
2. Enclosure to have forced air ventilation.
3. 1 master unit + 1 slave unit required.

Notes

1 of 9
Buro Happold

KAFD Plot 3.09


Power Factor Correction Unit Schedule

Reference General
Location Rating (kVAr) Manufacturer Range Ambient Temp Mounting
B1 Electrical Plant Room 350 ABB APC Max 50°C Separate Floor

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
600 550 2000 500 Refer to Architectural layouts 23

Technical
Steps Control Short CCT rating Voltage Frequency
PFC 2 7No 50KVAr Maximum Automatic 42kA rms 380 60Hz

Notes
1. All equipment to be contained within purpose made steel IP23 enclosure
2. Enclosure to have forced air ventilation.
3. 1 master unit + 1 slave unit required.

Notes

2 of 9
Buro Happold

KAFD Plot 3.09


Power Factor Correction Unit Schedule

Reference General
Location Rating (kVAr) Manufacturer Range Ambient Temp Mounting
B1 Electrical Plant Room 250 ABB APC Max 50°C Separate Floor

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
600 550 2000 500 Refer to Architectural layouts 23

Technical
Steps Control Short CCT rating Voltage Frequency
PFC 3 5No 50KVAr Maximum Automatic 42kA rms 380 60Hz

Notes
1. All equipment to be contained within purpose made steel IP23 enclosure
2. Enclosure to have forced air ventilation.

Notes

3 of 9
Buro Happold

KAFD Plot 3.09


Power Factor Correction Unit Schedule

Reference General
Location Rating (kVAr) Manufacturer Range Ambient Temp Mounting
B1 Electrical Plant Room 350 ABB APC Max 50°C Separate Floor

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
600 550 2000 500 Refer to Architectural layouts 23

Technical
Steps Control Short CCT rating Voltage Frequency
PFC 4 7No 50KVAr Maximum Automatic 42kA rms 380 60Hz

Notes
1. All equipment to be contained within purpose made steel IP23 enclosure
2. Enclosure to have forced air ventilation.
3. 1 master unit + 1 slave unit required.

Notes

4 of 9
Buro Happold

KAFD Plot 3.09


Power Factor Correction Unit Schedule

Reference General
Location Rating (kVAr) Manufacturer Range Ambient Temp Mounting
B1 Electrical Plant Room 400 ABB APC Max 50°C Separate Floor

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
600 550 2000 500 Refer to Architectural layouts 23

Technical
Steps Control Short CCT rating Voltage Frequency
PFC 5 8No 50KVAr Maximum Automatic 42kA rms 380 60Hz

Notes
1. All equipment to be contained within purpose made steel IP23 enclosure
2. Enclosure to have forced air ventilation.
3. 1 master unit + 1 slave unit required.

Notes

5 of 9
Buro Happold

KAFD Plot 3.09


Power Factor Correction Unit Schedule

Reference General
Location Rating (kVAr) Manufacturer Range Ambient Temp Mounting
L10 Electrical Plant Rm 250 ABB APC Max 50°C Separate Floor

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
600 550 2000 500 Refer to Architectural layouts 23

Technical
Steps Control Short CCT rating Voltage Frequency
PFC 6 5No 50KVAr Maximum Automatic 42kA rms 380 60Hz

Notes
1. All equipment to be contained within purpose made steel IP23 enclosure
2. Enclosure to have forced air ventilation.

Notes

6 of 9
Buro Happold

KAFD Plot 3.09


Power Factor Correction Unit Schedule

Reference General
Location Rating (kVAr) Manufacturer Range Ambient Temp Mounting
L10 Electrical Plant Rm 200 ABB APC Max 50°C Separate Floor

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
600 550 2000 500 Refer to Architectural layouts 23

Technical
Steps Control Short CCT rating Voltage Frequency
PFC 7 8No 25KVAr Maximum Automatic 42kA rms 380 60Hz

Notes
1. All equipment to be contained within purpose made steel IP23 enclosure
2. Enclosure to have forced air ventilation.

Notes

7 of 9
Buro Happold

KAFD Plot 3.09


Power Factor Correction Unit Schedule

Reference General
Location Rating (kVAr) Manufacturer Range Ambient Temp Mounting
L10 Electrical Plant Rm 200 ABB APC Max 50°C Separate Floor

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
600 550 2000 500 Refer to Architectural layouts 23

Technical
Steps Control Short CCT rating Voltage Frequency
PFC 8 8No 25KVAr Maximum Automatic 42kA rms 380 60Hz

Notes
1. All equipment to be contained within purpose made steel IP23 enclosure
2. Enclosure to have forced air ventilation.

Notes

8 of 9
Buro Happold

KAFD Plot 3.09


Power Factor Correction Unit Schedule

Reference General
Location Rating (kVAr) Manufacturer Range Ambient Temp Mounting
L10 Electrical Plant Rm 250 ABB APC Max 50°C Separate Floor

Physical
Length (mm) Width (mm) Height (mm) Mass(kg) Room Dim.'s (m) IP Rating
600 550 2000 500 Refer to Architectural layouts 23

Technical
Steps Control Short CCT rating Voltage Frequency
PFC 9 7No 50KVAr Maximum Automatic 42kA rms 380 60Hz

Notes
1. All equipment to be contained within purpose made steel IP23 enclosure
2. Enclosure to have forced air ventilation.

Notes

9 of 9
Buro Happold

KAFD Plot 3.09


Schedule of Public Address Equipment

Equipment Description Installation Manufacturer Model Finish Comments

Voice Controller Main control panel Within Rack Bosch LBB1990 Standard
Routers 6 zone Expansion Router Within Rack Bosch LBB1992 Standard
Remote Controller PA control from additional locations Desk Mounted Bosch LBB1996 Standard
Call Station 6 zone call station Desk Mounted Bosch LBB1956 Standard
Keypad 6 zone call station extension Desk Mounted Bosch LBB 1957 Standard
Recessed Ceiling Speaker Recessed Speaker Ceiling Bosch LC1 RAL T.B.C.
Speaker Cable Fully insulated 100V Line 2 core

Notes
1. Refer to specifcation and drawings for further details and description
2. Each call station, router and the main control panel shall have a separate SPN power supply which shall be derived from dedicated local socket outlets.
3. Contractor shall make allowance for the powder coating of the speakers a RAL colour that will be confirmed by the Project Architech.
4. Interconnecting cabling between control equipment shall be via shielded Cat 5e cable.

1 of 1
Buro Happold

Buro Happold Limited


Four Winds
Pacific Quay
Glasgow G51 1DY
UK
Telephone: +44 (0)141 419 3000
Facsimile: +44 (0)870 787 4146

KAFD Plot 3.09 Report Revision 0


026794 KAFD Plot 3.09
Electrical Calculations Book
Job no 026794 Jan 2011
Revision A
Buro Happold

Revision Description Issued by Date Checked by

0 Design Development Issue AP Jan 10 AP

A Final Design Issue TG April 11 AP

KAFD Plot 3.09 Report Revision 0


Buro Happold

Contents
1.0 Introduction

2.0 Maximum Demand Calculations

3.0 Transformer Load Breakdown.

4.0 Cable Calculations

4.1 Transformer TX1 – Cable Calculations.

4.2 Transformer TX2 – Cable Calculations.

4.3 Transformer TX3 – Cable Calculations.

4.4 Transformer TX4 – Cable Calculations.

4.5 Transformer TX5 – Cable Calculations.

4.6 Transformer TX6 – Cable Calculations.

4.7 Transformer TX7 – Cable Calculations.

4.8 Transformer TX8 – Cable Calculations.

4.9 Transformer TX9 – Cable Calculations.

5.0 Lighting Calculations

5.1 Substructure Package – Normal Lighting


Calculations.

5.2 Substructure Package – Emergency Lighting


Calculations.

5.3 Superstructure Package – Normal Lighting


Calculations

5.4 Superstructure Package 7 Emergency Lighting


Calculations

KAFD Plot 3.09 Report Revision 0


Buro Happold

1.0 Introduction

This document details the calculations for Plot 3.09 for the various electrical systems throughout the building
and should be read in conjunction with all relevant design drawings and documents.

KAFD Plot 3.09 Report Revision 0


Buro Happold

2.0 Maximum Demand Calculation

KAFD Plot 3.09 Report Revision 0


026794 - Plot 3.09 Electrical MD Calculation
09/08/2010 Rev 0
Fixed Undiversified Diversified Undiversified Transformer Loadings
Level Description Area (m2) Total Loads Load Diversity Load Tx 1 Tx 2 Tx 3 Tx 4 Tx 5 Tx 6 Tx 7 Tx 8 Tx 9
VA/m2 kVA kVA kVA Emergency CP/BOH Retail Office 1 Office 2 Kitchen/Bar/Spa/Gym Resi 1 Resi 2 Resi 3
2000kVA 2000kVA 2000kVA 2000kVA 2000kVA 1250kVA 1250kVA 1250kVA 1250kA
CAR PARK AND PLANT AREAS (SUB-STRUCTURE)

B4 Car Park (West) 2220 42.00 93.24 0.80 74.59


B4 Core (West) 294 55.00 16.17 0.80 12.94
B4 Mechanical Plant (West) 235 68.00 15.98 0.80 12.78
B4 Mechanical Plant (West) 357 68.00 24.28 0.80 19.42
B4 Storage (West) 13 68.00 0.88 0.80 0.71
B4 Elec Room (West) 12 68.00 0.78 0.80 0.63
B4 Emerg Elec Room (West) 6 68.00 0.41 0.80 0.33 Actual
B4 Comms Room (West) 6 1053.00 6.32 0.80 5.05 897
B4 Car Park (East) 2169 42.00 91.10 0.80 72.88 KVA
B4 Core (East) 238 55.00 13.09 0.80 10.47
B4 Mechanical Plant (East) 683 68.00 46.44 0.80 37.16
B4 Storage (East) 81 68.00 5.51 0.80 4.41
B4 Elec Room (East) 9 68.00 0.61 0.80 0.49 TX1 Calc
B4 Emerg Elec Room (East) 9 68.00 0.61 0.80 0.49 as per 1129
B4 Comms Room (East) 7 1053.00 7.37 0.80 5.90 EM TCL kVA
B3 Car Park (West) [copy of B2] 2544 42.00 106.85 0.80 85.48
B3 Core (West) [copy of B2] 294 55.00 16.17 0.80 12.94 1805
B3 Mechanical Plant (West) [copy of B2] 70 68.00 4.76 0.80 3.81 Amps
B3 Mechanical Plant (West) [copy of B2] 165 68.00 11.22 0.80 8.98
B3 Elec Room (West) [copy of B2] 12 68.00 0.82 0.80 0.65
B3 Emerg Elec Room (West) [copy of B2] 6 68.00 0.41 0.80 0.33
B3 Comms Room (West) [copy of B2] 6 1053.00 6.32 0.80 5.05
B3 Car Park (East) [copy of B2] 2587 42.00 108.65 0.80 86.92
B3 Core (East) [copy of B2] 238 55.00 13.09 0.80 10.47
B3 Mechanical Plant (East) [copy of B2] 281 68.00 19.11 0.80 15.29
B3 Mechanical Plant (East) [copy of B2] 83 68.00 5.64 0.80 4.52
B3 Elec Room (East) [copy of B2] 9 68.00 0.61 0.80 0.49
B3 Emerg Elec Room (East) [copy of B2] 9 68.00 0.61 0.80 0.49
B3 Comms Room (East) [copy of B2] 7 1053.00 7.37 0.80 5.90
B2 Car Park (West) 2544 42.00 106.85 0.80 85.48
B2 Core (West) 294 55.00 16.17 0.80 12.94
B2 Mechanical Plant (West) 70 68.00 4.76 0.80 3.81
B2 Mechanical Plant (West) 165 68.00 11.22 0.80 8.98
B2 Elec Room (West) 12 68.00 0.82 0.80 0.65
B2 Emerg Elec Room (West) 6 68.00 0.41 0.80 0.33
B2 Comms Room (West) 6 1053.00 6.32 0.80 5.05
B2 Car Park (East) 2587 42.00 108.65 0.80 86.92
B2 Core (East) 238 55.00 13.09 0.80 10.47
B2 Mechanical Plant (East) 281 68.00 19.11 0.80 15.29
B2 Mechanical Plant (East) 83 68.00 5.64 0.80 4.52
B2 Elec Room (East) 9 68.00 0.61 0.80 0.49
B2 Emerg Elec Room (East) 9 68.00 0.61 0.80 0.49
B2 Comms Room (East) 7 1053.00 7.37 0.80 5.90
B1 Car Park (West) 1195 42.00 50.19 0.80 40.15
B1 Core (West) 316 55.00 17.38 0.80 13.90
B1 Lobby (West) 310 55.00 17.05 0.80 13.64
B1 Cycle Store (West) 292 42.00 12.26 0.80 9.81
B1 Drivers Lounge (West) 91 114.00 10.37 0.80 8.30
B1 Mechanical Plant (West) 105 68.00 7.14 0.80 5.71
B1 Storage (West) 63 68.00 4.28 0.80 3.43
B1 Elec Room (West) 12 68.00 0.82 0.80 0.65
B1 Emerg Elec Room (West) 6 68.00 0.41 0.80 0.33
B1 Comms Room (West) 6 1053.00 6.32 0.80 5.05
B1 Retail 1 (West) 252 167.00 42.08 0.80 33.67
B1 Retail 2 (West) 354 167.00 59.12 0.80 47.29
B1 Car Park (East) 1839 42.00 77.24 0.80 61.79
B1 Core (East) 266 55.00 14.63 0.80 11.70
B1 Electrical Plant (East) 632 68.00 42.98 0.80 34.38
026794 - Plot 3.09 Electrical MD Calculation
09/08/2010 Rev 0
Fixed Undiversified Diversified Undiversified Transformer Loadings
Level Description Area (m2) Total Loads Load Diversity Load Tx 1 Tx 2 Tx 3 Tx 4 Tx 5 Tx 6 Tx 7 Tx 8 Tx 9
VA/m2 kVA kVA kVA Emergency CP/BOH Retail Office 1 Office 2 Kitchen/Bar/Spa/Gym Resi 1 Resi 2 Resi 3
2000kVA 2000kVA 2000kVA 2000kVA 2000kVA 1250kVA 1250kVA 1250kVA 1250kA
B1 Mechanical Plant (East) 338 68.00 22.98 0.80 18.39
B1 Elec Room (East) 9 68.00 0.61 0.80 0.49
B1 Emerg Elec Room (East) 9 68.00 0.61 0.80 0.49
B1 Comms Room (East) 7 1053.00 7.37 0.80 5.90
PGL Landscape Lighting 1631 2.00 3.26 0.80 2.61
PGL Water Features - 63 63.00 0.80 50.40
PGL Car Park (East) Ramp 592 42.00 24.86 0.80 19.89

27286 m2 CL: 1411 DL: 897 kVA

RETAIL, OFFICE & RESIDENTIAL (SUPER-STRUCTURE)

PGL Core (West) 275 55.00 15.13 0.80 12.10


PGL Retail 1 (West) 106 167.00 17.70 0.80 14.16
PGL Retail 2 (West) 538 167.00 89.85 0.80 71.88
PGL Retail 3 (West) 188 167.00 31.40 0.80 25.12
PGL Residential Lobby (West) 344 55.00 18.92 0.80 15.14
PGL Plant (West) 22 68.00 1.50 0.80 1.20
PGL Plant (West) 12 68.00 0.82 0.80 0.65
PGL Building Man & Sec Office (West) 58 114.00 6.61 0.80 5.29
PGL FC Room (West) 61 114.00 6.95 0.80 5.56
PGL Elec Room (West) 12 68.00 0.82 0.80 0.65
PGL Emerg Elec Room (West) 6 68.00 0.41 0.80 0.33
PGL Comms Room (West) 6 1053.00 6.32 0.80 5.05
PGL Office Lobby (West) 606 55.00 33.33 0.80 26.66
PGL Core (East) 470 55.00 25.85 0.80 20.68
PGL Retail 1 (East) 776 167.00 129.59 0.80 103.67
PGL Retail 2 (East) 112 167.00 18.70 0.80 14.96
PGL Retail 3 (East) 210 167.00 35.07 0.80 28.06
PGL Elec Room (East) 9 68.00 0.61 0.80 0.49
PGL Emerg Elec Room (East) 9 68.00 0.61 0.80 0.49
PGL Comms Room (East) 7 1053.00 7.37 0.80 5.90
PGL Office Lobby (East) 101 55.00 5.56 0.80 4.44
1 Core (West) 251 55.00 13.81 0.80 11.04 TX1
1 Retail 1 (West) 257 167.00 42.92 0.80 34.34 as per
1 Retail 2 (West) 335 167.00 55.95 0.80 44.76 EM TCL
1 Retail 3 (West) 228 167.00 38.08 0.80 30.46
1 Retail 4 (West) 66 167.00 11.02 0.80 8.82 802
1 Seating Area 1 (West) 45 167.00 7.52 0.80 6.01 kVA
1 Seating Area 2 (West) 83 167.00 13.86 0.80 11.09
1 Seating Area 3 (West) 50 167.00 8.35 0.80 6.68 1283
1 Seating Area 4 (West) 103 167.00 17.20 0.80 13.76 Amps
1 Lobby (West) 508 55.00 27.94 0.80 22.35
1 Elec Room (West) 12 68.00 0.82 0.80 0.65
1 Emerg Elec Room (West) 6 68.00 0.41 0.80 0.33
1 Comms Room (West) 6 1053.00 6.32 0.80 5.05
1 Public/Retail Lift 1 - - 35 35.00 0.60 21.00
1 Public/Retail Lift 2 - - 35 35.00 0.60 21.00
1 Core (East) 355 55.00 19.53 0.80 15.62
1 Retail 1 (East) 69 167.00 11.52 0.80 9.22
1 Retail 2 (East) 121 167.00 20.21 0.80 16.17
1 Retail 3 (East) 107 167.00 17.87 0.80 14.30
1 Retail 4 (East) 97 167.00 16.20 0.80 12.96
1 Retail 5 (East) 105 167.00 17.54 0.80 14.03
1 Retail 6 (East) 395 167.00 65.97 0.80 52.77
1 F&B (East) 355 167.00 59.29 0.80 47.43
1 Lobby (East) 301 55.00 16.56 0.80 13.24
1 Elec Room (East) 9 68.00 0.61 0.80 0.49
1 Emerg Elec Room (East) 9 68.00 0.61 0.80 0.49
1 Comms Room (East) 7 1053.00 7.37 0.80 5.90
026794 - Plot 3.09 Electrical MD Calculation
09/08/2010 Rev 0
Fixed Undiversified Diversified Undiversified Transformer Loadings
Level Description Area (m2) Total Loads Load Diversity Load Tx 1 Tx 2 Tx 3 Tx 4 Tx 5 Tx 6 Tx 7 Tx 8 Tx 9
VA/m2 kVA kVA kVA Emergency CP/BOH Retail Office 1 Office 2 Kitchen/Bar/Spa/Gym Resi 1 Resi 2 Resi 3
2000kVA 2000kVA 2000kVA 2000kVA 2000kVA 1250kVA 1250kVA 1250kVA 1250kA
2 Roof Garden Lighting 257 2.00 0.51 0.80 0.41
2 Plant 126 68.00 8.57 0.80 6.85
2 Plant 2283 68.00 155.24 0.80 124.20
2 Core (West) 266 55.00 14.63 0.80 11.70
2 Chaffeurs Accomodation (West) 357 147.40 52.62 0.80 42.10
2 Elec Room (West) 12 68.00 0.82 0.80 0.65
2 Emerg Elec Room (West) 6 68.00 0.41 0.80 0.33
2 Comms Room (West) 6 1053.00 6.32 0.80 5.05
2 Core (East) 308 55.00 16.94 0.80 13.55
2 Elec Room (East) 9 68.00 0.61 0.80 0.49
2 Emerg Elec Room (East) 9 68.00 0.61 0.80 0.49
2 Comms Room (East) 7 1053.00 7.37 0.80 5.90
3 Offices (West) 1250 114.00 142.50 0.60 85.50
3 Core (West) 208 55.00 11.44 0.60 6.86
3 Plant (West) 35 68.00 2.38 0.60 1.43
3 Plant (West) 30 68.00 2.04 0.80 1.63
3 Plant (West) 29 68.00 1.97 0.80 1.58
3 Elec Room (West) 12 68.00 0.82 0.80 0.65
3 Emerg Elec Room (West) 6 68.00 0.41 0.80 0.33
3 Comms Room (West) 6 1053.00 6.32 0.80 5.05
3 Offices (East) 1155 114.00 131.67 0.80 105.34
3 Core (East) 204 55.00 11.22 0.80 8.98
3 Plant (East) 28 68.00 1.90 0.80 1.52
3 Plant (East) 32 68.00 2.18 0.80 1.74 968
3 Plant (East) 26 68.00 1.77 0.80 1.41 kVA
3 Elec Room (East) 8 68.00 0.54 0.80 0.44
3 Emerg Elec Room (East) 8 68.00 0.54 0.80 0.44
3 Comms Room (East) 10 1053.00 10.53 0.80 8.42 1548
4 Offices (West) [copy of lvl 3] 1250 114.00 142.50 0.80 114.00 Amps
4 Core (West) [copy of lvl 3] 208 55.00 11.44 0.80 9.15
4 Plant (West) [copy of lvl 3] 35 68.00 2.38 0.80 1.90
4 Plant (West) [copy of lvl 3] 30 68.00 2.04 0.80 1.63
4 Plant (West) [copy of lvl 3] 29 68.00 1.97 0.80 1.58
4 Elec Room (West) [copy of lvl 3] 12 68.00 0.82 0.80 0.65
4 Emerg Elec Room (West) [copy of lvl 3] 6 68.00 0.41 0.80 0.33
4 Comms Room (West) [copy of lvl 3] 6 1053.00 6.32 0.80 5.05
4 Offices (East) [copy of lvl 3] 1155 114.00 131.67 0.80 105.34
4 Core (East) [copy of lvl 3] 204 55.00 11.22 0.80 8.98
4 Plant (East) [copy of lvl 3] 28 68.00 1.90 0.80 1.52
4 Plant (East) [copy of lvl 3] 32 68.00 2.18 0.80 1.74
4 Plant (East) [copy of lvl 3] 26 68.00 1.77 0.80 1.41
4 Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
4 Emerg Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
4 Comms Room (East) [copy of lvl 3] 10 1053.00 10.53 0.80 8.42
5 Offices (West) [copy of lvl 3] 1250 114.00 142.50 0.80 114.00
5 Core (West) [copy of lvl 3] 208 55.00 11.44 0.80 9.15
5 Plant (West) [copy of lvl 3] 35 68.00 2.38 0.80 1.90
5 Plant (West) [copy of lvl 3] 30 68.00 2.04 0.80 1.63
5 Plant (West) [copy of lvl 3] 29 68.00 1.97 0.80 1.58
5 Elec Room (West) [copy of lvl 3] 12 68.00 0.82 0.80 0.65
5 Emerg Elec Room (West) [copy of lvl 3] 6 68.00 0.41 0.80 0.33
5 Comms Room (West) [copy of lvl 3] 6 1053.00 6.32 0.80 5.05
5 Offices (East) [copy of lvl 3] 1155 114.00 131.67 0.80 105.34
5 Core (East) [copy of lvl 3] 204 55.00 11.22 0.80 8.98
5 Plant (East) [copy of lvl 3] 28 68.00 1.90 0.80 1.52
5 Plant (East) [copy of lvl 3] 32 68.00 2.18 0.80 1.74
5 Plant (East) [copy of lvl 3] 26 68.00 1.77 0.80 1.41
5 Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
5 Emerg Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
5 Comms Room (East) [copy of lvl 3] 10 1053.00 10.53 0.80 8.42
026794 - Plot 3.09 Electrical MD Calculation
09/08/2010 Rev 0
Fixed Undiversified Diversified Undiversified Transformer Loadings
Level Description Area (m2) Total Loads Load Diversity Load Tx 1 Tx 2 Tx 3 Tx 4 Tx 5 Tx 6 Tx 7 Tx 8 Tx 9
VA/m2 kVA kVA kVA Emergency CP/BOH Retail Office 1 Office 2 Kitchen/Bar/Spa/Gym Resi 1 Resi 2 Resi 3
2000kVA 2000kVA 2000kVA 2000kVA 2000kVA 1250kVA 1250kVA 1250kVA 1250kA
6 Offices (West) [copy of lvl 3] 1250 114.00 142.50 0.80 114.00
6 Core (West) [copy of lvl 3] 208 55.00 11.44 0.80 9.15
6 Plant (West) [copy of lvl 3] 35 68.00 2.38 0.80 1.90
6 Plant (West) [copy of lvl 3] 30 68.00 2.04 0.80 1.63
6 Plant (West) [copy of lvl 3] 29 68.00 1.97 0.80 1.58
6 Elec Room (West) [copy of lvl 3] 12 68.00 0.82 0.80 0.65
6 Emerg Elec Room (West) [copy of lvl 3] 6 68.00 0.41 0.80 0.33
6 Comms Room (West) [copy of lvl 3] 6 1053.00 6.32 0.80 5.05
6 Offices (East) [copy of lvl 3] 1155 114.00 131.67 0.80 105.34
6 Core (East) [copy of lvl 3] 204 55.00 11.22 0.80 8.98
6 Plant (East) [copy of lvl 3] 28 68.00 1.90 0.80 1.52
6 Plant (East) [copy of lvl 3] 32 68.00 2.18 0.80 1.74
6 Plant (East) [copy of lvl 3] 26 68.00 1.77 0.80 1.41
6 Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
6 Emerg Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
6 Comms Room (East) [copy of lvl 3] 10 1053.00 10.53 0.80 8.42
7 Offices (West) [copy of lvl 3] 1250 114.00 142.50 0.80 114.00
7 Core (West) [copy of lvl 3] 208 55.00 11.44 0.80 9.15
7 Plant (West) [copy of lvl 3] 35 68.00 2.38 0.80 1.90
7 Plant (West) [copy of lvl 3] 30 68.00 2.04 0.80 1.63
7 Plant (West) [copy of lvl 3] 29 68.00 1.97 0.80 1.58
7 Elec Room (West) [copy of lvl 3] 12 68.00 0.82 0.80 0.65
7 Emerg Elec Room (West) [copy of lvl 3] 6 68.00 0.41 0.80 0.33
7 Comms Room (West) [copy of lvl 3] 6 1053.00 6.32 0.80 5.05
7 Offices (East) [copy of lvl 3] 1155 114.00 131.67 0.80 105.34
7 Core (East) [copy of lvl 3] 204 55.00 11.22 0.80 8.98
7 Plant (East) [copy of lvl 3] 28 68.00 1.90 0.80 1.52
7 Plant (East) [copy of lvl 3] 32 68.00 2.18 0.80 1.74
7 Plant (East) [copy of lvl 3] 26 68.00 1.77 0.80 1.41
7 Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
7 Emerg Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
7 Comms Room (East) [copy of lvl 3] 10 1053.00 10.53 0.80 8.42
8 Offices (West) [copy of lvl 3] 1250 114.00 142.50 0.80 114.00
8 Core (West) [copy of lvl 3] 208 55.00 11.44 0.80 9.15
8 Plant (West) [copy of lvl 3] 35 68.00 2.38 0.80 1.90
8 Plant (West) [copy of lvl 3] 30 68.00 2.04 0.80 1.63
8 Plant (West) [copy of lvl 3] 29 68.00 1.97 0.80 1.58
8 Elec Room (West) [copy of lvl 3] 12 68.00 0.82 0.80 0.65
8 Emerg Elec Room (West) [copy of lvl 3] 6 68.00 0.41 0.80 0.33
8 Comms Room (West) [copy of lvl 3] 6 1053.00 6.32 0.80 5.05
8 Offices (East) [copy of lvl 3] 1155 114.00 131.67 0.80 105.34
8 Core (East) [copy of lvl 3] 204 55.00 11.22 0.80 8.98
8 Plant (East) [copy of lvl 3] 28 68.00 1.90 0.80 1.52
8 Plant (East) [copy of lvl 3] 32 68.00 2.18 0.80 1.74
8 Plant (East) [copy of lvl 3] 26 68.00 1.77 0.80 1.41
8 Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44 1218
8 Emerg Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44 kVA
8 Comms Room (East) [copy of lvl 3] 10 1053.00 10.53 0.80 8.42
9 Offices (West) [copy of lvl 3] 1250 114.00 142.50 0.80 114.00 1948
9 Core (West) [copy of lvl 3] 208 55.00 11.44 0.80 9.15 Amps
9 Plant (West) [copy of lvl 3] 35 68.00 2.38 0.80 1.90
9 Plant (West) [copy of lvl 3] 30 68.00 2.04 0.80 1.63
9 Plant (West) [copy of lvl 3] 29 68.00 1.97 0.80 1.58
9 Elec Room (West) [copy of lvl 3] 12 68.00 0.82 0.80 0.65
9 Emerg Elec Room (West) [copy of lvl 3] 6 68.00 0.41 0.80 0.33
9 Office Lift (West) - - 35 35.00 0.60 21.00
9 Office Lift (West) - - 35 35.00 0.60 21.00
9 Office Lift (West) - - 35 35.00 0.60 21.00
9 Office Lift (West) - - 35 35.00 0.60 21.00
9 Office Lift (West) - - 35 35.00 0.60 21.00
026794 - Plot 3.09 Electrical MD Calculation
09/08/2010 Rev 0
Fixed Undiversified Diversified Undiversified Transformer Loadings
Level Description Area (m2) Total Loads Load Diversity Load Tx 1 Tx 2 Tx 3 Tx 4 Tx 5 Tx 6 Tx 7 Tx 8 Tx 9
VA/m2 kVA kVA kVA Emergency CP/BOH Retail Office 1 Office 2 Kitchen/Bar/Spa/Gym Resi 1 Resi 2 Resi 3
2000kVA 2000kVA 2000kVA 2000kVA 2000kVA 1250kVA 1250kVA 1250kVA 1250kA
9 Comms Room (West) [copy of lvl 3] 6 1053.00 6.32 0.80 5.05
9 Offices (East) [copy of lvl 3] 1155 114.00 131.67 0.80 105.34
9 Core (East) [copy of lvl 3] 204 55.00 11.22 0.80 8.98
9 Plant (East) [copy of lvl 3] 28 68.00 1.90 0.80 1.52
9 Plant (East) [copy of lvl 3] 32 68.00 2.18 0.80 1.74
9 Plant (East) [copy of lvl 3] 26 68.00 1.77 0.80 1.41
9 Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
9 Emerg Elec Room (East) [copy of lvl 3] 8 68.00 0.54 0.80 0.44
9 Office Lift (East) - - 35 35.00 0.60 21.00
9 Office Lift (East) - - 35 35.00 0.60 21.00
9 Office Lift (East) - - 35 35.00 0.60 21.00
9 Comms Room (East) [copy of lvl 3] 10 1053.00 10.53 0.80 8.42
10 Plant 1032 68.00 70.18 0.80 56.14
10 West Core 144 55.00 7.92 0.80 6.34
10 Terrace & Sky Garden 289 2.00 0.58 0.80 0.46
10 Elec Room (West) 10 68.00 0.68 0.80 0.54
10 Elec Room (West) 8 68.00 0.54 0.80 0.44
10 Emerg Elec Room (West) 5 68.00 0.34 0.80 0.27
10 Comms Room (West) 8 1053.00 8.42 0.80 6.74
10 Comms Room (West) 5 1053.00 5.27 0.80 4.21
10 Landscape Roof 859 2.00 1.72 0.80 1.37
10 Plant (East) 86 68.00 5.85 0.80 4.68
10 Core (East) 121 55.00 6.66 0.80 5.32
10 Storage (East) 11 68.00 0.75 0.80 0.60 762
10 Storage (East) 16 68.00 1.09 0.80 0.87 kVA
10 Elec Room (East) 8 68.00 0.54 0.80 0.44
10 Emerg Elec Room (East) 8 68.00 0.54 0.80 0.44 1219
10 Comms Room (East) 10 1053.00 10.53 0.80 8.42 Amps
11 Spa/Gym 314 167.00 52.44 0.80 41.95
11 Bar/Lounge 177 167.00 29.56 0.80 23.65
11 Seating Area 135 167.00 22.55 0.80 18.04
11 Core 137 55.00 7.54 0.80 6.03
11 Lobby 103 55.00 5.67 0.80 4.53
11 Storage 5 68.00 0.34 0.80 0.27
11 Storage 20 68.00 1.36 0.80 1.09
11 Elec Room 10 68.00 0.68 0.80 0.54
11 Emerg Elec Room 5 68.00 0.34 0.80 0.27
11 Residential Shuttle Lift - - 35 35.00 0.60 21.00
11 Residential Shuttle Lift - - 35 35.00 0.60 21.00
11 Comms Room 10 1053.00 10.53 0.80 8.42
11 Landscape 110 2.00 0.22 0.80 0.18
11 Walkway 121 2.00 0.24 0.80 0.19
11 Terrace 129 2.00 0.26 0.80 0.21
11 Kitchen 44 500 500.00 0.80 400.00
11 Restaurant 394 167.00 65.80 0.80 52.64
11 Office Lift (East) - - 35 35.00 0.60 21.00
11 Office Lift (East) - - 35 35.00 0.60 21.00
11 Office Firefighting Lift - - 35 35.00 0.60 21.00
11 Core 41 55.00 2.26 0.80 1.80
12 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
12 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
12 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
12 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
12 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
13 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
13 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
13 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54 551
13 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42 kVA
13 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
14 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00 882
026794 - Plot 3.09 Electrical MD Calculation
09/08/2010 Rev 0
Fixed Undiversified Diversified Undiversified Transformer Loadings
Level Description Area (m2) Total Loads Load Diversity Load Tx 1 Tx 2 Tx 3 Tx 4 Tx 5 Tx 6 Tx 7 Tx 8 Tx 9
VA/m2 kVA kVA kVA Emergency CP/BOH Retail Office 1 Office 2 Kitchen/Bar/Spa/Gym Resi 1 Resi 2 Resi 3
2000kVA 2000kVA 2000kVA 2000kVA 2000kVA 1250kVA 1250kVA 1250kVA 1250kA
14 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64 Amps
14 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
14 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
14 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
15 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
15 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
15 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
15 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
15 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
16 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
16 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
16 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
16 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
16 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
17 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
17 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
17 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
17 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
17 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
18 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
18 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
18 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
18 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
18 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
19 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
19 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
19 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
19 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
19 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
20 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
20 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64 551
20 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54 kVA
20 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
20 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27 882
21 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00 Amps
21 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
21 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
21 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
21 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
22 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
22 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
22 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
22 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
22 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
23 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
23 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
23 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
23 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
23 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
24 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
24 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
24 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
24 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
24 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
25 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
25 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
25 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
25 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
25 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
26 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
026794 - Plot 3.09 Electrical MD Calculation
09/08/2010 Rev 0
Fixed Undiversified Diversified Undiversified Transformer Loadings
Level Description Area (m2) Total Loads Load Diversity Load Tx 1 Tx 2 Tx 3 Tx 4 Tx 5 Tx 6 Tx 7 Tx 8 Tx 9
VA/m2 kVA kVA kVA Emergency CP/BOH Retail Office 1 Office 2 Kitchen/Bar/Spa/Gym Resi 1 Resi 2 Resi 3
2000kVA 2000kVA 2000kVA 2000kVA 2000kVA 1250kVA 1250kVA 1250kVA 1250kA
26 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64 760
26 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54 kVA
26 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
26 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27 1215
27 Plant 550 68.00 52.90 0.66 34.92 Amps
27 Core 226 55.00 8.31 0.80 6.64
28 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
28 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
28 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
28 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
28 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
29 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
29 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
29 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
29 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
29 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
30 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
30 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
30 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
30 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
30 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
31 Residential Bedrooms (Copy of Lvl 20) 778 148.00 115.14 0.66 76.00
31 Core (Copy of Lvl 20) 151 55.00 8.31 0.80 6.64
31 Elec Room (Copy of Lvl 20) 10 68.00 0.68 0.80 0.54
31 Comms Room (Copy of Lvl 20) 10 1053.00 10.53 0.80 8.42
31 Store (Copy of Lvl 20) 5 68.00 0.34 0.80 0.27
31 Residential Passenger Lift - - 35 35.00 0.60 21.00
31 Residential Passenger Lift - - 35 35.00 0.60 21.00
31 Residential Fire Fighting Lift - - 35 35.00 0.60 21.00
Roof BMU 15 15.00 0.80 12.00

56060 m2 CL: 7605 DL: 5613 kVA

GRAND TOTALS 83346 m2 TCL: 9.02 TDL: 6.51 MVA

Emergency Load 1.20 MVA

Total Load 7.71 MVA

MV Diversity 0.80 6.17 MVA

20% Spare 7.40 MVA


Buro Happold

3.0 Transformer Load Breakdown

KAFD Plot 3.09 Report Revision 0


3.09 - Transformer Selections

Transformer Transformer Transformer Transformer Transformer


Equipment Reference Location Floors Served Load Max Rating Max Rating Actual Rating Actual Rating
MVA @64% @64%

Transformer TX1 B1 All - Emergency 1.20 2.00 1.28 2.00 1.28


Transformer TX2 B1 B5 - B1 0.90 2.00 1.28 1.60 1.00
Transformer TX3 B1 PGL & L1 0.80 2.00 1.28 1.25 0.80
Transformer TX4 B1 L2 - L5 0.97 2.00 1.28 1.60 1.00
Transformer TX5 B1 L6 - L9 1.22 2.00 1.28 2.00 1.28

Transformer TX6 L10 - Residential Tower L10 - L11 0.76 1.25 0.80 1.25 0.80
Transformer TX7 L10 - Residential Tower L12 - L17 0.55 1.25 0.80 1.00 0.64
Transformer TX8 L10 - Residential Tower L18 - L23 0.55 1.25 0.80 1.00 0.64
Transformer TX9 L10 - Residential Tower L24 - Roof 0.76 1.25 0.80 1.25 0.80

Totals (MVA) 7.71 15.00 9.60 12.95 8.24


Buro Happold

4.0 Cable Calculations

KAFD Plot 3.09 Report Revision 0


Buro Happold

4.1 Transformer TX1

KAFD Plot 3.09 Report Revision 0


Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-EMDB-1-SM011 ESMDB-B3B


Connection From: EMDB 1 To: ESMDB-B3B
Active Source: Transformer-TX 1
Load Type: Main cable to Switchboard Design Current Ib (A): 151.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 400 [f]
Neutral: 400 mm²[a] Length (m): 57
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 151.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 664.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 741.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 151.7 / 1.00 150.3 / 1.00 148.8 / 1.00 2.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.54 / 0.25 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 1.15 / 0.52 1.12 / 0.51 1.12 / 0.51 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00808 0.00547 0.00904 0.02204 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
9.94
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.78

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 39.510 / 35.219 Load End: 21.429 / 13.182
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.55 x 106 Adiabatic Limit k²S² (A²s): 3,271.84 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 1 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-EMDB-1-SM013 ESMDB-B4B


Connection From: EMDB 1 To: ESMDB-B4B
Active Source: Transformer-TX 1
Load Type: Main cable to Switchboard Design Current Ib (A): 233.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 400 [f]
Neutral: 400 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 233.0
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 674.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 741.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 230.9 / 1.00 233.0 / 1.00 227.2 / 1.00 5.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.98 / 0.45 0.96 / 0.44 0.91 / 0.41 -----
Voltage Drop - From Source (V/%) 1.59 / 0.73 1.57 / 0.72 1.52 / 0.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00808 0.00643 0.01062 0.02455 0.05038 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
8.92
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.10

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 39.510 / 35.219 Load End: 19.796 / 11.836
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.29 x 106 Adiabatic Limit k²S² (A²s): 3,271.84 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 2 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-EMDB-1-SM06 ESMDB-B1A


Connection From: EMDB 1 To: ESMDB-B1A
Active Source: Transformer-TX 1
Load Type: Main cable to Switchboard Design Current Ib (A): 150.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 400 [f]
Neutral: 400 mm²[a] Length (m): 85
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 150.5
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 664.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 741.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 145.1 / 1.00 148.3 / 1.00 150.5 / 1.00 4.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.72 / 0.33 0.80 / 0.36 0.78 / 0.36 -----
Voltage Drop - From Source (V/%) 1.33 / 0.61 1.41 / 0.64 1.39 / 0.64 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00808 0.00816 0.01347 0.02909 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.53
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 5.16

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 39.510 / 35.219 Load End: 17.399 / 9.993
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 948.78 x 103 Adiabatic Limit k²S² (A²s): 3,271.84 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 3 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-EMDB-1-SM07 ESMDB-B1B


Connection From: EMDB 1 To: ESMDB-B1B
Active Source: Transformer-TX 1
Load Type: Main cable to Switchboard Design Current Ib (A): 286.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS800 N MLogic 5.0A
Rating In (A):800 [f] Overload Setting Ir (A): 800 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 37
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 286.4
Device Rating In = 800 Overload Setting Ir = 800 [Ir >
_ Ib]
Min. Cable Capacity Iz = 570.8 [BS 7671, Appendix 4.5, Formula (2)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 282.1 / 1.00 286.4 / 1.00 280.9 / 1.00 4.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.39 / 0.18 0.40 / 0.18 0.38 / 0.17 -----
Voltage Drop - From Source (V/%) 1.00 / 0.46 1.01 / 0.46 0.99 / 0.45 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00808 0.00197 0.00544 0.01513 0.08296 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
14.47
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 46.91

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 39.510 / 35.219 Load End: 30.894 / 22.595
Protective Device Breaking Capacity (kA): Icu: 50 Ics: 37.5

Adiabatic Check: CPD Energy Let-through (A²s): 45.00 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 4 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-EMDB-1-SM08 ESMDB-B2A


Connection From: EMDB 1 To: ESMDB-B2A
Active Source: Transformer-TX 1
Load Type: Main cable to Switchboard Design Current Ib (A): 202.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 400 [f]
Neutral: 400 mm²[a] Length (m): 95
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 202.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 670.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 741.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 202.7 / 1.00 196.2 / 1.00 195.8 / 1.00 6.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.22 / 0.56 1.08 / 0.49 1.15 / 0.53 -----
Voltage Drop - From Source (V/%) 1.83 / 0.84 1.69 / 0.77 1.76 / 0.81 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00808 0.00912 0.01506 0.03161 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
6.93
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.81

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 39.510 / 35.219 Load End: 16.299 / 9.195
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 809.18 x 103 Adiabatic Limit k²S² (A²s): 3,271.84 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 5 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-EMDB-1-SM09 ESMDB-B2B


Connection From: EMDB 1 To: ESMDB-B2B
Active Source: Transformer-TX 1
Load Type: Main cable to Switchboard Design Current Ib (A): 150.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 400 [f]
Neutral: 400 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 150.9
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 664.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 741.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 149.0 / 1.00 150.8 / 1.00 150.9 / 1.00 1.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.42 / 0.19 0.44 / 0.20 0.43 / 0.20 -----
Voltage Drop - From Source (V/%) 1.03 / 0.47 1.05 / 0.48 1.04 / 0.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00808 0.00451 0.00745 0.01953 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
11.21
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 7.59

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 39.510 / 35.219 Load End: 23.345 / 14.864
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.49 x 106 Adiabatic Limit k²S² (A²s): 3,271.84 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 6 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-1-SM10 ESMDB-B3A


Connection From: EMDB 1 To: ESMDB-B3A
Active Source: Transformer-TX 1
Load Type: Main cable to Switchboard Design Current Ib (A): 200.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 400 [f]
Neutral: 400 mm²[a] Length (m): 105
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 200.9
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 670.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 741.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 200.9 / 1.00 197.2 / 1.00 196.8 / 1.00 3.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.32 / 0.60 1.23 / 0.56 1.27 / 0.58 -----
Voltage Drop - From Source (V/%) 1.93 / 0.88 1.84 / 0.84 1.88 / 0.86 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00808 0.01008 0.01665 0.03414 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
6.42
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.50

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 39.510 / 35.219 Load End: 15.327 / 8.515
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 690.06 x 103 Adiabatic Limit k²S² (A²s): 3,271.84 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 7 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-1-SM12 ESMDB-B4A


Connection From: EMDB 1 To: ESMDB-B4A
Active Source: Transformer-TX 1
Load Type: Main cable to Switchboard Design Current Ib (A): 344.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 400 [f]
Neutral: 400 mm²[a] Length (m): 115
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 344.3
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 696.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 741.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 344.0 / 1.00 344.3 / 1.00 335.4 / 1.00 8.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.58 / 1.18 2.47 / 1.13 2.36 / 1.08 -----
Voltage Drop - From Source (V/%) 3.19 / 1.46 3.08 / 1.41 2.97 / 1.36 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00808 0.01104 0.01823 0.03667 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
5.97
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.42

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 39.510 / 35.219 Load End: 14.464 / 7.927
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 591.43 x 103 Adiabatic Limit k²S² (A²s): 3,271.84 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 8 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B1A-SM01 EDB-B1PA


Connection From: ESMDB-B1A To: EDB-B1PA
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 8.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 8.1
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 104.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.4 / 1.00 3.2 / 1.00 8.1 / 1.00 6.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) -0.02 / -0.01 0.01 / 0.01 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 1.31 / 0.60 1.42 / 0.65 1.45 / 0.66 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02909 0.00503 0.00936 0.04014 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.46
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.40

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.399 / 9.993 Load End: 14.301 / 7.340
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 304.24 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 9 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B1A-SM02 EDB-B1LA


Connection From: ESMDB-B1A To: EDB-B1LA
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 3.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 3.7
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 83.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 2.3 / 1.00 3.7 / 1.00 1.0 / 1.00 2.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.01 / 0.01 0.03 / 0.01 -0.01 / 0.00 -----
Voltage Drop - From Source (V/%) 1.34 / 0.61 1.43 / 0.65 1.39 / 0.63 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02909 0.00503 0.00936 0.04014 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.46
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.399 / 9.993 Load End: 14.301 / 7.340
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 300.25 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 10 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B1A-SM03 EMCC-B1A


Connection From: ESMDB-B1A To: EMCC-B1A
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 141.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 75
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 141.4
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 277.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 141.4 / 1.00 141.4 / 1.00 141.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.79 / 0.36 0.79 / 0.36 0.79 / 0.36 -----
Voltage Drop - From Source (V/%) 2.11 / 0.96 2.19 / 1.00 2.18 / 0.99 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 150 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02909 0.00798 0.01523 0.05166 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.24
Adiabatic check (mm 2 ) CPC Section = Separate 150 Total = 150.0 Min. Section = 3.78

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.399 / 9.993 Load End: 11.275 / 5.822
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 371.10 x 103 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 11 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B1B-SM01 EDB-B1PB


Connection From: ESMDB-B1B To: EDB-B1PB
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 8.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 8.2
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 104.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 2.1 / 1.00 8.2 / 1.00 3.2 / 1.00 5.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.06 / 0.03 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 1.00 / 0.46 1.07 / 0.49 0.99 / 0.45 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01513 0.00503 0.00936 0.02600 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
8.42
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 4.10

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 30.894 / 22.595 Load End: 22.576 / 12.430
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 429.17 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 12 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B1B-SM02 EDB-B1LB


Connection From: ESMDB-B1B To: EDB-B1LB
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 7.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 7.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 83.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 7.0 / 1.00 5.2 / 1.00 4.8 / 1.00 2.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.02 / 0.01 0.02 / 0.01 -----
Voltage Drop - From Source (V/%) 1.04 / 0.48 1.03 / 0.47 1.00 / 0.46 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01513 0.00503 0.00936 0.02600 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
8.42
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 4.08

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 30.894 / 22.595 Load End: 22.576 / 12.430
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 431.60 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 13 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B1B-SM03 EMCC-B1B


Connection From: ESMDB-B1B To: EMCC-B1B
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 273.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR23SE
Rating In (A):400 [f] Overload Setting Ir (A): 320 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 185 [f]
Neutral: 185 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 273.0
Device Rating In = 400 Overload Setting Ir = 320 [Ir >
_ Ib]
Min. Cable Capacity Iz = 389.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 456.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 273.0 / 1.00 273.0 / 1.00 273.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.86 / 0.85 1.86 / 0.85 1.86 / 0.85 -----
Voltage Drop - From Source (V/%) 2.86 / 1.31 2.87 / 1.31 2.85 / 1.30 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 95 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01513 0.00803 0.01525 0.03656 0.11903 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
5.99
Adiabatic check (mm 2 ) CPC Section = Separate 95 Total = 95.0 Min. Section = 3.89

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 30.894 / 22.595 Load End: 16.610 / 8.842
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 747.38 x 103 Adiabatic Limit k²S² (A²s): 699.87 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 14 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B2A-SM01 EDB-B2PA


Connection From: ESMDB-B2A To: EDB-B2PA
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 5.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.9
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 104.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.9 / 1.00 5.0 / 1.00 1.4 / 1.00 4.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.03 / 0.01 -0.01 / -0.01 -----
Voltage Drop - From Source (V/%) 1.87 / 0.85 1.72 / 0.79 1.75 / 0.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03161 0.00503 0.00936 0.04266 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.13
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.32

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.299 / 9.195 Load End: 13.538 / 6.898
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 288.34 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 15 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B2A-SM02 EDB-B2LA


Connection From: ESMDB-B2A To: EDB-B2LA
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 6.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 6.5
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 83.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 6.5 / 1.00 1.0 / 1.00 4.2 / 1.00 4.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 -0.02 / -0.01 0.02 / 0.01 -----
Voltage Drop - From Source (V/%) 1.88 / 0.86 1.68 / 0.77 1.79 / 0.82 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03161 0.00503 0.00936 0.04266 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.13
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.15

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.299 / 9.195 Load End: 13.538 / 6.898
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 283.69 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 16 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B2A-SM03 EMCC-B2A


Connection From: ESMDB-B2A To: EMCC-B2A
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 190.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 75
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 190.2
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 290.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 190.2 / 1.00 190.2 / 1.00 190.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.07 / 0.49 1.07 / 0.49 1.07 / 0.49 -----
Voltage Drop - From Source (V/%) 2.90 / 1.32 2.76 / 1.26 2.83 / 1.29 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 150 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03161 0.00798 0.01523 0.05420 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.04
Adiabatic check (mm 2 ) CPC Section = Separate 150 Total = 150.0 Min. Section = 3.71

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.299 / 9.195 Load End: 10.796 / 5.540
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 356.98 x 103 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 17 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B2B-SM01 EDB-B2PB


Connection From: ESMDB-B2B To: EDB-B2PB
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 5.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 104.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 3.2 / 1.00 5.0 / 1.00 1.0 / 1.00 3.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.02 / 0.01 0.03 / 0.02 -0.01 / 0.00 -----
Voltage Drop - From Source (V/%) 1.05 / 0.48 1.08 / 0.49 1.03 / 0.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01953 0.00503 0.00936 0.03062 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
7.15
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.81

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 23.345 / 14.864 Load End: 18.203 / 9.694
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 388.98 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 18 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B2B-SM02 EDB-B2LB


Connection From: ESMDB-B2B To: EDB-B2LB
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 5.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.2
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 83.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.1 / 1.00 1.0 / 1.00 5.2 / 1.00 4.1
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) -0.01 / 0.00 0.00 / 0.00 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 1.02 / 0.47 1.05 / 0.48 1.08 / 0.49 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01953 0.00503 0.00936 0.03062 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.15
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.79

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 23.345 / 14.864 Load End: 18.203 / 9.694
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 388.52 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 19 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B2B-SM03 EMCC-B2B


Connection From: ESMDB-B2B To: EMCC-B2B
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 144.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 144.8
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 278.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 144.8 / 1.00 144.8 / 1.00 144.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.47 / 0.67 1.47 / 0.67 1.47 / 0.67 -----
Voltage Drop - From Source (V/%) 2.50 / 1.14 2.52 / 1.15 2.51 / 1.15 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01953 0.01156 0.02002 0.04830 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.53
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 3.87

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 23.345 / 14.864 Load End: 12.489 / 6.093
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 383.27 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 20 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B3A-SM01 EDB-B3PA


Connection From: ESMDB-B3A To: EDB-B3PA
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 5.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 104.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 3.2 / 1.00 5.0 / 1.00 1.4 / 1.00 3.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.02 / 0.01 0.03 / 0.02 -0.01 / 0.00 -----
Voltage Drop - From Source (V/%) 1.95 / 0.89 1.87 / 0.86 1.88 / 0.86 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03414 0.00503 0.00936 0.04517 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
4.85
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.21

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 15.327 / 8.515 Load End: 12.852 / 6.507
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 274.24 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 21 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B3A-SM02 EDB-B3LA


Connection From: ESMDB-B3A To: EDB-B3LA
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 6.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 6.5
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 83.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 6.5 / 1.00 1.0 / 1.00 4.2 / 1.00 4.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 -0.02 / -0.01 0.02 / 0.01 -----
Voltage Drop - From Source (V/%) 1.97 / 0.90 1.82 / 0.83 1.91 / 0.87 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03414 0.00503 0.00936 0.04517 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
4.85
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.02

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 15.327 / 8.515 Load End: 12.852 / 6.507
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 269.00 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 22 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B3A-SM03 EMCC-B3A


Connection From: ESMDB-B3A To: EMCC-B3A
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 191.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 75
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 191.2
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 290.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 191.2 / 1.00 191.2 / 1.00 191.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.07 / 0.49 1.07 / 0.49 1.07 / 0.49 -----
Voltage Drop - From Source (V/%) 3.00 / 1.37 2.91 / 1.33 2.96 / 1.35 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 150 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03414 0.00798 0.01523 0.05674 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
3.86
Adiabatic check (mm 2 ) CPC Section = Separate 150 Total = 150.0 Min. Section = 3.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 15.327 / 8.515 Load End: 10.357 / 5.283
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 344.16 x 103 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 23 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B3B-SM01 EDB-B3PB


Connection From: ESMDB-B3B To: EDB-B3PB
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 5.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.9
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 104.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.9 / 1.00 4.6 / 1.00 1.0 / 1.00 4.4
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.02 / 0.01 -0.01 / -0.01 -----
Voltage Drop - From Source (V/%) 1.19 / 0.54 1.14 / 0.52 1.11 / 0.51 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02204 0.00503 0.00936 0.03312 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.61
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.69

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.429 / 13.182 Load End: 16.984 / 8.940
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 361.85 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 24 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B3B-SM02 EDB-B3LB


Connection From: ESMDB-B3B To: EDB-B3LB
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 3.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 3.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 83.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.1 / 1.00 1.0 / 1.00 3.0 / 1.00 2.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 0.02 / 0.01 -----
Voltage Drop - From Source (V/%) 1.15 / 0.52 1.12 / 0.51 1.15 / 0.52 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02204 0.00503 0.00936 0.03312 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.61
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.65

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.429 / 13.182 Load End: 16.984 / 8.940
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 360.26 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 25 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B3B-SM03 EMCC-B3B


Connection From: ESMDB-B3B To: EMCC-B3B
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 144.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 144.8
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 278.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 144.8 / 1.00 144.8 / 1.00 144.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.47 / 0.67 1.47 / 0.67 1.47 / 0.67 -----
Voltage Drop - From Source (V/%) 2.62 / 1.20 2.59 / 1.18 2.59 / 1.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02204 0.01156 0.02002 0.05077 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.31
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 3.80

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.429 / 13.182 Load End: 11.906 / 5.789
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 369.47 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 26 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B4A-SM01 EDB-B4PA


Connection From: ESMDB-B4A To: EDB-B4PA
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 6.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 6.2
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 104.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 4.5 / 1.00 6.2 / 1.00 1.8 / 1.00 3.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.03 / 0.01 0.04 / 0.02 -0.01 / 0.00 -----
Voltage Drop - From Source (V/%) 3.22 / 1.47 3.12 / 1.42 2.96 / 1.35 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03667 0.00503 0.00936 0.04769 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
4.59
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.09

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 14.464 / 7.927 Load End: 12.232 / 6.157
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 261.65 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 27 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B4A-SM02 EDB-B4LA


Connection From: ESMDB-B4A To: EDB-B4LA
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 6.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 6.4
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 83.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.6 / 1.00 6.4 / 1.00 1.9 / 1.00 4.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.03 / 0.02 0.04 / 0.02 -0.01 / 0.00 -----
Voltage Drop - From Source (V/%) 3.23 / 1.47 3.12 / 1.42 2.96 / 1.35 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03667 0.00503 0.00936 0.04769 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
4.59
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.90

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 14.464 / 7.927 Load End: 12.232 / 6.157
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 255.88 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 28 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B4A-SM03 EMCC-B4A


Connection From: ESMDB-B4A To: EMCC-B4A
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 186.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 75
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 186.4
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 289.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 186.4 / 1.00 186.4 / 1.00 186.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.04 / 0.48 1.04 / 0.48 1.04 / 0.48 -----
Voltage Drop - From Source (V/%) 4.24 / 1.94 4.12 / 1.88 4.01 / 1.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 150 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03667 0.00798 0.01523 0.05928 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
3.69
Adiabatic check (mm 2 ) CPC Section = Separate 150 Total = 150.0 Min. Section = 3.65

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 14.464 / 7.927 Load End: 9.951 / 5.050
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 332.48 x 103 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 29 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B4A-SM04 EMCC-B4A1


Connection From: ESMDB-B4A To: EMCC-B4A1
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 147.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 75
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 147.6
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 278.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 147.6 / 1.00 145.4 / 1.00 145.4 / 1.00 2.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.83 / 0.38 0.81 / 0.37 0.81 / 0.37 -----
Voltage Drop - From Source (V/%) 4.03 / 1.84 3.89 / 1.78 3.78 / 1.73 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 150 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03667 0.00798 0.01523 0.05928 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
3.69
Adiabatic check (mm 2 ) CPC Section = Separate 150 Total = 150.0 Min. Section = 3.65

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 14.464 / 7.927 Load End: 9.951 / 5.050
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 332.48 x 103 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 30 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B4B-SM01 EDB-B4PB


Connection From: ESMDB-B4B To: EDB-B4PB
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 7.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 7.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 104.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.3 / 1.00 7.3 / 1.00 1.0 / 1.00 5.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.03 / 0.02 0.05 / 0.02 -0.02 / -0.01 -----
Voltage Drop - From Source (V/%) 1.62 / 0.74 1.62 / 0.74 1.50 / 0.68 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02455 0.00503 0.00936 0.03562 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.15
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.57

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.796 / 11.836 Load End: 15.918 / 8.295
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 338.62 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 31 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B4B-SM02 EDB-B4LB


Connection From: ESMDB-B4B To: EDB-B4LB
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 5.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.7
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 83.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.1 / 1.00 5.2 / 1.00 5.7 / 1.00 0.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.03 / 0.01 0.03 / 0.02 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 1.62 / 0.74 1.61 / 0.73 1.56 / 0.71 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02455 0.00754 0.01403 0.04192 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.22
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.18

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.796 / 11.836 Load End: 14.303 / 7.105
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 291.42 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 32 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B4B-SM03 EMCC-B4B


Connection From: ESMDB-B4B To: EMCC-B4B
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 136.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 136.4
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 276.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 136.4 / 1.00 136.4 / 1.00 136.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.38 / 0.63 1.38 / 0.63 1.38 / 0.63 -----
Voltage Drop - From Source (V/%) 2.97 / 1.36 2.95 / 1.35 2.90 / 1.32 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02455 0.01156 0.02002 0.05324 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.11
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 3.74

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.796 / 11.836 Load End: 11.375 / 5.514
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 355.70 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 33 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-ESMDB-B4B-SM04 EMBB-B4B1


Connection From: ESMDB-B4B To: EMCC-B4B1
Active Source: Transformer-TX 1
Load Type: Distribution Board Design Current Ib (A): 84.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 84.1
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 176.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 84.1 / 1.00 84.1 / 1.00 84.1 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.83 / 0.38 0.83 / 0.38 0.83 / 0.38 -----
Voltage Drop - From Source (V/%) 2.42 / 1.11 2.41 / 1.10 2.35 / 1.07 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02455 0.01156 0.02002 0.05324 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
4.11
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 3.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.796 / 11.836 Load End: 11.375 / 5.514
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 278.13 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 34 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-TX1 EMDB 1


Connection From: Transformer-TX 1 To: EMDB 1
Active Source: Transformer-TX 1
Load Type: Main cable to Switchboard Design Current Ib (A): 2,400.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS3200 H MLogic 5.0A
Rating In (A):3200 [f] Overload Setting Ir (A): 2560 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 3 x 4 x 1c Size (mm2): 630 [f]
Neutral: 630 mm²[a] Length (m): 20
34 - On a ladder Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.96 [BS 7671, Table 4C5]
No. of ladders = 1 No. of circuits per ladder = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 2,400.0
Device Rating In = 3200 Overload Setting Ir = 2560 [Ir >
_ Ib]
Min. Cable Capacity Iz = 925.9 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 1,151.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 2400.0 / 1.00 2400.0 / 1.00 2400.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.61 / 0.28 0.61 / 0.28 0.61 / 0.28 -----
Voltage Drop - From Source (V/%) 0.61 / 0.28 0.61 / 0.28 0.61 / 0.28 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 630 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00491 0.00067 0.00252 0.00808 0.02592 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
27.10
Adiabatic check (mm 2 ) CPC Section = Separate 630 Total = 630.0 Min. Section = 88.46

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 44.711 / 44.710 Load End: 39.510 / 35.219
Protective Device Breaking Capacity (kA): Icu: 125 Ics: 93.7

Adiabatic Check: CPD Energy Let-through (A²s): 160.00 x 106 Adiabatic Limit k²S² (A²s): 8,116.21 x 106

Project: KAFD 3.09 Tx 1 & Gen rev 2.p17 Page 35 of 35 Printed on: 17/01/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Buro Happold

4.2 Transformer TX2

KAFD Plot 3.09 Report Revision 0


Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-2-SM02 SMDB-B1B


Connection From: MDB 2 To: SMDB-B1B
Active Source: Transformer-TX 2
Load Type: Main cable to Switchboard Design Current Ib (A): 146.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 400 [f]
Neutral: 400 mm²[a] Length (m): 75
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 146.6
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 663.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 741.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 132.7 / 1.00 130.4 / 1.00 146.6 / 1.00 15.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.50 / 0.23 0.61 / 0.28 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 1.38 / 0.63 1.49 / 0.68 1.62 / 0.74 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01267 0.00720 0.01189 0.03102 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.06
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.89

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.860 / 25.000 Load End: 16.217 / 9.743
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 905.05 x 103 Adiabatic Limit k²S² (A²s): 3,271.84 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 1 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-2-SM03 SMDB-B1A


Connection From: MDB 2 To: SMDB-B1A
Active Source: Transformer-TX 2
Load Type: Main cable to Switchboard Design Current Ib (A): 401.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 400 [f]
Neutral: 400 mm²[a] Length (m): 125
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 401.6
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 710.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 741.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 399.8 / 1.00 401.6 / 1.00 397.4 / 1.00 3.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.23 / 1.47 3.22 / 1.47 3.13 / 1.43 -----
Voltage Drop - From Source (V/%) 4.10 / 1.87 4.09 / 1.87 4.01 / 1.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01267 0.01200 0.01982 0.04359 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
5.02
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.42

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.860 / 25.000 Load End: 12.344 / 6.853
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 465.11 x 103 Adiabatic Limit k²S² (A²s): 3,271.84 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 2 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-2-SM04 SMDB-B2B


Connection From: MDB 2 To: SMDB-B2B
Active Source: Transformer-TX 2
Load Type: Main cable to Switchboard Design Current Ib (A): 46.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 320 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 185 [f]
Neutral: 185 mm²[a] Length (m): 85
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 46.0
Device Rating In = 400 Overload Setting Ir = 320 [Ir >
_ Ib]
Min. Cable Capacity Iz = 334.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 456.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 46.0 / 1.00 33.9 / 1.00 35.3 / 1.00 11.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.56 / 0.25 0.21 / 0.10 0.36 / 0.17 -----
Voltage Drop - From Source (V/%) 1.43 / 0.65 1.08 / 0.49 1.24 / 0.57 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 95 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01267 0.01242 0.02358 0.04569 0.07439 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.79
Adiabatic check (mm 2 ) CPC Section = Separate 95 Total = 95.0 Min. Section = 3.37

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.860 / 25.000 Load End: 13.168 / 6.926
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 444.31 x 103 Adiabatic Limit k²S² (A²s): 699.87 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 3 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-2-SM05 SMDB-B2A


Connection From: MDB 2 To: SMDB-B2A
Active Source: Transformer-TX 2
Load Type: Main cable to Switchboard Design Current Ib (A): 62.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 320 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 185 [f]
Neutral: 185 mm²[a] Length (m): 135
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 62.7
Device Rating In = 400 Overload Setting Ir = 320 [Ir >
_ Ib]
Min. Cable Capacity Iz = 336.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 456.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 62.7 / 1.00 58.7 / 1.00 56.4 / 1.00 5.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.08 / 0.49 0.85 / 0.39 0.85 / 0.39 -----
Voltage Drop - From Source (V/%) 1.96 / 0.89 1.73 / 0.79 1.72 / 0.79 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 95 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01267 0.01972 0.03744 0.06657 0.07439 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
3.29
Adiabatic check (mm 2 ) CPC Section = Separate 95 Total = 95.0 Min. Section = 8.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.860 / 25.000 Load End: 9.708 / 4.758
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 229.24 x 103 Adiabatic Limit k²S² (A²s): 699.87 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 4 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-2-SM06 SMDB-B3B


Connection From: MDB 2 To: SMDB-B3B
Active Source: Transformer-TX 2
Load Type: Main cable to Switchboard Design Current Ib (A): 46.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 320 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 185 [f]
Neutral: 185 mm²[a] Length (m): 95
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 46.0
Device Rating In = 400 Overload Setting Ir = 320 [Ir >
_ Ib]
Min. Cable Capacity Iz = 334.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 456.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 46.0 / 1.00 31.5 / 1.00 33.5 / 1.00 13.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.64 / 0.29 0.18 / 0.08 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 1.52 / 0.69 1.05 / 0.48 1.27 / 0.58 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 95 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01267 0.01388 0.02635 0.04984 0.07439 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.39
Adiabatic check (mm 2 ) CPC Section = Separate 95 Total = 95.0 Min. Section = 3.17

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.860 / 25.000 Load End: 12.299 / 6.350
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 360.75 x 103 Adiabatic Limit k²S² (A²s): 699.87 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 5 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-2-SM07 SMDB-B3A


Connection From: MDB 2 To: SMDB-B3A
Active Source: Transformer-TX 2
Load Type: Main cable to Switchboard Design Current Ib (A): 59.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 320 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 185 [f]
Neutral: 185 mm²[a] Length (m): 145
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 59.8
Device Rating In = 400 Overload Setting Ir = 320 [Ir >
_ Ib]
Min. Cable Capacity Iz = 335.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 456.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 59.8 / 1.00 56.0 / 1.00 56.4 / 1.00 3.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.06 / 0.49 0.87 / 0.40 0.95 / 0.44 -----
Voltage Drop - From Source (V/%) 1.94 / 0.88 1.75 / 0.80 1.83 / 0.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 95 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01267 0.02118 0.04022 0.07076 0.07439 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
3.09
Adiabatic check (mm 2 ) CPC Section = Separate 95 Total = 95.0 Min. Section = 8.10

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.860 / 25.000 Load End: 9.219 / 4.476
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 210.94 x 103 Adiabatic Limit k²S² (A²s): 699.87 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 6 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-2-SM08 SMDB-B4B


Connection From: MDB 2 To: SMDB-B4B
Active Source: Transformer-TX 2
Load Type: Main cable to Switchboard Design Current Ib (A): 96.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 320 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 185 [f]
Neutral: 185 mm²[a] Length (m): 105
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 96.5
Device Rating In = 400 Overload Setting Ir = 320 [Ir >
_ Ib]
Min. Cable Capacity Iz = 339.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 456.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 94.8 / 1.00 96.5 / 1.00 92.0 / 1.00 3.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.19 / 0.55 1.20 / 0.55 1.07 / 0.49 -----
Voltage Drop - From Source (V/%) 2.07 / 0.94 2.07 / 0.95 1.94 / 0.89 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 95 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01267 0.01534 0.02912 0.05401 0.07439 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.05
Adiabatic check (mm 2 ) CPC Section = Separate 95 Total = 95.0 Min. Section = 3.00

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.860 / 25.000 Load End: 11.534 / 5.861
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 300.96 x 103 Adiabatic Limit k²S² (A²s): 699.87 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 7 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-2-SM09 SMDB-B4A


Connection From: MDB 2 To: SMDB-B4A
Active Source: Transformer-TX 2
Load Type: Main cable to Switchboard Design Current Ib (A): 116.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 320 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 185 [f]
Neutral: 185 mm²[a] Length (m): 155
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 116.8
Device Rating In = 400 Overload Setting Ir = 320 [Ir >
_ Ib]
Min. Cable Capacity Iz = 342.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 456.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 116.8 / 1.00 106.9 / 1.00 111.4 / 1.00 8.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.21 / 1.01 1.75 / 0.80 2.10 / 0.96 -----
Voltage Drop - From Source (V/%) 3.09 / 1.41 2.62 / 1.20 2.98 / 1.36 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01267 0.02264 0.03590 0.06831 0.07439 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
3.21
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 8.39

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.860 / 25.000 Load End: 8.775 / 4.226
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 194.66 x 103 Adiabatic Limit k²S² (A²s): 699.87 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 8 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B1A-SM01 DB-B1PA


Connection From: SMDB-B1A To: DB-B1PA
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 39.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 39.4
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 107.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 26.7 / 1.00 39.4 / 1.00 37.3 / 1.00 11.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.05 / 0.02 0.15 / 0.07 0.12 / 0.06 -----
Voltage Drop - From Source (V/%) 4.15 / 1.90 4.24 / 1.94 4.13 / 1.88 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04359 0.00349 0.00688 0.05144 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
4.26
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.93

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.344 / 6.853 Load End: 11.106 / 5.844
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 250.37 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 9 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B1A-SM02 DB-B1LA


Connection From: SMDB-B1A To: DB-B1LA
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 10.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.6
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 83.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 7.8 / 1.00 10.6 / 1.00 8.4 / 1.00 2.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.03 / 0.01 0.06 / 0.03 0.03 / 0.01 -----
Voltage Drop - From Source (V/%) 4.13 / 1.89 4.15 / 1.89 4.04 / 1.84 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04359 0.00503 0.00936 0.05426 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
4.04
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.64

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.344 / 6.853 Load End: 10.720 / 5.514
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 223.26 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 10 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B1A-SM03 MCC-B1A


Connection From: SMDB-B1A To: MCC-B1A
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 159.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 159.3
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 281.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 159.3 / 1.00 145.6 / 1.00 145.6 / 1.00 13.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.89 / 0.41 0.76 / 0.35 0.76 / 0.35 -----
Voltage Drop - From Source (V/%) 4.99 / 2.28 4.85 / 2.21 4.76 / 2.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04359 0.00683 0.01274 0.06206 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
3.53
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 3.62

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.344 / 6.853 Load End: 9.387 / 4.853
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 322.63 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 11 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B1A-SM04 MCC-WF


Connection From: SMDB-B1A To: MCC-WF
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 30.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 75
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 30.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 106.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.0 / 1.00 30.0 / 1.00 30.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 4.50 / 2.06 4.49 / 2.05 4.41 / 2.01 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04359 0.01576 0.02730 0.08243 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.66
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 2.04

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.344 / 6.853 Load End: 7.553 / 3.597
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 135.80 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 12 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B1A-SM05 RETAIL 1


Connection From: SMDB-B1A To: RETAIL 1
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 64.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 30
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 64.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 112.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 64.0 / 1.00 64.0 / 1.00 64.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.34 / 0.16 0.34 / 0.16 0.34 / 0.16 -----
Voltage Drop - From Source (V/%) 4.45 / 2.03 4.43 / 2.02 4.35 / 1.99 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04359 0.00630 0.01092 0.05842 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
3.75
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.344 / 6.853 Load End: 9.934 / 5.082
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 222.95 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 13 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B1A-SM06 RETAIL 2


Connection From: SMDB-B1A To: RETAIL 2
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 112.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 112.0
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 183.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 112.0 / 1.00 112.0 / 1.00 112.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.31 / 0.14 0.31 / 0.14 0.31 / 0.14 -----
Voltage Drop - From Source (V/%) 4.41 / 2.01 4.40 / 2.01 4.31 / 1.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04359 0.00315 0.00546 0.05082 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
4.31
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 3.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.344 / 6.853 Load End: 11.036 / 5.854
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 293.45 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 14 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B1B-SM01 DB-B1PB


Connection From: SMDB-B1B To: DB-B1PB
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 118.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 118.3
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 184.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 112.9 / 1.00 109.8 / 1.00 118.3 / 1.00 7.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.53 / 0.24 0.50 / 0.23 0.61 / 0.28 -----
Voltage Drop - From Source (V/%) 1.91 / 0.87 1.99 / 0.91 2.23 / 1.02 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03102 0.00503 0.00936 0.04160 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.26
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.217 / 9.743 Load End: 13.594 / 7.267
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 334.84 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 15 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B1B-SM02 DB-B1LB


Connection From: SMDB-B1B To: DB-B1LB
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 26.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 26.9
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 85.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 18.5 / 1.00 19.3 / 1.00 26.9 / 1.00 8.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.08 / 0.04 0.16 / 0.07 -----
Voltage Drop - From Source (V/%) 1.44 / 0.66 1.56 / 0.71 1.78 / 0.81 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03102 0.00503 0.00936 0.04160 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.26
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.20

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.217 / 9.743 Load End: 13.594 / 7.267
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 297.50 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 16 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B1B-SM03 MCC-B1B


Connection From: SMDB-B1B To: MCC-B1B
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 1.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1.4
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 166.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.4 / 1.00 1.4 / 1.00 1.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.01 / 0.01 0.01 / 0.01 0.01 / 0.01 -----
Voltage Drop - From Source (V/%) 1.39 / 0.64 1.50 / 0.69 1.63 / 0.75 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03102 0.01156 0.02002 0.05905 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.71
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 3.06

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.217 / 9.743 Load End: 10.166 / 5.051
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 257.31 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 17 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B2A-SM01 DB-B2PA


Connection From: SMDB-B2A To: DB-B2PA
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 46.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 46.9
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 108.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 40.5 / 1.00 46.9 / 1.00 40.0 / 1.00 6.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.06 0.17 / 0.08 0.11 / 0.05 -----
Voltage Drop - From Source (V/%) 2.08 / 0.95 1.89 / 0.86 1.83 / 0.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.06657 0.00349 0.00688 0.07611 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.88
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.15

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.708 / 4.758 Load End: 8.786 / 4.176
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 170.57 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 18 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B2A-SM02 DB-B2LA


Connection From: SMDB-B2A To: DB-B2LA
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 22.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 22.3
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 84.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.3 / 1.00 11.9 / 1.00 16.4 / 1.00 9.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.13 / 0.06 0.02 / 0.01 0.08 / 0.04 -----
Voltage Drop - From Source (V/%) 2.09 / 0.95 1.74 / 0.80 1.80 / 0.82 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.06657 0.00503 0.00936 0.07958 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
2.75
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.04

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.708 / 4.758 Load End: 8.482 / 3.976
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 138.95 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 19 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B2B-SM01 DB-B2PB


Connection From: SMDB-B2B To: DB-B2PB
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 27.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 27.4
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 105.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 27.4 / 1.00 24.7 / 1.00 25.0 / 1.00 2.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.14 / 0.06 0.10 / 0.05 0.11 / 0.05 -----
Voltage Drop - From Source (V/%) 1.57 / 0.72 1.19 / 0.54 1.35 / 0.62 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04569 0.00503 0.00936 0.05845 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
3.75
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 13.168 / 6.926 Load End: 11.085 / 5.408
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 234.70 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 20 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B2B-SM02 DB-B2LB


Connection From: SMDB-B2B To: DB-B2LB
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 18.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 18.6
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 84.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 18.6 / 1.00 9.2 / 1.00 10.3 / 1.00 8.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.06 0.01 / 0.01 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 1.55 / 0.71 1.10 / 0.50 1.28 / 0.58 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04569 0.00503 0.00936 0.05845 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
3.75
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.51

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 13.168 / 6.926 Load End: 11.085 / 5.408
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 217.46 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 21 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B3A-SM01 DB-B3PA


Connection From: SMDB-B3A To: DB-B3PA
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 44.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 44.1
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 108.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 40.5 / 1.00 44.1 / 1.00 40.0 / 1.00 3.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.06 0.15 / 0.07 0.11 / 0.05 -----
Voltage Drop - From Source (V/%) 2.06 / 0.94 1.90 / 0.87 1.94 / 0.89 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.07076 0.00349 0.00688 0.08033 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.73
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.07

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.219 / 4.476 Load End: 8.379 / 3.956
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 157.39 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 22 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B3A-SM02 DB-B3LA


Connection From: SMDB-B3A To: DB-B3LA
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 19.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 19.4
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 84.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 19.4 / 1.00 11.9 / 1.00 16.4 / 1.00 6.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.11 / 0.05 0.02 / 0.01 0.08 / 0.04 -----
Voltage Drop - From Source (V/%) 2.05 / 0.93 1.77 / 0.81 1.91 / 0.87 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.07076 0.00503 0.00936 0.08381 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
2.61
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 1.97

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.219 / 4.476 Load End: 8.101 / 3.776
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 130.15 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 23 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B3B-SM01 DB-B3PB


Connection From: SMDB-B3B To: DB-B3PB
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 27.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 27.4
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 105.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 27.4 / 1.00 22.3 / 1.00 23.2 / 1.00 4.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.14 / 0.07 0.08 / 0.04 0.10 / 0.05 -----
Voltage Drop - From Source (V/%) 1.66 / 0.76 1.14 / 0.52 1.37 / 0.63 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04984 0.00503 0.00936 0.06268 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
3.49
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.52

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.299 / 6.350 Load End: 10.445 / 5.045
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 221.62 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 24 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B3B-SM02 DB-B3LB


Connection From: SMDB-B3B To: DB-B3LB
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 18.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 18.6
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 84.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 18.6 / 1.00 9.2 / 1.00 10.3 / 1.00 8.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.06 0.01 / 0.01 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 1.64 / 0.75 1.07 / 0.49 1.31 / 0.60 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04984 0.00503 0.00936 0.06268 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
3.49
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.40

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.299 / 6.350 Load End: 10.445 / 5.045
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 197.48 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 25 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B4A-SM01 DB-B4PA


Connection From: SMDB-B4A To: DB-B4PA
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 48.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 48.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 109.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 48.0 / 1.00 45.4 / 1.00 42.1 / 1.00 5.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.16 / 0.08 0.14 / 0.06 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 3.25 / 1.48 2.76 / 1.26 3.10 / 1.41 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.06831 0.00349 0.00688 0.07769 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.82
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.12

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 8.775 / 4.226 Load End: 8.008 / 3.759
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 145.52 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 26 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B4A-SM02 DB-B4LA


Connection From: SMDB-B4A To: DB-B4LA
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 23.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 23.9
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 84.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.5 / 1.00 16.1 / 1.00 23.9 / 1.00 7.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.04 / 0.02 0.13 / 0.06 -----
Voltage Drop - From Source (V/%) 3.20 / 1.46 2.66 / 1.22 3.11 / 1.42 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.06831 0.00503 0.00936 0.08108 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
2.70
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.01

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 8.775 / 4.226 Load End: 7.752 / 3.595
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 122.19 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 27 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B4A-SM03 MCC-B4A


Connection From: SMDB-B4A To: MCC-B4A
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 45.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 45.4
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 108.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.4 / 1.00 45.4 / 1.00 45.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.45 / 0.20 0.45 / 0.20 0.45 / 0.20 -----
Voltage Drop - From Source (V/%) 3.53 / 1.61 3.07 / 1.40 3.42 / 1.56 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.06831 0.01156 0.02002 0.09885 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.22
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 1.79

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 8.775 / 4.226 Load End: 6.466 / 2.945
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 97.59 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 28 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B4B-SM01 DB-B4PB


Connection From: SMDB-B4B To: DB-B4PB
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 30.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 30.7
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 106.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.7 / 1.00 26.4 / 1.00 27.3 / 1.00 4.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.16 / 0.07 0.11 / 0.05 0.12 / 0.06 -----
Voltage Drop - From Source (V/%) 2.23 / 1.02 2.18 / 0.99 2.06 / 0.94 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.05401 0.00503 0.00936 0.06690 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.27
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.39

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 11.534 / 5.861 Load End: 9.875 / 4.727
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 203.65 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 29 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B4B-SM02 DB-B4LB


Connection From: SMDB-B4B To: DB-B4LB
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 20.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.1
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 84.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.1 / 1.00 20.1 / 1.00 14.8 / 1.00 5.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.05 / 0.02 0.12 / 0.05 0.05 / 0.02 -----
Voltage Drop - From Source (V/%) 2.12 / 0.97 2.19 / 1.00 1.99 / 0.91 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.05401 0.00503 0.00936 0.06690 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
3.27
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.30

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 11.534 / 5.861 Load End: 9.875 / 4.727
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 180.01 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 30 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-B4B-SM03 MCC-B4B


Connection From: SMDB-B4B To: MCC-B4B
Active Source: Transformer-TX 2
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 109.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.49 / 0.22 0.49 / 0.22 0.49 / 0.22 -----
Voltage Drop - From Source (V/%) 2.56 / 1.17 2.56 / 1.17 2.43 / 1.11 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.05401 0.01156 0.02002 0.08468 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.59
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 2.00

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 11.534 / 5.861 Load End: 7.884 / 3.665
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 139.88 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 31 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign 100 Job Number:


Document No: Created On : 03/06/2010 Rev Date :
Created By : apainter Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-TX2 MDB 2


Connection From: Transformer-TX 2 To: MDB 2
Active Source: Transformer-TX 2
Load Type: Main cable to Switchboard Design Current Ib (A): 1,700.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS2000 N MLogic 5.0A
Rating In (A):2000 [f] Overload Setting Ir (A): 1800 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 3 x 4 x 1c Size (mm2): 630 [f]
Neutral: 630 mm²[a] Length (m): 42
34 - On a ladder Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 35.0 Ca = 0.96 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.93 [BS 7671, Table 4C5]
No. of ladders = 2 No. of circuits per ladder = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,700.0
Device Rating In = 2000 Overload Setting Ir = 1800 [Ir >
_ Ib]
Min. Cable Capacity Iz = 672.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 1,151.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1700.0 / 1.00 1700.0 / 1.00 1700.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.87 / 0.40 0.87 / 0.40 0.87 / 0.40 -----
Voltage Drop - From Source (V/%) 0.87 / 0.40 0.87 / 0.40 0.87 / 0.40 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 630 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00599 0.00141 0.00530 0.01267 0.03687 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
17.29
Adiabatic check (mm 2 ) CPC Section = Separate 630 Total = 630.0 Min. Section = 88.46

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 36.627 / 36.627 Load End: 29.860 / 25.000
Protective Device Breaking Capacity (kA): Icu: 85 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 160.00 x 106 Adiabatic Limit k²S² (A²s): 8,116.21 x 106

Project: KAFD 3.09 Tx 2 rev 2.p17 Page 32 of 32 Printed on: 17/01/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Buro Happold

4.3 Transformer TX3

KAFD Plot 3.09 Report Revision 0


Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MBD3-1-SM01 SMDB-GA


Connection From: TO-1 To: SMDB-GA
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 217.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 400 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 217.7
Device Rating In = 400 Overload Setting Ir = 400 [Ir >
_ Ib]
Min. Cable Capacity Iz = 459.8 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 217.7 / 1.00 217.7 / 1.00 217.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.04 0.10 / 0.04 0.10 / 0.04 -----
Voltage Drop - From Source (V/%) 3.48 / 1.59 3.48 / 1.59 3.48 / 1.59 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03328 0.00062 0.00116 0.03485 0.05951 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
6.28
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 4.14

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.719 / 12.133 Load End: 17.064 / 11.425
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.01 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 1 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MBD3-1-SM02 RETAIL G.2


Connection From: TO-2 To: RETAIL G.2
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 355.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 400 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =5 Cg = 0.75 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 5
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 355.3
Device Rating In = 400 Overload Setting Ir = 400 [Ir >
_ Ib]
Min. Cable Capacity Iz = 544.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 355.3 / 1.00 355.3 / 1.00 355.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.01 / 0.46 1.01 / 0.46 1.01 / 0.46 -----
Voltage Drop - From Source (V/%) 4.41 / 2.01 4.41 / 2.01 4.41 / 2.01 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 150 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03334 0.00383 0.00731 0.04378 0.11903 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
5.00
Adiabatic check (mm 2 ) CPC Section = Separate 150 Total = 150.0 Min. Section = 3.46

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.692 / 12.101 Load End: 14.092 / 8.625
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 709.44 x 103 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 2 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MBD3-1-SM03 SMDB-1A


Connection From: TO-3 To: SMDB-1A
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 431.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 431.3
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 431.3 / 1.00 431.3 / 1.00 431.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.05 0.10 / 0.05 0.10 / 0.05 -----
Voltage Drop - From Source (V/%) 3.54 / 1.62 3.54 / 1.62 3.54 / 1.62 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03364 0.00031 0.00079 0.03470 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
6.31
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.43

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.560 / 11.941 Load End: 17.232 / 11.587
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.25 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 3 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MBD3-2-SM02 RETAIL G.5


Connection From: TO-5 To: RETAIL G.5
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 341.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 400 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 341.7
Device Rating In = 400 Overload Setting Ir = 400 [Ir >
_ Ib]
Min. Cable Capacity Iz = 538.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 341.7 / 1.00 341.7 / 1.00 341.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.03 / 0.47 1.03 / 0.47 1.03 / 0.47 -----
Voltage Drop - From Source (V/%) 3.33 / 1.52 3.33 / 1.52 3.33 / 1.52 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 150 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02314 0.00405 0.00772 0.03408 0.11903 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
6.43
Adiabatic check (mm 2 ) CPC Section = Separate 150 Total = 150.0 Min. Section = 4.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.013 / 15.873 Load End: 15.961 / 10.235
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 960.59 x 103 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 4 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MBD3-2-SM03 SMDB-1B


Connection From: TO-6 To: SMDB-1B
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 542.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 542.1
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 542.1 / 1.00 542.1 / 1.00 542.1 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.13 / 0.06 0.13 / 0.06 0.13 / 0.06 -----
Voltage Drop - From Source (V/%) 2.46 / 1.12 2.46 / 1.12 2.46 / 1.12 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02331 0.00031 0.00079 0.02435 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
8.99
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.15

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.904 / 15.716 Load End: 20.453 / 15.127
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.42 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 5 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB3-2-SM01 SMDB-GB


Connection From: TO-4 To: SMDB-GB
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 259.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 400 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 259.7
Device Rating In = 400 Overload Setting Ir = 400 [Ir >
_ Ib]
Min. Cable Capacity Iz = 459.8 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 259.7 / 1.00 259.7 / 1.00 259.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 2.40 / 1.10 2.40 / 1.10 2.40 / 1.10 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02308 0.00062 0.00116 0.02461 0.07604 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
8.90
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 6.08

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.049 / 15.926 Load End: 20.152 / 14.762
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.16 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 6 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-3-SM01 RETAIL LIFT


Connection From: MDB 3 To: RETAIL LIFT
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 165
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.87 / 2.22 4.87 / 2.22 4.87 / 2.22 -----
Voltage Drop - From Source (V/%) 5.34 / 2.44 5.34 / 2.44 5.34 / 2.44 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01262 0.15300 0.23925 0.39562 0.58564 Current (kA)

Disconnection time (s): From characteristic: 3.49 Maximum for circuit: 5.00
0.55
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 7.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.339 / 23.867 Load End: 1.788 / 0.709
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 15.92 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 7 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-3-SM02 ESCALATOR


Connection From: MDB 3 To: ESCALATOR
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 191
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 49.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.0 / 1.00 22.0 / 1.00 22.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.62 / 1.65 3.62 / 1.65 3.62 / 1.65 -----
Voltage Drop - From Source (V/%) 4.09 / 1.87 4.09 / 1.87 4.09 / 1.87 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01262 0.17711 0.27695 0.45734 0.58564 Current (kA)

Disconnection time (s): From characteristic: 3.92 Maximum for circuit: 5.00
0.48
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 6.63

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.339 / 23.867 Load End: 1.550 / 0.613
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 14.00 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 8 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-3-SM03 ESCALATOR


Connection From: MDB 3 To: ESCALATOR
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 193
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 49.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.0 / 1.00 22.0 / 1.00 22.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.66 / 1.67 3.66 / 1.67 3.66 / 1.67 -----
Voltage Drop - From Source (V/%) 4.13 / 1.88 4.13 / 1.88 4.13 / 1.88 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01262 0.17897 0.27985 0.46209 0.58564 Current (kA)

Disconnection time (s): From characteristic: 3.96 Maximum for circuit: 5.00
0.47
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 6.60

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.339 / 23.867 Load End: 1.534 / 0.607
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 14.00 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 9 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-3-SM04 BB-MBD3-1


Connection From: MDB 3 To: EF-1
Active Source: Tx 3
Load Type: Busbar EndFeed Design Current Ib (A): 1,004.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW16 H1 MLogic 5.0A High
Rating In (A):1600 [f] Overload Setting Ir (A): 1600 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 3 x 4 x 1c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 109
31 - On horizontal/vertical perforated tray Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.87 [BS 7671, Table 4C5]
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,004.3
Device Rating In = 1600 Overload Setting Ir = 1600 [Ir >
_ Ib]
Min. Cable Capacity Iz = 704.6 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 736.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1004.3 / 1.00 1004.3 / 1.00 1004.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.65 / 1.21 2.65 / 1.21 2.65 / 1.21 -----
Voltage Drop - From Source (V/%) 3.12 / 1.42 3.12 / 1.42 3.12 / 1.42 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01262 0.00439 0.01603 0.03257 0.04148 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
6.72
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 17.59

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.339 / 23.867 Load End: 18.043 / 12.533
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 173.06 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 10 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-3-SM05 BB-MDB3-2


Connection From: MDB 3 To: EF-2
Active Source: Tx 3
Load Type: Busbar EndFeed Design Current Ib (A): 1,143.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW16 H1 MLogic 5.0A High
Rating In (A):1600 [f] Overload Setting Ir (A): 1600 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 3 x 4 x 1c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 54
31 - On horizontal/vertical perforated tray Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.87 [BS 7671, Table 4C5]
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,143.5
Device Rating In = 1600 Overload Setting Ir = 1600 [Ir >
_ Ib]
Min. Cable Capacity Iz = 704.6 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 736.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1143.5 / 1.00 1143.5 / 1.00 1143.5 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.51 / 0.69 1.51 / 0.69 1.51 / 0.69 -----
Voltage Drop - From Source (V/%) 1.98 / 0.91 1.98 / 0.91 1.98 / 0.91 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01262 0.00218 0.00794 0.02240 0.04148 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
9.77
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 25.58

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.339 / 23.867 Load End: 21.491 / 16.580
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 173.06 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 11 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-3-SM06 ESCALATOR


Connection From: MDB 3 To: ESCALATOR
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 108
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 49.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.0 / 1.00 22.0 / 1.00 22.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.05 / 0.93 2.05 / 0.93 2.05 / 0.93 -----
Voltage Drop - From Source (V/%) 2.52 / 1.15 2.52 / 1.15 2.52 / 1.15 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01262 0.10015 0.15660 0.26033 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.84
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.98

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.339 / 23.867 Load End: 2.694 / 1.077
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 26.20 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 12 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-3-SM07 ESCALATOR


Connection From: MDB 3 To: ESCALATOR
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 110
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 49.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.0 / 1.00 22.0 / 1.00 22.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.08 / 0.95 2.08 / 0.95 2.08 / 0.95 -----
Voltage Drop - From Source (V/%) 2.55 / 1.17 2.55 / 1.17 2.55 / 1.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01262 0.10200 0.15950 0.26507 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.83
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.97

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.339 / 23.867 Load End: 2.647 / 1.057
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 25.67 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 13 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-3-SM08 ESCALATOR


Connection From: MDB 3 To: ESCALATOR
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 171
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 49.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.0 / 1.00 22.0 / 1.00 22.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.24 / 1.48 3.24 / 1.48 3.24 / 1.48 -----
Voltage Drop - From Source (V/%) 3.71 / 1.69 3.71 / 1.69 3.71 / 1.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01262 0.15857 0.24795 0.40986 0.58564 Current (kA)

Disconnection time (s): From characteristic: 3.57 Maximum for circuit: 5.00
0.53
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 7.06

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.339 / 23.867 Load End: 1.727 / 0.684
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 15.23 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 14 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-3-SM09 ESCALATOR


Connection From: MDB 3 To: ESCALATOR
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 173
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 49.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.0 / 1.00 22.0 / 1.00 22.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.28 / 1.50 3.28 / 1.50 3.28 / 1.50 -----
Voltage Drop - From Source (V/%) 3.75 / 1.71 3.75 / 1.71 3.75 / 1.71 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01262 0.16042 0.25085 0.41461 0.58564 Current (kA)

Disconnection time (s): From characteristic: 3.60 Maximum for circuit: 5.00
0.53
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 7.00

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.339 / 23.867 Load End: 1.707 / 0.676
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 15.01 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 15 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1A-SM01 DB-1PA


Connection From: SMDB-1A/1/L1,L2,L3 To: DB-1PA
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 60.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 60.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 123.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 60.0 / 1.00 60.0 / 1.00 60.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.14 / 0.06 0.14 / 0.06 0.14 / 0.06 -----
Voltage Drop - From Source (V/%) 3.68 / 1.68 3.68 / 1.68 3.68 / 1.68 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03470 0.00251 0.00468 0.03947 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.55
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.42

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.232 / 11.587 Load End: 15.808 / 9.791
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 392.48 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 16 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1A-SM02 DB-1LA


Connection From: SMDB-1A/2/L1,L2,L3 To: DB-1LA
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 30.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 30.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 94.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.0 / 1.00 30.0 / 1.00 30.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.09 / 0.04 0.09 / 0.04 0.09 / 0.04 -----
Voltage Drop - From Source (V/%) 3.63 / 1.66 3.63 / 1.66 3.63 / 1.66 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03470 0.00334 0.00725 0.04111 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.33
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.232 / 11.587 Load End: 15.458 / 9.331
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 374.92 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 17 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1A-SM03 RETAIL 1.1


Connection From: SMDB-1A/3/L1,L2,L3 To: RETAIL 1.1
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 108.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 95 [f]
Neutral: 95 mm²[a] Length (m): 61
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 108.1
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 200.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 298.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 108.1 / 1.00 108.1 / 1.00 108.1 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.55 / 0.71 1.55 / 0.71 1.55 / 0.71 -----
Voltage Drop - From Source (V/%) 5.09 / 2.33 5.09 / 2.33 5.09 / 2.33 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 50 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03470 0.01582 0.03130 0.07555 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.90
Adiabatic check (mm 2 ) CPC Section = Separate 50 Total = 50.0 Min. Section = 2.60

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.232 / 11.587 Load End: 9.459 / 4.646
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 239.06 x 103 Adiabatic Limit k²S² (A²s): 184.55 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 18 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1A-SM04 RETAIL 1.2


Connection From: SMDB-1A/4/L1,L2,L3 To: RETAIL 1.2
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 98.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 98.3
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 198.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 98.3 / 1.00 98.3 / 1.00 98.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.15 / 0.53 1.15 / 0.53 1.15 / 0.53 -----
Voltage Drop - From Source (V/%) 4.69 / 2.14 4.69 / 2.14 4.69 / 2.14 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03470 0.01256 0.02478 0.06535 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.35
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.86

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.232 / 11.587 Load End: 10.819 / 5.439
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 274.76 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 19 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1A-SM05 RETAIL 1.3


Connection From: SMDB-1A/5/L1,L2,L3 To: RETAIL 1.3
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 106.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 106.2
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 200.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 106.2 / 1.00 106.2 / 1.00 106.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.32 / 0.60 1.32 / 0.60 1.32 / 0.60 -----
Voltage Drop - From Source (V/%) 4.86 / 2.22 4.86 / 2.22 4.86 / 2.22 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03470 0.01325 0.02616 0.06725 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.26
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.81

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.232 / 11.587 Load End: 10.570 / 5.268
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 267.05 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 20 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1A-SM06 RETAIL 1.4


Connection From: SMDB-1A/6/L1,L2,L3 To: RETAIL 1.4
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 28.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 28.8
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 94.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 28.8 / 1.00 28.8 / 1.00 28.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.97 / 0.44 0.97 / 0.44 0.97 / 0.44 -----
Voltage Drop - From Source (V/%) 4.51 / 2.06 4.51 / 2.06 4.51 / 2.06 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03470 0.03616 0.05655 0.11422 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.92
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.56

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.232 / 11.587 Load End: 6.106 / 2.593
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 78.09 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 21 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1B-SM01 DB-1PB


Connection From: SMDB-1B/1/L1,L2,L3 To: DB-1PB
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 60.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 60.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 123.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 60.0 / 1.00 60.0 / 1.00 60.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.14 / 0.06 0.14 / 0.06 0.14 / 0.06 -----
Voltage Drop - From Source (V/%) 2.60 / 1.19 2.60 / 1.19 2.60 / 1.19 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02435 0.00251 0.00468 0.02907 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
7.53
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.90

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.453 / 15.127 Load End: 18.556 / 12.283
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 427.40 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 22 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1B-SM02 DB-1LB


Connection From: SMDB-1B/2/L1,L2,L3 To: DB-1LB
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 30.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 30.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 94.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.0 / 1.00 30.0 / 1.00 30.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.09 / 0.04 0.09 / 0.04 0.09 / 0.04 -----
Voltage Drop - From Source (V/%) 2.55 / 1.17 2.55 / 1.17 2.55 / 1.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02435 0.00334 0.00725 0.03080 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.11
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.78

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.453 / 15.127 Load End: 18.090 / 11.567
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 420.37 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 23 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1B-SM03 RETAIL 1.5


Connection From: SMDB-1B/3/L1,L2,L3 To: RETAIL 1.5
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 21.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 53
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 21.6
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 21.6 / 1.00 21.6 / 1.00 21.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.99 / 0.45 0.99 / 0.45 0.99 / 0.45 -----
Voltage Drop - From Source (V/%) 3.45 / 1.57 3.45 / 1.57 3.45 / 1.57 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02435 0.04915 0.07685 0.13902 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.58
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.40

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.453 / 15.127 Load End: 4.985 / 2.057
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 54.52 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 24 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1B-SM04 RETAIL 1.6


Connection From: SMDB-1B/4/L1,L2,L3 To: RETAIL 1.6
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 129.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):200 [f] Overload Setting Ir (A): 200 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 95 [f]
Neutral: 95 mm²[a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 129.0
Device Rating In = 200 Overload Setting Ir = 200 [Ir >
_ Ib]
Min. Cable Capacity Iz = 250.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 298.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 129.0 / 1.00 129.0 / 1.00 129.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.23 / 0.56 1.23 / 0.56 1.23 / 0.56 -----
Voltage Drop - From Source (V/%) 3.69 / 1.69 3.69 / 1.69 3.69 / 1.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 50 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02435 0.01037 0.02052 0.05053 0.13036 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
4.33
Adiabatic check (mm 2 ) CPC Section = Separate 50 Total = 50.0 Min. Section = 3.51

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.453 / 15.127 Load End: 12.732 / 6.767
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 388.33 x 103 Adiabatic Limit k²S² (A²s): 184.55 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 25 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1B-SM05 RETAIL 1.7


Connection From: SMDB-1B/5/L1,L2,L3 To: RETAIL 1.7
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 135.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):200 [f] Overload Setting Ir (A): 200 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 95 [f]
Neutral: 95 mm²[a] Length (m): 51
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 135.1
Device Rating In = 200 Overload Setting Ir = 200 [Ir >
_ Ib]
Min. Cable Capacity Iz = 252.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 298.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 135.1 / 1.00 135.1 / 1.00 135.1 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.65 / 0.75 1.65 / 0.75 1.65 / 0.75 -----
Voltage Drop - From Source (V/%) 4.11 / 1.88 4.11 / 1.88 4.11 / 1.88 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 50 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02435 0.01323 0.02617 0.05854 0.13036 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.74
Adiabatic check (mm 2 ) CPC Section = Separate 50 Total = 50.0 Min. Section = 3.19

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.453 / 15.127 Load End: 11.387 / 5.794
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 339.68 x 103 Adiabatic Limit k²S² (A²s): 184.55 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 26 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1B-SM06 RETAIL 1.8


Connection From: SMDB-1B/6/L1,L2,L3 To: RETAIL 1.8
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 42.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 63
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 42.1
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 97.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 42.1 / 1.00 42.1 / 1.00 42.1 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.32 / 1.06 2.32 / 1.06 2.32 / 1.06 -----
Voltage Drop - From Source (V/%) 4.78 / 2.18 4.78 / 2.18 4.78 / 2.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02435 0.05842 0.09135 0.16253 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.35
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.453 / 15.127 Load End: 4.292 / 1.754
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 45.11 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 27 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1B-SM07 RETAIL 1.9


Connection From: SMDB-1B/7/L1,L2,L3 To: RETAIL 1.9
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 39.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 70
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 39.5
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 96.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 39.5 / 1.00 39.5 / 1.00 39.5 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.72 / 0.79 1.72 / 0.79 1.72 / 0.79 -----
Voltage Drop - From Source (V/%) 4.18 / 1.91 4.18 / 1.91 4.18 / 1.91 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02435 0.04680 0.10150 0.16104 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.36
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.453 / 15.127 Load End: 5.149 / 2.145
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 58.36 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 28 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1B-SM08 RETAIL 1.10


Connection From: SMDB-1B/8/L1,L2,L3 To: RETAIL 1.10
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 42.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 80
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 42.6
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 97.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 42.6 / 1.00 42.6 / 1.00 42.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.58 / 0.72 1.58 / 0.72 1.58 / 0.72 -----
Voltage Drop - From Source (V/%) 4.04 / 1.85 4.04 / 1.85 4.04 / 1.85 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02435 0.04021 0.07484 0.13051 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.68
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 1.45

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.453 / 15.127 Load End: 5.762 / 2.448
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 71.70 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 29 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-1B-SM09 RETAIL 1.11


Connection From: SMDB-1B/9/L1,L2,L3 To: RETAIL 1.11
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 42.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 69
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =9 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 9
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 42.2
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 97.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 42.2 / 1.00 42.2 / 1.00 42.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.82 / 0.83 1.82 / 0.83 1.82 / 0.83 -----
Voltage Drop - From Source (V/%) 4.28 / 1.95 4.28 / 1.95 4.28 / 1.95 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02435 0.04613 0.10005 0.15894 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.38
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.30

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.453 / 15.127 Load End: 5.212 / 2.173
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 59.61 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 30 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GA-SM01 DB-GPA


Connection From: SMDB-GA/1/L1,L2,L3 To: DB-GPA
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 80.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =5 Cg = 0.75 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 5
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 80.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 127.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 80.0 / 1.00 80.0 / 1.00 80.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.19 / 0.09 0.19 / 0.09 0.19 / 0.09 -----
Voltage Drop - From Source (V/%) 3.66 / 1.67 3.66 / 1.67 3.66 / 1.67 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03485 0.00251 0.00468 0.03965 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.52
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.42

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.064 / 11.425 Load End: 15.662 / 9.672
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 388.21 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 31 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GA-SM02 DB-GLA


Connection From: SMDB-GA/2/L1,L2,L3 To: DB-GLA
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 40.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =5 Cg = 0.75 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 5
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 40.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 96.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 40.0 / 1.00 40.0 / 1.00 40.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.06 0.12 / 0.06 0.12 / 0.06 -----
Voltage Drop - From Source (V/%) 3.60 / 1.64 3.60 / 1.64 3.60 / 1.64 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03485 0.00334 0.00725 0.04130 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.30
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.064 / 11.425 Load End: 15.317 / 9.223
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 370.88 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 32 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GA-SM03 DB-EXTLA


Connection From: SMDB-GA/3/L1,L2,L3 To: DB-EXTLA
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 25.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =5 Cg = 0.75 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 5
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 25.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 25.0 / 1.00 25.0 / 1.00 25.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.17 / 0.08 0.17 / 0.08 0.17 / 0.08 -----
Voltage Drop - From Source (V/%) 3.64 / 1.66 3.64 / 1.66 3.64 / 1.66 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03485 0.00722 0.00725 0.04371 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.01
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.09

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.064 / 11.425 Load End: 13.920 / 7.516
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 306.86 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 33 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GA-SM04 RETAIL G.1


Connection From: SMDB-GA/4/L1,L2,L3 To: RETAIL G.1
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 72.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =5 Cg = 0.75 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 5
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 72.7
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 152.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 72.7 / 1.00 72.7 / 1.00 72.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.47 / 0.67 1.47 / 0.67 1.47 / 0.67 -----
Voltage Drop - From Source (V/%) 4.94 / 2.26 4.94 / 2.26 4.94 / 2.26 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03485 0.02161 0.04023 0.08757 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.50
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.10

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.064 / 11.425 Load End: 8.369 / 3.831
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 169.88 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 34 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GB-SM01 DB-GPB


Connection From: SMDB-GB/1/L1,L2,L3 To: DB-GPB
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 80.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 80.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 129.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 80.0 / 1.00 80.0 / 1.00 80.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.19 / 0.09 0.19 / 0.09 0.19 / 0.09 -----
Voltage Drop - From Source (V/%) 2.59 / 1.18 2.59 / 1.18 2.59 / 1.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02461 0.00251 0.00468 0.02939 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
7.45
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.88

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.152 / 14.762 Load End: 18.295 / 12.025
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 424.30 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 35 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GB-SM02 DB-GLB


Connection From: SMDB-GB/2/L1,L2,L3 To: DB-GLB
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 40.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 40.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 96.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 40.0 / 1.00 40.0 / 1.00 40.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.06 0.12 / 0.06 0.12 / 0.06 -----
Voltage Drop - From Source (V/%) 2.52 / 1.15 2.52 / 1.15 2.52 / 1.15 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02461 0.00334 0.00725 0.03115 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.03
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.76

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.152 / 14.762 Load End: 17.838 / 11.336
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 417.37 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 36 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GB-SM03 DB-EXTLB


Connection From: SMDB-GB/3/L1,L2,L3 To: DB-EXTLB
Active Source: Tx 3
Load Type: Distribution Board Design Current Ib (A): 25.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 25.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 25.0 / 1.00 25.0 / 1.00 25.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.17 / 0.08 0.17 / 0.08 0.17 / 0.08 -----
Voltage Drop - From Source (V/%) 2.57 / 1.17 2.57 / 1.17 2.57 / 1.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02461 0.00722 0.00725 0.03373 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.49
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.62

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.152 / 14.762 Load End: 15.957 / 8.801
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 355.04 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 37 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GB-SM04 RETAIL G.3


Connection From: SMDB-GB/4/L1,L2,L3 To: RETAIL G.3
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 39.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 29
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 39.7
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 96.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 39.7 / 1.00 39.7 / 1.00 39.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.00 / 0.46 1.00 / 0.46 1.00 / 0.46 -----
Voltage Drop - From Source (V/%) 3.40 / 1.55 3.40 / 1.55 3.40 / 1.55 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02461 0.02689 0.04205 0.08359 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
2.62
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.97

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.152 / 14.762 Load End: 7.989 / 3.487
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 117.41 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 38 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GB-SM05 RETAIL G.4


Connection From: SMDB-GB/5/L1,L2,L3 To: RETAIL G.4
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 45.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 97.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.0 / 1.00 45.0 / 1.00 45.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.32 / 0.60 1.32 / 0.60 1.32 / 0.60 -----
Voltage Drop - From Source (V/%) 3.72 / 1.70 3.72 / 1.70 3.72 / 1.70 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02461 0.03142 0.06815 0.11343 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.93
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.56

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.152 / 14.762 Load End: 7.046 / 3.040
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 97.78 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 39 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GB-SM06 SKYBRIDGE


Connection From: SMDB-GB/10/L1,L2,L3 To: SKYBRIDGE
Active Source: Tx 3
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 30.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 78
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 30.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 94.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.0 / 1.00 30.0 / 1.00 30.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.45 / 0.66 1.45 / 0.66 1.45 / 0.66 -----
Voltage Drop - From Source (V/%) 3.85 / 1.76 3.85 / 1.76 3.85 / 1.76 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02461 0.05214 0.07297 0.14059 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.56
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 1.39

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 20.152 / 14.762 Load End: 4.682 / 1.937
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 50.23 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 40 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 10/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-Tx3 MDB 3


Connection From: Tx 3 To: MDB 3
Active Source: Tx 3
Load Type: Main cable to Switchboard Design Current Ib (A): 1,519.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW20 H1 MLogic 5.0A High
Rating In (A):2000 [f] Overload Setting Ir (A): 2000 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 630 [f]
Neutral: 630 mm²[a] Length (m): 34
34 - On a ladder Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.97 [BS 7671, Table 4C5]
No. of ladders = 1 No. of circuits per ladder = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,519.4
Device Rating In = 2000 Overload Setting Ir = 2000 [Ir >
_ Ib]
Min. Cable Capacity Iz = 592.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 1,151.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1519.4 / 1.00 1519.4 / 1.00 1519.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.47 / 0.21 0.47 / 0.21 0.47 / 0.21 -----
Voltage Drop - From Source (V/%) 0.47 / 0.21 0.47 / 0.21 0.47 / 0.21 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 630 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00751 0.00086 0.00429 0.01262 0.02012 Current (kA)

Disconnection time (s): From characteristic: 1.72 Maximum for circuit: 5.00
17.35
Adiabatic check (mm 2 ) CPC Section = Separate 630 Total = 630.0 Min. Section = 159.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.229 / 29.229 Load End: 26.339 / 23.867
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 14.25 Actual disconnection time (s) = 0.14

Project: KAFD 3.09 Tx 3 rev 0.p17 Page 41 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Buro Happold

4.4 Transformer TX4

KAFD Plot 3.09 Report Revision 0


Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-1-SM01 SMDB-2A


Connection From: TO-1 To: SMDB-2A
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 70.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UET
Rating In (A):400 [f] Overload Setting Ir (A): 400 [f]
Earth fault protection: : 400A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 70.0
Device Rating In = 400 Overload Setting Ir = 400 [Ir >
_ Ib]
Min. Cable Capacity Iz = 459.8 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 70.0 / 1.00 70.0 / 1.00 70.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.03 / 0.01 0.03 / 0.01 0.03 / 0.01 -----
Voltage Drop - From Source (V/%) 4.10 / 1.87 4.10 / 1.87 4.10 / 1.87 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02812 0.00062 0.00116 0.02970 0.45624 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.37
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 4.99

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 23.002 / 15.990 Load End: 21.913 / 14.781
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.17 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 1 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-1-SM02 MCC-2A


Connection From: TO-9 To: MCC-2A
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 720.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS800 N MLogic 5.0A
Rating In (A):800 [f] Overload Setting Ir (A): 800 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 59
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 720.2
Device Rating In = 800 Overload Setting Ir = 800 [Ir >
_ Ib]
Min. Cable Capacity Iz = 522.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 720.2 / 0.99 720.2 / 0.99 720.2 / 0.99 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.80 / 0.82 1.80 / 0.82 1.80 / 0.82 -----
Voltage Drop - From Source (V/%) 5.97 / 2.72 5.97 / 2.72 5.97 / 2.72 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02831 0.00314 0.00868 0.03994 0.04977 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
5.48
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 46.91

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.864 / 15.815 Load End: 17.994 / 11.040
Protective Device Breaking Capacity (kA): Icu: 50 Ics: 37.5

Adiabatic Check: CPD Energy Let-through (A²s): 45.00 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 2 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-1-SM03 SMDB-3A


Connection From: TO-2 To: SMDB-3A
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 421.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 421.4
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 421.4 / 1.00 421.4 / 1.00 421.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.05 0.10 / 0.05 0.10 / 0.05 -----
Voltage Drop - From Source (V/%) 4.29 / 1.96 4.29 / 1.96 4.29 / 1.96 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02836 0.00031 0.00079 0.02942 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.44
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 5.11

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.830 / 15.772 Load End: 22.280 / 15.160
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.42 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 3 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-1-SM04 SMDB-4A


Connection From: TO-3 To: SMDB-4A
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 421.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 421.4
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 421.4 / 1.00 421.4 / 1.00 421.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.05 0.10 / 0.05 0.10 / 0.05 -----
Voltage Drop - From Source (V/%) 4.33 / 1.98 4.33 / 1.98 4.33 / 1.98 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02860 0.00031 0.00079 0.02966 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.38
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 5.08

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.659 / 15.560 Load End: 22.116 / 14.961
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.46 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 4 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-1-SM05 SMDB-5A


Connection From: TO-4 To: SMDB-5A
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 421.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 421.4
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 421.4 / 1.00 421.4 / 1.00 421.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.05 0.10 / 0.05 0.10 / 0.05 -----
Voltage Drop - From Source (V/%) 4.35 / 1.99 4.35 / 1.99 4.35 / 1.99 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02883 0.00031 0.00079 0.02990 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.32
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 5.05

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.490 / 15.352 Load End: 21.953 / 14.767
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.51 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 5 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-2-SM01 SMDB-2B


Connection From: TO-5 To: SMDB-2B
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 70.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UET
Rating In (A):400 [f] Overload Setting Ir (A): 400 [f]
Earth fault protection: : 400A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 70.0
Device Rating In = 400 Overload Setting Ir = 400 [Ir >
_ Ib]
Min. Cable Capacity Iz = 459.8 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 70.0 / 1.00 70.0 / 1.00 70.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.03 / 0.01 0.03 / 0.01 0.03 / 0.01 -----
Voltage Drop - From Source (V/%) 2.29 / 1.04 2.28 / 1.04 2.28 / 1.04 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02108 0.00062 0.00116 0.02263 0.45624 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
9.68
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 6.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.906 / 19.307 Load End: 24.552 / 17.603
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.29 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 6 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-2-SM02 MCC-2B


Connection From: TO-10 To: MCC-2B
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 556.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 53
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 556.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 556.7 / 0.99 555.0 / 0.99 555.0 / 0.99 1.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.53 / 0.70 1.51 / 0.69 1.51 / 0.69 -----
Voltage Drop - From Source (V/%) 3.86 / 1.76 3.85 / 1.76 3.85 / 1.76 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02126 0.00329 0.00840 0.03257 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
6.72
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.69

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.735 / 19.062 Load End: 19.809 / 12.479
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.41 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 7 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-2-SM03 SMDB-3B


Connection From: TO-6 To: SMDB-3B
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 408.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 408.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 408.7 / 1.00 408.7 / 1.00 408.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.04 0.10 / 0.04 0.10 / 0.04 -----
Voltage Drop - From Source (V/%) 2.45 / 1.12 2.44 / 1.12 2.44 / 1.12 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02131 0.00031 0.00079 0.02236 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
9.79
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.69

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.692 / 19.001 Load End: 25.009 / 18.137
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 686.39 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 8 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-2-SM04 SMDB-4B


Connection From: TO-7 To: SMDB-4B
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 408.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 408.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 408.7 / 1.00 408.7 / 1.00 408.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.04 0.10 / 0.04 0.10 / 0.04 -----
Voltage Drop - From Source (V/%) 2.49 / 1.14 2.49 / 1.13 2.49 / 1.13 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02154 0.00031 0.00079 0.02259 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
9.69
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.62

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.481 / 18.704 Load End: 24.806 / 17.861
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 754.17 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 9 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB4-2-SM05 SMDB-5B


Connection From: TO-8 To: SMDB-5B
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 408.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 408.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 408.7 / 1.00 408.7 / 1.00 408.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.04 0.10 / 0.04 0.10 / 0.04 -----
Voltage Drop - From Source (V/%) 2.51 / 1.15 2.51 / 1.14 2.51 / 1.14 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02177 0.00031 0.00079 0.02283 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
9.59
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.56

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.272 / 18.412 Load End: 24.606 / 17.590
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 820.43 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 10 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM01 3.09-02-EF-02


Connection From: Starter-2 To: 3.09-02-EF-02
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 1.1
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 1.07 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 60
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 1.1
Device Rating In = 20 Motor Overload Setting Ir = 1.07 [Ir >
_ Ib]
Min. Cable Capacity Iz = 1.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.1 / 0.72 1.1 / 0.72 1.1 / 0.72 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.17 / 0.08 0.17 / 0.08 0.17 / 0.08 -----
Voltage Drop - From Source (V/%) 6.14 / 2.80 6.14 / 2.80 6.14 / 2.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.23556 0.23700 0.49420 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.44
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 1.158 / 0.768
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 11 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM02 3.09-02-EF-03


Connection From: Starter-3 To: 3.09-02-EF-03
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 1.1
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 1.07 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 60
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 1.1
Device Rating In = 20 Motor Overload Setting Ir = 1.07 [Ir >
_ Ib]
Min. Cable Capacity Iz = 1.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.1 / 0.72 1.1 / 0.72 1.1 / 0.72 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.17 / 0.08 0.17 / 0.08 0.17 / 0.08 -----
Voltage Drop - From Source (V/%) 6.14 / 2.80 6.14 / 2.80 6.14 / 2.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.23556 0.23700 0.49420 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.44
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 1.158 / 0.768
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 12 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM03 3.09-02-EF-01


Connection From: Starter-4 To: 3.09-02-EF-01
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 1.1
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 1.07 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 60
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 1.1
Device Rating In = 20 Motor Overload Setting Ir = 1.07 [Ir >
_ Ib]
Min. Cable Capacity Iz = 1.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.1 / 0.72 1.1 / 0.72 1.1 / 0.72 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.17 / 0.08 0.17 / 0.08 0.17 / 0.08 -----
Voltage Drop - From Source (V/%) 6.14 / 2.80 6.14 / 2.80 6.14 / 2.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.23556 0.23700 0.49420 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.44
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 1.158 / 0.768
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 13 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM04 3.09-02-AHU-01


Connection From: Starter To: 3.09-02-AHU-01
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 32.2
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 32.18 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 16 [f]
Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 32.2
Device Rating In = 40 Motor Overload Setting Ir = 32.18 [Ir >
_ Ib]
Min. Cable Capacity Iz = 51.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 32.2 / 0.78 32.2 / 0.78 32.2 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.23 / 0.56 1.23 / 0.56 1.23 / 0.56 -----
Voltage Drop - From Source (V/%) 7.20 / 3.29 7.20 / 3.29 7.20 / 3.29 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.05196 0.05220 0.12925 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
1.69
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.83

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 4.668 / 2.907
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 138.95 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 14 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM05 3.09-02-AHU-01


Connection From: Starter-5 To: 3.09-02-AHU-01
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 32.2
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 32.18 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 16 [f]
Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 32.2
Device Rating In = 40 Motor Overload Setting Ir = 32.18 [Ir >
_ Ib]
Min. Cable Capacity Iz = 51.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 32.2 / 0.78 32.2 / 0.78 32.2 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.23 / 0.56 1.23 / 0.56 1.23 / 0.56 -----
Voltage Drop - From Source (V/%) 7.20 / 3.29 7.20 / 3.29 7.20 / 3.29 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.05196 0.05220 0.12925 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
1.69
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.83

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 4.668 / 2.907
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 138.95 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 15 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM06 3.09-02-AHU-01


Connection From: Starter-6 To: 3.09-02-AHU-01
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.38 / 0.63 1.38 / 0.63 1.38 / 0.63 -----
Voltage Drop - From Source (V/%) 7.35 / 3.36 7.35 / 3.36 7.35 / 3.36 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.07852 0.07990 0.18213 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.20
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 3.258 / 2.081
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 85.24 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 16 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM07 3.09-02-AHU-01


Connection From: Starter-7 To: 3.09-02-AHU-01
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.38 / 0.63 1.38 / 0.63 1.38 / 0.63 -----
Voltage Drop - From Source (V/%) 7.35 / 3.36 7.35 / 3.36 7.35 / 3.36 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.07852 0.07990 0.18213 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.20
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 3.258 / 2.081
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 85.24 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 17 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM08 3.09-02-AHU-01


Connection From: MCC-2A/8/L1,L2,L3 To: 3.09-02-AHU-01
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 270.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UET
Rating In (A):400 [f] Overload Setting Ir (A): 280 [f]
RCD Trip rating : 400A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 32
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 270.4
Device Rating In = 400 Overload Setting Ir = 280 [Ir >
_ Ib]
Min. Cable Capacity Iz = 431.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 270.4 / 1.00 270.4 / 1.00 270.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.85 / 0.39 0.85 / 0.39 0.85 / 0.39 -----
Voltage Drop - From Source (V/%) 6.82 / 3.11 6.82 / 3.11 6.82 / 3.11 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.00397 0.00741 0.05045 0.45624 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.34
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 3.14

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 14.244 / 7.977
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 596.70 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 18 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM09 3.09-02-AHU-03


Connection From: Starter-8 To: 3.09-02-AHU-03
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 28
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.14 / 0.52 1.14 / 0.52 1.14 / 0.52 -----
Voltage Drop - From Source (V/%) 7.11 / 3.24 7.11 / 3.24 7.11 / 3.24 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.06466 0.06580 0.15477 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.42
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.69

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 3.870 / 2.444
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 108.89 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 19 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM10 3.09-02-AHU-03


Connection From: Starter-9 To: 3.09-02-AHU-03
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 28
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.14 / 0.52 1.14 / 0.52 1.14 / 0.52 -----
Voltage Drop - From Source (V/%) 7.11 / 3.24 7.11 / 3.24 7.11 / 3.24 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.06466 0.06580 0.15477 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.42
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.69

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 3.870 / 2.444
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 108.89 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 20 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM11 3.09-02-AHU-03


Connection From: Starter-10 To: 3.09-02-AHU-03
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.83 / 0.38 0.83 / 0.38 0.83 / 0.38 -----
Voltage Drop - From Source (V/%) 6.79 / 3.10 6.79 / 3.10 6.79 / 3.10 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.06928 0.07050 0.16387 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.34
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.64

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 3.642 / 2.310
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 100.16 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 21 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM12 3.09-02-AHU-03


Connection From: Starter-11 To: 3.09-02-AHU-03
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.83 / 0.38 0.83 / 0.38 0.83 / 0.38 -----
Voltage Drop - From Source (V/%) 6.79 / 3.10 6.79 / 3.10 6.79 / 3.10 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.06928 0.07050 0.16387 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.34
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.64

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 3.642 / 2.310
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 100.16 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 22 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM13 3.09-02-AHU-03


Connection From: MCC-2A/13/L1,L2,L3 To: 3.09-02-AHU-03
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 165.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):200 [f] Overload Setting Ir (A): 200 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 120 [f]
Neutral: 120 mm²[a] Length (m): 32
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 165.6
Device Rating In = 200 Overload Setting Ir = 200 [Ir >
_ Ib]
Min. Cable Capacity Iz = 264.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 346.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 165.6 / 1.00 165.6 / 1.00 165.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.01 / 0.46 1.01 / 0.46 1.01 / 0.46 -----
Voltage Drop - From Source (V/%) 6.98 / 3.19 6.98 / 3.19 6.98 / 3.19 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 70 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.00673 0.01165 0.05554 0.13036 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.94
Adiabatic check (mm 2 ) CPC Section = Separate 70 Total = 70.0 Min. Section = 3.30

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 13.074 / 6.872
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 393.58 x 103 Adiabatic Limit k²S² (A²s): 294.47 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 23 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM14 3.09-02-AHU-02


Connection From: Starter-12 To: 3.09-02-AHU-02
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.46 / 0.67 1.46 / 0.67 1.46 / 0.67 -----
Voltage Drop - From Source (V/%) 7.43 / 3.39 7.43 / 3.39 7.43 / 3.39 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.08314 0.08460 0.19129 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.14
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 3.094 / 1.982
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 79.32 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 24 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM15 3.09-02-AHU-02


Connection From: Starter-13 To: 3.09-02-AHU-02
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.46 / 0.67 1.46 / 0.67 1.46 / 0.67 -----
Voltage Drop - From Source (V/%) 7.43 / 3.39 7.43 / 3.39 7.43 / 3.39 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.08314 0.08460 0.19129 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.14
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 3.094 / 1.982
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 79.32 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 25 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM16 3.09-02-AHU-02


Connection From: Starter-14 To: 3.09-02-AHU-02
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.99 / 0.45 0.99 / 0.45 0.99 / 0.45 -----
Voltage Drop - From Source (V/%) 6.96 / 3.18 6.96 / 3.18 6.96 / 3.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.14919 0.15010 0.32157 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.68
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 1.796 / 1.178
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 26 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM17 3.09-02-AHU-02


Connection From: Starter-15 To: 3.09-02-AHU-02
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-2A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.99 / 0.45 0.99 / 0.45 0.99 / 0.45 -----
Voltage Drop - From Source (V/%) 6.96 / 3.18 6.96 / 3.18 6.96 / 3.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.14919 0.15010 0.32157 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.68
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 1.796 / 1.178
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 27 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2A-SM18 3.09-02-AHU-02


Connection From: MCC-2A/18/L1,L2,L3 To: 3.09-02-AHU-02
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 176.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):200 [f] Overload Setting Ir (A): 200 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 95 [f]
Neutral: 95 mm²[a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 18 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 176.2
Device Rating In = 200 Overload Setting Ir = 200 [Ir >
_ Ib]
Min. Cable Capacity Iz = 281.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 298.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 176.2 / 1.00 176.2 / 1.00 176.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.74 / 0.79 1.74 / 0.79 1.74 / 0.79 -----
Voltage Drop - From Source (V/%) 7.70 / 3.52 7.70 / 3.52 7.70 / 3.52 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 50 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03994 0.01037 0.02052 0.06590 0.13036 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.32
Adiabatic check (mm 2 ) CPC Section = Separate 50 Total = 50.0 Min. Section = 2.95

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.994 / 11.040 Load End: 11.511 / 5.712
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 335.61 x 103 Adiabatic Limit k²S² (A²s): 184.55 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 28 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM01 3.09-02-EF-05


Connection From: Starter-16 To: Motor-4
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 3.3
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 3.26 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 3.3
Device Rating In = 20 Motor Overload Setting Ir = 3.26 [Ir >
_ Ib]
Min. Cable Capacity Iz = 5.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 3.3 / 0.69 3.3 / 0.69 3.3 / 0.69 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.21 / 0.10 0.21 / 0.10 0.21 / 0.10 -----
Voltage Drop - From Source (V/%) 4.07 / 1.86 4.06 / 1.85 4.06 / 1.85 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.10208 0.10270 0.22392 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.98
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 2.580 / 1.677
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 67.87 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 29 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM02 3.09-02-EF-06


Connection From: Starter-17 To: 3.09-02-EF-06
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 3.3
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 3.26 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 3.3
Device Rating In = 20 Motor Overload Setting Ir = 3.26 [Ir >
_ Ib]
Min. Cable Capacity Iz = 5.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 3.3 / 0.69 3.3 / 0.69 3.3 / 0.69 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.21 / 0.10 0.21 / 0.10 0.21 / 0.10 -----
Voltage Drop - From Source (V/%) 4.07 / 1.86 4.06 / 1.85 4.06 / 1.85 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.10208 0.10270 0.22392 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.98
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 2.580 / 1.677
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 67.87 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 30 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM03 3.09-02-AHU-04


Connection From: Starter-18 To: 3.09-02-AHU-04
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.71 / 0.78 1.71 / 0.78 1.71 / 0.78 -----
Voltage Drop - From Source (V/%) 5.57 / 2.54 5.55 / 2.54 5.55 / 2.54 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.09699 0.09870 0.21491 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.02
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 2.705 / 1.755
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 70.80 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 31 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM04 3.09-02-AHU-04


Connection From: Starter-19 To: 3.09-02-AHU-04
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.71 / 0.78 1.71 / 0.78 1.71 / 0.78 -----
Voltage Drop - From Source (V/%) 5.57 / 2.54 5.55 / 2.54 5.55 / 2.54 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.09699 0.09870 0.21491 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.02
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 2.705 / 1.755
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 70.80 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 32 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM05 3.09-02-AHU-04


Connection From: Starter-20 To: 3.09-02-AHU-04
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.24 / 0.57 1.24 / 0.57 1.24 / 0.57 -----
Voltage Drop - From Source (V/%) 5.10 / 2.33 5.09 / 2.32 5.09 / 2.32 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.10392 0.10575 0.22878 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.96
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 2.537 / 1.650
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 66.87 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 33 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM06 3.09-02-AHU-04


Connection From: Starter-21 To: 3.09-02-AHU-04
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.24 / 0.57 1.24 / 0.57 1.24 / 0.57 -----
Voltage Drop - From Source (V/%) 5.10 / 2.33 5.09 / 2.32 5.09 / 2.32 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.10392 0.10575 0.22878 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.96
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 2.537 / 1.650
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 66.87 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 34 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM07 3.09-02-AHU-04


Connection From: MCC-2B/7/L1,L2,L3 To: 3.09-02-AHU-04
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 145.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 145.9
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 232.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 145.9 / 1.00 145.9 / 1.00 145.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.32 / 1.06 2.32 / 1.06 2.32 / 1.06 -----
Voltage Drop - From Source (V/%) 6.18 / 2.82 6.16 / 2.81 6.16 / 2.81 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.01639 0.03235 0.07514 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.91
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 10.015 / 4.621
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 237.93 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 35 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM08 3.09-02-AHU-05


Connection From: Starter-22 To: 3.09-02-AHU-05
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 65
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 2.64 / 1.21 2.64 / 1.21 2.64 / 1.21 -----
Voltage Drop - From Source (V/%) 6.50 / 2.97 6.49 / 2.96 6.49 / 2.96 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.15011 0.15275 0.32149 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
0.68
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 1.793 / 1.179
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 36 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM09 3.09-02-AHU-05


Connection From: Starter-23 To: 3.09-02-AHU-05
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 23.9
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 23.86 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 65
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 23.9
Device Rating In = 40 Motor Overload Setting Ir = 23.86 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 23.9 / 0.78 23.9 / 0.78 23.9 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 2.64 / 1.21 2.64 / 1.21 2.64 / 1.21 -----
Voltage Drop - From Source (V/%) 6.50 / 2.97 6.49 / 2.96 6.49 / 2.96 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.15011 0.15275 0.32149 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
0.68
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 1.793 / 1.179
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 37 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM10 3.09-02-AHU-05


Connection From: Starter-24 To: 3.09-02-AHU-05
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 68
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.77 / 0.81 1.77 / 0.81 1.77 / 0.81 -----
Voltage Drop - From Source (V/%) 5.63 / 2.57 5.61 / 2.56 5.61 / 2.56 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.26697 0.26860 0.55370 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.40
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 1.028 / 0.684
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 38 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM11 3.09-02-AHU-05


Connection From: Starter-25 To: 3.09-02-AHU-05
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 68
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.77 / 0.81 1.77 / 0.81 1.77 / 0.81 -----
Voltage Drop - From Source (V/%) 5.63 / 2.57 5.61 / 2.56 5.61 / 2.56 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.26697 0.26860 0.55370 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.40
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 1.028 / 0.684
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 39 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM12 3.09-02-AHU-05


Connection From: MCC-2B/12/L1,L2,L3 To: 3.09-02-AHU-05
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 176.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):200 [f] Overload Setting Ir (A): 200 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 95 [f]
Neutral: 95 mm²[a] Length (m): 69
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 176.2
Device Rating In = 200 Overload Setting Ir = 200 [Ir >
_ Ib]
Min. Cable Capacity Iz = 281.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 298.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 176.2 / 1.00 176.2 / 1.00 176.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.99 / 1.37 2.99 / 1.37 2.99 / 1.37 -----
Voltage Drop - From Source (V/%) 6.86 / 3.13 6.84 / 3.12 6.84 / 3.12 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 50 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.01790 0.03540 0.08055 0.13036 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.72
Adiabatic check (mm 2 ) CPC Section = Separate 50 Total = 50.0 Min. Section = 2.72

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 9.285 / 4.301
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 249.35 x 103 Adiabatic Limit k²S² (A²s): 184.55 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 40 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM13 3.09-02-EF-07


Connection From: Starter-26 To: 3.09-02-EF-07
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 1.1
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 1.07 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 70
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 1.1
Device Rating In = 20 Motor Overload Setting Ir = 1.07 [Ir >
_ Ib]
Min. Cable Capacity Iz = 1.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.1 / 0.72 1.1 / 0.72 1.1 / 0.72 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.20 / 0.09 0.20 / 0.09 0.20 / 0.09 -----
Voltage Drop - From Source (V/%) 4.06 / 1.85 4.04 / 1.85 4.04 / 1.85 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.27482 0.27650 0.56943 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.38
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 0.999 / 0.665
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 41 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM14 3.09-02-EF-08


Connection From: Starter-27 To: 3.09-02-EF-08
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 1.1
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 1.07 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 70
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 1.1
Device Rating In = 20 Motor Overload Setting Ir = 1.07 [Ir >
_ Ib]
Min. Cable Capacity Iz = 1.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.1 / 0.72 1.1 / 0.72 1.1 / 0.72 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.20 / 0.09 0.20 / 0.09 0.20 / 0.09 -----
Voltage Drop - From Source (V/%) 4.06 / 1.85 4.04 / 1.85 4.04 / 1.85 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.27482 0.27650 0.56943 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.38
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 0.999 / 0.665
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 42 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM15 3.09-02-AHU-06


Connection From: Starter-28 To: 3.09-02-AHU-06
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 63
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.74 / 0.79 1.74 / 0.79 1.74 / 0.79 -----
Voltage Drop - From Source (V/%) 5.60 / 2.56 5.58 / 2.55 5.58 / 2.55 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.14549 0.14805 0.31221 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.70
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 1.847 / 1.214
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 43 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM16 3.09-02-AHU-06


Connection From: Starter-29 To: 3.09-02-AHU-06
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 63
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.74 / 0.79 1.74 / 0.79 1.74 / 0.79 -----
Voltage Drop - From Source (V/%) 5.60 / 2.56 5.58 / 2.55 5.58 / 2.55 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.14549 0.14805 0.31221 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.70
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 1.847 / 1.214
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 44 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM17 3.09-02-AHU-06


Connection From: Starter-30 To: 3.09-02-AHU-06
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 66
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.72 / 0.78 1.72 / 0.78 1.72 / 0.78 -----
Voltage Drop - From Source (V/%) 5.58 / 2.55 5.56 / 2.54 5.56 / 2.54 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.25911 0.26070 0.53797 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.41
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 1.058 / 0.704
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 45 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM18 3.09-02-AHU-06


Connection From: Starter-31 To: 3.09-02-AHU-06
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 66
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.72 / 0.78 1.72 / 0.78 1.72 / 0.78 -----
Voltage Drop - From Source (V/%) 5.58 / 2.55 5.56 / 2.54 5.56 / 2.54 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.25911 0.26070 0.53797 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.41
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 1.058 / 0.704
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 46 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM19 3.09-02-AHU-06


Connection From: MCC-2B/19/L1,L2,L3 To: 3.09-02-AHU-06
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 145.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 68
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 145.9
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 232.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 145.9 / 1.00 145.9 / 1.00 145.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.35 / 1.53 3.35 / 1.53 3.35 / 1.53 -----
Voltage Drop - From Source (V/%) 7.21 / 3.29 7.20 / 3.29 7.20 / 3.29 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.02372 0.04681 0.09608 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.28
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.19

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 8.018 / 3.549
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 180.70 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 47 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-2B-SM20 3.09-02-EF-01


Connection From: Starter-32 To: 3.09-02-EF-01
Active Source: Tx 4
Load Type: Motor, Soft Start, single phase Design Current Ib (A): 1.7
Motor Starter Position: at MCC-2B
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 1.68 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 6 [f]
Neutral: 6 mm²[a] Length (m): 73
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 1.7
Device Rating In = 20 Motor Overload Setting Ir = 1.68 [Ir >
_ Ib]
Min. Cable Capacity Iz = 1.9 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 63.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.7 / 0.96 0.0 / 0.00 0.0 / 0.00 1.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.80 / 0.37 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 4.66 / 2.13 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03257 0.28835 0.28835 0.59479 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 0.40
0.37
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.809 / 12.479 Load End: 0.486 / 0.373
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 48 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.1-SM01 3.1 AHU SUPPLY FAN


Connection From: Starter-1 To: 3.1 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-3.1
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.32 / 3.80 8.32 / 3.80 8.32 / 3.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12731 0.04157 0.04230 0.20856 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.05
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.374 / 2.216 Load End: 3.042 / 1.361
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 56.05 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 49 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.1-SM02 3.1 AHU HEATER BATTERY


Connection From: MCC-3.1/2/L1,L2,L3 To: 3.1 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.32 / 3.80 8.32 / 3.80 8.32 / 3.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12731 0.02309 0.02320 0.17185 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.27
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.25

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.374 / 2.216 Load End: 3.779 / 1.520
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.57 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 50 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.1-SM03 3.1 ELEC HUMIDIFIER


Connection From: MCC-3.1/3/L1,L2,L3 To: 3.1 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 22
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.86 / 0.39 0.86 / 0.39 0.86 / 0.39 -----
Voltage Drop - From Source (V/%) 8.70 / 3.97 8.70 / 3.97 8.70 / 3.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12731 0.02040 0.03190 0.17803 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.374 / 2.216 Load End: 3.887 / 1.572
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 40.05 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 51 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.2-SM01 3.2 AHU SUPPLY FAN


Connection From: Starter-1 To: 3.2 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-3.2
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 7.07 / 3.23 7.07 / 3.23 7.07 / 3.23 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11326 0.03464 0.03525 0.18168 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.21
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.400 / 3.143 Load End: 3.966 / 1.838
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 73.92 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 52 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.2-SM02 3.2 AHU HEATER BATTERY


Connection From: MCC-3.2/2/L1,L2,L3 To: 3.2 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 7.19 / 3.28 7.19 / 3.28 7.19 / 3.28 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11326 0.02454 0.02465 0.16128 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.36
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.400 / 3.143 Load End: 4.602 / 1.862
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 48.16 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 53 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.2-SM03 3.2 ELEC HUMIDIFIER


Connection From: MCC-3.2/3/L1,L2,L3 To: 3.2 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.02 / 0.46 1.02 / 0.46 1.02 / 0.46 -----
Voltage Drop - From Source (V/%) 7.69 / 3.51 7.69 / 3.51 7.69 / 3.51 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11326 0.02411 0.03770 0.17399 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.26
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.400 / 3.143 Load End: 4.581 / 1.866
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 48.26 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 54 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.3-SM01 3.3 AHU SUPPLY FAN


Connection From: Starter-1 To: 3.3 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-3.3
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.53 / 0.24 0.53 / 0.24 0.53 / 0.24 -----
Voltage Drop - From Source (V/%) 8.37 / 3.82 8.37 / 3.82 8.37 / 3.82 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12731 0.04619 0.04700 0.21771 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.01
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.374 / 2.216 Load End: 2.900 / 1.318
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 54.44 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 55 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.3-SM02 3.3 AHU HEATER BATTERY


Connection From: MCC-3.3/2/L1,L2,L3 To: 3.3 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.54 / 0.25 0.54 / 0.25 0.54 / 0.25 -----
Voltage Drop - From Source (V/%) 8.38 / 3.83 8.38 / 3.83 8.38 / 3.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12731 0.02598 0.02610 0.17748 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.374 / 2.216 Load End: 3.642 / 1.462
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 36.96 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 56 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.3-SM03 3.3 ELEC HUMIDIFIER


Connection From: MCC-3.3/3/L1,L2,L3 To: 3.3 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 24
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.67 / 0.31 0.67 / 0.31 0.67 / 0.31 -----
Voltage Drop - From Source (V/%) 8.51 / 3.89 8.51 / 3.89 8.51 / 3.89 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12731 0.01604 0.03480 0.17660 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.24
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.374 / 2.216 Load End: 4.124 / 1.675
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 42.93 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 57 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.4-SM01 3.4 AHU SUPPLY FAN


Connection From: Starter-1 To: 3.4 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-3.4
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 5.87 / 2.68 5.87 / 2.68 5.87 / 2.68 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12894 0.04388 0.04465 0.21655 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.01
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.494 / 2.706 Load End: 3.283 / 1.533
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.47 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 58 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.4-SM02 3.4 AHU HEATER BATTERY


Connection From: MCC-3.4/2/L1,L2,L3 To: 3.4 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 5.88 / 2.68 5.87 / 2.68 5.87 / 2.68 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12894 0.02454 0.02465 0.17750 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.494 / 2.706 Load End: 4.214 / 1.696
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.51 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 59 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.4-SM03 3.4 ELEC HUMIDIFIER


Connection From: MCC-3.4/3/L1,L2,L3 To: 3.4 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 6.07 / 2.77 6.07 / 2.77 6.07 / 2.77 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12894 0.01669 0.02610 0.17132 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.28
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.25

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.494 / 2.706 Load End: 4.717 / 1.921
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 49.78 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 60 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.5-SM01 3.5 AHU SUPPLY FAN


Connection From: Starter-1 To: 3.5 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-3.5
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 5.90 / 2.69 5.89 / 2.69 5.89 / 2.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13103 0.04157 0.04230 0.21403 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.02
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.397 / 2.663 Load End: 3.345 / 1.544
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.91 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 61 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.5-SM02 3.5 AHU HEATER BATTERY


Connection From: MCC-3.5/2/L1,L2,L3 To: 3.5 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 5.90 / 2.69 5.90 / 2.69 5.90 / 2.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13103 0.02309 0.02320 0.17674 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.24
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.397 / 2.663 Load End: 4.261 / 1.716
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 44.08 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 62 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.5-SM03 3.5 ELEC HUMIDIFIER


Connection From: MCC-3.5/3/L1,L2,L3 To: 3.5 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 25
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.98 / 0.45 0.98 / 0.45 0.98 / 0.45 -----
Voltage Drop - From Source (V/%) 6.40 / 2.92 6.39 / 2.92 6.39 / 2.92 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13103 0.02318 0.03625 0.18994 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.15
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.18

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.397 / 2.663 Load End: 4.217 / 1.707
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.82 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 63 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.6-SM01 3.6 AHU SUPPLY FAN


Connection From: Starter-1 To: 3.6 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-3.6
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 5.50 / 2.51 5.50 / 2.51 5.50 / 2.51 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11850 0.03464 0.03525 0.18750 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.17
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.023 / 2.948 Load End: 3.840 / 1.756
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 70.86 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 64 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.6-SM02 3.6 AHU HEATER BATTERY


Connection From: MCC-3.6/2/L1,L2,L3 To: 3.6 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 5.61 / 2.56 5.61 / 2.56 5.61 / 2.56 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11850 0.02454 0.02465 0.16698 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.31
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.27

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.023 / 2.948 Load End: 4.436 / 1.789
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 46.10 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 65 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-3.6-SM03 3.6 ELEC HUMIDIFIER


Connection From: MCC-3.6/3/L1,L2,L3 To: 3.6 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.74 / 0.34 0.74 / 0.34 0.74 / 0.34 -----
Voltage Drop - From Source (V/%) 5.84 / 2.67 5.84 / 2.67 5.84 / 2.67 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11850 0.01762 0.02755 0.16317 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.34
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.023 / 2.948 Load End: 4.915 / 2.005
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 52.24 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 66 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.1-SM01 4.1 AHU SUPPLY FAN


Connection From: Starter-1 To: 4.1 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-4.1
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.36 / 3.82 8.36 / 3.82 8.36 / 3.82 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12763 0.04157 0.04230 0.20888 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.05
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.362 / 2.211 Load End: 3.038 / 1.359
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 55.97 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 67 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.1-SM02 4.1 AHU HEATER BATTERY


Connection From: MCC-4.1/2/L1,L2,L3 To: 4.1 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.37 / 3.82 8.37 / 3.82 8.37 / 3.82 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12763 0.02309 0.02320 0.17217 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.27
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.362 / 2.211 Load End: 3.774 / 1.517
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.51 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 68 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.1-SM03 4.1 ELEC HUMIDIFIER


Connection From: MCC-4.1/3/L1,L2,L3 To: 4.1 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 22
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.86 / 0.39 0.86 / 0.39 0.86 / 0.39 -----
Voltage Drop - From Source (V/%) 8.75 / 3.99 8.75 / 3.99 8.75 / 3.99 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12763 0.02040 0.03190 0.17835 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.362 / 2.211 Load End: 3.881 / 1.570
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 39.98 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 69 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.2-SM01 4.2 AHU SUPPLY FAN


Connection From: Starter-1 To: 4.2 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-4.2
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 7.12 / 3.25 7.12 / 3.25 7.12 / 3.25 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11358 0.03464 0.03525 0.18200 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.20
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.378 / 3.132 Load End: 3.960 / 1.834
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 73.77 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 70 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.2-SM02 4.2 AHU HEATER BATTERY


Connection From: MCC-4.2/2/L1,L2,L3 To: 4.2 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 7.23 / 3.30 7.23 / 3.30 7.23 / 3.30 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11358 0.02454 0.02465 0.16160 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.36
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.378 / 3.132 Load End: 4.594 / 1.859
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 48.06 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 71 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.2-SM03 4.2 ELEC HUMIDIFIER


Connection From: MCC-4.2/3/L1,L2,L3 To: 4.2 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.02 / 0.46 1.02 / 0.46 1.02 / 0.46 -----
Voltage Drop - From Source (V/%) 7.73 / 3.53 7.73 / 3.53 7.73 / 3.53 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11358 0.02411 0.03770 0.17431 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.26
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.378 / 3.132 Load End: 4.573 / 1.863
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 48.16 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 72 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.3-SM01 4.3 AHU SUPPLY FAN


Connection From: Starter-1 To: 4.3 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-4.3
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.53 / 0.24 0.53 / 0.24 0.53 / 0.24 -----
Voltage Drop - From Source (V/%) 8.42 / 3.84 8.42 / 3.84 8.42 / 3.84 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12763 0.04619 0.04700 0.21803 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.00
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.362 / 2.211 Load End: 2.897 / 1.316
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 54.36 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 73 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.3-SM02 4.3 AHU HEATER BATTERY


Connection From: MCC-4.3/2/L1,L2,L3 To: 4.3 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.54 / 0.25 0.54 / 0.25 0.54 / 0.25 -----
Voltage Drop - From Source (V/%) 8.43 / 3.85 8.43 / 3.85 8.43 / 3.85 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12763 0.02598 0.02610 0.17780 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.362 / 2.211 Load End: 3.637 / 1.459
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 36.90 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 74 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.3-SM03 4.3 ELEC HUMIDIFIER


Connection From: MCC-4.3/3/L1,L2,L3 To: 4.3 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 24
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.67 / 0.31 0.67 / 0.31 0.67 / 0.31 -----
Voltage Drop - From Source (V/%) 8.55 / 3.91 8.55 / 3.91 8.55 / 3.91 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12763 0.01604 0.03480 0.17693 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.24
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.362 / 2.211 Load End: 4.117 / 1.672
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 42.85 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 75 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.4-SM01 4.4 AHU SUPPLY FAN


Connection From: Starter-1 To: 4.4 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-4.4
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 5.91 / 2.70 5.91 / 2.70 5.91 / 2.70 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12926 0.04388 0.04465 0.21686 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.01
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.477 / 2.699 Load End: 3.279 / 1.530
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.37 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 76 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.4-SM02 4.4 AHU HEATER BATTERY


Connection From: MCC-4.4/2/L1,L2,L3 To: 4.4 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 5.92 / 2.70 5.91 / 2.70 5.91 / 2.70 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12926 0.02454 0.02465 0.17782 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.477 / 2.699 Load End: 4.207 / 1.693
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.43 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 77 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.4-SM03 4.4 ELEC HUMIDIFIER


Connection From: MCC-4.4/3/L1,L2,L3 To: 4.4 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 6.11 / 2.79 6.11 / 2.79 6.11 / 2.79 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12926 0.01669 0.02610 0.17164 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.28
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.25

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.477 / 2.699 Load End: 4.708 / 1.917
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 49.68 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 78 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.5-SM01 4.5 AHU SUPPLY FAN


Connection From: Starter-1 To: 4.5 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-4.5
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 5.94 / 2.71 5.94 / 2.71 5.94 / 2.71 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13136 0.04157 0.04230 0.21434 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.02
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.381 / 2.655 Load End: 3.341 / 1.542
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.81 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 79 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.5-SM02 4.5 AHU HEATER BATTERY


Connection From: MCC-4.5/2/L1,L2,L3 To: 4.5 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 5.94 / 2.71 5.94 / 2.71 5.94 / 2.71 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13136 0.02309 0.02320 0.17706 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.24
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.381 / 2.655 Load End: 4.254 / 1.713
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.99 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 80 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.5-SM03 4.5 ELEC HUMIDIFIER


Connection From: MCC-4.5/3/L1,L2,L3 To: 4.5 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 25
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.98 / 0.45 0.98 / 0.45 0.98 / 0.45 -----
Voltage Drop - From Source (V/%) 6.44 / 2.94 6.43 / 2.94 6.43 / 2.94 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13136 0.02318 0.03625 0.19026 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.15
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.18

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.381 / 2.655 Load End: 4.210 / 1.704
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.74 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 81 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.6-SM01 4.6 AHU SUPPLY FAN


Connection From: Starter-1 To: 4.6 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-4.6
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 5.54 / 2.53 5.54 / 2.53 5.54 / 2.53 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11882 0.03464 0.03525 0.18782 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.17
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.003 / 2.939 Load End: 3.834 / 1.753
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 70.72 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 82 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.6-SM02 4.6 AHU HEATER BATTERY


Connection From: MCC-4.6/2/L1,L2,L3 To: 4.6 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 5.65 / 2.58 5.65 / 2.58 5.65 / 2.58 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11882 0.02454 0.02465 0.16730 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.31
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.003 / 2.939 Load End: 4.429 / 1.786
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 46.01 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 83 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-4.6-SM03 4.6 ELEC HUMIDIFIER


Connection From: MCC-4.6/3/L1,L2,L3 To: 4.6 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.74 / 0.34 0.74 / 0.34 0.74 / 0.34 -----
Voltage Drop - From Source (V/%) 5.89 / 2.69 5.88 / 2.69 5.88 / 2.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11882 0.01762 0.02755 0.16349 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.34
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.003 / 2.939 Load End: 4.906 / 2.001
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 52.05 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 84 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.1-SM01 5.1 AHU SUPPLY FAN


Connection From: Starter-1 To: 5.1 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-5.1
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.39 / 3.83 8.39 / 3.83 8.39 / 3.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12796 0.04157 0.04230 0.20920 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.05
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.351 / 2.206 Load End: 3.035 / 1.357
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 55.89 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 85 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.1-SM02 5.1 AHU HEATER BATTERY


Connection From: MCC-5.1/2/L1,L2,L3 To: 5.1 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.39 / 3.83 8.39 / 3.83 8.39 / 3.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12796 0.02309 0.02320 0.17249 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.27
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.351 / 2.206 Load End: 3.768 / 1.515
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.44 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 86 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.1-SM03 5.1 ELEC HUMIDIFIER


Connection From: MCC-5.1/3/L1,L2,L3 To: 5.1 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 22
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.61 / 0.28 0.61 / 0.28 0.61 / 0.28 -----
Voltage Drop - From Source (V/%) 8.52 / 3.89 8.52 / 3.89 8.52 / 3.89 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12796 0.01471 0.03190 0.17311 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.27
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.351 / 2.206 Load End: 4.192 / 1.704
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.73 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 87 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.2-SM01 5.2 AHU SUPPLY FAN


Connection From: Starter-1 To: 5.2 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-5.2
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 7.14 / 3.26 7.14 / 3.26 7.14 / 3.26 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11391 0.03464 0.03525 0.18232 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.20
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.356 / 3.122 Load End: 3.954 / 1.830
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 73.62 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 88 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.2-SM02 5.2 AHU HEATER BATTERY


Connection From: MCC-5.2/2/L1,L2,L3 To: 5.2 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 7.25 / 3.31 7.25 / 3.31 7.25 / 3.31 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11391 0.02454 0.02465 0.16192 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.35
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.29

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.356 / 3.122 Load End: 4.585 / 1.855
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 47.96 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 89 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.2-SM03 5.2 ELEC HUMIDIFIER


Connection From: MCC-5.2/3/L1,L2,L3 To: 5.2 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.02 / 0.46 1.02 / 0.46 1.02 / 0.46 -----
Voltage Drop - From Source (V/%) 7.76 / 3.54 7.76 / 3.54 7.76 / 3.54 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11391 0.02411 0.03770 0.17463 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.25
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.356 / 3.122 Load End: 4.564 / 1.859
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 48.06 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 90 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.3-SM01 5.3 AHU SUPPLY FAN


Connection From: Starter-1 To: 5.3 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-5.3
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.53 / 0.24 0.53 / 0.24 0.53 / 0.24 -----
Voltage Drop - From Source (V/%) 8.44 / 3.85 8.44 / 3.85 8.44 / 3.85 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12796 0.04619 0.04700 0.21835 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.00
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.351 / 2.206 Load End: 2.893 / 1.314
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 54.28 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 91 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.3-SM02 5.3 AHU HEATER BATTERY


Connection From: MCC-5.3/2/L1,L2,L3 To: 5.3 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.54 / 0.25 0.54 / 0.25 0.54 / 0.25 -----
Voltage Drop - From Source (V/%) 8.45 / 3.86 8.45 / 3.86 8.45 / 3.86 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12796 0.02598 0.02610 0.17812 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.351 / 2.206 Load End: 3.632 / 1.457
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 36.84 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 92 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.3-SM03 5.3 ELEC HUMIDIFIER


Connection From: MCC-5.3/3/L1,L2,L3 To: 5.3 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 24
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.67 / 0.31 0.67 / 0.31 0.67 / 0.31 -----
Voltage Drop - From Source (V/%) 8.58 / 3.92 8.58 / 3.92 8.58 / 3.92 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12796 0.01604 0.03480 0.17725 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.24
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.351 / 2.206 Load End: 4.111 / 1.669
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 42.76 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 93 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.4-SM01 5.4 AHU SUPPLY FAN


Connection From: Starter-1 To: 5.4 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-5.4
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 5.93 / 2.71 5.93 / 2.71 5.93 / 2.71 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12959 0.04388 0.04465 0.21718 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.01
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.460 / 2.691 Load End: 3.275 / 1.527
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.26 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 94 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.4-SM02 5.4 AHU HEATER BATTERY


Connection From: MCC-5.4/2/L1,L2,L3 To: 5.4 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 5.94 / 2.71 5.94 / 2.71 5.94 / 2.71 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12959 0.02454 0.02465 0.17814 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.460 / 2.691 Load End: 4.200 / 1.690
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.35 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 95 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.4-SM03 5.4 ELEC HUMIDIFIER


Connection From: MCC-5.4/3/L1,L2,L3 To: 5.4 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 6.13 / 2.80 6.13 / 2.80 6.13 / 2.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12959 0.01669 0.02610 0.17196 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.27
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.25

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.460 / 2.691 Load End: 4.699 / 1.913
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 49.57 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 96 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.5-SM01 5.5 AHU SUPPLY FAN


Connection From: Starter-1 To: 5.5 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-5.5
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 5.96 / 2.72 5.96 / 2.72 5.96 / 2.72 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13168 0.04157 0.04230 0.21466 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.02
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.364 / 2.648 Load End: 3.337 / 1.539
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.70 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 97 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.5-SM02 5.5 AHU HEATER BATTERY


Connection From: MCC-5.5/2/L1,L2,L3 To: 5.5 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 5.96 / 2.72 5.96 / 2.72 5.96 / 2.72 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13168 0.02309 0.02320 0.17738 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.364 / 2.648 Load End: 4.247 / 1.710
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.91 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 98 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.5-SM03 5.5 ELEC HUMIDIFIER


Connection From: MCC-5.5/3/L1,L2,L3 To: 5.5 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 25
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.98 / 0.45 0.98 / 0.45 0.98 / 0.45 -----
Voltage Drop - From Source (V/%) 6.46 / 2.95 6.46 / 2.95 6.46 / 2.95 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13168 0.02318 0.03625 0.19058 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.15
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.17

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.364 / 2.648 Load End: 4.203 / 1.701
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.65 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 99 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.6-SM01 5.6 AHU SUPPLY FAN


Connection From: Starter-1 To: 5.6 AHU SUPPLY FAN
Active Source: Tx 4
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-5.6
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 5.56 / 2.54 5.56 / 2.54 5.56 / 2.54 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11914 0.03464 0.03525 0.18814 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.16
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.984 / 2.930 Load End: 3.828 / 1.749
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 70.59 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 100 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.6-SM02 5.6 AHU HEATER BATTERY


Connection From: MCC-5.6/2/L1,L2,L3 To: 5.6 AHU HEATER BATTERY
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 5.67 / 2.59 5.67 / 2.59 5.67 / 2.59 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11914 0.02454 0.02465 0.16762 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.31
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.984 / 2.930 Load End: 4.421 / 1.782
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 45.92 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 101 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-5.6-SM03 5.6 ELEC HUMIDIFIER


Connection From: MCC-5.6/3/L1,L2,L3 To: 5.6 ELEC HUMIDIFIER
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.74 / 0.34 0.74 / 0.34 0.74 / 0.34 -----
Voltage Drop - From Source (V/%) 5.91 / 2.70 5.90 / 2.70 5.90 / 2.70 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11914 0.01762 0.02755 0.16381 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.34
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.984 / 2.930 Load End: 4.896 / 1.997
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 51.92 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 102 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-4-SM01 BB-MDB4-1


Connection From: MDB4 To: EF-1
Active Source: Tx 4
Load Type: Busbar EndFeed Design Current Ib (A): 1,526.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW20 H1 MLogic 5.0A High
Rating In (A):2000 [f] Overload Setting Ir (A): 2000 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 96
31 - On horizontal/vertical perforated tray Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.87 [BS 7671, Table 4C5]
No. of trays = 2 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,526.8
Device Rating In = 2000 Overload Setting Ir = 2000 [Ir >
_ Ib]
Min. Cable Capacity Iz = 660.6 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 736.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1526.8 / 1.00 1526.8 / 1.00 1526.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.95 / 1.35 2.95 / 1.35 2.95 / 1.35 -----
Voltage Drop - From Source (V/%) 3.49 / 1.59 3.49 / 1.59 3.49 / 1.59 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01050 0.00290 0.01412 0.02715 0.03318 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
8.07
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 21.11

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 32.664 / 29.340 Load End: 23.748 / 16.955
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 270.40 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 103 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-4-SM02 BB-MDB4-2


Connection From: MDB4 To: EF-2
Active Source: Tx 4
Load Type: Busbar EndFeed Design Current Ib (A): 1,170.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW20 H1 MLogic 5.0A High
Rating In (A):2000 [f] Overload Setting Ir (A): 2000 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 56
31 - On horizontal/vertical perforated tray Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.87 [BS 7671, Table 4C5]
No. of trays = 2 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,170.0
Device Rating In = 2000 Overload Setting Ir = 2000 [Ir >
_ Ib]
Min. Cable Capacity Iz = 660.6 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 736.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1170.0 / 1.00 1168.9 / 1.00 1168.9 / 1.00 1.2
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.29 / 0.59 1.28 / 0.59 1.28 / 0.59 -----
Voltage Drop - From Source (V/%) 1.83 / 0.83 1.82 / 0.83 1.82 / 0.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01050 0.00169 0.00824 0.02014 0.03318 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
10.87
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 28.45

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 32.664 / 29.340 Load End: 26.830 / 20.661
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 270.40 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 104 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-2A-SM01 DB-2PA


Connection From: SMDB-2A/1/L1,L2,L3 To: DB-2PA
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 118.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.11 / 0.05 0.11 / 0.05 0.11 / 0.05 -----
Voltage Drop - From Source (V/%) 4.21 / 1.92 4.21 / 1.92 4.21 / 1.92 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02970 0.00251 0.00468 0.03463 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.32
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.62

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.913 / 14.781 Load End: 19.605 / 11.906
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 422.87 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 105 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-2A-SM02 DB-2LA


Connection From: SMDB-2A/2/L1,L2,L3 To: DB-2LA
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 4.16 / 1.90 4.16 / 1.90 4.16 / 1.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02970 0.00334 0.00725 0.03641 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.02
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.50

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.913 / 14.781 Load End: 19.035 / 11.196
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 415.55 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 106 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-2B-SM01 DB-2PB


Connection From: SMDB-2B/1/L1,L2,L3 To: DB-2PB
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 118.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.11 / 0.05 0.11 / 0.05 0.11 / 0.05 -----
Voltage Drop - From Source (V/%) 2.40 / 1.10 2.40 / 1.09 2.40 / 1.09 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02263 0.00251 0.00468 0.02759 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
7.94
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.99

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.552 / 17.603 Load End: 21.750 / 13.709
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 444.51 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 107 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-2B-SM02 DB-2LB


Connection From: SMDB-2B/2/L1,L2,L3 To: DB-2LB
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 2.35 / 1.07 2.34 / 1.07 2.34 / 1.07 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02263 0.00334 0.00725 0.02947 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.43
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.85

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.552 / 17.603 Load End: 21.056 / 12.768
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 435.99 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 108 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3A-SM01 DB-3PA


Connection From: SMDB-3A/1/L1,L2,L3 To: DB-3PA
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 4.40 / 2.01 4.40 / 2.01 4.40 / 2.01 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02942 0.00251 0.00468 0.03430 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.38
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.63

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.280 / 15.160 Load End: 19.914 / 12.163
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 425.95 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 109 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3A-SM02 DB-3LA


Connection From: SMDB-3A/2/L1,L2,L3 To: DB-3LA
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 4.35 / 1.99 4.35 / 1.99 4.35 / 1.99 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02942 0.00334 0.00725 0.03605 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.07
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.52

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.280 / 15.160 Load End: 19.329 / 11.424
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 418.52 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 110 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3A-SM03 OFFICE 3.1


Connection From: SMDB-3A/3/L1,L2,L3 To: OFFICE 3.1
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 30.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 30.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.9 / 1.00 30.9 / 1.00 30.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.63 / 0.29 0.63 / 0.29 0.63 / 0.29 -----
Voltage Drop - From Source (V/%) 4.91 / 2.24 4.91 / 2.24 4.91 / 2.24 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02942 0.02211 0.04116 0.08457 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.59
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.16

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.280 / 15.160 Load End: 9.107 / 4.026
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 181.55 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 111 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3A-SM04 OFFICE 3.2


Connection From: SMDB-3A/4/L1,L2,L3 To: OFFICE 3.2
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 41.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 41.6
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 147.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 41.6 / 1.00 41.6 / 1.00 41.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.64 / 0.29 0.64 / 0.29 0.64 / 0.29 -----
Voltage Drop - From Source (V/%) 4.92 / 2.25 4.92 / 2.25 4.92 / 2.25 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02942 0.01659 0.03087 0.06949 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.15
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.51

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.280 / 15.160 Load End: 10.932 / 5.018
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 241.07 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 112 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3A-SM05 OFFICE 3.3


Connection From: SMDB-3A/5/L1,L2,L3 To: OFFICE 3.3
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.4 / 1.00 35.4 / 1.00 35.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 4.99 / 2.28 4.99 / 2.28 4.99 / 2.28 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02942 0.02161 0.04023 0.08318 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.63
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.19

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.280 / 15.160 Load End: 9.249 / 4.100
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 185.99 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 113 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3A-SM06 MCC-3.1


Connection From: SMDB-3A/6/L1,L2,L3 To: MCC-3.1
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.84 / 3.58 7.84 / 3.58 7.84 / 3.58 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02942 0.04479 0.06268 0.12731 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.72
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.280 / 15.160 Load End: 5.374 / 2.216
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 149.12 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 114 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3A-SM07 MCC-3.2


Connection From: SMDB-3A/7/L1,L2,L3 To: MCC-3.2
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.39 / 1.09 2.39 / 1.09 2.39 / 1.09 -----
Voltage Drop - From Source (V/%) 6.67 / 3.05 6.67 / 3.05 6.67 / 3.05 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02942 0.03008 0.06525 0.11326 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.93
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.280 / 15.160 Load End: 7.400 / 3.143
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 165.36 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 115 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3A-SM08 MCC-3.3


Connection From: SMDB-3A/8/L1,L2,L3 To: MCC-3.3
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.84 / 3.58 7.84 / 3.58 7.84 / 3.58 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02942 0.04479 0.06268 0.12731 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.72
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.280 / 15.160 Load End: 5.374 / 2.216
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 149.12 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 116 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3B-SM01 DB-3PB


Connection From: SMDB-3B/1/L1,L2,L3 To: DB-3PB
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 2.56 / 1.17 2.56 / 1.17 2.56 / 1.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02236 0.00251 0.00468 0.02725 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
8.04
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 4.01

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.009 / 18.137 Load End: 22.130 / 14.052
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 448.62 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 117 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3B-SM02 DB-3LB


Connection From: SMDB-3B/2/L1,L2,L3 To: DB-3LB
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 2.51 / 1.15 2.50 / 1.14 2.50 / 1.14 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02236 0.00334 0.00725 0.02911 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.52
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.88

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.009 / 18.137 Load End: 21.416 / 13.066
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 439.86 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 118 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3B-SM03 OFFICE 3.4


Connection From: SMDB-3B/3/L1,L2,L3 To: OFFICE 3.4
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 25.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 25.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 25.0 / 1.00 25.0 / 1.00 25.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.45 / 0.21 0.45 / 0.21 0.45 / 0.21 -----
Voltage Drop - From Source (V/%) 2.90 / 1.32 2.89 / 1.32 2.89 / 1.32 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02236 0.01960 0.03649 0.07167 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.06
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.46

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.009 / 18.137 Load End: 10.332 / 4.624
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 217.44 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 119 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3B-SM04 OFFICE 3.5


Connection From: SMDB-3B/4/L1,L2,L3 To: OFFICE 3.5
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 34.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.4 / 1.00 34.4 / 1.00 34.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 3.20 / 1.46 3.19 / 1.46 3.19 / 1.46 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02236 0.02362 0.04397 0.08285 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.64
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.20

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.009 / 18.137 Load End: 9.059 / 3.963
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 177.80 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 120 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3B-SM05 OFFICE 3.6


Connection From: SMDB-3B/5/L1,L2,L3 To: OFFICE 3.6
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.7
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.7 / 1.00 35.7 / 1.00 35.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.56 / 0.26 0.56 / 0.26 0.56 / 0.26 -----
Voltage Drop - From Source (V/%) 3.01 / 1.37 3.00 / 1.37 3.00 / 1.37 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02236 0.01709 0.03181 0.06473 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.38
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.64

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.009 / 18.137 Load End: 11.309 / 5.158
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 249.51 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 121 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3B-SM06 MCC-3.4


Connection From: SMDB-3B/6/L1,L2,L3 To: MCC-3.4
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.92 / 1.33 2.92 / 1.33 2.92 / 1.33 -----
Voltage Drop - From Source (V/%) 5.37 / 2.45 5.36 / 2.45 5.36 / 2.45 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02236 0.03677 0.07975 0.12894 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.70
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.009 / 18.137 Load End: 6.494 / 2.706
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.80 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 122 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3B-SM07 MCC-3.5


Connection From: SMDB-3B/7/L1,L2,L3 To: MCC-3.5
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 56
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.97 / 1.36 2.97 / 1.36 2.97 / 1.36 -----
Voltage Drop - From Source (V/%) 5.42 / 2.47 5.41 / 2.47 5.41 / 2.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02236 0.03744 0.08120 0.13103 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.67
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.009 / 18.137 Load End: 6.397 / 2.663
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.47 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 123 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-3B-SM08 MCC-3.6


Connection From: SMDB-3B/8/L1,L2,L3 To: MCC-3.6
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.65 / 1.21 2.65 / 1.21 2.65 / 1.21 -----
Voltage Drop - From Source (V/%) 5.10 / 2.33 5.10 / 2.33 5.10 / 2.33 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02236 0.03343 0.07250 0.11850 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.85
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.009 / 18.137 Load End: 7.023 / 2.948
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 154.61 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 124 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4A-SM01 DB-4PA


Connection From: SMDB-4A/1/L1,L2,L3 To: DB-4PA
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 4.45 / 2.03 4.45 / 2.03 4.45 / 2.03 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02966 0.00251 0.00468 0.03457 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.33
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.62

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.116 / 14.961 Load End: 19.770 / 12.018
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 424.22 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 125 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4A-SM02 DB-4LA


Connection From: SMDB-4A/2/L1,L2,L3 To: DB-4LA
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 4.39 / 2.01 4.39 / 2.01 4.39 / 2.01 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02966 0.00334 0.00725 0.03634 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.03
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.50

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.116 / 14.961 Load End: 19.190 / 11.294
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 416.82 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 126 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4A-SM03 OFFICE 4.1


Connection From: SMDB-4A/3/L1,L2,L3 To: OFFICE 4.1
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 30.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 30.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.9 / 1.00 30.9 / 1.00 30.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.63 / 0.29 0.63 / 0.29 0.63 / 0.29 -----
Voltage Drop - From Source (V/%) 4.96 / 2.26 4.96 / 2.26 4.96 / 2.26 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02966 0.02211 0.04116 0.08489 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.58
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.15

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.116 / 14.961 Load End: 9.073 / 4.009
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 180.51 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 127 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4A-SM04 OFFICE 4.2


Connection From: SMDB-4A/4/L1,L2,L3 To: OFFICE 4.2
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 41.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 41.6
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 147.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 41.6 / 1.00 41.6 / 1.00 41.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.64 / 0.29 0.64 / 0.29 0.64 / 0.29 -----
Voltage Drop - From Source (V/%) 4.97 / 2.27 4.97 / 2.27 4.97 / 2.27 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02966 0.01659 0.03087 0.06981 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.14
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.50

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.116 / 14.961 Load End: 10.884 / 4.991
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 239.46 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 128 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4A-SM05 OFFICE 4.3


Connection From: SMDB-4A/5/L1,L2,L3 To: OFFICE 4.3
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.4 / 1.00 35.4 / 1.00 35.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 5.03 / 2.30 5.03 / 2.30 5.03 / 2.30 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02966 0.02161 0.04023 0.08351 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.62
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.18

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.116 / 14.961 Load End: 9.214 / 4.082
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 184.92 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 129 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4A-SM06 MCC-4.1


Connection From: SMDB-4A/6/L1,L2,L3 To: MCC-4.1
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.89 / 3.60 7.89 / 3.60 7.89 / 3.60 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02966 0.04479 0.06268 0.12763 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.72
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.116 / 14.961 Load End: 5.362 / 2.211
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 149.09 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 130 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4A-SM07 MCC-4.2


Connection From: SMDB-4A/7/L1,L2,L3 To: MCC-4.2
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.39 / 1.09 2.39 / 1.09 2.39 / 1.09 -----
Voltage Drop - From Source (V/%) 6.72 / 3.07 6.72 / 3.07 6.72 / 3.07 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02966 0.03008 0.06525 0.11358 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.93
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.116 / 14.961 Load End: 7.378 / 3.132
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 164.60 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 131 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4A-SM08 MCC-4.3


Connection From: SMDB-4A/8/L1,L2,L3 To: MCC-4.3
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.89 / 3.60 7.89 / 3.60 7.89 / 3.60 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02966 0.04479 0.06268 0.12763 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.72
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.116 / 14.961 Load End: 5.362 / 2.211
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 149.09 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 132 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4B-SM01 DB-4PB


Connection From: SMDB-4B/1/L1,L2,L3 To: DB-4PB
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 2.61 / 1.19 2.60 / 1.19 2.60 / 1.19 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02259 0.00251 0.00468 0.02753 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
7.96
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 4.00

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.806 / 17.861 Load End: 21.953 / 13.859
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 446.30 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 133 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4B-SM02 DB-4LB


Connection From: SMDB-4B/2/L1,L2,L3 To: DB-4LB
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 2.55 / 1.16 2.55 / 1.16 2.55 / 1.16 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02259 0.00334 0.00725 0.02940 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.45
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.86

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.806 / 17.861 Load End: 21.246 / 12.895
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 437.63 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 134 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4B-SM03 OFFICE 4.4


Connection From: SMDB-4B/3/L1,L2,L3 To: OFFICE 4.4
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 25.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 25.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 25.0 / 1.00 25.0 / 1.00 25.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.45 / 0.21 0.45 / 0.21 0.45 / 0.21 -----
Voltage Drop - From Source (V/%) 2.94 / 1.34 2.93 / 1.34 2.93 / 1.34 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02259 0.01960 0.03649 0.07199 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.04
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.45

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.806 / 17.861 Load End: 10.288 / 4.601
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 216.08 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 135 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4B-SM04 OFFICE 4.5


Connection From: SMDB-4B/4/L1,L2,L3 To: OFFICE 4.5
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 34.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.4 / 1.00 34.4 / 1.00 34.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 3.24 / 1.48 3.23 / 1.48 3.23 / 1.48 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02259 0.02362 0.04397 0.08318 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.63
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.19

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.806 / 17.861 Load End: 9.026 / 3.947
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 176.81 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 136 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4B-SM05 OFFICE 4.6


Connection From: SMDB-4B/5/L1,L2,L3 To: OFFICE 4.6
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.7
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.7 / 1.00 35.7 / 1.00 35.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.56 / 0.26 0.56 / 0.26 0.56 / 0.26 -----
Voltage Drop - From Source (V/%) 3.05 / 1.39 3.05 / 1.39 3.05 / 1.39 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02259 0.01709 0.03181 0.06505 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.37
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.64

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.806 / 17.861 Load End: 11.257 / 5.130
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 247.81 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 137 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4B-SM06 MCC-4.4


Connection From: SMDB-4B/6/L1,L2,L3 To: MCC-4.4
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.92 / 1.33 2.92 / 1.33 2.92 / 1.33 -----
Voltage Drop - From Source (V/%) 5.41 / 2.47 5.40 / 2.47 5.40 / 2.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02259 0.03677 0.07975 0.12926 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.69
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.806 / 17.861 Load End: 6.477 / 2.699
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.74 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 138 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4B-SM07 MCC-4.5


Connection From: SMDB-4B/7/L1,L2,L3 To: MCC-4.5
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 56
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.97 / 1.36 2.97 / 1.36 2.97 / 1.36 -----
Voltage Drop - From Source (V/%) 5.46 / 2.49 5.46 / 2.49 5.46 / 2.49 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02259 0.03744 0.08120 0.13136 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.67
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.806 / 17.861 Load End: 6.381 / 2.655
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.41 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 139 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-4B-SM08 MCC-4.6


Connection From: SMDB-4B/8/L1,L2,L3 To: MCC-4.6
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.65 / 1.21 2.65 / 1.21 2.65 / 1.21 -----
Voltage Drop - From Source (V/%) 5.14 / 2.35 5.14 / 2.35 5.14 / 2.35 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02259 0.03343 0.07250 0.11882 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.84
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.806 / 17.861 Load End: 7.003 / 2.939
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 154.54 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 140 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5A-SM01 DB-5PA


Connection From: SMDB-5A/1/L1,L2,L3 To: DB-5PA
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.23 / 0.11 0.23 / 0.11 0.23 / 0.11 -----
Voltage Drop - From Source (V/%) 4.58 / 2.09 4.58 / 2.09 4.58 / 2.09 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02990 0.00503 0.00936 0.04047 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.41
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.39

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.953 / 14.767 Load End: 17.463 / 9.692
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 388.91 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 141 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5A-SM02 DB-5LA


Connection From: SMDB-5A/2/L1,L2,L3 To: DB-5LA
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.06 0.12 / 0.06 0.12 / 0.06 -----
Voltage Drop - From Source (V/%) 4.47 / 2.04 4.47 / 2.04 4.47 / 2.04 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02990 0.00669 0.01450 0.04486 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
4.88
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.04

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.953 / 14.767 Load End: 16.395 / 8.665
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 349.93 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 142 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5A-SM03 OFFICE 5.1


Connection From: SMDB-5A/3/L1,L2,L3 To: OFFICE 5.1
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 30.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 30.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.9 / 1.00 30.9 / 1.00 30.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.63 / 0.29 0.63 / 0.29 0.63 / 0.29 -----
Voltage Drop - From Source (V/%) 4.98 / 2.27 4.98 / 2.27 4.98 / 2.27 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02990 0.02211 0.04116 0.08521 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.57
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.15

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.953 / 14.767 Load End: 9.039 / 3.992
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 179.49 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 143 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5A-SM04 OFFICE 5.2


Connection From: SMDB-5A/4/L1,L2,L3 To: OFFICE 5.2
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 41.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 41.6
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 147.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 41.6 / 1.00 41.6 / 1.00 41.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.64 / 0.29 0.64 / 0.29 0.64 / 0.29 -----
Voltage Drop - From Source (V/%) 4.99 / 2.28 4.99 / 2.28 4.99 / 2.28 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02990 0.01659 0.03087 0.07013 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.12
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.50

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.953 / 14.767 Load End: 10.835 / 4.965
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 237.87 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 144 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5A-SM05 OFFICE 5.3


Connection From: SMDB-5A/5/L1,L2,L3 To: OFFICE 5.3
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.4 / 1.00 35.4 / 1.00 35.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 5.06 / 2.31 5.06 / 2.31 5.06 / 2.31 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02990 0.02161 0.04023 0.08383 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.61
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.18

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.953 / 14.767 Load End: 9.179 / 4.064
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 183.86 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 145 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5A-SM06 MCC-5.1


Connection From: SMDB-5A/6/L1,L2,L3 To: MCC-5.1
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.91 / 3.61 7.91 / 3.61 7.91 / 3.61 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02990 0.04479 0.06268 0.12796 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.71
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.953 / 14.767 Load End: 5.351 / 2.206
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 149.05 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 146 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5A-SM07 MCC-5.2


Connection From: SMDB-5A/7/L1,L2,L3 To: MCC-5.2
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.39 / 1.09 2.39 / 1.09 2.39 / 1.09 -----
Voltage Drop - From Source (V/%) 6.74 / 3.08 6.74 / 3.08 6.74 / 3.08 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02990 0.03008 0.06525 0.11391 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.92
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.953 / 14.767 Load End: 7.356 / 3.122
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 163.85 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 147 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5A-SM08 MCC-5.3


Connection From: SMDB-5A/8/L1,L2,L3 To: MCC-5.3
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.91 / 3.61 7.91 / 3.61 7.91 / 3.61 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02990 0.04479 0.06268 0.12796 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.71
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.953 / 14.767 Load End: 5.351 / 2.206
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 149.05 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 148 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5B-SM01 DB-5PB


Connection From: SMDB-5B/1/L1,L2,L3 To: DB-5PB
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 2.63 / 1.20 2.62 / 1.20 2.62 / 1.20 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02283 0.00251 0.00468 0.02781 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
7.88
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.98

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.606 / 17.590 Load End: 21.778 / 13.671
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 444.05 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 149 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5B-SM02 DB-5LB


Connection From: SMDB-5B/2/L1,L2,L3 To: DB-5LB
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 2.57 / 1.17 2.57 / 1.17 2.57 / 1.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02283 0.00334 0.00725 0.02969 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.38
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.84

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.606 / 17.590 Load End: 21.078 / 12.728
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 435.46 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 150 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5B-SM03 OFFICE 5.4


Connection From: SMDB-5B/3/L1,L2,L3 To: OFFICE 5.4
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 25.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 25.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 25.0 / 1.00 25.0 / 1.00 25.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.45 / 0.21 0.45 / 0.21 0.45 / 0.21 -----
Voltage Drop - From Source (V/%) 2.96 / 1.35 2.96 / 1.35 2.96 / 1.35 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02283 0.01960 0.03649 0.07231 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.03
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.44

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.606 / 17.590 Load End: 10.245 / 4.579
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 214.74 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 151 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5B-SM04 OFFICE 5.5


Connection From: SMDB-5B/4/L1,L2,L3 To: OFFICE 5.5
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 34.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.4 / 1.00 34.4 / 1.00 34.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 3.26 / 1.49 3.25 / 1.49 3.25 / 1.49 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02283 0.02362 0.04397 0.08350 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.62
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.18

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.606 / 17.590 Load End: 8.993 / 3.930
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 175.82 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 152 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5B-SM05 OFFICE 5.6


Connection From: SMDB-5B/5/L1,L2,L3 To: OFFICE 5.6
Active Source: Tx 4
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.7
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.7 / 1.00 35.7 / 1.00 35.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.56 / 0.26 0.56 / 0.26 0.56 / 0.26 -----
Voltage Drop - From Source (V/%) 3.07 / 1.40 3.07 / 1.40 3.07 / 1.40 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02283 0.01709 0.03181 0.06538 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.35
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.63

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.606 / 17.590 Load End: 11.205 / 5.102
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 246.13 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 153 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5B-SM06 MCC-5.4


Connection From: SMDB-5B/6/L1,L2,L3 To: MCC-5.4
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.92 / 1.33 2.92 / 1.33 2.92 / 1.33 -----
Voltage Drop - From Source (V/%) 5.43 / 2.48 5.42 / 2.48 5.42 / 2.48 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02283 0.03677 0.07975 0.12959 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.69
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.606 / 17.590 Load End: 6.460 / 2.691
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.68 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 154 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5B-SM07 MCC-5.5


Connection From: SMDB-5B/7/L1,L2,L3 To: MCC-5.5
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 56
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.97 / 1.36 2.97 / 1.36 2.97 / 1.36 -----
Voltage Drop - From Source (V/%) 5.48 / 2.50 5.48 / 2.50 5.48 / 2.50 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02283 0.03744 0.08120 0.13168 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.66
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.606 / 17.590 Load End: 6.364 / 2.648
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.36 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 155 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-5B-SM08 MCC-5.6


Connection From: SMDB-5B/8/L1,L2,L3 To: MCC-5.6
Active Source: Tx 4
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.65 / 1.21 2.65 / 1.21 2.65 / 1.21 -----
Voltage Drop - From Source (V/%) 5.16 / 2.36 5.16 / 2.36 5.16 / 2.36 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02283 0.03343 0.07250 0.11914 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.84
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 24.606 / 17.590 Load End: 6.984 / 2.930
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 154.47 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 156 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-Tx4 MDB4


Connection From: Tx 4 To: MDB4
Active Source: Tx 4
Load Type: Main cable to Switchboard Design Current Ib (A): 1,944.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW32 H1 MLogic 5.0A High
Rating In (A):2500 [f] Overload Setting Ir (A): 2500 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 630 [f]
Neutral: 630 mm²[a] Length (m): 30
34 - On a ladder Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.97 [BS 7671, Table 4C5]
No. of ladders = 1 No. of circuits per ladder = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,944.2
Device Rating In = 2500 Overload Setting Ir = 2500 [Ir >
_ Ib]
Min. Cable Capacity Iz = 740.6 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 1,151.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1944.2 / 1.00 1944.2 / 1.00 1944.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.54 / 0.25 0.54 / 0.25 0.54 / 0.25 -----
Voltage Drop - From Source (V/%) 0.54 / 0.25 0.54 / 0.25 0.54 / 0.25 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 630 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00599 0.00076 0.00379 0.01050 0.01188 Current (kA)

Disconnection time (s): From characteristic: 3.77 Maximum for circuit: 5.00
20.85
Adiabatic check (mm 2 ) CPC Section = Separate 630 Total = 630.0 Min. Section = 283.12

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 36.627 / 36.627 Load End: 32.664 / 29.340
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 422.50 x 106 Adiabatic Limit k²S² (A²s): 8,116.21 x 106

Project: KAFD 3.09 Tx 4 rev 0.p17 Page 157 of 157 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Buro Happold

4.5 Transformer TX5

KAFD Plot 3.09 Report Revision 0


Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB5-1-SM01 SMDB-6A


Connection From: TO-1 To: SMDB-6A
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 421.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 421.4
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 421.4 / 1.00 421.4 / 1.00 421.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.05 0.10 / 0.05 0.10 / 0.05 -----
Voltage Drop - From Source (V/%) 4.04 / 1.84 4.04 / 1.84 4.04 / 1.84 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02914 0.00031 0.00079 0.03022 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.25
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 5.00

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 23.589 / 15.043 Load End: 22.994 / 14.476
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.58 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 1 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB5-1-SM02 SMDB-7A


Connection From: TO-2 To: SMDB-7A
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 421.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 421.4
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 421.4 / 1.00 421.4 / 1.00 421.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.05 0.10 / 0.05 0.10 / 0.05 -----
Voltage Drop - From Source (V/%) 4.13 / 1.89 4.13 / 1.89 4.13 / 1.89 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02946 0.00031 0.00079 0.03054 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.17
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.96

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 23.350 / 14.788 Load End: 22.765 / 14.237
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.64 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 2 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB5-1-SM03 SMDB-8A


Connection From: TO-3 To: SMDB-8A
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 421.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 421.4
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 421.4 / 1.00 421.4 / 1.00 421.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.05 0.10 / 0.05 0.10 / 0.05 -----
Voltage Drop - From Source (V/%) 4.20 / 1.92 4.20 / 1.92 4.20 / 1.92 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02978 0.00031 0.00079 0.03086 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.10
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.91

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 23.114 / 14.540 Load End: 22.539 / 14.005
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.70 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 3 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB5-1-SM04 SMDB-9A


Connection From: TO-4 To: SMDB-9A
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 421.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 421.4
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 421.4 / 1.00 421.4 / 1.00 421.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.05 0.10 / 0.05 0.10 / 0.05 -----
Voltage Drop - From Source (V/%) 4.23 / 1.93 4.23 / 1.93 4.23 / 1.93 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03010 0.00031 0.00079 0.03118 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.02
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.87

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.882 / 14.300 Load End: 22.317 / 13.779
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.66 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 4 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB5-2-SM01 SMDB-6B


Connection From: TO-5 To: SMDB-6B
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 408.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 408.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 408.7 / 1.00 408.7 / 1.00 408.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.04 0.10 / 0.04 0.10 / 0.04 -----
Voltage Drop - From Source (V/%) 2.95 / 1.35 2.95 / 1.35 2.95 / 1.35 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02119 0.00031 0.00079 0.02225 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
9.84
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.72

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 27.128 / 18.433 Load End: 26.356 / 17.600
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 818.04 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 5 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB5-2-SM02 SMBD-7B


Connection From: TO-6 To: SMDB-7B
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 408.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 408.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 408.7 / 1.00 408.7 / 1.00 408.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.04 0.10 / 0.04 0.10 / 0.04 -----
Voltage Drop - From Source (V/%) 3.04 / 1.39 3.04 / 1.39 3.04 / 1.39 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02150 0.00031 0.00079 0.02257 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
9.70
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.63

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.819 / 18.060 Load End: 26.061 / 17.255
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 902.58 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 6 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB5-2-SM03 SMDB-8B


Connection From: TO-7 To: SMDB-8B
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 408.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 408.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 408.7 / 1.00 408.7 / 1.00 408.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.04 0.10 / 0.04 0.10 / 0.04 -----
Voltage Drop - From Source (V/%) 3.11 / 1.42 3.11 / 1.42 3.11 / 1.42 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02181 0.00031 0.00079 0.02289 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
9.57
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.54

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.514 / 17.699 Load End: 25.770 / 16.921
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 984.33 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 7 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB5-2-SM04 SMDB-9B


Connection From: TO-8 To: SMDB-9B
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 408.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 408.7
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 408.7 / 1.00 408.7 / 1.00 408.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.10 / 0.04 0.10 / 0.04 0.10 / 0.04 -----
Voltage Drop - From Source (V/%) 3.14 / 1.43 3.14 / 1.43 3.14 / 1.43 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02213 0.00031 0.00079 0.02321 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
9.44
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.45

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.215 / 17.351 Load End: 25.485 / 16.598
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.06 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 8 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.1-SM01 6.1 AHU SUPPLY FAN


Connection From: Starter-1 To: 6.1 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-6.1
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.07 / 3.69 8.07 / 3.69 8.07 / 3.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12866 0.04157 0.04230 0.20994 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.04
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.372 / 2.196 Load End: 3.039 / 1.353
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 55.73 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 9 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.1-SM02 6.1 AHU HEATER BATTERY


Connection From: MCC-6.1/2/L1,L2,L3 To: 6.1 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.07 / 3.69 8.07 / 3.69 8.07 / 3.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12866 0.02309 0.02320 0.17322 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.26
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.372 / 2.196 Load End: 3.776 / 1.510
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.31 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 10 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.1-SM03 6.1 ELEC HUMIDIFIER


Connection From: MCC-6.1/3/L1,L2,L3 To: 6.1 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 22
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.86 / 0.39 0.86 / 0.39 0.86 / 0.39 -----
Voltage Drop - From Source (V/%) 8.45 / 3.86 8.45 / 3.86 8.45 / 3.86 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12866 0.02040 0.03190 0.17940 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.372 / 2.196 Load End: 3.884 / 1.562
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 39.77 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 11 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.2-SM01 6.2 AHU SUPPLY FAN


Connection From: Starter-1 To: 6.2 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-6.2
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 6.82 / 3.12 6.82 / 3.12 6.82 / 3.12 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11463 0.03464 0.03525 0.18307 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.20
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.406 / 3.103 Load End: 3.961 / 1.822
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 73.32 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 12 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.2-SM02 6.2 AHU HEATER BATTERY


Connection From: MCC-6.2/2/L1,L2,L3 To: 6.2 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.94 / 3.17 6.94 / 3.17 6.94 / 3.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11463 0.02454 0.02465 0.16267 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.35
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.406 / 3.103 Load End: 4.597 / 1.848
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 47.76 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 13 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.2-SM03 6.2 ELEC HUMIDIFIER


Connection From: MCC-6.2/3/L1,L2,L3 To: 6.2 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.02 / 0.46 1.02 / 0.46 1.02 / 0.46 -----
Voltage Drop - From Source (V/%) 7.44 / 3.40 7.44 / 3.40 7.44 / 3.40 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11463 0.02411 0.03770 0.17537 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.25
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.406 / 3.103 Load End: 4.578 / 1.852
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 47.87 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 14 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.3-SM01 6.3 AHU SUPPLY FAN


Connection From: Starter-1 To: 6.3 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-6.3
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.53 / 0.24 0.53 / 0.24 0.53 / 0.24 -----
Voltage Drop - From Source (V/%) 8.12 / 3.71 8.12 / 3.71 8.12 / 3.71 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12866 0.04619 0.04700 0.21910 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.00
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.372 / 2.196 Load End: 2.897 / 1.310
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 54.13 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 15 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.3-SM02 6.3 AHU HEATER BATTERY


Connection From: MCC-6.3/2/L1,L2,L3 To: 6.3 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.54 / 0.25 0.54 / 0.25 0.54 / 0.25 -----
Voltage Drop - From Source (V/%) 8.13 / 3.71 8.13 / 3.71 8.13 / 3.71 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12866 0.02598 0.02610 0.17886 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.372 / 2.196 Load End: 3.638 / 1.453
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 36.72 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 16 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.3-SM03 6.3 ELEC HUMIDIFIER


Connection From: MCC-6.3/3/L1,L2,L3 To: 6.3 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 24
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.94 / 0.43 0.94 / 0.43 0.94 / 0.43 -----
Voltage Drop - From Source (V/%) 8.53 / 3.90 8.53 / 3.90 8.53 / 3.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12866 0.02225 0.03480 0.18406 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.19
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.20

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.372 / 2.196 Load End: 3.788 / 1.522
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.65 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 17 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.4-SM01 6.4 AHU SUPPLY FAN


Connection From: Starter-1 To: 6.4 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-6.4
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.37 / 2.91 6.37 / 2.91 6.37 / 2.91 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12972 0.04388 0.04465 0.21738 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.01
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.515 / 2.684 Load End: 3.284 / 1.524
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.16 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 18 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.4-SM02 6.4 AHU HEATER BATTERY


Connection From: MCC-6.4/2/L1,L2,L3 To: 6.4 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.38 / 2.91 6.38 / 2.91 6.38 / 2.91 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12972 0.02454 0.02465 0.17832 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.515 / 2.684 Load End: 4.217 / 1.687
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.27 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 19 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.4-SM03 6.4 ELEC HUMIDIFIER


Connection From: MCC-6.4/3/L1,L2,L3 To: 6.4 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 6.57 / 3.00 6.57 / 3.00 6.57 / 3.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12972 0.01669 0.02610 0.17212 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.27
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.515 / 2.684 Load End: 4.724 / 1.910
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 49.47 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 20 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.5-SM01 6.5 AHU SUPPLY FAN


Connection From: Starter-1 To: 6.5 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-6.5
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 6.40 / 2.92 6.40 / 2.92 6.40 / 2.92 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13182 0.04157 0.04230 0.21486 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.02
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.418 / 2.641 Load End: 3.346 / 1.536
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.60 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 21 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.5-SM02 6.5 AHU HEATER BATTERY


Connection From: MCC-6.5/2/L1,L2,L3 To: 6.5 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 6.40 / 2.92 6.40 / 2.92 6.40 / 2.92 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13182 0.02309 0.02320 0.17756 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.418 / 2.641 Load End: 4.264 / 1.707
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.83 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 22 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.5-SM03 6.5 ELEC HUMIDIFIER


Connection From: MCC-6.5/3/L1,L2,L3 To: 6.5 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 25
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.98 / 0.45 0.98 / 0.45 0.98 / 0.45 -----
Voltage Drop - From Source (V/%) 6.90 / 3.15 6.90 / 3.15 6.90 / 3.15 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13182 0.02318 0.03625 0.19076 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.15
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.17

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.418 / 2.641 Load End: 4.222 / 1.698
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.58 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 23 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.6-SM01 6.6 AHU SUPPLY FAN


Connection From: Starter-1 To: 6.6 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-6.6
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 6.00 / 2.74 6.00 / 2.74 6.00 / 2.74 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11927 0.03464 0.03525 0.18832 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.16
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.050 / 2.922 Load End: 3.842 / 1.746
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 70.46 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 24 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.6-SM02 6.6 AHU HEATER BATTERY


Connection From: MCC-6.6/2/L1,L2,L3 To: 6.6 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.11 / 2.79 6.11 / 2.79 6.11 / 2.79 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11927 0.02454 0.02465 0.16780 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.31
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.050 / 2.922 Load End: 4.440 / 1.779
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 45.83 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 25 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-6.6-SM03 6.6 ELEC HUMIDIFIER


Connection From: MCC-6.6/3/L1,L2,L3 To: 6.6 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.74 / 0.34 0.74 / 0.34 0.74 / 0.34 -----
Voltage Drop - From Source (V/%) 6.35 / 2.90 6.35 / 2.90 6.35 / 2.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11927 0.01762 0.02755 0.16397 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.34
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.050 / 2.922 Load End: 4.924 / 1.993
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 51.81 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 26 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.1-SM01 7.1 AHU SUPPLY FAN


Connection From: Starter-1 To: 7.1 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-7.1
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.17 / 3.73 8.17 / 3.73 8.17 / 3.73 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12908 0.04157 0.04230 0.21036 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.04
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.358 / 2.190 Load End: 3.034 / 1.350
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 55.62 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 27 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.1-SM02 7.1 AHU HEATER BATTERY


Connection From: MCC-7.1/2/L1,L2,L3 To: 7.1 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.17 / 3.73 8.17 / 3.73 8.17 / 3.73 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12908 0.02309 0.02320 0.17364 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.26
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.358 / 2.190 Load End: 3.769 / 1.507
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.23 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 28 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.1-SM03 7.1 ELEC HUMIDIFIER


Connection From: MCC-7.1/3/L1,L2,L3 To: 7.1 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 22
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.86 / 0.39 0.86 / 0.39 0.86 / 0.39 -----
Voltage Drop - From Source (V/%) 8.55 / 3.90 8.55 / 3.90 8.55 / 3.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12908 0.02040 0.03190 0.17982 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.21

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.358 / 2.190 Load End: 3.877 / 1.559
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 39.68 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 29 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.2-SM01 7.2 AHU SUPPLY FAN


Connection From: Starter-1 To: 7.2 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-7.2
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 6.92 / 3.16 6.92 / 3.16 6.92 / 3.16 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11505 0.03464 0.03525 0.18348 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.19
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.378 / 3.090 Load End: 3.954 / 1.817
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 73.13 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 30 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.2-SM02 7.2 AHU HEATER BATTERY


Connection From: MCC-7.2/2/L1,L2,L3 To: 7.2 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 7.03 / 3.21 7.03 / 3.21 7.03 / 3.21 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11505 0.02454 0.02465 0.16308 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.34
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.378 / 3.090 Load End: 4.587 / 1.844
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 47.64 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 31 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.2-SM03 7.2 ELEC HUMIDIFIER


Connection From: MCC-7.2/3/L1,L2,L3 To: 7.2 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.02 / 0.46 1.02 / 0.46 1.02 / 0.46 -----
Voltage Drop - From Source (V/%) 7.54 / 3.44 7.54 / 3.44 7.54 / 3.44 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11505 0.02411 0.03770 0.17579 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.25
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.378 / 3.090 Load End: 4.568 / 1.848
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 47.74 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 32 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.3-SM01 7.3 AHU SUPPLY FAN


Connection From: Starter-1 To: 7.3 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-7.3
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.53 / 0.24 0.53 / 0.24 0.53 / 0.24 -----
Voltage Drop - From Source (V/%) 8.22 / 3.75 8.22 / 3.75 8.22 / 3.75 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12908 0.04619 0.04700 0.21951 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.00
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.358 / 2.190 Load End: 2.893 / 1.308
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 54.04 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 33 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.3-SM02 7.3 AHU HEATER BATTERY


Connection From: MCC-7.3/2/L1,L2,L3 To: 7.3 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.54 / 0.25 0.54 / 0.25 0.54 / 0.25 -----
Voltage Drop - From Source (V/%) 8.23 / 3.76 8.23 / 3.76 8.23 / 3.76 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12908 0.02598 0.02610 0.17927 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.358 / 2.190 Load End: 3.632 / 1.450
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 36.64 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 34 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.3-SM03 7.3 ELEC HUMIDIFIER


Connection From: MCC-7.3/3/L1,L2,L3 To: 7.3 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 24
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.94 / 0.43 0.94 / 0.43 0.94 / 0.43 -----
Voltage Drop - From Source (V/%) 8.63 / 3.94 8.63 / 3.94 8.63 / 3.94 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12908 0.02225 0.03480 0.18448 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.19
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.20

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.358 / 2.190 Load End: 3.781 / 1.519
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.56 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 35 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.4-SM01 7.4 AHU SUPPLY FAN


Connection From: Starter-1 To: 7.4 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-7.4
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.47 / 2.95 6.47 / 2.95 6.47 / 2.95 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13014 0.04388 0.04465 0.21779 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.01
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.494 / 2.675 Load End: 3.279 / 1.521
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.03 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 36 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.4-SM02 7.4 AHU HEATER BATTERY


Connection From: MCC-7.4/2/L1,L2,L3 To: 7.4 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.47 / 2.96 6.47 / 2.96 6.47 / 2.96 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13014 0.02454 0.02465 0.17873 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.494 / 2.675 Load End: 4.209 / 1.684
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.16 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 37 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.4-SM03 7.4 ELEC HUMIDIFIER


Connection From: MCC-7.4/3/L1,L2,L3 To: 7.4 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 6.67 / 3.04 6.67 / 3.04 6.67 / 3.04 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13014 0.01669 0.02610 0.17254 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.27
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.494 / 2.675 Load End: 4.713 / 1.905
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 49.34 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 38 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.5-SM01 7.5 AHU SUPPLY FAN


Connection From: Starter-1 To: 7.5 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-7.5
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 6.50 / 2.97 6.50 / 2.97 6.50 / 2.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13223 0.04157 0.04230 0.21527 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.02
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.397 / 2.632 Load End: 3.341 / 1.532
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.47 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 39 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.5-SM02 7.5 AHU HEATER BATTERY


Connection From: MCC-7.5/2/L1,L2,L3 To: 7.5 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 6.50 / 2.97 6.50 / 2.97 6.50 / 2.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13223 0.02309 0.02320 0.17797 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.397 / 2.632 Load End: 4.255 / 1.704
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.72 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 40 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.5-SM03 7.5 ELEC HUMIDIFIER


Connection From: MCC-7.5/3/L1,L2,L3 To: 7.5 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 25
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.98 / 0.45 0.98 / 0.45 0.98 / 0.45 -----
Voltage Drop - From Source (V/%) 6.99 / 3.19 6.99 / 3.19 6.99 / 3.19 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13223 0.02318 0.03625 0.19117 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.15
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.17

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.397 / 2.632 Load End: 4.213 / 1.695
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.47 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 41 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.6-SM01 7.6 AHU SUPPLY FAN


Connection From: Starter-1 To: 7.6 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-7.6
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 6.10 / 2.78 6.10 / 2.78 6.10 / 2.78 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11968 0.03464 0.03525 0.18874 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.16
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.025 / 2.910 Load End: 3.834 / 1.741
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 70.28 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 42 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.6-SM02 7.6 AHU HEATER BATTERY


Connection From: MCC-7.6/2/L1,L2,L3 To: 7.6 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.21 / 2.84 6.21 / 2.84 6.21 / 2.84 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11968 0.02454 0.02465 0.16821 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.30
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.025 / 2.910 Load End: 4.431 / 1.775
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 45.71 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 43 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-7.6-SM03 7.6 ELEC HUMIDIFIER


Connection From: MCC-7.6/3/L1,L2,L3 To: 7.6 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.74 / 0.34 0.74 / 0.34 0.74 / 0.34 -----
Voltage Drop - From Source (V/%) 6.44 / 2.94 6.44 / 2.94 6.44 / 2.94 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11968 0.01762 0.02755 0.16439 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.33
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.025 / 2.910 Load End: 4.912 / 1.988
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 51.67 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 44 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.1-SM01 8.1 AHU SUPPLY FAN


Connection From: Starter-1 To: 8.1 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-8.1
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.23 / 3.76 8.23 / 3.76 8.23 / 3.76 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12950 0.04157 0.04230 0.21077 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.04
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.343 / 2.184 Load End: 3.030 / 1.347
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 55.52 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 45 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.1-SM02 8.1 AHU HEATER BATTERY


Connection From: MCC-8.1/2/L1,L2,L3 To: 8.1 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.24 / 3.76 8.24 / 3.76 8.24 / 3.76 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12950 0.02309 0.02320 0.17406 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.26
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.343 / 2.184 Load End: 3.762 / 1.504
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.15 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 46 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.1-SM03 8.1 ELEC HUMIDIFIER


Connection From: MCC-8.1/3/L1,L2,L3 To: 8.1 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 22
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.86 / 0.39 0.86 / 0.39 0.86 / 0.39 -----
Voltage Drop - From Source (V/%) 8.61 / 3.93 8.61 / 3.93 8.61 / 3.93 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12950 0.02040 0.03190 0.18024 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.21

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.343 / 2.184 Load End: 3.869 / 1.556
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 39.59 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 47 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.2-SM01 8.2 AHU SUPPLY FAN


Connection From: Starter-1 To: 8.2 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-8.2
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 6.99 / 3.19 6.99 / 3.19 6.99 / 3.19 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11547 0.03464 0.03525 0.18390 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.19
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.350 / 3.077 Load End: 3.946 / 1.812
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 72.95 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 48 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.2-SM02 8.2 AHU HEATER BATTERY


Connection From: MCC-8.2/2/L1,L2,L3 To: 8.2 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 7.10 / 3.24 7.10 / 3.24 7.10 / 3.24 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11547 0.02454 0.02465 0.16350 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.34
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.350 / 3.077 Load End: 4.576 / 1.839
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 47.51 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 49 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.2-SM03 8.2 ELEC HUMIDIFIER


Connection From: MCC-8.2/3/L1,L2,L3 To: 8.2 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.02 / 0.46 1.02 / 0.46 1.02 / 0.46 -----
Voltage Drop - From Source (V/%) 7.60 / 3.47 7.60 / 3.47 7.60 / 3.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11547 0.02411 0.03770 0.17620 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.24
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.350 / 3.077 Load End: 4.557 / 1.843
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 47.62 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 50 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.3-SM01 8.3 AHU SUPPLY FAN


Connection From: Starter-1 To: 8.3 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-8.3
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.53 / 0.24 0.53 / 0.24 0.53 / 0.24 -----
Voltage Drop - From Source (V/%) 8.29 / 3.78 8.29 / 3.78 8.29 / 3.78 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12950 0.04619 0.04700 0.21993 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.00
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.343 / 2.184 Load End: 2.889 / 1.305
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.94 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 51 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.3-SM02 8.3 AHU HEATER BATTERY


Connection From: MCC-8.3/2/L1,L2,L3 To: 8.3 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.54 / 0.25 0.54 / 0.25 0.54 / 0.25 -----
Voltage Drop - From Source (V/%) 8.30 / 3.79 8.30 / 3.79 8.30 / 3.79 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12950 0.02598 0.02610 0.17969 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.21

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.343 / 2.184 Load End: 3.625 / 1.448
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 36.56 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 52 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.3-SM03 8.3 ELEC HUMIDIFIER


Connection From: MCC-8.3/3/L1,L2,L3 To: 8.3 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 24
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.94 / 0.43 0.94 / 0.43 0.94 / 0.43 -----
Voltage Drop - From Source (V/%) 8.69 / 3.97 8.69 / 3.97 8.69 / 3.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12950 0.02225 0.03480 0.18489 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.18
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.20

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.343 / 2.184 Load End: 3.774 / 1.516
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.48 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 53 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.4-SM01 8.4 AHU SUPPLY FAN


Connection From: Starter-1 To: 8.4 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-8.4
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.53 / 2.98 6.53 / 2.98 6.53 / 2.98 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13055 0.04388 0.04465 0.21820 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.00
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.472 / 2.665 Load End: 3.273 / 1.517
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 61.90 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 54 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.4-SM02 8.4 AHU HEATER BATTERY


Connection From: MCC-8.4/2/L1,L2,L3 To: 8.4 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.54 / 2.98 6.54 / 2.98 6.54 / 2.98 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13055 0.02454 0.02465 0.17914 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.472 / 2.665 Load End: 4.200 / 1.680
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.06 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 55 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.4-SM03 8.4 ELEC HUMIDIFIER


Connection From: MCC-8.4/3/L1,L2,L3 To: 8.4 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 6.73 / 3.07 6.73 / 3.07 6.73 / 3.07 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13055 0.01669 0.02610 0.17295 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.27
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.472 / 2.665 Load End: 4.702 / 1.900
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 49.20 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 56 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.5-SM01 8.5 AHU SUPPLY FAN


Connection From: Starter-1 To: 8.5 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-8.5
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 6.56 / 2.99 6.56 / 2.99 6.56 / 2.99 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13264 0.04157 0.04230 0.21568 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.02
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.376 / 2.623 Load End: 3.336 / 1.529
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.33 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 57 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.5-SM02 8.5 AHU HEATER BATTERY


Connection From: MCC-8.5/2/L1,L2,L3 To: 8.5 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 6.56 / 3.00 6.56 / 3.00 6.56 / 3.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13264 0.02309 0.02320 0.17838 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.23
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.376 / 2.623 Load End: 4.247 / 1.700
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.61 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 58 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.5-SM03 8.5 ELEC HUMIDIFIER


Connection From: MCC-8.5/3/L1,L2,L3 To: 8.5 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 25
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.98 / 0.45 0.98 / 0.45 0.98 / 0.45 -----
Voltage Drop - From Source (V/%) 7.06 / 3.22 7.06 / 3.22 7.06 / 3.22 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13264 0.02318 0.03625 0.19158 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.14
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.17

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.376 / 2.623 Load End: 4.204 / 1.691
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.36 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 59 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.6-SM01 8.6 AHU SUPPLY FAN


Connection From: Starter-1 To: 8.6 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-8.6
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 6.16 / 2.81 6.16 / 2.81 6.16 / 2.81 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12010 0.03464 0.03525 0.18914 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.16
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.000 / 2.899 Load End: 3.827 / 1.736
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 70.11 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 60 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.6-SM02 8.6 AHU HEATER BATTERY


Connection From: MCC-8.6/2/L1,L2,L3 To: 8.6 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.27 / 2.86 6.27 / 2.86 6.27 / 2.86 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12010 0.02454 0.02465 0.16862 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.30
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.000 / 2.899 Load End: 4.421 / 1.771
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 45.60 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 61 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-8.6-SM03 8.6 ELEC HUMIDIFIER


Connection From: MCC-8.6/3/L1,L2,L3 To: 8.6 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.74 / 0.34 0.74 / 0.34 0.74 / 0.34 -----
Voltage Drop - From Source (V/%) 6.50 / 2.97 6.50 / 2.97 6.50 / 2.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12010 0.01762 0.02755 0.16480 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.33
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.000 / 2.899 Load End: 4.900 / 1.983
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 51.52 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 62 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.1-SM01 9.1 AHU SUPPLY FAN


Connection From: Starter-1 To: 9.1 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-9.1
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.26 / 3.77 8.26 / 3.77 8.26 / 3.77 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12992 0.04157 0.04230 0.21119 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.04
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.329 / 2.177 Load End: 3.025 / 1.344
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 55.42 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 63 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.1-SM02 9.1 AHU HEATER BATTERY


Connection From: MCC-9.1/2/L1,L2,L3 To: 9.1 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 8.27 / 3.77 8.27 / 3.77 8.27 / 3.77 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12992 0.02309 0.02320 0.17447 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.26
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.329 / 2.177 Load End: 3.755 / 1.501
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.06 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 64 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.1-SM03 9.1 ELEC HUMIDIFIER


Connection From: MCC-9.1/3/L1,L2,L3 To: 9.1 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 22
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.86 / 0.39 0.86 / 0.39 0.86 / 0.39 -----
Voltage Drop - From Source (V/%) 8.65 / 3.95 8.65 / 3.95 8.65 / 3.95 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12992 0.02040 0.03190 0.18065 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.21
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.21

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.329 / 2.177 Load End: 3.862 / 1.553
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 39.50 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 65 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.2-SM01 9.2 AHU SUPPLY FAN


Connection From: Starter-1 To: 9.2 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-9.2
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 7.02 / 3.20 7.02 / 3.20 7.02 / 3.20 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11588 0.03464 0.03525 0.18431 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.19
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.322 / 3.064 Load End: 3.938 / 1.807
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 72.76 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 66 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.2-SM02 9.2 AHU HEATER BATTERY


Connection From: MCC-9.2/2/L1,L2,L3 To: 9.2 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 7.13 / 3.26 7.13 / 3.26 7.13 / 3.26 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11588 0.02454 0.02465 0.16391 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.34
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.28

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.322 / 3.064 Load End: 4.566 / 1.835
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 47.39 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 67 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.2-SM03 9.2 ELEC HUMIDIFIER


Connection From: MCC-9.2/3/L1,L2,L3 To: 9.2 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.02 / 0.46 1.02 / 0.46 1.02 / 0.46 -----
Voltage Drop - From Source (V/%) 7.63 / 3.49 7.63 / 3.49 7.63 / 3.49 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.11588 0.02411 0.03770 0.17661 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.24
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.23

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 7.322 / 3.064 Load End: 4.547 / 1.839
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 47.49 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 68 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.3-SM01 9.3 AHU SUPPLY FAN


Connection From: Starter-1 To: 9.3 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-9.3
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.53 / 0.24 0.53 / 0.24 0.53 / 0.24 -----
Voltage Drop - From Source (V/%) 8.32 / 3.80 8.32 / 3.80 8.32 / 3.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12992 0.04619 0.04700 0.22034 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.99
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.329 / 2.177 Load End: 2.885 / 1.302
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.84 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 69 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.3-SM02 9.3 AHU HEATER BATTERY


Connection From: MCC-9.3/2/L1,L2,L3 To: 9.3 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.54 / 0.25 0.54 / 0.25 0.54 / 0.25 -----
Voltage Drop - From Source (V/%) 8.33 / 3.80 8.33 / 3.80 8.33 / 3.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12992 0.02598 0.02610 0.18010 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.21

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.329 / 2.177 Load End: 3.619 / 1.445
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 36.49 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 70 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.3-SM03 9.3 ELEC HUMIDIFIER


Connection From: MCC-9.3/3/L1,L2,L3 To: 9.3 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 24
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.94 / 0.43 0.94 / 0.43 0.94 / 0.43 -----
Voltage Drop - From Source (V/%) 8.72 / 3.98 8.72 / 3.98 8.72 / 3.98 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12992 0.02225 0.03480 0.18531 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.18
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.19

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.329 / 2.177 Load End: 3.767 / 1.513
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 38.39 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 71 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.4-SM01 9.4 AHU SUPPLY FAN


Connection From: Starter-1 To: 9.4 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-9.4
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.56 / 3.00 6.56 / 3.00 6.56 / 3.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13096 0.04388 0.04465 0.21861 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.00
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.451 / 2.656 Load End: 3.268 / 1.514
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 61.77 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 72 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.4-SM02 9.4 AHU HEATER BATTERY


Connection From: MCC-9.4/2/L1,L2,L3 To: 9.4 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.57 / 3.00 6.57 / 3.00 6.57 / 3.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13096 0.02454 0.02465 0.17955 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.451 / 2.656 Load End: 4.191 / 1.676
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 42.96 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 73 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.4-SM03 9.4 ELEC HUMIDIFIER


Connection From: MCC-9.4/3/L1,L2,L3 To: 9.4 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 6.76 / 3.09 6.76 / 3.09 6.76 / 3.09 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13096 0.01669 0.02610 0.17336 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.26
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.24

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.451 / 2.656 Load End: 4.691 / 1.895
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 49.07 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 74 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.5-SM01 9.5 AHU SUPPLY FAN


Connection From: Starter-1 To: 9.5 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-9.5
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 18
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 6.59 / 3.01 6.59 / 3.01 6.59 / 3.01 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13306 0.04157 0.04230 0.21609 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.01
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.355 / 2.614 Load End: 3.330 / 1.525
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.20 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 75 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.5-SM02 9.5 AHU HEATER BATTERY


Connection From: MCC-9.5/2/L1,L2,L3 To: 9.5 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 16
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.48 / 0.22 0.48 / 0.22 0.48 / 0.22 -----
Voltage Drop - From Source (V/%) 6.59 / 3.01 6.59 / 3.01 6.59 / 3.01 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13306 0.02309 0.02320 0.17879 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.22

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.355 / 2.614 Load End: 4.238 / 1.696
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.51 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 76 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.5-SM03 9.5 ELEC HUMIDIFIER


Connection From: MCC-9.5/3/L1,L2,L3 To: 9.5 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 25
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.98 / 0.45 0.98 / 0.45 0.98 / 0.45 -----
Voltage Drop - From Source (V/%) 7.09 / 3.24 7.09 / 3.24 7.09 / 3.24 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.13306 0.02318 0.03625 0.19199 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.14
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.17

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.355 / 2.614 Load End: 4.196 / 1.687
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.26 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 77 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.6-SM01 9.6 AHU SUPPLY FAN


Connection From: Starter-1 To: 9.6 AHU SUPPLY FAN
Active Source: Tx 5
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.5
Motor Starter Position: at MCC-9.6
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 14.54 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 15
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 14.5
Device Rating In = 20 Motor Overload Setting Ir = 14.54 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.5 / 0.87 14.5 / 0.87 14.5 / 0.87 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.40 / 0.18 0.40 / 0.18 0.40 / 0.18 -----
Voltage Drop - From Source (V/%) 6.19 / 2.83 6.19 / 2.83 6.19 / 2.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12051 0.03464 0.03525 0.18955 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.16
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.975 / 2.888 Load End: 3.820 / 1.732
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 69.94 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 78 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.6-SM02 9.6 AHU HEATER BATTERY


Connection From: MCC-9.6/2/L1,L2,L3 To: 9.6 AHU HEATER BATTERY
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 22.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):32 [f] Overload Setting Ir (A): 32 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm²[a] Length (m): 17
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 22.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 38.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 22.8 / 1.00 22.8 / 1.00 22.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.23 0.51 / 0.23 0.51 / 0.23 -----
Voltage Drop - From Source (V/%) 6.30 / 2.88 6.30 / 2.88 6.30 / 2.88 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12051 0.02454 0.02465 0.16903 0.45626 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.30
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.26

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.975 / 2.888 Load End: 4.411 / 1.767
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 45.48 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 79 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-9.6-SM03 9.6 ELEC HUMIDIFIER


Connection From: MCC-9.6/3/L1,L2,L3 To: 9.6 ELEC HUMIDIFIER
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 45.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):50 [f] Overload Setting Ir (A): 50 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 19
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.6
Device Rating In = 50 Overload Setting Ir = 50 [Ir >
_ Ib]
Min. Cable Capacity Iz = 63.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.6 / 1.00 45.6 / 1.00 45.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.74 / 0.34 0.74 / 0.34 0.74 / 0.34 -----
Voltage Drop - From Source (V/%) 6.53 / 2.98 6.53 / 2.98 6.53 / 2.98 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.12051 0.01762 0.02755 0.16521 0.55369 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.33
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.27

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 6.975 / 2.888 Load End: 4.888 / 1.978
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 51.38 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 80 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-5-SM01 OFFICE LIFT


Connection From: MDB 5 To: OFFICE LIFT
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 158
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.66 / 2.13 4.66 / 2.13 4.66 / 2.13 -----
Voltage Drop - From Source (V/%) 5.41 / 2.47 5.41 / 2.47 5.41 / 2.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01052 0.14651 0.22910 0.37838 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.58
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.83

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 35.973 / 29.944 Load End: 1.879 / 0.742
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 16.84 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 81 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-5-SM02 OFFICE LIFT


Connection From: MDB 5 To: OFFICE LIFT
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 160
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.72 / 2.16 4.72 / 2.16 4.72 / 2.16 -----
Voltage Drop - From Source (V/%) 5.47 / 2.50 5.47 / 2.50 5.47 / 2.50 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01052 0.14837 0.23200 0.38313 0.58564 Current (kA)

Disconnection time (s): From characteristic: 3.42 Maximum for circuit: 5.00
0.57
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 7.39

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 35.973 / 29.944 Load End: 1.856 / 0.732
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 16.58 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 82 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-5-SM03 OFFICE LIFT


Connection From: MDB 5 To: OFFICE LIFT
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 159
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.69 / 2.14 4.69 / 2.14 4.69 / 2.14 -----
Voltage Drop - From Source (V/%) 5.44 / 2.49 5.44 / 2.49 5.44 / 2.49 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01052 0.14744 0.23055 0.38076 0.58564 Current (kA)

Disconnection time (s): From characteristic: 3.41 Maximum for circuit: 5.00
0.58
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 7.43

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 35.973 / 29.944 Load End: 1.868 / 0.737
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 16.71 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 83 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-5-SM04 OFFICE LIFT


Connection From: MDB 5 To: OFFICE LIFT
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 162
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.42 / 1.56 3.42 / 1.56 3.42 / 1.56 -----
Voltage Drop - From Source (V/%) 4.17 / 1.90 4.17 / 1.90 4.17 / 1.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01052 0.10830 0.23490 0.34585 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.63
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.83

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 35.973 / 29.944 Load End: 2.515 / 0.999
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 24.04 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 84 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-5-SM05 BB-MDB5-1


Connection From: MDB 5 To: EF-1
Active Source: Tx 5
Load Type: Busbar EndFeed Design Current Ib (A): 1,180.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW16 H1 MLogic 5.0A High
Rating In (A):1600 [f] Overload Setting Ir (A): 1600 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 93
31 - On horizontal/vertical perforated tray Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.87 [BS 7671, Table 4C5]
No. of trays = 2 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,180.0
Device Rating In = 1600 Overload Setting Ir = 1600 [Ir >
_ Ib]
Min. Cable Capacity Iz = 528.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 736.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1180.0 / 1.00 1180.0 / 1.00 1180.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.10 / 0.96 2.10 / 0.96 2.10 / 0.96 -----
Voltage Drop - From Source (V/%) 2.85 / 1.30 2.85 / 1.30 2.85 / 1.30 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01052 0.00281 0.01368 0.02664 0.04148 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
8.22
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 21.51

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 35.973 / 29.944 Load End: 25.699 / 17.421
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 173.06 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 85 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-5-SM06 BB-MDB5-2


Connection From: MDB 5 To: EF-2
Active Source: Tx 5
Load Type: Busbar EndFeed Design Current Ib (A): 1,144.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW16 H1 MLogic 5.0A High
Rating In (A):1600 [f] Overload Setting Ir (A): 1600 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 48
31 - On horizontal/vertical perforated tray Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.87 [BS 7671, Table 4C5]
No. of trays = 2 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,144.2
Device Rating In = 1600 Overload Setting Ir = 1600 [Ir >
_ Ib]
Min. Cable Capacity Iz = 528.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 736.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1144.2 / 1.00 1144.2 / 1.00 1144.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.05 / 0.48 1.05 / 0.48 1.05 / 0.48 -----
Voltage Drop - From Source (V/%) 1.80 / 0.82 1.80 / 0.82 1.80 / 0.82 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01052 0.00145 0.00706 0.01876 0.04148 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
11.67
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 91.99

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 35.973 / 29.944 Load End: 29.866 / 21.948
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 192.90 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 86 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-5-SM07 OFFICE LIFT


Connection From: MDB 5 To: OFFICE LIFT
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 115
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.39 / 1.55 3.39 / 1.55 3.39 / 1.55 -----
Voltage Drop - From Source (V/%) 4.15 / 1.89 4.15 / 1.89 4.15 / 1.89 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01052 0.10664 0.16675 0.27630 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.79
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.95

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 35.973 / 29.944 Load End: 2.564 / 1.016
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 24.50 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 87 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-5-SM08 OFFICE LIFT


Connection From: MDB 5 To: OFFICE LIFT
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 119
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.51 / 1.60 3.51 / 1.60 3.51 / 1.60 -----
Voltage Drop - From Source (V/%) 4.26 / 1.95 4.26 / 1.95 4.26 / 1.95 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01052 0.11035 0.17255 0.28580 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.77
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.93

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 35.973 / 29.944 Load End: 2.480 / 0.982
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 23.55 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 88 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6A-SM01 DB-6PA


Connection From: SMDB-6A/1/L1,L2,L3 To: DB-6PA
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 4.15 / 1.90 4.15 / 1.90 4.15 / 1.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03022 0.00251 0.00468 0.03527 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.21
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.59

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.994 / 14.476 Load End: 20.393 / 11.650
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 419.80 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 89 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6A-SM02 DB-6LA


Connection From: SMDB-6A/2/L1,L2,L3 To: DB-6LA
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 4.10 / 1.87 4.10 / 1.87 4.10 / 1.87 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03022 0.00334 0.00725 0.03710 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.90
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.46

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.994 / 14.476 Load End: 19.750 / 10.957
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 412.44 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 90 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6A-SM03 OFFICE 6.1


Connection From: SMDB-6A/3/L1,L2,L3 To: OFFICE 6.1
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 30.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 30.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.9 / 1.00 30.9 / 1.00 30.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.63 / 0.29 0.63 / 0.29 0.63 / 0.29 -----
Voltage Drop - From Source (V/%) 4.66 / 2.13 4.66 / 2.13 4.66 / 2.13 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03022 0.02211 0.04116 0.08588 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.55
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.13

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.994 / 14.476 Load End: 9.133 / 3.960
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 177.61 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 91 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6A-SM04 OFFICE 6.2


Connection From: SMDB-6A/4/L1,L2,L3 To: OFFICE 6.2
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 41.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 41.6
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 147.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 41.6 / 1.00 41.6 / 1.00 41.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.64 / 0.29 0.64 / 0.29 0.64 / 0.29 -----
Voltage Drop - From Source (V/%) 4.67 / 2.13 4.67 / 2.13 4.67 / 2.13 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03022 0.01659 0.03087 0.07077 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.09
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.48

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.994 / 14.476 Load End: 10.987 / 4.917
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 234.99 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 92 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6A-SM05 OFFICE 6.3


Connection From: SMDB-6A/5/L1,L2,L3 To: OFFICE 6.3
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.4 / 1.00 35.4 / 1.00 35.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 4.74 / 2.17 4.74 / 2.17 4.74 / 2.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03022 0.02161 0.04023 0.08449 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.59
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.16

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.994 / 14.476 Load End: 9.277 / 4.032
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 181.91 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 93 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6A-SM06 MCC-6.1


Connection From: SMDB-6A/6/L1,L2,L3 To: MCC-6.1
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.59 / 3.47 7.59 / 3.47 7.59 / 3.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03022 0.04479 0.06268 0.12866 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.70
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.994 / 14.476 Load End: 5.372 / 2.196
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 148.97 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 94 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6A-SM07 MCC-6.2


Connection From: SMDB-6A/7/L1,L2,L3 To: MCC-6.2
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.39 / 1.09 2.39 / 1.09 2.39 / 1.09 -----
Voltage Drop - From Source (V/%) 6.42 / 2.93 6.42 / 2.93 6.42 / 2.93 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03022 0.03008 0.06525 0.11463 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.91
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.994 / 14.476 Load End: 7.406 / 3.103
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 162.44 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 95 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6A-SM08 MCC-6.3


Connection From: SMDB-6A/8/L1,L2,L3 To: MCC-6.3
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.59 / 3.47 7.59 / 3.47 7.59 / 3.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03022 0.04479 0.06268 0.12866 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.70
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.994 / 14.476 Load End: 5.372 / 2.196
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 148.97 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 96 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6B-SM01 DB-6PB


Connection From: SMDB-6B/1/L1,L2,L3 To: DB-6PB
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 3.07 / 1.40 3.07 / 1.40 3.07 / 1.40 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02225 0.00251 0.00468 0.02738 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
8.00
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 4.00

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.356 / 17.600 Load End: 23.058 / 13.617
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 443.41 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 97 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6B-SM02 DB-6LB


Connection From: SMDB-6B/2/L1,L2,L3 To: DB-6LB
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 3.01 / 1.38 3.01 / 1.38 3.01 / 1.38 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02225 0.00334 0.00725 0.02935 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.46
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.86

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.356 / 17.600 Load End: 22.242 / 12.667
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 434.67 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 98 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6B-SM03 OFFICE 6.4


Connection From: SMDB-6B/3/L1,L2,L3 To: OFFICE 6.4
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 25.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 25.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 25.0 / 1.00 25.0 / 1.00 25.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.45 / 0.21 0.45 / 0.21 0.45 / 0.21 -----
Voltage Drop - From Source (V/%) 3.40 / 1.55 3.40 / 1.55 3.40 / 1.55 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02225 0.01960 0.03649 0.07226 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.03
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.44

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.356 / 17.600 Load End: 10.429 / 4.562
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 213.73 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 99 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6B-SM04 OFFICE 6.5


Connection From: SMDB-6B/4/L1,L2,L3 To: OFFICE 6.5
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 34.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.4 / 1.00 34.4 / 1.00 34.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 3.70 / 1.69 3.70 / 1.69 3.70 / 1.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02225 0.02362 0.04397 0.08348 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.62
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.18

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.356 / 17.600 Load End: 9.126 / 3.917
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 175.05 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 100 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6B-SM05 OFFICE 6.6


Connection From: SMDB-6B/5/L1,L2,L3 To: OFFICE 6.6
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.7
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.7 / 1.00 35.7 / 1.00 35.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.56 / 0.26 0.56 / 0.26 0.56 / 0.26 -----
Voltage Drop - From Source (V/%) 3.51 / 1.60 3.51 / 1.60 3.51 / 1.60 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02225 0.01709 0.03181 0.06530 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.35
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.63

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.356 / 17.600 Load End: 11.435 / 5.082
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 244.92 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 101 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6B-SM06 MCC-6.4


Connection From: SMDB-6B/6/L1,L2,L3 To: MCC-6.4
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.92 / 1.33 2.92 / 1.33 2.92 / 1.33 -----
Voltage Drop - From Source (V/%) 5.87 / 2.68 5.87 / 2.68 5.87 / 2.68 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02225 0.03677 0.07975 0.12972 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.69
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.356 / 17.600 Load End: 6.515 / 2.684
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.63 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 102 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6B-SM07 MCC-6.5


Connection From: SMDB-6B/7/L1,L2,L3 To: MCC-6.5
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 56
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.97 / 1.36 2.97 / 1.36 2.97 / 1.36 -----
Voltage Drop - From Source (V/%) 5.92 / 2.70 5.92 / 2.70 5.92 / 2.70 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02225 0.03744 0.08120 0.13182 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.66
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.356 / 17.600 Load End: 6.418 / 2.641
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.31 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 103 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-6B-SM08 MCC-6.6


Connection From: SMDB-6B/8/L1,L2,L3 To: MCC-6.6
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.65 / 1.21 2.65 / 1.21 2.65 / 1.21 -----
Voltage Drop - From Source (V/%) 5.60 / 2.56 5.60 / 2.56 5.60 / 2.56 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02225 0.03343 0.07250 0.11927 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.84
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.356 / 17.600 Load End: 7.050 / 2.922
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 154.41 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 104 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7A-SM01 DB-7PA


Connection From: SMDB-7A/1/L1,L2,L3 To: DB-7PA
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 4.25 / 1.94 4.25 / 1.94 4.25 / 1.94 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03054 0.00251 0.00468 0.03563 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.15
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.57

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.765 / 14.237 Load End: 20.196 / 11.479
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 417.74 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 105 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7A-SM02 DB-7LA


Connection From: SMDB-7A/2/L1,L2,L3 To: DB-7LA
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 4.20 / 1.92 4.20 / 1.92 4.20 / 1.92 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03054 0.00334 0.00725 0.03748 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.84
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.44

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.765 / 14.237 Load End: 19.562 / 10.802
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 410.42 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 106 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7A-SM03 OFFICE 7.1


Connection From: SMDB-7A/3/L1,L2,L3 To: OFFICE 7.1
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 30.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 30.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.9 / 1.00 30.9 / 1.00 30.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.63 / 0.29 0.63 / 0.29 0.63 / 0.29 -----
Voltage Drop - From Source (V/%) 4.76 / 2.17 4.76 / 2.17 4.76 / 2.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03054 0.02211 0.04116 0.08629 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.54
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.12

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.765 / 14.237 Load End: 9.089 / 3.939
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 176.33 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 107 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7A-SM04 OFFICE 7.2


Connection From: SMDB-7A/4/L1,L2,L3 To: OFFICE 7.2
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 41.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 41.6
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 147.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 41.6 / 1.00 41.6 / 1.00 41.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.64 / 0.29 0.64 / 0.29 0.64 / 0.29 -----
Voltage Drop - From Source (V/%) 4.77 / 2.18 4.77 / 2.18 4.77 / 2.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03054 0.01659 0.03087 0.07118 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.08
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.47

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.765 / 14.237 Load End: 10.924 / 4.884
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 233.02 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 108 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7A-SM05 OFFICE 7.3


Connection From: SMDB-7A/5/L1,L2,L3 To: OFFICE 7.3
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.4 / 1.00 35.4 / 1.00 35.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 4.84 / 2.21 4.84 / 2.21 4.84 / 2.21 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03054 0.02161 0.04023 0.08491 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.58
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.15

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.765 / 14.237 Load End: 9.232 / 4.010
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 180.58 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 109 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7A-SM06 MCC-7.1


Connection From: SMDB-7A/6/L1,L2,L3 To: MCC-7.1
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.69 / 3.51 7.69 / 3.51 7.69 / 3.51 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03054 0.04479 0.06268 0.12908 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.70
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.765 / 14.237 Load End: 5.358 / 2.190
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 148.93 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 110 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7A-SM07 MCC-7.2


Connection From: SMDB-7A/7/L1,L2,L3 To: MCC-7.2
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.39 / 1.09 2.39 / 1.09 2.39 / 1.09 -----
Voltage Drop - From Source (V/%) 6.52 / 2.98 6.52 / 2.98 6.52 / 2.98 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03054 0.03008 0.06525 0.11505 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.90
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.765 / 14.237 Load End: 7.378 / 3.090
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 161.50 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 111 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7A-SM08 MCC-7.3


Connection From: SMDB-7A/8/L1,L2,L3 To: MCC-7.3
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.69 / 3.51 7.69 / 3.51 7.69 / 3.51 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03054 0.04479 0.06268 0.12908 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.70
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.765 / 14.237 Load End: 5.358 / 2.190
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 148.93 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 112 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7B-SM01 DB-7PB


Connection From: SMDB-7B/1/L1,L2,L3 To: DB-7PB
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 3.16 / 1.44 3.16 / 1.44 3.16 / 1.44 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02257 0.00251 0.00468 0.02774 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
7.89
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.98

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.061 / 17.255 Load End: 22.807 / 13.383
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 440.59 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 113 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7B-SM02 DB-7LB


Connection From: SMDB-7B/2/L1,L2,L3 To: DB-7LB
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 3.11 / 1.42 3.11 / 1.42 3.11 / 1.42 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02257 0.00334 0.00725 0.02973 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.37
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.84

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.061 / 17.255 Load End: 22.004 / 12.460
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 431.97 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 114 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7B-SM03 OFFICE 7.4


Connection From: SMDB-7B/3/L1,L2,L3 To: OFFICE 7.4
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 25.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 25.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 25.0 / 1.00 25.0 / 1.00 25.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.45 / 0.21 0.45 / 0.21 0.45 / 0.21 -----
Voltage Drop - From Source (V/%) 3.49 / 1.60 3.49 / 1.60 3.49 / 1.60 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02257 0.01960 0.03649 0.07268 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.01
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.43

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.061 / 17.255 Load End: 10.372 / 4.534
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 212.03 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 115 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7B-SM04 OFFICE 7.5


Connection From: SMDB-7B/4/L1,L2,L3 To: OFFICE 7.5
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 34.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.4 / 1.00 34.4 / 1.00 34.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 3.79 / 1.73 3.79 / 1.73 3.79 / 1.73 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02257 0.02362 0.04397 0.08390 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.61
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.17

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.061 / 17.255 Load End: 9.082 / 3.897
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 173.80 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 116 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7B-SM05 OFFICE 7.6


Connection From: SMDB-7B/5/L1,L2,L3 To: OFFICE 7.6
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.7
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.7 / 1.00 35.7 / 1.00 35.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.56 / 0.26 0.56 / 0.26 0.56 / 0.26 -----
Voltage Drop - From Source (V/%) 3.61 / 1.65 3.61 / 1.65 3.61 / 1.65 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02257 0.01709 0.03181 0.06572 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.33
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.62

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.061 / 17.255 Load End: 11.367 / 5.047
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 242.82 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 117 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7B-SM06 MCC-7.4


Connection From: SMDB-7B/6/L1,L2,L3 To: MCC-7.4
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.92 / 1.33 2.92 / 1.33 2.92 / 1.33 -----
Voltage Drop - From Source (V/%) 5.96 / 2.72 5.96 / 2.72 5.96 / 2.72 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02257 0.03677 0.07975 0.13014 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.68
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.061 / 17.255 Load End: 6.494 / 2.675
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.56 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 118 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7B-SM07 MCC-7.5


Connection From: SMDB-7B/7/L1,L2,L3 To: MCC-7.5
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 56
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.97 / 1.36 2.97 / 1.36 2.97 / 1.36 -----
Voltage Drop - From Source (V/%) 6.02 / 2.75 6.02 / 2.75 6.02 / 2.75 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02257 0.03744 0.08120 0.13223 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.66
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.061 / 17.255 Load End: 6.397 / 2.632
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.24 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 119 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-7B-SM08 MCC-7.6


Connection From: SMDB-7B/8/L1,L2,L3 To: MCC-7.6
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.65 / 1.21 2.65 / 1.21 2.65 / 1.21 -----
Voltage Drop - From Source (V/%) 5.70 / 2.60 5.70 / 2.60 5.70 / 2.60 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02257 0.03343 0.07250 0.11968 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.83
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.061 / 17.255 Load End: 7.025 / 2.910
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 154.33 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 120 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8A-SM01 DB-8PA


Connection From: SMDB-8A/1/L1,L2,L3 To: DB-8PA
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 4.32 / 1.97 4.32 / 1.97 4.32 / 1.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03086 0.00251 0.00468 0.03598 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.09
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.56

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.539 / 14.005 Load End: 20.003 / 11.312
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 415.75 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 121 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8A-SM02 DB-8LA


Connection From: SMDB-8A/2/L1,L2,L3 To: DB-8LA
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 4.26 / 1.95 4.26 / 1.95 4.26 / 1.95 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03086 0.00334 0.00725 0.03785 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.79
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.41

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.539 / 14.005 Load End: 19.377 / 10.652
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 408.47 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 122 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8A-SM03 OFFICE 8.1


Connection From: SMDB-8A/3/L1,L2,L3 To: OFFICE 8.1
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 30.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 30.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.9 / 1.00 30.9 / 1.00 30.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.63 / 0.29 0.63 / 0.29 0.63 / 0.29 -----
Voltage Drop - From Source (V/%) 4.83 / 2.20 4.83 / 2.20 4.83 / 2.20 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03086 0.02211 0.04116 0.08671 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.53
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.12

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.539 / 14.005 Load End: 9.046 / 3.918
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 175.07 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 123 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8A-SM04 OFFICE 8.2


Connection From: SMDB-8A/4/L1,L2,L3 To: OFFICE 8.2
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 41.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 41.6
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 147.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 41.6 / 1.00 41.6 / 1.00 41.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.64 / 0.29 0.64 / 0.29 0.64 / 0.29 -----
Voltage Drop - From Source (V/%) 4.84 / 2.21 4.84 / 2.21 4.84 / 2.21 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03086 0.01659 0.03087 0.07160 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.06
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.46

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.539 / 14.005 Load End: 10.861 / 4.851
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 231.08 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 124 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8A-SM05 OFFICE 8.3


Connection From: SMDB-8A/5/L1,L2,L3 To: OFFICE 8.3
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.4 / 1.00 35.4 / 1.00 35.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 4.90 / 2.24 4.90 / 2.24 4.90 / 2.24 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03086 0.02161 0.04023 0.08532 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.57
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.14

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.539 / 14.005 Load End: 9.187 / 3.988
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 179.28 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 125 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8A-SM06 MCC-8.1


Connection From: SMDB-8A/6/L1,L2,L3 To: MCC-8.1
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.75 / 3.54 7.75 / 3.54 7.75 / 3.54 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03086 0.04479 0.06268 0.12950 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.69
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.539 / 14.005 Load End: 5.343 / 2.184
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 148.88 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 126 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8A-SM07 MCC-8.2


Connection From: SMDB-8A/7/L1,L2,L3 To: MCC-8.2
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.39 / 1.09 2.39 / 1.09 2.39 / 1.09 -----
Voltage Drop - From Source (V/%) 6.59 / 3.01 6.59 / 3.01 6.59 / 3.01 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03086 0.03008 0.06525 0.11547 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.90
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.539 / 14.005 Load End: 7.350 / 3.077
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 160.57 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 127 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8A-SM08 MCC-8.3


Connection From: SMDB-8A/8/L1,L2,L3 To: MCC-8.3
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.75 / 3.54 7.75 / 3.54 7.75 / 3.54 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03086 0.04479 0.06268 0.12950 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.69
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.539 / 14.005 Load End: 5.343 / 2.184
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 148.88 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 128 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8B-SM01 DB-8PB


Connection From: SMDB-8B/1/L1,L2,L3 To: DB-8PB
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 3.22 / 1.47 3.22 / 1.47 3.22 / 1.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02289 0.00251 0.00468 0.02811 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
7.79
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.96

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.770 / 16.921 Load End: 22.562 / 13.157
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 437.88 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 129 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8B-SM02 DB-8LB


Connection From: SMDB-8B/2/L1,L2,L3 To: DB-8LB
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 3.17 / 1.45 3.17 / 1.45 3.17 / 1.45 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02289 0.00334 0.00725 0.03012 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.27
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.82

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.770 / 16.921 Load End: 21.770 / 12.259
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 429.37 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 130 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8B-SM03 OFFICE 8.4


Connection From: SMDB-8B/3/L1,L2,L3 To: OFFICE 8.4
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 25.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 25.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 25.0 / 1.00 25.0 / 1.00 25.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.45 / 0.21 0.45 / 0.21 0.45 / 0.21 -----
Voltage Drop - From Source (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02289 0.01960 0.03649 0.07310 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.00
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.42

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.770 / 16.921 Load End: 10.316 / 4.506
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 210.37 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 131 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8B-SM04 OFFICE 8.5


Connection From: SMDB-8B/4/L1,L2,L3 To: OFFICE 8.5
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 34.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.4 / 1.00 34.4 / 1.00 34.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 3.86 / 1.76 3.86 / 1.76 3.86 / 1.76 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02289 0.02362 0.04397 0.08432 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.60
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.16

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.770 / 16.921 Load End: 9.039 / 3.876
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 172.57 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 132 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8B-SM05 OFFICE 8.6


Connection From: SMDB-8B/5/L1,L2,L3 To: OFFICE 8.6
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.7
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.7 / 1.00 35.7 / 1.00 35.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.56 / 0.26 0.56 / 0.26 0.56 / 0.26 -----
Voltage Drop - From Source (V/%) 3.67 / 1.68 3.67 / 1.68 3.67 / 1.68 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02289 0.01709 0.03181 0.06613 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.31
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.60

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.770 / 16.921 Load End: 11.300 / 5.012
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 240.75 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 133 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8B-SM06 MCC-8.4


Connection From: SMDB-8B/6/L1,L2,L3 To: MCC-8.4
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.92 / 1.33 2.92 / 1.33 2.92 / 1.33 -----
Voltage Drop - From Source (V/%) 6.03 / 2.75 6.03 / 2.75 6.03 / 2.75 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02289 0.03677 0.07975 0.13055 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.68
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.770 / 16.921 Load End: 6.472 / 2.665
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.49 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 134 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8B-SM07 MCC-8.5


Connection From: SMDB-8B/7/L1,L2,L3 To: MCC-8.5
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 56
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.97 / 1.36 2.97 / 1.36 2.97 / 1.36 -----
Voltage Drop - From Source (V/%) 6.08 / 2.78 6.08 / 2.78 6.08 / 2.78 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02289 0.03744 0.08120 0.13264 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.65
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.770 / 16.921 Load End: 6.376 / 2.623
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.17 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 135 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-8B-SM08 MCC-8.6


Connection From: SMDB-8B/8/L1,L2,L3 To: MCC-8.6
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.65 / 1.21 2.65 / 1.21 2.65 / 1.21 -----
Voltage Drop - From Source (V/%) 5.76 / 2.63 5.76 / 2.63 5.76 / 2.63 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02289 0.03343 0.07250 0.12010 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.82
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.770 / 16.921 Load End: 7.000 / 2.899
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 154.24 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 136 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9A-SM01 DB-9PA


Connection From: SMDB-9A/1/L1,L2,L3 To: DB-9PA
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 4.35 / 1.98 4.35 / 1.98 4.35 / 1.98 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03118 0.00251 0.00468 0.03634 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.03
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.54

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.317 / 13.779 Load End: 19.813 / 11.151
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 413.81 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 137 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9A-SM02 DB-9LA


Connection From: SMDB-9A/2/L1,L2,L3 To: DB-9LA
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 4.29 / 1.96 4.29 / 1.96 4.29 / 1.96 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03118 0.00334 0.00725 0.03822 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.73
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.39

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.317 / 13.779 Load End: 19.195 / 10.506
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 406.57 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 138 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9A-SM03 OFFICE 9.1


Connection From: SMDB-9A/3/L1,L2,L3 To: OFFICE 9.1
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 30.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 30.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 30.9 / 1.00 30.9 / 1.00 30.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.63 / 0.29 0.63 / 0.29 0.63 / 0.29 -----
Voltage Drop - From Source (V/%) 4.86 / 2.22 4.86 / 2.22 4.86 / 2.22 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03118 0.02211 0.04116 0.08712 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.51
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.11

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.317 / 13.779 Load End: 9.003 / 3.897
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 173.83 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 139 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9A-SM04 OFFICE 9.2


Connection From: SMDB-9A/4/L1,L2,L3 To: OFFICE 9.2
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 41.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 41.6
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 147.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 41.6 / 1.00 41.6 / 1.00 41.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.64 / 0.29 0.64 / 0.29 0.64 / 0.29 -----
Voltage Drop - From Source (V/%) 4.87 / 2.22 4.87 / 2.22 4.87 / 2.22 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03118 0.01659 0.03087 0.07201 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.04
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.45

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.317 / 13.779 Load End: 10.800 / 4.820
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 229.17 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 140 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9A-SM05 OFFICE 9.3


Connection From: SMDB-9A/5/L1,L2,L3 To: OFFICE 9.3
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.4 / 1.00 35.4 / 1.00 35.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 4.93 / 2.25 4.93 / 2.25 4.93 / 2.25 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03118 0.02161 0.04023 0.08574 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.55
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.14

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.317 / 13.779 Load End: 9.143 / 3.966
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 177.99 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 141 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9A-SM06 MCC-9.1


Connection From: SMDB-9A/6/L1,L2,L3 To: MCC-9.1
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.79 / 3.56 7.79 / 3.56 7.79 / 3.56 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03118 0.04479 0.06268 0.12992 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.69
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.317 / 13.779 Load End: 5.329 / 2.177
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 148.83 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 142 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9A-SM07 MCC-9.2


Connection From: SMDB-9A/7/L1,L2,L3 To: MCC-9.2
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.39 / 1.09 2.39 / 1.09 2.39 / 1.09 -----
Voltage Drop - From Source (V/%) 6.62 / 3.02 6.62 / 3.02 6.62 / 3.02 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03118 0.03008 0.06525 0.11588 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.89
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.317 / 13.779 Load End: 7.322 / 3.064
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 159.66 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 143 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9A-SM08 MCC-9.3


Connection From: SMDB-9A/8/L1,L2,L3 To: MCC-9.3
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 67
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.56 / 1.62 3.56 / 1.62 3.56 / 1.62 -----
Voltage Drop - From Source (V/%) 7.79 / 3.56 7.79 / 3.56 7.79 / 3.56 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03118 0.04479 0.06268 0.12992 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.69
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.317 / 13.779 Load End: 5.329 / 2.177
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 148.83 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 144 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9B-SM01 DB-9PB


Connection From: SMDB-9B/1/L1,L2,L3 To: DB-9PB
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 50.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 50.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 121.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 50.0 / 1.00 50.0 / 1.00 50.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.05 0.12 / 0.05 0.12 / 0.05 -----
Voltage Drop - From Source (V/%) 3.25 / 1.49 3.25 / 1.49 3.25 / 1.49 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02321 0.00251 0.00468 0.02848 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
7.69
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.94

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.485 / 16.598 Load End: 22.321 / 12.938
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 435.25 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 145 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9B-SM02 DB-9LB


Connection From: SMDB-9B/2/L1,L2,L3 To: DB-9LB
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 93.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 3.20 / 1.46 3.20 / 1.46 3.20 / 1.46 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02321 0.00334 0.00725 0.03050 0.18252 Current (kA)

Disconnection time (s): From characteristic: < 0.1 Maximum for circuit: 5.00
7.18
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.79

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.485 / 16.598 Load End: 21.540 / 12.065
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 426.84 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 146 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9B-SM03 OFFICE 9.4


Connection From: SMDB-9B/3/L1,L2,L3 To: OFFICE 9.4
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 25.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 25.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 145.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 25.0 / 1.00 25.0 / 1.00 25.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.45 / 0.21 0.45 / 0.21 0.45 / 0.21 -----
Voltage Drop - From Source (V/%) 3.59 / 1.64 3.59 / 1.64 3.59 / 1.64 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02321 0.01960 0.03649 0.07351 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.98
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.41

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.485 / 16.598 Load End: 10.261 / 4.479
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 208.73 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 147 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9B-SM04 OFFICE 9.5


Connection From: SMDB-9B/4/L1,L2,L3 To: OFFICE 9.5
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 47
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 34.4
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.4 / 1.00 34.4 / 1.00 34.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 3.89 / 1.77 3.89 / 1.77 3.89 / 1.77 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02321 0.02362 0.04397 0.08473 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.58
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.16

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.485 / 16.598 Load End: 8.997 / 3.856
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 171.36 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 148 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9B-SM05 OFFICE 9.6


Connection From: SMDB-9B/5/L1,L2,L3 To: OFFICE 9.6
Active Source: Tx 5
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 35.7

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 35.7
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 146.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 35.7 / 1.00 35.7 / 1.00 35.7 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.56 / 0.26 0.56 / 0.26 0.56 / 0.26 -----
Voltage Drop - From Source (V/%) 3.70 / 1.69 3.70 / 1.69 3.70 / 1.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02321 0.01709 0.03181 0.06655 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.29
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.59

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.485 / 16.598 Load End: 11.233 / 4.979
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 238.72 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 149 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9B-SM06 MCC-9.4


Connection From: SMDB-9B/6/L1,L2,L3 To: MCC-9.4
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.92 / 1.33 2.92 / 1.33 2.92 / 1.33 -----
Voltage Drop - From Source (V/%) 6.06 / 2.77 6.06 / 2.77 6.06 / 2.77 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02321 0.03677 0.07975 0.13096 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.67
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.485 / 16.598 Load End: 6.451 / 2.656
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.42 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 150 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9B-SM07 MCC-9.5


Connection From: SMDB-9B/7/L1,L2,L3 To: MCC-9.5
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 56
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.97 / 1.36 2.97 / 1.36 2.97 / 1.36 -----
Voltage Drop - From Source (V/%) 6.11 / 2.79 6.11 / 2.79 6.11 / 2.79 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02321 0.03744 0.08120 0.13306 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.65
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.485 / 16.598 Load End: 6.355 / 2.614
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 152.10 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 151 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-9B-SM08 MCC-9.6


Connection From: SMDB-9B/8/L1,L2,L3 To: MCC-9.6
Active Source: Tx 5
Load Type: Distribution Board Design Current Ib (A): 81.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =8 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 8
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 81.3
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 130.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 81.3 / 1.00 81.3 / 1.00 81.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.65 / 1.21 2.65 / 1.21 2.65 / 1.21 -----
Voltage Drop - From Source (V/%) 5.79 / 2.64 5.79 / 2.64 5.79 / 2.64 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02321 0.03343 0.07250 0.12051 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.82
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 25.485 / 16.598 Load End: 6.975 / 2.888
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 154.16 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 152 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-Tx5 MDB 5


Connection From: Tx 5 To: MDB 5
Active Source: Tx 5
Load Type: Main cable to Switchboard Design Current Ib (A): 2,431.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW32 H1 MLogic 5.0A High
Rating In (A):3200 [f] Overload Setting Ir (A): 2720 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 630 [f]
Neutral: 630 mm²[a] Length (m): 35
34 - On a ladder Configuration: Horizontal Flat Spaced Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.97 [BS 7671, Table 4C5]
No. of ladders = 1 No. of circuits per ladder = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 2,431.0
Device Rating In = 3200 Overload Setting Ir = 2720 [Ir >
_ Ib]
Min. Cable Capacity Iz = 805.8 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 1,454.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 2431.0 / 1.00 2431.0 / 1.00 2431.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 630 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00491 0.00121 0.00442 0.01052 0.01479 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
20.83
Adiabatic check (mm 2 ) CPC Section = Separate 630 Total = 630.0 Min. Section = 54.49

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 44.711 / 44.710 Load End: 35.973 / 29.944
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 692.22 x 106 Adiabatic Limit k²S² (A²s): 8,116.21 x 106

Project: KAFD 3.09 Tx 5 rev 0.p17 Page 153 of 153 Printed on: 14/04/2011
Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Buro Happold

4.6 Transformer TX6

KAFD Plot 3.09 Report Revision 0


Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM01 3.09-10-AHU-02


Connection From: Starter-1 To: 3.09-10-AHU-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 87
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 2.40 / 1.09 2.40 / 1.09 2.40 / 1.09 -----
Voltage Drop - From Source (V/%) 5.39 / 2.46 5.39 / 2.46 5.39 / 2.46 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.20092 0.20445 0.42049 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.52
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.353 / 0.899
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 1 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM02 3.09-10-AHU-02


Connection From: Starter-2 To: 3.09-10-AHU-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 86
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 2.37 / 1.08 2.37 / 1.08 2.37 / 1.08 -----
Voltage Drop - From Source (V/%) 5.37 / 2.45 5.37 / 2.45 5.37 / 2.45 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.19861 0.20210 0.41584 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.53
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.369 / 0.909
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 2 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM03 3.09-10-AHU-02


Connection From: Starter-3 To: 3.09-10-AHU-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 12.5
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 12.46 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 85
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 12.5
Device Rating In = 20 Motor Overload Setting Ir = 12.46 [Ir >
_ Ib]
Min. Cable Capacity Iz = 19.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 12.5 / 0.78 12.5 / 0.78 12.5 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.78 / 0.81 1.78 / 0.81 1.78 / 0.81 -----
Voltage Drop - From Source (V/%) 4.77 / 2.18 4.77 / 2.18 4.77 / 2.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.19630 0.19975 0.41119 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.53
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.384 / 0.919
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 3 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM04 3.09-10-AHU-02


Connection From: Starter-4 To: 3.09-10-AHU-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 12.5
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 12.46 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 84
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 12.5
Device Rating In = 20 Motor Overload Setting Ir = 12.46 [Ir >
_ Ib]
Min. Cable Capacity Iz = 19.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 12.5 / 0.78 12.5 / 0.78 12.5 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.76 / 0.80 1.76 / 0.80 1.76 / 0.80 -----
Voltage Drop - From Source (V/%) 4.75 / 2.17 4.75 / 2.17 4.75 / 2.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.19399 0.19740 0.40654 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.54
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.400 / 0.929
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 4 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM05 3.09-10-AHU-02


Connection From: MCC-10A/5/L1,L2,L3 To: 3.09-10-AHU-02
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 112.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 83
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 112.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 180.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 112.9 / 1.00 112.9 / 1.00 112.9 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.61 / 2.11 4.61 / 2.11 4.61 / 2.11 -----
Voltage Drop - From Source (V/%) 7.61 / 3.47 7.61 / 3.47 7.61 / 3.47 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.04172 0.07765 0.13968 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.57
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 1.52

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 5.350 / 2.269
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 76.14 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 5 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM06 3.09-10-AHU-01


Connection From: Starter-5 To: 3.09-10-AHU-01
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 45.0
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):50 [f] Overload Setting Ir (A): 45 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 16 [f]
Length (m): 73
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.0
Device Rating In = 50 Motor Overload Setting Ir = 45 [Ir >
_ Ib]
Min. Cable Capacity Iz = 71.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.0 / 0.81 45.0 / 0.81 45.0 / 0.81 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 3.70 / 1.69 3.70 / 1.69 3.70 / 1.69 -----
Voltage Drop - From Source (V/%) 6.70 / 3.06 6.70 / 3.06 6.70 / 3.06 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.10537 0.10585 0.22707 0.38780 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.96
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 2.499 / 1.635
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 66.29 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 6 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM07 3.09-10-AHU-01


Connection From: Starter-6 To: 3.09-10-AHU-01
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 45.0
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):50 [f] Overload Setting Ir (A): 45 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 16 [f]
Length (m): 72
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 45.0
Device Rating In = 50 Motor Overload Setting Ir = 45 [Ir >
_ Ib]
Min. Cable Capacity Iz = 71.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 100.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 45.0 / 0.81 45.0 / 0.81 45.0 / 0.81 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 3.65 / 1.67 3.65 / 1.67 3.65 / 1.67 -----
Voltage Drop - From Source (V/%) 6.65 / 3.04 6.65 / 3.04 6.65 / 3.04 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.10392 0.10440 0.22420 0.38780 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.98
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 2.531 / 1.655
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 67.06 x 103 Adiabatic Limit k²S² (A²s): 5.23 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 7 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM08 3.09-10-AHU-01


Connection From: Starter-7 To: 3.09-10-AHU-01
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 71
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.96 / 0.89 1.96 / 0.89 1.96 / 0.89 -----
Voltage Drop - From Source (V/%) 4.95 / 2.26 4.95 / 2.26 4.95 / 2.26 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.16397 0.16685 0.34612 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.63
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.646 / 1.089
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 8 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM09 3.09-10-AHU-01


Connection From: Starter-8 To: 3.09-10-AHU-01
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 70
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.93 / 0.88 1.93 / 0.88 1.93 / 0.88 -----
Voltage Drop - From Source (V/%) 4.93 / 2.25 4.93 / 2.25 4.93 / 2.25 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.16166 0.16450 0.34148 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.64
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.668 / 1.103
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 9 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM10 3.09-10-AHU-01


Connection From: MCC-10A/10/L1,L2,L3 To: 3.09-10-AHU-01
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 402.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
RCD Trip rating : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 69
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.73 [BS 7671, Table 4C4] Subject to Simultaneous Overload
No. of trays = 5 No. of circuits per tray = 4
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 402.6
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 496.0 [BS 7671, Appendix 4.5, Formula (2)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 402.6 / 1.00 402.6 / 1.00 402.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.33 / 0.61 1.33 / 0.61 1.33 / 0.61 -----
Voltage Drop - From Source (V/%) 4.33 / 1.98 4.33 / 1.98 4.33 / 1.98 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.00428 0.01094 0.04518 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.85
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.42

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 13.939 / 8.295
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 651.55 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 10 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM11 3.09-10-EF-02


Connection From: Starter-9 To: 3.09-10-EF-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 55
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.43 / 0.65 1.43 / 0.65 1.43 / 0.65 -----
Voltage Drop - From Source (V/%) 4.43 / 2.02 4.43 / 2.02 4.43 / 2.02 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.21593 0.21725 0.44824 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.49
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.262 / 0.840
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 11 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM12 3.09-10-EF-02


Connection From: Starter-10 To: 3.09-10-EF-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 54
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.40 / 0.64 1.40 / 0.64 1.40 / 0.64 -----
Voltage Drop - From Source (V/%) 4.40 / 2.01 4.40 / 2.01 4.40 / 2.01 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.21200 0.21330 0.44038 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.50
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.285 / 0.854
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 12 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM13 3.09-10-EF-01


Connection From: Starter-11 To: 3.09-10-EF-01
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 53
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.46 / 0.67 1.46 / 0.67 1.46 / 0.67 -----
Voltage Drop - From Source (V/%) 4.46 / 2.04 4.46 / 2.04 4.46 / 2.04 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.12240 0.12455 0.26259 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.83
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 2.172 / 1.427
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 58.51 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 13 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM14 3.09-10-EF-01


Connection From: Starter-12 To: 3.09-10-EF-01
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 52
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.43 / 0.65 1.43 / 0.65 1.43 / 0.65 -----
Voltage Drop - From Source (V/%) 4.43 / 2.02 4.43 / 2.02 4.43 / 2.02 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.12009 0.12220 0.25795 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.85
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 2.212 / 1.452
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 59.45 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 14 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM15 3.09-10-EF-03


Connection From: Starter-13 To: 3.09-10-EF-03
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 53
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.38 / 0.63 1.38 / 0.63 1.38 / 0.63 -----
Voltage Drop - From Source (V/%) 4.37 / 2.00 4.37 / 2.00 4.37 / 2.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.20808 0.20935 0.43252 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.51
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.308 / 0.870
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 15 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM16 3.09-10-EF-03


Connection From: Starter-14 To: 3.09-10-EF-03
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 54
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.40 / 0.64 1.40 / 0.64 1.40 / 0.64 -----
Voltage Drop - From Source (V/%) 4.40 / 2.01 4.40 / 2.01 4.40 / 2.01 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.21200 0.21330 0.44038 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.50
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.285 / 0.854
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 16 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM17 3.09-10-GB-02


Connection From: Starter-15 To: 3.09-10-GB-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 34
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.88 / 0.40 0.88 / 0.40 0.88 / 0.40 -----
Voltage Drop - From Source (V/%) 3.88 / 1.77 3.88 / 1.77 3.88 / 1.77 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.13348 0.13430 0.28332 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.77
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 2.002 / 1.318
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 54.42 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 17 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM18 3.09-10-GB-02


Connection From: Starter-16 To: 3.09-10-GB-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.94 / 0.43 0.94 / 0.43 0.94 / 0.43 -----
Voltage Drop - From Source (V/%) 3.93 / 1.80 3.93 / 1.80 3.93 / 1.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.14134 0.14220 0.29900 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.73
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 1.896 / 1.250
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 18 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM19 3.09-10-DB-02


Connection From: Starter-17 To: 3.09-10-DB-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 37
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.02 / 0.47 1.02 / 0.47 1.02 / 0.47 -----
Voltage Drop - From Source (V/%) 4.02 / 1.83 4.02 / 1.83 4.02 / 1.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.08545 0.08695 0.18858 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.16
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 3.031 / 1.968
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 78.81 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 19 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-10A-SM20 3.09-10-DB-02


Connection From: Starter-18 To: 3.09-10-DB-02
Active Source: Tx 6
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 16.2
Motor Starter Position: at MCC-10A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 16.15 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 16.2
Device Rating In = 20 Motor Overload Setting Ir = 16.15 [Ir >
_ Ib]
Min. Cable Capacity Iz = 25.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 16.2 / 0.79 16.2 / 0.79 16.2 / 0.79 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.07 / 0.49 1.07 / 0.49 1.07 / 0.49 -----
Voltage Drop - From Source (V/%) 4.07 / 1.86 4.07 / 1.86 4.07 / 1.86 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03041 0.09007 0.09165 0.19781 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.11
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.812 / 11.996 Load End: 2.889 / 1.879
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 75.48 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 20 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM01 SMDB-10A


Connection From: MDB 6 To: SMDB-10A
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 140.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 400 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 140.0
Device Rating In = 400 Overload Setting Ir = 400 [Ir >
_ Ib]
Min. Cable Capacity Iz = 472.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 140.0 / 1.00 140.0 / 1.00 140.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.66 / 0.30 0.66 / 0.30 0.66 / 0.30 -----
Voltage Drop - From Source (V/%) 1.05 / 0.48 1.05 / 0.48 1.05 / 0.48 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.00621 0.01158 0.02759 0.07935 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
7.94
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 5.38

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 16.999 / 10.971
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 993.68 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 21 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM02 RESI SHUTTLE LIFT


Connection From: MDB 6 To: RESI SHUTTLE LIFT
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 55.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):63 [f] Overload Setting Ir (A): 63 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 68
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 55.0
Device Rating In = 63 Overload Setting Ir = 63 [Ir >
_ Ib]
Min. Cable Capacity Iz = 87.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 55.0 / 1.00 55.0 / 1.00 55.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.32 / 1.52 3.32 / 1.52 3.32 / 1.52 -----
Voltage Drop - From Source (V/%) 3.71 / 1.69 3.71 / 1.69 3.71 / 1.69 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.06306 0.09860 0.16510 0.43945 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.33
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.27

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 4.178 / 1.696
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 43.50 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 22 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM03 RESI SHUTTLE LIFT


Connection From: MDB 6 To: RESI SHUTTLE LIFT
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 55.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):63 [f] Overload Setting Ir (A): 63 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 70
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 55.0
Device Rating In = 63 Overload Setting Ir = 63 [Ir >
_ Ib]
Min. Cable Capacity Iz = 87.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 55.0 / 1.00 55.0 / 1.00 55.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.42 / 1.56 3.42 / 1.56 3.42 / 1.56 -----
Voltage Drop - From Source (V/%) 3.81 / 1.74 3.81 / 1.74 3.81 / 1.74 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.06491 0.10150 0.16984 0.43945 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.29
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.25

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 4.067 / 1.648
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 42.18 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 23 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM04 MCC-10A


Connection From: MDB 6 To: MCC-10A
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 648.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS1000 N MLogic 5.0A
Rating In (A):1000 [f] Overload Setting Ir (A): 800 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 97
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
No. of trays = 4 No. of circuits per tray = 1
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 648.4
Device Rating In = 1000 Overload Setting Ir = 800 [Ir >
_ Ib]
Min. Cable Capacity Iz = 459.8 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 648.4 / 0.99 648.4 / 0.99 648.4 / 0.99 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.61 / 1.19 2.61 / 1.19 2.61 / 1.19 -----
Voltage Drop - From Source (V/%) 3.00 / 1.37 3.00 / 1.37 3.00 / 1.37 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.00516 0.01427 0.03041 0.05030 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
7.20
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 46.91

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 17.812 / 11.996
Protective Device Breaking Capacity (kA): Icu: 50 Ics: 37.5

Adiabatic Check: CPD Energy Let-through (A²s): 45.00 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 24 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM05 RESI LIFT


Connection From: MDB 6 To: RESI LIFT
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 55.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):63 [f] Overload Setting Ir (A): 63 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 148
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 55.0
Device Rating In = 63 Overload Setting Ir = 63 [Ir >
_ Ib]
Min. Cable Capacity Iz = 87.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 55.0 / 1.00 55.0 / 1.00 55.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.81 / 1.74 3.81 / 1.74 3.81 / 1.74 -----
Voltage Drop - From Source (V/%) 4.19 / 1.91 4.19 / 1.91 4.19 / 1.91 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.07439 0.13846 0.21763 0.43945 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.01
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 1.09

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 3.526 / 1.438
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 36.29 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 25 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM06 RESI LIFT


Connection From: MDB 6 To: RESI LIFT
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 55.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):63 [f] Overload Setting Ir (A): 63 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 150
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 55.0
Device Rating In = 63 Overload Setting Ir = 63 [Ir >
_ Ib]
Min. Cable Capacity Iz = 87.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 55.0 / 1.00 55.0 / 1.00 55.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.86 / 1.76 3.86 / 1.76 3.86 / 1.76 -----
Voltage Drop - From Source (V/%) 4.24 / 1.94 4.24 / 1.94 4.24 / 1.94 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.07539 0.14033 0.22050 0.43945 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.99
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 1.08

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 3.482 / 1.419
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 35.77 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 26 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM07 GYM


Connection From: MDB 6 To: GYM
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 172.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N TM D
Rating In (A):200 [f] Overload Setting Ir (A): 200 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 95 [f]
Neutral: 95 mm²[a] Length (m): 83
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 172.6
Device Rating In = 200 Overload Setting Ir = 200 [Ir >
_ Ib]
Min. Cable Capacity Iz = 275.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 298.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 172.6 / 1.00 172.6 / 1.00 172.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.52 / 1.61 3.52 / 1.61 3.52 / 1.61 -----
Voltage Drop - From Source (V/%) 3.90 / 1.78 3.90 / 1.78 3.90 / 1.78 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 50 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.02153 0.04259 0.07065 0.13036 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.10
Adiabatic check (mm 2 ) CPC Section = Separate 50 Total = 50.0 Min. Section = 2.82

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 9.635 / 4.553
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 267.57 x 103 Adiabatic Limit k²S² (A²s): 184.55 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 27 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM08 ROOF BMU/CRANE


Connection From: MDB 6 To: ROOF BMU/CRANE
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 24.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 153
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 24.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 49.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 24.0 / 1.00 24.0 / 1.00 24.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.17 / 1.45 3.17 / 1.45 3.17 / 1.45 -----
Voltage Drop - From Source (V/%) 3.55 / 1.62 3.55 / 1.62 3.55 / 1.62 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.14188 0.22185 0.36678 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.60
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.83

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 1.926 / 0.764
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 17.47 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 28 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM09 KITCHEN


Connection From: MDB 6 To: KITCHEN
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 214.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 150 [f]
Neutral: 150 mm²[a] Length (m): 129
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 214.5
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 342.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 399.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 214.5 / 1.00 214.5 / 1.00 214.5 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.39 / 2.00 4.39 / 2.00 4.39 / 2.00 -----
Voltage Drop - From Source (V/%) 4.77 / 2.18 4.77 / 2.18 4.77 / 2.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 95 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.02284 0.03578 0.06677 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
3.28
Adiabatic check (mm 2 ) CPC Section = Separate 95 Total = 95.0 Min. Section = 3.57

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 8.792 / 4.250
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 292.51 x 103 Adiabatic Limit k²S² (A²s): 460.10 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 29 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM10 RESTAURANT


Connection From: MDB 6 To: RESTAURANT
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 124.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 95 [f]
Neutral: 95 mm²[a] Length (m): 139
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 124.3
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 207.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 298.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 124.3 / 1.00 124.3 / 1.00 124.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.12 / 1.88 4.12 / 1.88 4.12 / 1.88 -----
Voltage Drop - From Source (V/%) 4.50 / 2.06 4.50 / 2.06 4.50 / 2.06 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 50 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.03605 0.07132 0.11363 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.93
Adiabatic check (mm 2 ) CPC Section = Separate 50 Total = 50.0 Min. Section = 1.94

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 6.442 / 2.847
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 135.07 x 103 Adiabatic Limit k²S² (A²s): 184.55 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 30 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM11 OFFICE LIFT


Connection From: MDB 6 To: OFFICE LIFT
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 131
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.87 / 1.77 3.87 / 1.77 3.87 / 1.77 -----
Voltage Drop - From Source (V/%) 4.25 / 1.94 4.25 / 1.94 4.25 / 1.94 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.12147 0.18995 0.31455 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.70
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.87

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 2.239 / 0.891
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 21.01 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 31 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM12 OFFICE LIFT


Connection From: MDB 6 To: OFFICE LIFT
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 133
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.93 / 1.79 3.93 / 1.79 3.93 / 1.79 -----
Voltage Drop - From Source (V/%) 4.31 / 1.97 4.31 / 1.97 4.31 / 1.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.12333 0.19285 0.31930 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.69
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.86

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 2.206 / 0.878
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 20.64 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 32 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM13 RESTAURANT SERVICE LIFT


Connection From: MDB 6 To: RESTAURANT SERVICE LIFT
Active Source: Tx 6
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 34.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):40 [f] Overload Setting Ir (A): 40 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 142
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 5.48 V (User defined)
Design Current Ib = 34.0
Device Rating In = 40 Overload Setting Ir = 40 [Ir >
_ Ib]
Min. Cable Capacity Iz = 54.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 34.0 / 1.00 34.0 / 1.00 34.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.19 / 1.91 4.19 / 1.91 4.19 / 1.91 -----
Voltage Drop - From Source (V/%) 4.58 / 2.09 4.58 / 2.09 4.58 / 2.09 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.13168 0.20590 0.34066 0.58564 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.64
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 0.83

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 2.071 / 0.823
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 19.10 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 33 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM14 KITCHEN MCC


Connection From: MDB 6 To: KITCHEN MCC
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 0.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 95 [f]
Neutral: 95 mm²[a] Length (m): 115
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 0.0
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 287.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 298.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 0.0 / 0.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 50 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.02983 0.05900 0.09518 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.06 Maximum for circuit: 5.00
2.30
Adiabatic check (mm 2 ) CPC Section = Separate 50 Total = 50.0 Min. Section = 3.43

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 7.518 / 3.393
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 263.81 x 103 Adiabatic Limit k²S² (A²s): 184.55 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 34 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-6-SM15 SMDB-10B


Connection From: MDB 6 To: SMDB-10B
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 140.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 400 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 103
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 140.0
Device Rating In = 400 Overload Setting Ir = 400 [Ir >
_ Ib]
Min. Cable Capacity Iz = 472.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 140.0 / 1.00 140.0 / 1.00 140.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.37 / 0.62 1.37 / 0.62 1.37 / 0.62 -----
Voltage Drop - From Source (V/%) 1.75 / 0.80 1.75 / 0.80 1.75 / 0.80 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.01279 0.02386 0.04597 0.07935 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
4.76
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 3.35

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 11.994 / 6.683
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 408.97 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 35 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-10A-SM01 DB-10PA


Connection From: SMDB-10A/1/L1,L2,L3 To: DB-10PA
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 80.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 80.0
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 189.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 80.0 / 1.00 80.0 / 1.00 80.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.13 / 0.06 0.13 / 0.06 0.13 / 0.06 -----
Voltage Drop - From Source (V/%) 1.18 / 0.54 1.18 / 0.54 1.18 / 0.54 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02759 0.00174 0.00344 0.03181 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.88
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 3.98

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.999 / 10.971 Load End: 15.827 / 9.631
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 399.86 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 36 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-10A-SM02 DB-10LA


Connection From: SMDB-10A/2/L1,L2,L3 To: DB-10LA
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 40.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 40.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 117.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 40.0 / 1.00 40.0 / 1.00 40.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.09 / 0.04 0.09 / 0.04 0.09 / 0.04 -----
Voltage Drop - From Source (V/%) 1.14 / 0.52 1.14 / 0.52 1.14 / 0.52 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02759 0.00251 0.00468 0.03332 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
6.57
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 3.68

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.999 / 10.971 Load End: 15.462 / 9.182
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 370.56 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 37 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-10A-SM03 DB-10AEXT


Connection From: SMDB-10A/3/L1,L2,L3 To: DB-10AEXT
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.08 / 0.04 0.08 / 0.04 0.08 / 0.04 -----
Voltage Drop - From Source (V/%) 1.13 / 0.52 1.13 / 0.52 1.13 / 0.52 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02759 0.00464 0.00725 0.03658 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
5.99
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.49

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.999 / 10.971 Load End: 14.477 / 8.083
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 328.12 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 38 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-10B-SM01 DB-10PB


Connection From: SMDB-10B/1/L1,L2,L3 To: DB-10PB
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 80.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 80.0
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 189.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 80.0 / 1.00 80.0 / 1.00 80.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.13 / 0.06 0.13 / 0.06 0.13 / 0.06 -----
Voltage Drop - From Source (V/%) 1.88 / 0.86 1.88 / 0.86 1.88 / 0.86 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04597 0.00174 0.00344 0.05045 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
4.34
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 3.32

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 11.994 / 6.683 Load End: 11.342 / 6.128
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 303.53 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 39 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-10B-SM03 DB-10BEXT


Connection From: SMDB-10B/3/L1,L2,L3 To: DB-10BEXT
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.08 / 0.04 0.08 / 0.04 0.08 / 0.04 -----
Voltage Drop - From Source (V/%) 1.84 / 0.84 1.84 / 0.84 1.84 / 0.84 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04597 0.00464 0.00725 0.05542 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
3.95
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.60

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 11.994 / 6.683 Load End: 10.568 / 5.441
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 219.28 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 40 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-GB-SM02 DB-10LB


Connection From: SMDB-10B/2/L1,L2,L3 To: DB-10LB
Active Source: Tx 6
Load Type: Distribution Board Design Current Ib (A): 40.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =3 Cg = 0.82 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 40.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 117.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 192.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 40.0 / 1.00 40.0 / 1.00 40.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.09 / 0.04 0.09 / 0.04 0.09 / 0.04 -----
Voltage Drop - From Source (V/%) 1.85 / 0.84 1.85 / 0.84 1.85 / 0.84 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.04597 0.00251 0.00468 0.05204 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 5.00
4.21
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.90

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 11.994 / 6.683 Load End: 11.130 / 5.933
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 253.58 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 41 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-Tx6 Tx 6
Connection From: Tx 6 To: MDB 6
Active Source: Tx 6
Load Type: Main cable to Switchboard Design Current Ib (A): 1,519.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW20 H1 MLogic 5.0A High
Rating In (A):2000 [f] Overload Setting Ir (A): 1600 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 630 [f]
Neutral: 630 mm²[a] Length (m): 28
34 - On a ladder Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.97 [BS 7671, Table 4C5]
No. of ladders = 1 No. of circuits per ladder = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,519.4
Device Rating In = 2000 Overload Setting Ir = 1600 [Ir >
_ Ib]
Min. Cable Capacity Iz = 474.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 1,151.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1519.4 / 1.00 1519.4 / 1.00 1519.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.39 / 0.18 0.39 / 0.18 0.39 / 0.18 -----
Voltage Drop - From Source (V/%) 0.39 / 0.18 0.39 / 0.18 0.39 / 0.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 630 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00751 0.00071 0.00353 0.01172 0.02515 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
18.69
Adiabatic check (mm 2 ) CPC Section = Separate 630 Total = 630.0 Min. Section = 114.99

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.229 / 29.229 Load End: 26.807 / 24.669
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 270.40 x 106 Adiabatic Limit k²S² (A²s): 8,116.21 x 106

Project: KAFD 3.09 Tx 6 rev 0.p17 Page 42 of 42 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Buro Happold

4.7 Transformer TX7

KAFD Plot 3.09 Report Revision 0


Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB7-1-SM01 SMDB-12A


Connection From: TO-1 To: SMDB-12A
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 472.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 472.2
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 472.2 / 1.00 472.2 / 1.00 472.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.11 / 0.05 0.11 / 0.05 0.11 / 0.05 -----
Voltage Drop - From Source (V/%) 1.68 / 0.77 1.68 / 0.77 1.76 / 0.81 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02339 0.00031 0.00079 0.02443 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
8.96
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 6.13

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.958 / 15.394 Load End: 18.592 / 14.844
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.49 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 1 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB7-1-SM02 SMDB-15A


Connection From: TO-2 To: SMDB-15A
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 514.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 514.3
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 472.2 / 1.00 472.2 / 1.00 514.3 / 1.00 42.1
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.11 / 0.05 0.11 / 0.05 0.13 / 0.06 -----
Voltage Drop - From Source (V/%) 1.79 / 0.82 1.79 / 0.82 1.91 / 0.87 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02402 0.00031 0.00079 0.02507 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
8.74
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 5.97

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.644 / 14.879 Load End: 18.287 / 14.356
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.61 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 2 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-7-SM01 BB-MDB-7-1


Connection From: MDB 7 To: EF-1
Active Source: Tx 7
Load Type: Busbar EndFeed Design Current Ib (A): 986.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW12 H1 MLogic 5.0A High
Rating In (A):1250 [f] Overload Setting Ir (A): 1250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 53
31 - On horizontal/vertical perforated tray Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.78 [BS 7671, Table 4C5] Subject to Simultaneous Overload
No. of trays = 3 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 986.5
Device Rating In = 1250 Overload Setting Ir = 1250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 460.5 [BS 7671, Appendix 4.5, Formula (2)]
Actual Cable Rating It = 736.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 944.3 / 1.00 944.3 / 1.00 986.5 / 1.00 42.1
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.93 / 0.43 0.93 / 0.43 0.99 / 0.45 -----
Voltage Drop - From Source (V/%) 1.24 / 0.57 1.24 / 0.57 1.30 / 0.59 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01345 0.00160 0.00780 0.02251 0.05309 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
9.73
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 71.87

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 22.123 / 20.647 Load End: 19.428 / 16.183
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 105.63 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 3 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM01 DB-12PA


Connection From: SMDB-12A/1/L1,L2,L3 To: DB-12PA
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 116.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 1.74 / 0.79 1.74 / 0.79 1.83 / 0.83 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.00334 0.00725 0.03073 0.38088 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
7.13
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.65

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 16.720 / 11.534
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 399.95 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 4 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM02 DB-12LA


Connection From: SMDB-12A/2/L1,L2,L3 To: DB-12LA
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 10.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.0 / 1.00 10.0 / 1.00 10.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.04 / 0.02 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 1.72 / 0.78 1.72 / 0.78 1.81 / 0.82 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.00464 0.00725 0.03164 0.47607 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.92
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.60

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 16.106 / 10.528
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 386.86 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 5 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM03 CU-1201


Connection From: SMDB-12A/3/L1 To: CU-1201
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 94.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 32
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 94.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 161.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 94.9 / 1.00 0.0 / 0.00 0.0 / 0.00 94.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.00 / 1.83 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.67 / 2.59 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02174 0.04640 0.08211 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.67
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.21

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 5.428 / 4.181
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 190.84 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 6 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM04 CU-1202


Connection From: SMDB-12A/3/L2 To: CU-1202
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 57.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 57.9
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 102.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 57.9 / 1.00 0.0 / 0.00 57.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 2.95 / 1.35 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 4.63 / 2.11 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02718 0.05800 0.09861 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.22
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.74

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 4.507 / 3.477
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 117.00 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 7 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM05 CU-1203


Connection From: SMDB-12A/3/L3 To: CU-1203
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 89.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 89.5
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 159.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 89.5 / 1.00 89.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 4.45 / 2.03 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 6.22 / 2.84 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02582 0.05510 0.09447 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.32
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.97

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 4.707 / 3.630
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 157.83 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 8 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM06 CU-1204


Connection From: SMDB-12A/4/L1 To: CU-1204
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 100.0 / 1.00 0.0 / 0.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.37 / 2.00 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 6.05 / 2.76 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02242 0.04785 0.08416 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.60
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.17

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 5.294 / 4.078
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 184.68 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 9 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM07 CU-1205


Connection From: SMDB-12A/4/L2 To: CU-1205
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 100.0 / 1.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.62 / 1.66 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.30 / 2.42 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.01904 0.03555 0.07112 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.08
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.47

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 5.946 / 4.603
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 216.17 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 10 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM08 CU-1301


Connection From: SMDB-12A/4/L3 To: CU-1301
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 94.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 94.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 161.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 94.9 / 1.00 94.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.24 / 1.48 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.01 / 2.29 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.01804 0.03368 0.06837 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.20
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.54

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 6.199 / 4.798
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 227.85 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 11 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM09 CU-1302


Connection From: SMDB-12A/5/L1 To: CU-1302
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 57.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 57.9
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 102.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 57.9 / 1.00 0.0 / 0.00 0.0 / 0.00 57.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.25 / 1.48 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 4.92 / 2.25 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02990 0.06380 0.10693 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.05
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.63

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 4.152 / 3.206
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 105.06 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 12 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM10 CU-1303


Connection From: SMDB-12A/5/L2 To: CU-1303
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 89.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 89.5
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 159.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 89.5 / 1.00 0.0 / 0.00 89.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.56 / 1.62 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.23 / 2.39 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02104 0.03929 0.07664 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.86
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.33

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 5.494 / 4.256
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 195.36 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 13 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM11 CU-1304


Connection From: SMDB-12A/5/L3 To: CU-1304
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 37
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 100.0 / 1.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.53 / 1.61 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.29 / 2.42 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.01854 0.03461 0.06974 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.14
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.51

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 6.070 / 4.698
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 221.90 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 14 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM12 CU-1305


Connection From: SMDB-12A/6/L1 To: CU-1305
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 100.0 / 1.00 0.0 / 0.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.01 / 1.83 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.68 / 2.59 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02104 0.03929 0.07664 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.86
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.33

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 5.494 / 4.256
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 195.36 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 15 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM13 CU-1401


Connection From: SMDB-12A/6/L2 To: CU-1401
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 94.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 94.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 161.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 94.9 / 1.00 0.0 / 0.00 94.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.60 / 1.65 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.28 / 2.41 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02004 0.03742 0.07387 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.96
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.40

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 5.712 / 4.423
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 205.37 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 16 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM14 CU-1402


Connection From: SMDB-12A/6/L3 To: CU-1402
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 57.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 48
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 57.9
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 102.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 57.9 / 1.00 57.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.54 / 1.62 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.31 / 2.42 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.03261 0.06960 0.11527 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.90
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.55

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 3.848 / 2.973
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 94.82 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 17 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM15 CU-1403


Connection From: SMDB-12A/7/L1 To: CU-1403
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 89.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 46
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 89.5
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 159.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 89.5 / 1.00 0.0 / 0.00 0.0 / 0.00 89.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.90 / 1.78 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.57 / 2.54 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02305 0.04303 0.08219 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.66
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.21

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 5.105 / 3.956
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 177.38 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 18 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM16 CU-1404


Connection From: SMDB-12A/7/L2 To: CU-1404
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 41
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 100.0 / 1.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.91 / 1.79 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.59 / 2.55 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02054 0.03836 0.07526 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.91
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.37

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 5.601 / 4.338
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 200.27 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 19 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-12A-SM17 CU-1405


Connection From: SMDB-12A/7/L3 To: CU-1405
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 46
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 100.0 / 1.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 4.39 / 2.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 6.15 / 2.81 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02443 0.02305 0.04303 0.08219 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.66
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.21

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.592 / 14.844 Load End: 5.105 / 3.956
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 177.38 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 20 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM01 DP-15PA


Connection From: SMDB-15A/1/L1,L2,L3 To: DB-15PA
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 116.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 1.85 / 0.84 1.85 / 0.84 1.97 / 0.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.00334 0.00725 0.03154 0.38088 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.94
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.60

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 16.441 / 11.178
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 395.32 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 21 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM02 DB-15LA


Connection From: SMDB-15A/2/L1,L2,L3 To: DB-15LA
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 10.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.0 / 1.00 10.0 / 1.00 10.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.04 / 0.02 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 1.83 / 0.84 1.83 / 0.84 1.96 / 0.89 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.00464 0.00725 0.03246 0.47607 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.75
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.55

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 15.839 / 10.221
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 382.87 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 22 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM03 CU-1501


Connection From: SMDB-15A/3/L1 To: CU-1501
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 94.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 32
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 94.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 161.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 94.9 / 1.00 0.0 / 0.00 0.0 / 0.00 94.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.00 / 1.83 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.79 / 2.64 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02174 0.04640 0.08302 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.64
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.19

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 5.395 / 4.129
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 187.75 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 23 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM04 CU-1502


Connection From: SMDB-15A/3/L2 To: CU-1502
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 57.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 57.9
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 102.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 57.9 / 1.00 0.0 / 0.00 57.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 2.95 / 1.35 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 4.74 / 2.16 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02718 0.05800 0.09953 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.20
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.72

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 4.484 / 3.442
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 115.43 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 24 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM05 CU-1503


Connection From: SMDB-15A/3/L3 To: CU-1503
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 89.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 89.5
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 159.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 89.5 / 1.00 89.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 4.45 / 2.03 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 6.37 / 2.91 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02582 0.05510 0.09539 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.30
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.95

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 4.683 / 3.592
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 155.50 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 25 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM06 CU-1504


Connection From: SMDB-15A/4/L1 To: CU-1504
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 100.0 / 1.00 0.0 / 0.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.37 / 2.00 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 6.16 / 2.81 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02242 0.04785 0.08508 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.57
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 2.15

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 5.262 / 4.029
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 181.74 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 26 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM07 CU-1505


Connection From: SMDB-15A/4/L2 To: CU-1505
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 100.0 / 1.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.62 / 1.66 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.41 / 2.47 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.01904 0.03555 0.07203 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.04
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.45

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 5.906 / 4.540
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 212.42 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 27 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM08 CU-1601


Connection From: SMDB-15A/4/L3 To: CU-1601
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 94.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 94.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 161.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 94.9 / 1.00 94.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.24 / 1.48 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.16 / 2.35 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.01804 0.03368 0.06928 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.16
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.52

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 6.155 / 4.730
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 223.77 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 28 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM09 CU-1602


Connection From: SMDB-15A/5/L1 To: CU-1602
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 57.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 57.9
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 102.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 185.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 57.9 / 1.00 0.0 / 0.00 0.0 / 0.00 57.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.25 / 1.48 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.03 / 2.30 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02990 0.06380 0.10784 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.03
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.62

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 4.133 / 3.176
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 103.73 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 29 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM10 CU-1603


Connection From: SMDB-15A/5/L2 To: CU-1603
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 89.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 89.5
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 159.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 89.5 / 1.00 0.0 / 0.00 89.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.56 / 1.62 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.34 / 2.44 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02104 0.03929 0.07755 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.82
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 5.460 / 4.202
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 192.15 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 30 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM11 CU-1604


Connection From: SMDB-15A/5/L3 To: CU-1604
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 37
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 100.0 / 1.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.53 / 1.61 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.44 / 2.48 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.01854 0.03461 0.07065 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.10
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.48

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 6.028 / 4.633
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 217.98 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 31 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM12 CU-1605


Connection From: SMDB-15A/6/L1 To: CU-1605
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 100.0 / 1.00 0.0 / 0.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.01 / 1.83 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.79 / 2.65 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02104 0.03929 0.07755 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.82
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.31

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 5.460 / 4.202
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 192.15 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 32 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM13 CU-1701


Connection From: SMDB-15A/6/L2 To: CU-1701
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 94.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 94.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 161.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 94.9 / 1.00 0.0 / 0.00 94.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.60 / 1.65 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.39 / 2.46 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02004 0.03742 0.07478 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.93
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.38

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 5.675 / 4.365
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 201.90 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 33 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM14 CU-1702


Connection From: SMDB-15A/6/L3 To: CU-1702
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 48
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 100.0 / 1.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 4.58 / 2.09 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 6.49 / 2.96 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02405 0.04491 0.08590 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.55
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.13

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 4.902 / 3.778
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 166.70 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 34 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM15 CU-1703


Connection From: SMDB-15A/7/L1 To: CU-1703
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 89.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 46
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 89.5
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 159.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 89.5 / 1.00 0.0 / 0.00 0.0 / 0.00 89.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.90 / 1.78 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.68 / 2.59 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02305 0.04303 0.08311 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.64
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.19

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 5.075 / 3.910
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 174.61 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 35 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM16 CU-1704


Connection From: SMDB-15A/7/L2 To: CU-1704
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 41
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 100.0 / 1.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.91 / 1.79 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.70 / 2.60 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02054 0.03836 0.07617 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.88
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.35

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 5.565 / 4.282
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 196.93 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 36 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-15A-SM17 CU-1705


Connection From: SMDB-15A/7/L3 To: CU-1705
Active Source: Tx 7
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 46
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 17 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 20
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 100.0 / 1.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 4.39 / 2.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 6.30 / 2.88 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02507 0.02305 0.04303 0.08311 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.64
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.19

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.287 / 14.356 Load End: 5.075 / 3.910
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 174.61 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 37 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-Tx7 MDB 7


Connection From: Tx 7 To: MDB 7
Active Source: Tx 7
Load Type: Main cable to Switchboard Design Current Ib (A): 1,215.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW20 H1 MLogic 5.0A High
Rating In (A):1600 [f] Overload Setting Ir (A): 1600 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 630 [f]
Neutral: 630 mm²[a] Length (m): 28
34 - On a ladder Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.97 [BS 7671, Table 4C5]
No. of ladders = 1 No. of circuits per ladder = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,215.4
Device Rating In = 1600 Overload Setting Ir = 1600 [Ir >
_ Ib]
Min. Cable Capacity Iz = 474.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 1,151.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1215.4 / 1.00 1215.4 / 1.00 1215.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.31 / 0.14 0.31 / 0.14 0.31 / 0.14 -----
Voltage Drop - From Source (V/%) 0.31 / 0.14 0.31 / 0.14 0.31 / 0.14 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 630 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00924 0.00071 0.00353 0.01345 0.01857 Current (kA)

Disconnection time (s): From characteristic: 0.14 Maximum for circuit: 5.00
16.28
Adiabatic check (mm 2 ) CPC Section = Separate 630 Total = 630.0 Min. Section = 42.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 23.747 / 23.747 Load End: 22.123 / 20.647
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 19.04 Actual disconnection time (s) = 0.14

Project: KAFD 3.09 Tx 7 rev 0.p17 Page 38 of 38 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Buro Happold

4.8 Transformer TX8

KAFD Plot 3.09 Report Revision 0


Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB8-1-SM01 SMDB-18A


Connection From: TO-1 To: SMDB-18A
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 514.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 514.3
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 514.3 / 1.00 414.3 / 1.00 414.3 / 1.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.11 / 0.05 0.08 / 0.04 0.08 / 0.04 -----
Voltage Drop - From Source (V/%) 2.43 / 1.11 2.12 / 0.97 2.12 / 0.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02459 0.00027 0.00074 0.02557 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
8.56
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 5.85

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.388 / 14.480 Load End: 18.067 / 14.030
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.69 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 1 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB8-1-SM02 SMDB-21A


Connection From: TO-2 To: SMDB-21A
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 569.2

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 569.2
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 621.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 569.2 / 1.00 569.2 / 1.00 569.2 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.11 / 0.05 0.11 / 0.05 0.11 / 0.05 -----
Voltage Drop - From Source (V/%) 2.54 / 1.16 2.26 / 1.03 2.26 / 1.03 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02519 0.00027 0.00074 0.02617 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
8.37
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 5.70

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.114 / 14.048 Load End: 17.801 / 13.620
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.63 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 2 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-8-SM01 BB-MDB-8-1


Connection From: MDB 8 To: EF-1
Active Source: Tx 8
Load Type: Busbar EndFeed Design Current Ib (A): 1,083.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW12 H1 MLogic 5.0A High
Rating In (A):1250 [f] Overload Setting Ir (A): 1250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 51
31 - On horizontal/vertical perforated tray Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.87 [BS 7671, Table 4C5]
No. of trays = 2 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,083.5
Device Rating In = 1250 Overload Setting Ir = 1250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 412.9 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 736.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1083.5 / 1.00 983.5 / 1.00 983.5 / 1.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.08 / 0.49 0.95 / 0.43 0.95 / 0.43 -----
Voltage Drop - From Source (V/%) 1.42 / 0.65 1.29 / 0.59 1.29 / 0.59 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01390 0.00154 0.00750 0.02262 0.05309 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
9.68
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 71.87

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 21.962 / 20.361 Load End: 19.393 / 16.137
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 105.63 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 3 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM01 DB-18PA


Connection From: SMDB-18A/1/L1,L2,L3 To: DB-18PA
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 116.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 2.49 / 1.14 2.18 / 1.00 2.18 / 1.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.00334 0.00725 0.03209 0.38088 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.82
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.57

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 16.252 / 10.957
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 392.45 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 4 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM02 DB-18LA


Connection From: SMDB-18A/2/L1,L2,L3 To: DB-18LA
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 10.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.0 / 1.00 10.0 / 1.00 10.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.04 / 0.02 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 2.47 / 1.13 2.16 / 0.99 2.16 / 0.99 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.00464 0.00725 0.03301 0.47607 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.63
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.52

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 15.661 / 10.033
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 380.43 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 5 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM03 CU-1801


Connection From: SMDB-18A/3/L1 To: CU-1801
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 94.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 32
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 94.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 161.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 94.9 / 1.00 0.0 / 0.00 0.0 / 0.00 94.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.88 / 1.32 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.31 / 2.43 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.01603 0.02994 0.06437 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.40
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 6.689 / 5.110
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 246.57 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 6 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM04 CU-1803


Connection From: SMDB-18A/3/L3 To: CU-1803
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 89.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 89.5
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 159.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 89.5 / 1.00 89.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.22 / 1.47 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.34 / 2.44 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.01904 0.03555 0.07258 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.02
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.43

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 5.882 / 4.504
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 210.21 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 7 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM05 CU-1804


Connection From: SMDB-18A/4/L1 To: CU-1804
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 100.0 / 1.00 0.0 / 0.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.15 / 1.44 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 5.58 / 2.55 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.01653 0.03087 0.06573 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.33
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.62

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 6.540 / 4.998
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 239.88 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 8 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM06 CU-1805


Connection From: SMDB-18A/4/L2 To: CU-1805
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 100.0 / 1.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.72 / 1.70 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.84 / 2.67 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.01954 0.03649 0.07396 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.96
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.40

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 5.765 / 4.416
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 204.94 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 9 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM07 CU-1901


Connection From: SMDB-18A/4/L3 To: CU-1901
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 94.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 94.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 161.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 94.9 / 1.00 94.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.24 / 1.48 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.36 / 2.45 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.01804 0.03368 0.06983 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.14
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.50

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 6.130 / 4.690
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 221.37 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 10 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM08 CU-1902


Connection From: SMDB-18A/5/L1 To: CU-1902
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 100.0 / 1.00 0.0 / 0.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.10 / 1.87 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 6.53 / 2.98 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.02154 0.04023 0.07949 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.76
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.27

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 5.339 / 4.095
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 185.72 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 11 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM09 CU-1903


Connection From: SMDB-18A/5/L2 To: CU-1903
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 89.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 89.5
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 159.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 89.5 / 1.00 0.0 / 0.00 89.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.56 / 1.62 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.68 / 2.59 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.02104 0.03929 0.07810 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.80
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.30

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 5.440 / 4.171
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 190.26 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 12 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM10 CU-1904


Connection From: SMDB-18A/5/L3 To: CU-1904
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 37
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 100.0 / 1.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.53 / 1.61 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.65 / 2.58 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.01854 0.03461 0.07120 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.08
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.47

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 6.003 / 4.595
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 215.68 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 13 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM11 CU-1905


Connection From: SMDB-18A/6/L1 To: CU-1905
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 43
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 100.0 / 1.00 0.0 / 0.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.10 / 1.87 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 6.53 / 2.98 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.02154 0.04023 0.07949 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.76
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.27

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 5.339 / 4.095
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 185.72 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 14 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM12 CU-2001


Connection From: SMDB-18A/6/L2 To: CU-2001
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 94.9

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 94.9
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 161.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 94.9 / 1.00 0.0 / 0.00 94.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.60 / 1.65 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 5.72 / 2.61 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.02004 0.03742 0.07534 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.91
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.37

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 5.653 / 4.331
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 199.87 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 15 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM13 CU-2003


Connection From: SMDB-18A/7/L1 To: CU-2003
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 89.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 46
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 89.5
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 159.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 89.5 / 1.00 0.0 / 0.00 0.0 / 0.00 89.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 3.90 / 1.78 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 6.33 / 2.89 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.02305 0.04303 0.08366 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.62
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.18

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 5.058 / 3.883
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 172.98 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 16 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM14 CU-2004


Connection From: SMDB-18A/7/L2 To: CU-2004
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 41
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 100.0 / 1.00 0.0 / 0.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 3.91 / 1.79 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 6.03 / 2.75 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.02054 0.03836 0.07672 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.85
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.33

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 5.544 / 4.250
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 194.98 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 17 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-18A-SM15 CU-2005


Connection From: SMDB-18A/7/L3 To: CU-2005
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 100.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):125 [f] Overload Setting Ir (A): 125 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 2c Size (mm2): 50 [f]
Neutral: 50 mm²[a] Length (m): 46
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 15 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 16
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 100.0
Device Rating In = 125 Overload Setting Ir = 125 [Ir >
_ Ib]
Min. Cable Capacity Iz = 162.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 225.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 100.0 / 1.00 100.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 4.39 / 2.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 6.51 / 2.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02557 0.02305 0.04303 0.08366 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.62
Adiabatic check (mm 2 ) CPC Section = Separate 25 Total = 25.0 Min. Section = 2.18

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.067 / 14.030 Load End: 5.058 / 3.883
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 172.98 x 103 Adiabatic Limit k²S² (A²s): 51.12 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 18 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM01 DP-21PA


Connection From: SMDB-21A/1/L1,L2,L3 To: DB-21PA
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 116.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 2.60 / 1.19 2.33 / 1.06 2.33 / 1.06 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.00334 0.00725 0.03283 0.38088 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.67
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.53

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 16.011 / 10.662
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 388.60 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 19 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM02 DB-21LA


Connection From: SMDB-21A/2/L1,L2,L3 To: DB-21LA
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 10.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.0 / 1.00 10.0 / 1.00 10.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.04 / 0.02 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 2.59 / 1.18 2.31 / 1.05 2.31 / 1.05 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.00464 0.00725 0.03376 0.47607 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.49
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.48

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 15.429 / 9.777
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 371.64 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 20 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM03 CU-2101


Connection From: SMDB-21A/3/L1,L2,L3 To: CU-2101
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 66.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 31
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 66.6
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 125.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 66.6 / 1.00 66.6 / 1.00 66.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.86 / 0.85 1.86 / 0.85 1.86 / 0.85 -----
Voltage Drop - From Source (V/%) 4.41 / 2.01 4.13 / 1.88 4.13 / 1.88 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.02875 0.04495 0.08974 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.44
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.92

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 7.360 / 3.251
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 115.05 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 21 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM04 CU-2102


Connection From: SMDB-21A/4/L1,L2,L3 To: CU-2102
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 61.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 37
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 61.8
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 124.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 61.8 / 1.00 61.8 / 1.00 61.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.05 / 0.94 2.05 / 0.94 2.05 / 0.94 -----
Voltage Drop - From Source (V/%) 4.60 / 2.10 4.32 / 1.97 4.32 / 1.97 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.03431 0.05365 0.10359 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.11
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.73

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 6.474 / 2.797
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 91.07 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 22 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM05 CU-2103


Connection From: SMDB-21A/5/L1,L2,L3 To: CU-2103
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 63.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 32
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 63.4
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 124.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 63.4 / 1.00 63.4 / 1.00 63.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.82 / 0.83 1.82 / 0.83 1.82 / 0.83 -----
Voltage Drop - From Source (V/%) 4.37 / 1.99 4.09 / 1.87 4.09 / 1.87 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.02967 0.04640 0.09204 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.38
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.89

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 7.197 / 3.165
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 109.93 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 23 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM06 CU-2104


Connection From: SMDB-21A/6/L1,L2,L3 To: CU-2104
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 77.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 37
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 77.8
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 129.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 77.8 / 1.00 77.8 / 1.00 77.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.86 / 0.85 1.86 / 0.85 1.86 / 0.85 -----
Voltage Drop - From Source (V/%) 4.40 / 2.01 4.12 / 1.88 4.12 / 1.88 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.02473 0.05365 0.09429 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.32
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.85

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 8.048 / 3.658
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 139.49 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 24 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM07 CU-2301


Connection From: SMDB-21A/7/L1,L2,L3 To: CU-2301
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 66.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 38
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 66.6
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 125.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 66.6 / 1.00 66.6 / 1.00 66.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.28 / 1.04 2.28 / 1.04 2.28 / 1.04 -----
Voltage Drop - From Source (V/%) 4.83 / 2.20 4.55 / 2.08 4.55 / 2.08 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.03524 0.05510 0.10591 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.07
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.70

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 6.346 / 2.733
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 88.26 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 25 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM08 CU-2302


Connection From: SMDB-21A/8/L1,L2,L3 To: CU-2302
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 61.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 61.8
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 124.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 61.8 / 1.00 61.8 / 1.00 61.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.44 / 1.11 2.44 / 1.11 2.44 / 1.11 -----
Voltage Drop - From Source (V/%) 4.98 / 2.28 4.70 / 2.15 4.70 / 2.15 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.04080 0.06380 0.11987 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.83
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.58

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 5.666 / 2.404
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 73.77 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 26 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM09 CU-2303


Connection From: SMDB-21A/9/L1,L2,L3 To: CU-2303
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 63.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 63.4
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 124.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 63.4 / 1.00 63.4 / 1.00 63.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.22 / 1.02 2.22 / 1.02 2.22 / 1.02 -----
Voltage Drop - From Source (V/%) 4.77 / 2.18 4.49 / 2.05 4.49 / 2.05 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.03616 0.05655 0.10823 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.02
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.67

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 6.222 / 2.672
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 85.58 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 27 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-21A-SM10 CU-2304


Connection From: SMDB-21A/10/L1,L2,L3 To: CU-2304
Active Source: Tx 8
Load Type: Distribution Board Design Current Ib (A): 77.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 44
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 77.8
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 129.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 77.8 / 1.00 77.8 / 1.00 77.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.21 / 1.01 2.21 / 1.01 2.21 / 1.01 -----
Voltage Drop - From Source (V/%) 4.75 / 2.17 4.47 / 2.04 4.47 / 2.04 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02617 0.02941 0.06380 0.10873 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.01
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 17.801 / 13.620 Load End: 7.157 / 3.173
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 110.38 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 28 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 13/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-Tx8 MDB 8


Connection From: Tx 8 To: MDB 8
Active Source: Tx 8
Load Type: Main cable to Switchboard Design Current Ib (A): 1,215.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW20 H1 MLogic 5.0A High
Rating In (A):1600 [f] Overload Setting Ir (A): 1600 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 630 [f]
Neutral: 630 mm²[a] Length (m): 31
34 - On a ladder Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.93 [BS 7671, Table 4C5]
No. of ladders = 2 No. of circuits per ladder = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,215.4
Device Rating In = 1600 Overload Setting Ir = 1600 [Ir >
_ Ib]
Min. Cable Capacity Iz = 494.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 1,151.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1215.4 / 1.00 1215.4 / 1.00 1215.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.34 / 0.16 0.34 / 0.16 0.34 / 0.16 -----
Voltage Drop - From Source (V/%) 0.34 / 0.16 0.34 / 0.16 0.34 / 0.16 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 630 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00924 0.00078 0.00391 0.01390 0.01857 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
15.75
Adiabatic check (mm 2 ) CPC Section = Separate 630 Total = 630.0 Min. Section = 91.99

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 23.747 / 23.747 Load End: 21.962 / 20.361
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 173.06 x 106 Adiabatic Limit k²S² (A²s): 8,116.21 x 106

Project: KAFD 3.09 Tx 8 rev 0.p17 Page 29 of 29 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Buro Happold

4.9 Transformer TX9

KAFD Plot 3.09 Report Revision 0


Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB9-1-SM01 SMDB-25A


Connection From: TO-1 To: SMDB-25A
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 299.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS400N STR53UE
Rating In (A):400 [f] Overload Setting Ir (A): 400 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 299.6
Device Rating In = 400 Overload Setting Ir = 400 [Ir >
_ Ib]
Min. Cable Capacity Iz = 459.8 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 299.6 / 1.00 299.6 / 1.00 299.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.14 / 0.06 0.14 / 0.06 0.14 / 0.06 -----
Voltage Drop - From Source (V/%) 3.92 / 1.79 3.92 / 1.79 3.92 / 1.79 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 120 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02451 0.00062 0.00116 0.02614 0.07935 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
8.38
Adiabatic check (mm 2 ) CPC Section = Separate 120 Total = 120.0 Min. Section = 5.71

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.810 / 14.018 Load End: 18.989 / 13.058
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.09 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 1 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB9-1-SM02 MCC-27A


Connection From: TO-2 To: MCC-27A
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 406.3

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UET
Rating In (A):630 [f] Overload Setting Ir (A): 630 [m]
Earth fault protection: : 630A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 49
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 406.3
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 406.3 / 0.99 406.3 / 0.99 406.3 / 0.99 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.03 / 0.47 1.03 / 0.47 1.03 / 0.47 -----
Voltage Drop - From Source (V/%) 5.02 / 2.29 5.02 / 2.29 5.02 / 2.29 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02516 0.00304 0.00777 0.03579 0.28968 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
6.12
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 4.42

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.477 / 13.577 Load End: 16.058 / 10.005
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 950.93 x 103 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 2 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-BB-MDB9-1-SM03 SMDB-27A


Connection From: TO-3 To: SMDB-27A
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 526.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS630N STR53UE
Rating In (A):630 [f] Overload Setting Ir (A): 630 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 2 x 1 x 4c Size (mm2): 240 [f]
Neutral: 240 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.88 [BS 7671, Table 4C4]
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 526.1
Device Rating In = 630 Overload Setting Ir = 630 [Ir >
_ Ib]
Min. Cable Capacity Iz = 411.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 538.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 526.1 / 1.00 526.1 / 1.00 526.1 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.12 / 0.06 0.12 / 0.06 0.12 / 0.06 -----
Voltage Drop - From Source (V/%) 4.16 / 1.90 4.16 / 1.90 4.16 / 1.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 240 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02549 0.00031 0.00079 0.02657 0.07557 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
8.24
Adiabatic check (mm 2 ) CPC Section = Separate 240 Total = 240.0 Min. Section = 5.60

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 19.314 / 13.366 Load End: 18.913 / 12.910
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 45

Adiabatic Check: CPD Energy Let-through (A²s): 1.50 x 106 Adiabatic Limit k²S² (A²s): 1,177.86 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 3 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM01 3.09-27-EF-01


Connection From: Starter-1 To: 3.09-27-EF-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 59
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.42 / 0.65 1.42 / 0.65 1.42 / 0.65 -----
Voltage Drop - From Source (V/%) 6.44 / 2.94 6.44 / 2.94 6.44 / 2.94 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.23163 0.23305 0.48671 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.45
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 1.171 / 0.773
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 4 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM02 3.09-27-EF-01


Connection From: Starter-2 To: 3.09-27-EF-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 58
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.40 / 0.64 1.40 / 0.64 1.40 / 0.64 -----
Voltage Drop - From Source (V/%) 6.41 / 2.93 6.41 / 2.93 6.41 / 2.93 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.22771 0.22910 0.47885 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.46
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 1.190 / 0.785
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 5 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM03 3.09-27-EF-02


Connection From: Starter-3 To: 3.09-27-EF-02
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 57
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.37 / 0.63 1.37 / 0.63 1.37 / 0.63 -----
Voltage Drop - From Source (V/%) 6.39 / 2.92 6.39 / 2.92 6.39 / 2.92 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.22378 0.22515 0.47099 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.46
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 1.210 / 0.798
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 6 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM04 3.09-27-EF-02


Connection From: Starter-4 To: 3.09-27-EF-02
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 56
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.35 / 0.62 1.35 / 0.62 1.35 / 0.62 -----
Voltage Drop - From Source (V/%) 6.36 / 2.91 6.36 / 2.91 6.36 / 2.91 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.21985 0.22120 0.46313 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.47
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 1.231 / 0.812
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 7 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM05 3.09-27-GB-01


Connection From: Starter-5 To: 3.09-27-GB-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 5.6
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 5.61 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 4 [f]
Length (m): 50
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 5.6
Device Rating In = 20 Motor Overload Setting Ir = 5.61 [Ir >
_ Ib]
Min. Cable Capacity Iz = 6.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 42.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.6 / 0.74 5.6 / 0.74 5.6 / 0.74 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.03 / 0.47 1.03 / 0.47 1.03 / 0.47 -----
Voltage Drop - From Source (V/%) 6.05 / 2.76 6.05 / 2.76 6.05 / 2.76 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.28868 0.30000 0.61053 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 0.40
0.36
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 0.946 / 0.628
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 8 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM06 3.09-27-GB-01


Connection From: Starter-6 To: 3.09-27-GB-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 5.6
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 5.61 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 4 [f]
Length (m): 49
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 5.6
Device Rating In = 20 Motor Overload Setting Ir = 5.61 [Ir >
_ Ib]
Min. Cable Capacity Iz = 6.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 42.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.6 / 0.74 5.6 / 0.74 5.6 / 0.74 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.01 / 0.46 1.01 / 0.46 1.01 / 0.46 -----
Voltage Drop - From Source (V/%) 6.03 / 2.75 6.03 / 2.75 6.03 / 2.75 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.28290 0.29400 0.59877 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 0.40
0.37
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 0.965 / 0.640
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 9 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM07 3.09-27-GB-01


Connection From: Starter-7 To: 3.09-27-GB-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 5.6
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 5.61 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 4 [f]
Length (m): 47
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 5.6
Device Rating In = 20 Motor Overload Setting Ir = 5.61 [Ir >
_ Ib]
Min. Cable Capacity Iz = 6.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 42.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.6 / 0.74 5.6 / 0.74 5.6 / 0.74 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.97 / 0.44 0.97 / 0.44 0.97 / 0.44 -----
Voltage Drop - From Source (V/%) 5.99 / 2.73 5.99 / 2.73 5.99 / 2.73 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.27135 0.28200 0.57525 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.38
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 1.005 / 0.666
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 53.00 x 103 Adiabatic Limit k²S² (A²s): 327.18 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 10 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM08 3.09-27-AHU-01


Connection From: Starter-8 To: 3.09-27-AHU-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 12.5
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 12.46 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 31
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 12.5
Device Rating In = 20 Motor Overload Setting Ir = 12.46 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.3 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 12.5 / 0.78 12.5 / 0.78 12.5 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.03 / 0.47 1.03 / 0.47 1.03 / 0.47 -----
Voltage Drop - From Source (V/%) 6.04 / 2.76 6.04 / 2.76 6.04 / 2.76 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.12171 0.12245 0.26689 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.82
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 2.154 / 1.393
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 57.24 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 11 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM09 3.09-27-AHU-01


Connection From: Starter-9 To: 3.09-27-AHU-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 12.5
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 12.46 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 12.5
Device Rating In = 20 Motor Overload Setting Ir = 12.46 [Ir >
_ Ib]
Min. Cable Capacity Iz = 14.3 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 12.5 / 0.78 12.5 / 0.78 12.5 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.99 / 0.45 0.99 / 0.45 0.99 / 0.45 -----
Voltage Drop - From Source (V/%) 6.01 / 2.74 6.01 / 2.74 6.01 / 2.74 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.11778 0.11850 0.25906 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.85
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 2.221 / 1.434
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 58.78 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 12 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM10 3.09-27-AHU-01


Connection From: Starter-10 To: 3.09-27-AHU-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 29
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 5.71 / 2.61 5.71 / 2.61 5.71 / 2.61 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.11385 0.11455 0.25124 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.87
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 2.291 / 1.477
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 60.40 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 13 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM11 3.09-27-AHU-01


Connection From: Starter-11 To: 3.09-27-AHU-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.72 / 0.33 0.72 / 0.33 0.72 / 0.33 -----
Voltage Drop - From Source (V/%) 5.74 / 2.62 5.74 / 2.62 5.74 / 2.62 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.11778 0.11850 0.25906 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.85
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 2.221 / 1.434
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 58.78 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 14 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM12 3.09-27-AHU-01


Connection From: MCC-27A/12/L1,L2,L3 To: 3.09-27-AHU-01
Active Source: Tx 9
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 74.5

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 31
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 74.5
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 74.5 / 1.00 74.5 / 1.00 74.5 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.97 / 0.90 1.97 / 0.90 1.97 / 0.90 -----
Voltage Drop - From Source (V/%) 6.98 / 3.19 6.98 / 3.19 6.98 / 3.19 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.02875 0.04495 0.09981 0.18252 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.19
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.72

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 6.855 / 2.949
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 93.76 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 15 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM13 3.09-27-DB-01


Connection From: Starter-12 To: 3.09-27-DB-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.72 / 0.33 0.72 / 0.33 0.72 / 0.33 -----
Voltage Drop - From Source (V/%) 5.74 / 2.62 5.74 / 2.62 5.74 / 2.62 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.11778 0.11850 0.25906 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.85
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 2.221 / 1.434
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 58.78 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 16 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM14 3.09-27-DB-01


Connection From: Starter-13 To: 3.09-27-DB-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 29
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.70 / 0.32 0.70 / 0.32 0.70 / 0.32 -----
Voltage Drop - From Source (V/%) 5.71 / 2.61 5.71 / 2.61 5.71 / 2.61 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.11385 0.11455 0.25124 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.87
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 2.291 / 1.477
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 60.40 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 17 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM15 3.09-27-DB-01


Connection From: Starter-14 To: 3.09-27-DB-01
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 28
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.67 / 0.31 0.67 / 0.31 0.67 / 0.31 -----
Voltage Drop - From Source (V/%) 5.69 / 2.60 5.69 / 2.60 5.69 / 2.60 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.10993 0.11060 0.24342 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.90
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 2.366 / 1.523
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 62.13 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 18 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM16 3.09-27-AHU-02


Connection From: Starter-15 To: 3.09-27-AHU-02
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 32.2
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 32.18 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 26
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 32.2
Device Rating In = 40 Motor Overload Setting Ir = 32.18 [Ir >
_ Ib]
Min. Cable Capacity Iz = 37.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 32.2 / 0.78 32.2 / 0.78 32.2 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.35 / 0.61 1.35 / 0.61 1.35 / 0.61 -----
Voltage Drop - From Source (V/%) 6.36 / 2.90 6.36 / 2.90 6.36 / 2.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.06004 0.06110 0.14521 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.51
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.73

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 4.038 / 2.513
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 113.32 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 19 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM17 3.09-27-AHU-02


Connection From: Starter-16 To: 3.09-27-AHU-02
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 32.2
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):40 [f] Overload Setting Ir (A): 32.18 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 10 [f]
Length (m): 27
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 32.2
Device Rating In = 40 Motor Overload Setting Ir = 32.18 [Ir >
_ Ib]
Min. Cable Capacity Iz = 37.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 32.2 / 0.78 32.2 / 0.78 32.2 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.40 / 0.64 1.40 / 0.64 1.40 / 0.64 -----
Voltage Drop - From Source (V/%) 6.41 / 2.93 6.41 / 2.93 6.41 / 2.93 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.06235 0.06345 0.14978 0.48476 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
1.46
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 1.71

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 3.911 / 2.440
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 108.60 x 103 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 20 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM18 3.09-27-AHU-02


Connection From: Starter-17 To: 3.09-27-AHU-02
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.72 / 0.33 0.72 / 0.33 0.72 / 0.33 -----
Voltage Drop - From Source (V/%) 5.74 / 2.62 5.74 / 2.62 5.74 / 2.62 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.11778 0.11850 0.25906 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.85
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 2.221 / 1.434
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 58.78 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 21 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM19 3.09-27-AHU-02


Connection From: Starter-18 To: 3.09-27-AHU-02
Active Source: Tx 9
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 9.1
Motor Starter Position: at MCC-27A
Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22ME
Rating In (A):20 [f] Overload Setting Ir (A): 9.11 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 3c Size (mm2): 6 [f]
Length (m): 31
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 9.1
Device Rating In = 20 Motor Overload Setting Ir = 9.11 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 54.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.1 / 0.78 9.1 / 0.78 9.1 / 0.78 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.75 / 0.34 0.75 / 0.34 0.75 / 0.34 -----
Voltage Drop - From Source (V/%) 5.76 / 2.63 5.76 / 2.63 5.76 / 2.63 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.12171 0.12245 0.26689 0.70197 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
0.82
Adiabatic check (mm 2 ) CPC Section = Separate 6 Total = 6.0 Min. Section = 1.61

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 2.154 / 1.393
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 57.24 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 22 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MCC-27A-SM20 3.09-27-AHU-02


Connection From: MCC-27A/20/L1,L2,L3 To: 3.09-27-AHU-02
Active Source: Tx 9
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 240.1

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS250N STR22SE
Rating In (A):250 [f] Overload Setting Ir (A): 250 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 95 [f]
Neutral: 95 mm²[a] Length (m): 33
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 240.1
Device Rating In = 250 Overload Setting Ir = 250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 287.4 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 298.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 240.1 / 1.00 240.1 / 1.00 240.1 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.93 / 0.88 1.93 / 0.88 1.93 / 0.88 -----
Voltage Drop - From Source (V/%) 6.94 / 3.17 6.94 / 3.17 6.94 / 3.17 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 50 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.03579 0.00856 0.01693 0.05804 0.15237 Current (kA)

Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 5.00
3.77
Adiabatic check (mm 2 ) CPC Section = Separate 50 Total = 50.0 Min. Section = 3.66

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 16.058 / 10.005 Load End: 11.381 / 5.879
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 373.93 x 103 Adiabatic Limit k²S² (A²s): 184.55 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 23 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-MDB-9-SM01 BB-MDB9-1


Connection From: MDB 9 To: EF-1
Active Source: Tx 9
Load Type: Busbar EndFeed Design Current Ib (A): 1,228.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW12 H1 MLogic 5.0A High
Rating In (A):1250 [f] Overload Setting Ir (A): 1250 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 3 x 4 x 1c Size (mm2): 300 [f]
Neutral: 300 mm²[a] Length (m): 49
31 - On horizontal/vertical perforated tray Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.87 [BS 7671, Table 4C5]
No. of trays = 1 No. of circuits per tray = 3
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,228.0
Device Rating In = 1250 Overload Setting Ir = 1250 [Ir >
_ Ib]
Min. Cable Capacity Iz = 550.5 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 736.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1228.0 / 1.00 1228.0 / 1.00 1228.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.59 / 0.73 1.59 / 0.73 1.59 / 0.73 -----
Voltage Drop - From Source (V/%) 1.98 / 0.90 1.98 / 0.90 1.98 / 0.90 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 300 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.01172 0.00197 0.00721 0.02058 0.05309 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
10.64
Adiabatic check (mm 2 ) CPC Section = Separate 300 Total = 300.0 Min. Section = 71.87

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 26.807 / 24.669 Load End: 22.191 / 17.487
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 122.32 x 106 Adiabatic Limit k²S² (A²s): 1,840.41 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 24 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-25A-SM01 DB-25PA


Connection From: SMDB-25A/1/L1,L2,L3 To: DB-25PA
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 115.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 3.98 / 1.82 3.98 / 1.82 3.98 / 1.82 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02614 0.00334 0.00725 0.03348 0.38088 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.54
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.50

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.989 / 13.058 Load End: 16.777 / 10.112
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 381.46 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 25 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-25A-SM02 DB-25LA


Connection From: SMDB-25A/2/L1,L2,L3 To: DB-25LA
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 10.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.0 / 1.00 10.0 / 1.00 10.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.04 / 0.02 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 3.96 / 1.81 3.96 / 1.81 3.96 / 1.81 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02614 0.00464 0.00725 0.03448 0.47607 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.35
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.45

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.989 / 13.058 Load End: 16.073 / 9.267
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 352.50 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 26 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-25A-SM03 CU-2501


Connection From: SMDB-25A/3/L1,L2,L3 To: CU-2501
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 66.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 32
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 66.6
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 125.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 66.6 / 1.00 66.6 / 1.00 66.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.92 / 0.88 1.92 / 0.88 1.92 / 0.88 -----
Voltage Drop - From Source (V/%) 5.84 / 2.66 5.84 / 2.66 5.84 / 2.66 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02614 0.02967 0.04640 0.09376 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.34
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.86

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.989 / 13.058 Load End: 7.205 / 3.089
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 105.32 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 27 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-25A-SM04 CU-2502


Connection From: SMDB-25A/4/L1,L2,L3 To: CU-2502
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 61.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 37
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 61.8
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 123.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 61.8 / 1.00 61.8 / 1.00 61.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.05 / 0.94 2.05 / 0.94 2.05 / 0.94 -----
Voltage Drop - From Source (V/%) 5.96 / 2.72 5.96 / 2.72 5.96 / 2.72 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02614 0.03431 0.05365 0.10536 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.08
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.71

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.989 / 13.058 Load End: 6.473 / 2.736
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 88.40 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 28 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-25A-SM05 CU-2503


Connection From: SMDB-25A/5/L1,L2,L3 To: CU-2503
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 63.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 32
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 63.4
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 124.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 63.4 / 1.00 63.4 / 1.00 63.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.82 / 0.83 1.82 / 0.83 1.82 / 0.83 -----
Voltage Drop - From Source (V/%) 5.74 / 2.62 5.74 / 2.62 5.74 / 2.62 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02614 0.02967 0.04640 0.09376 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.34
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.86

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.989 / 13.058 Load End: 7.205 / 3.089
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 105.32 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 29 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-25A-SM06 CU-2504


Connection From: SMDB-25A/6/L1,L2,L3 To: CU-2504
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 77.8

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 37
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 77.8
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 128.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 77.8 / 1.00 77.8 / 1.00 77.8 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.85 / 0.85 1.85 / 0.85 1.85 / 0.85 -----
Voltage Drop - From Source (V/%) 5.77 / 2.63 5.77 / 2.63 5.77 / 2.63 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02614 0.02473 0.05365 0.09602 0.14601 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
2.28
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 1.83

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.989 / 13.058 Load End: 8.083 / 3.559
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 133.52 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 30 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-27A-SM01 DB-27PA


Connection From: SMDB-27A/1/L1,L2,L3 To: DB-27PA
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):100 [f] Overload Setting Ir (A): 100 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 35 [f]
Neutral: 35 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 20.0
Device Rating In = 100 Overload Setting Ir = 100 [Ir >
_ Ib]
Min. Cable Capacity Iz = 115.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 158.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.06 / 0.03 0.06 / 0.03 -----
Voltage Drop - From Source (V/%) 4.23 / 1.93 4.23 / 1.93 4.23 / 1.93 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02657 0.00334 0.00725 0.03396 0.38088 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.45
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.47

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.913 / 12.910 Load End: 16.702 / 10.000
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 380.00 x 103 Adiabatic Limit k²S² (A²s): 25.05 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 31 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-27A-SM02 DB-27LA


Connection From: SMDB-27A/2/L1,L2,L3 To: DB-27LA
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 10.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N STR22SE
Rating In (A):80 [f] Overload Setting Ir (A): 80 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 25 [f]
Neutral: 25 mm²[a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.0
Device Rating In = 80 Overload Setting Ir = 80 [Ir >
_ Ib]
Min. Cable Capacity Iz = 92.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 127.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.0 / 1.00 10.0 / 1.00 10.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.04 / 0.02 0.04 / 0.02 -----
Voltage Drop - From Source (V/%) 4.21 / 1.92 4.21 / 1.92 4.21 / 1.92 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02657 0.00464 0.00725 0.03496 0.47607 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
6.26
Adiabatic check (mm 2 ) CPC Section = Separate 16 Total = 16.0 Min. Section = 3.43

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.913 / 12.910 Load End: 15.999 / 9.167
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 348.77 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 32 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-27A-SM03 CU-2801


Connection From: SMDB-27A/3/L1,L2,L3 To: CU-2801
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 123.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 36
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 123.0
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 205.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 123.0 / 1.00 123.0 / 1.00 123.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.46 / 0.67 1.46 / 0.67 1.46 / 0.67 -----
Voltage Drop - From Source (V/%) 5.63 / 2.57 5.63 / 2.57 5.63 / 2.57 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02657 0.01256 0.02478 0.05943 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.68
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 3.04

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.913 / 12.910 Load End: 11.320 / 5.593
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 281.68 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 33 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-27A-SM04 CU-2802


Connection From: SMDB-27A/4/L1,L2,L3 To: CU-2802
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 127.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 39
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 127.6
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 207.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 127.6 / 1.00 127.6 / 1.00 127.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.65 / 0.75 1.65 / 0.75 1.65 / 0.75 -----
Voltage Drop - From Source (V/%) 5.82 / 2.66 5.82 / 2.66 5.82 / 2.66 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02657 0.01360 0.02685 0.06240 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.51
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.95

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.913 / 12.910 Load End: 10.906 / 5.321
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 269.44 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 34 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-27A-SM05 CU-2803


Connection From: SMDB-27A/5/L1,L2,L3 To: CU-2803
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 121.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 121.0
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 204.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 121.0 / 1.00 121.0 / 1.00 121.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.68 / 0.77 1.68 / 0.77 1.68 / 0.77 -----
Voltage Drop - From Source (V/%) 5.84 / 2.67 5.84 / 2.67 5.84 / 2.67 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02657 0.01465 0.02891 0.06538 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.35
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.86

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.913 / 12.910 Load End: 10.518 / 5.073
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 258.29 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 35 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-SMDB-27A-SM06 CU-2804


Connection From: SMDB-27A/6/L1,L2,L3 To: CU-2804
Active Source: Tx 9
Load Type: Distribution Board Design Current Ib (A): 124.6

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Compact MCCB NS160N TM D
Rating In (A):160 [f] Overload Setting Ir (A): 160 [m]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm²[a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =6 Cg = 0.73 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 6
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 124.6
Device Rating In = 160 Overload Setting Ir = 160 [Ir >
_ Ib]
Min. Cable Capacity Iz = 206.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 246.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 124.6 / 1.00 124.6 / 1.00 124.6 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.65 / 0.75 1.65 / 0.75 1.65 / 0.75 -----
Voltage Drop - From Source (V/%) 5.81 / 2.65 5.81 / 2.65 5.81 / 2.65 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 35 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.02657 0.01395 0.02753 0.06339 0.14260 Current (kA)

Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
3.45
Adiabatic check (mm 2 ) CPC Section = Separate 35 Total = 35.0 Min. Section = 2.92

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 18.913 / 12.910 Load End: 10.774 / 5.236
Protective Device Breaking Capacity (kA): Icu: 36 Ics: 36

Adiabatic Check: CPD Energy Let-through (A²s): 265.61 x 103 Adiabatic Limit k²S² (A²s): 100.20 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 36 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable CAB-Tx9 MDB 9


Connection From: Tx 9 To: MDB 9
Active Source: Tx 9
Load Type: Main cable to Switchboard Design Current Ib (A): 1,519.4

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Masterpact NW ACB NW20 H1 MLogic 5.0A High
Rating In (A):2000 [f] Overload Setting Ir (A): 1600 [f]

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 4 x 4 x 1c Size (mm2): 630 [f]
Neutral: 630 mm²[a] Length (m): 28
34 - On a ladder Configuration: Flat Touching Arrangement: Horizontal Flat Touching

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 0.97 [BS 7671, Table 4C5]
No. of ladders = 1 No. of circuits per ladder = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1,519.4
Device Rating In = 2000 Overload Setting Ir = 1600 [Ir >
_ Ib]
Min. Cable Capacity Iz = 474.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 1,151.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1519.4 / 1.00 1519.4 / 1.00 1519.4 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.39 / 0.18 0.39 / 0.18 0.39 / 0.18 -----
Voltage Drop - From Source (V/%) 0.39 / 0.18 0.39 / 0.18 0.39 / 0.18 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 630 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.00751 0.00071 0.00353 0.01172 0.02515 Current (kA)

Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 5.00
18.69
Adiabatic check (mm 2 ) CPC Section = Separate 630 Total = 630.0 Min. Section = 114.99

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 29.229 / 29.229 Load End: 26.807 / 24.669
Protective Device Breaking Capacity (kA): Icu: 65 Ics: 65

Adiabatic Check: CPD Energy Let-through (A²s): 270.40 x 106 Adiabatic Limit k²S² (A²s): 8,116.21 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 37 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable Cbl_FC-1 PRIVATE LIFT


Connection From: CU-2804/1/L1,L2,L3 To: PRIVATE LIFT
Active Source: Tx 9
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Multi9 MCB C60H Type B BS EN60947-2
Rating In (A):20 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 10 [f]
Neutral: 10 mm²[a] Length (m): 30
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 20.0
Device Rating In = 20 Overload Setting Ir = N/A [Ir >
_ Ib]
Min. Cable Capacity Iz = 23.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.21 / 0.55 1.21 / 0.55 1.21 / 0.55 -----
Voltage Drop - From Source (V/%) 7.02 / 3.21 7.02 / 3.21 7.02 / 3.21 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.06339 0.06928 0.07050 0.19780 2.18997 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.11
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 0.59

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 10.774 / 5.236 Load End: 3.112 / 1.242
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 38 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable Cbl_FC-2 PRIVATE LIFT


Connection From: CU-2803/1/L1,L2,L3 To: PRIVATE LIFT
Active Source: Tx 9
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Multi9 MCB C60H Type B BS EN60947-2
Rating In (A):20 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 10 [f]
Neutral: 10 mm²[a] Length (m): 30
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 20.0
Device Rating In = 20 Overload Setting Ir = N/A [Ir >
_ Ib]
Min. Cable Capacity Iz = 23.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.21 / 0.55 1.21 / 0.55 1.21 / 0.55 -----
Voltage Drop - From Source (V/%) 7.05 / 3.22 7.05 / 3.22 7.05 / 3.22 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.06538 0.06928 0.07050 0.19987 2.18997 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.10
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 0.59

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 10.518 / 5.073 Load End: 3.088 / 1.232
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 39 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable Cbl_FC-3 PRIVATE LIFT


Connection From: CU-2802/1/L1,L2,L3 To: PRIVATE LIFT
Active Source: Tx 9
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Multi9 MCB C60H Type B BS EN60947-2
Rating In (A):20 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 10 [f]
Neutral: 10 mm²[a] Length (m): 30
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 20.0
Device Rating In = 20 Overload Setting Ir = N/A [Ir >
_ Ib]
Min. Cable Capacity Iz = 23.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.21 / 0.55 1.21 / 0.55 1.21 / 0.55 -----
Voltage Drop - From Source (V/%) 7.02 / 3.21 7.02 / 3.21 7.02 / 3.21 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.06240 0.06928 0.07050 0.19676 2.18997 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.11
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 0.59

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 10.906 / 5.321 Load End: 3.124 / 1.246
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 40 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Cable Calculation Report

Project Reference: ProDesign Job Number:


Document No: Created On : 14/12/2010 Rev Date :
Created By : tgilchri Modified By: Rev No:

Calculated in accordance with BS7671

Cable Cbl_FC-4 PRIVATE LIFT


Connection From: CU-2801/1/L1,L2,L3 To: PRIVATE LIFT
Active Source: Tx 9
Load Type: Fixed equipment three phase and neutral Design Current Ib (A): 20.0

Comments

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.


Overcurrent protection: Merlin Gerin Multi9 MCB C60H Type B BS EN60947-2
Rating In (A):20 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double


Multicore, 90°C thermosetting insulated/sheathed, non-arm Cu Table 4E2 1 x 1 x 4c Size (mm2): 10 [f]
Neutral: 10 mm²[a] Length (m): 30
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature(°C) = 45.0 Ca = 0.87 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00


CPD and Installation Factor Cc = 1.00 [Factor: 0.725 for CPD type BS 30365; 0.9 for Installation Methods 70-73]

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 8.76 V (User defined)
Design Current Ib = 20.0
Device Rating In = 20 Overload Setting Ir = N/A [Ir >
_ Ib]
Min. Cable Capacity Iz = 23.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 75.0 [It >
_ Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.0 / 1.00 20.0 / 1.00 20.0 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.21 / 0.55 1.21 / 0.55 1.21 / 0.55 -----
Voltage Drop - From Source (V/%) 6.84 / 3.12 6.84 / 3.12 6.84 / 3.12 -----

Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 10 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Ze Z1 Z2 Zs Max. Zs Earth Fault


Impedance ( ): 0.05943 0.06928 0.07050 0.19366 2.18997 Current (kA)

Disconnection time (s): From characteristic: 0.01 Maximum for circuit: 0.40
1.13
Adiabatic check (mm 2 ) CPC Section = Separate 10 Total = 10.0 Min. Section = 0.59

Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 11.320 / 5.593 Load End: 3.161 / 1.261
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 2.04 x 106

Project: KAFD 3.09 Tx 9 rev 0.p17 Page 41 of 41 Printed on: 14/04/2011


Created using: v17.0.1 (BS7671:2008) - Buro Happold Ltd Copyright © AMTECH Power Software Ltd 2010
Buro Happold

5.0 Lighting Calculations

KAFD Plot 3.09 Report Revision 0


Buro Happold

5.1 Substructure Package Normal


Lighting Calculations

KAFD Plot 3.09 Report Revision 0


3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
10.01.2011

Operator
Telephone
Fax
e-Mail

Retail Lobby (West) / Summary

13.76 m

12.64
11.64

9.95
160 9.24
160 160 120 8.45
7.47
120
160
120 6.12
120 160 5.45
160
160 4.45
160
120 3.30
160

0.70
0.00
0.00 4.87 6.31 7.64 9.02 10.86 13.55 m

Height of Room: 2.300 m, Mounting Height: 2.410 m, Maintenance factor: Values in Lux, Scale 1:177
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 126 7.73 189 0.062
Floor 20 102 1.07 189 0.011
Ceiling 70 21 1.09 57 0.052
Walls (4) 50 44 1.55 242 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.354, Ceiling / Working Plane: 0.167.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 10 Zumtobel 42177424 SLOT2 1x1/35W LRO LDE IP40 [STD] (1.000) 3300 38.6
Total: 33000 386.0

Specific connected load: 4.13 W/m² = 3.29 W/m²/100 lx (Ground area: 93.49 m²)

Page 1
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
10.01.2011

Operator
Telephone
Fax
e-Mail

Office Lobby (West) / Summary

14.06 m
13.05

10.89
10.11

8.30
120
6.77
6.10
120 5.31
150
4.57
120
120 2.98
150 1.98

0.70
0.00
0.00 1.60 4.02 5.36 6.72 8.54 11.50 m

Height of Room: 2.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:181

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 121 76 208 0.626
Floor 20 113 47 200 0.413
Ceiling 70 22 15 36 0.693
Walls (26) 50 46 14 155 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.376, Ceiling / Working Plane: 0.178.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 5 ERCO 83260000 Compact 100 Downlight 2xTC-DEL 13W (1.000) 1800 26.0
2 4 ERCO 88100000 Gimbal Recessed spotlight 1xQR-CBC35 20W 38° (1.000) 320 20.0
3 3 Zumtobel 42177422 SLOT2 1x1/28W LRO LDE IP40 [STD] (1.000) 2600 30.5
Total: 18080 301.5

Specific connected load: 5.77 W/m² = 4.76 W/m²/100 lx (Ground area: 52.24 m²)

Page 2
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
10.01.2011

Operator
Telephone
Fax
e-Mail

Residential Lobby (West) / Summary

7.64 m

6.93
120
120
130 5.61
130
130 130
130
120
130 130
120 130
130 130 2.06

0.71

0.00
0.00 2.30 4.72 7.03 m

Height of Room: 2.300 m, Mounting Height: 2.500 m, Maintenance factor: Values in Lux, Scale 1:99
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 123 92 133 0.750
Floor 20 107 50 133 0.467
Ceiling 70 16 11 18 0.712
Walls (4) 50 28 11 63 /

Workplane:
Height: 0.000 m
Grid: 32 x 64 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.227, Ceiling / Working Plane: 0.129.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel 60811226 PANOS Q HM 1/26W TC-TELI EVG 250 TI [STD]
1 3 1800 28.5
(1.000)
Total: 5400 85.5

Specific connected load: 3.78 W/m² = 3.09 W/m²/100 lx (Ground area: 22.61 m²)

Page 3
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
10.01.2011

Operator
Telephone
Fax
e-Mail

Office Lobby (East) / Summary

14.12 m
13.43
150
120 120 11.65

120 120
150 8.63
120
7.96
150
7.30
120 6.59
180 5.90
150
5.01
4.11

1.51
0.70
0.00
0.00 1.98 7.36 8.80 10.77 12.71 14.74 18.76 m

Height of Room: 2.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:182

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 129 65 192 0.504
Floor 20 117 33 190 0.282
Ceiling 70 22 13 50 0.588
Walls (26) 50 47 13 196 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.362, Ceiling / Working Plane: 0.173.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 6 ERCO 83260000 Compact 100 Downlight 2xTC-DEL 13W (1.000) 1800 26.0
2 4 ERCO 88100000 Gimbal Recessed spotlight 1xQR-CBC35 20W 38° (1.000) 320 20.0
3 5 Zumtobel 42177422 SLOT2 1x1/28W LRO LDE IP40 [STD] (1.000) 2600 30.5
Total: 25080 388.5

Specific connected load: 5.45 W/m² = 4.24 W/m²/100 lx (Ground area: 71.24 m²)

Page 4
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
10.01.2011

Operator
Telephone
Fax
e-Mail

Staircases / Summary

6.63 m

5.92

5.33
80
4.89
4.55

60
20

40
20

20 1.76

0.71

0.00
0.00 0.70 1.84 2.67 4.13 5.39 6.09 m

Height of Room: 7.000 m, Maintenance factor: 0.50 Values in Lux, Scale 1:86

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 32 3.72 82 0.115
Floor 20 32 3.39 83 0.107
Ceiling 70 25 17 31 0.673
Walls (4) 50 58 2.93 589 /

Workplane:
Height: 0.000 m
Grid: 32 x 16 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.827, Ceiling / Working Plane: 0.776.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 13200 153.0

Specific connected load: 9.09 W/m² = 28.13 W/m²/100 lx (Ground area: 16.83 m²)

Page 5
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
10.01.2011

Operator
Telephone
Fax
e-Mail

Staircases / 3D Rendering

Page 6
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
10.01.2011

Operator
Telephone
Fax
e-Mail

Staircases / False Colour Rendering

0 25 50 75 100 125 150 175 200 lx

Page 7
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

B4 Car Park / Single Sheet Output

107.68 m
100.29
93.86
88.50
83.51
78.39
73.33
68.36
62.82
150 57.70
150
52.53
150
120 150 47.35
42.25
37.07
31.90
26.73
21.43
16.25
120 11.11
5.84
0.00
0.00 10.60 23.03 35.45 47.85 61.87 74.41 86.83 100.11 124.05 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:1383
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 126 27 160 0.213
Floor 20 125 14 159 0.112
Ceiling 50 62 9.20 682 0.148
Walls (96) 40 102 1.71 3054 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.825, Ceiling / Working Plane: 0.481.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 209 Zumtobel 42174402 SCUBA PC 1/58W T26 EVG V2A [STD] (1.000) 5200 54.0
Total: 1086800 11286.0

Specific connected load: 2.67 W/m² = 2.12 W/m²/100 lx (Ground area: 4222.99 m²)

Page 1
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Air Extract Fan Chamber (West) / Summary

6.76 m

6.05

240
240 270

300 300
240 270 270
240 3.62
210 270 300
300 270 3.13
240 300
270 240

240
240
210

0.70

0.00
0.00 0.70 2.71 4.23 6.24 6.95 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:87
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 254 182 313 0.717
Floor 20 177 126 223 0.713
Ceiling 50 126 49 594 0.392
Walls (4) 40 159 87 380 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.678, Ceiling / Working Plane: 0.498.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 9.24 W/m² = 3.64 W/m²/100 lx (Ground area: 23.16 m²)

Page 6
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Air Supply Fan Chamber (West) / Summary

15.86 m

250 12.93
250 11.94
250 250
250 250
250 250
250 9.50
250

250 250 250


250
250 6.13
250 250 5.00
250
250
3.78
250 250
2.67

0.00
0.00 2.07 4.75 7.57 9.51 12.73 17.29 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:204
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 227 87 289 0.381
Floor 20 197 38 250 0.191
Ceiling 50 104 27 592 0.263
Walls (8) 40 165 54 325 /

Workplane:
Height: 0.800 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.769, Ceiling / Working Plane: 0.458.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 8 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 83200 856.0

Specific connected load: 6.86 W/m² = 3.02 W/m²/100 lx (Ground area: 124.76 m²)

Page 7
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Air Extract Fan Chamber (East) / Summary

6.47 m

150

180
180 180

180 210
150 210 180
150
210 3.15
210
120 180 210 180
210 2.53
150
180 180
180 180

0.00
0.00 2.77 6.16 7.50 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:84
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 171 101 220 0.594
Floor 20 171 98 219 0.572
Ceiling 50 117 39 590 0.332
Walls (4) 40 146 66 324 /

Workplane:
Height: 0.000 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.856, Ceiling / Working Plane: 0.684.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 8.45 W/m² = 4.96 W/m²/100 lx (Ground area: 25.31 m²)

Page 8
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Comms Room (West) / Summary

4.49 m

360

420 420 360


420
420 2.87
420
480 360
420 420
480
360 420
420 1.62
420
420
360 360

0.00
0.00 1.34 3.47 4.81 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:58
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 378 228 484 0.603
Floor 20 264 202 315 0.764
Ceiling 50 115 92 149 0.800
Walls (4) 40 247 100 583 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 20 17
Grid: 32 x 16 Points Lower Wall 21 16
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.720, Ceiling / Working Plane: 0.305.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 13200 153.0

Specific connected load: 16.19 W/m² = 4.28 W/m²/100 lx (Ground area: 9.45 m²)

Page 9
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Elec Room (West) / Summary

2.88 m

270
300
300 300 270
330
330 330 300 270
300
330 1.54
330 300 240
270
300 330 330 1.34
270
330 330
300 330 300
270
300
270

240

0.00
0.00 1.28 1.62 2.89 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:37
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 292 214 354 0.730
Floor 20 182 154 204 0.848
Ceiling 50 85 69 98 0.811
Walls (4) 40 226 71 565 /

Workplane:
Height: 0.800 m
Grid: 16 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.893, Ceiling / Working Plane: 0.292.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 18.21 W/m² = 6.23 W/m²/100 lx (Ground area: 4.20 m²)

Page 10
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Emerg Elec Room (West) / Summary

3.26 m

240

280 280 240


280
280 320 320 240
320
320
1.72
240 280 320 320
280 1.54
200 320 320
240
280
280
240

200

0.00
0.00 1.27 2.08 3.36 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:42
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 262 171 340 0.653
Floor 20 168 134 195 0.796
Ceiling 50 73 55 84 0.756
Walls (4) 40 191 62 547 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.830, Ceiling / Working Plane: 0.277.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 14.17 W/m² = 5.41 W/m²/100 lx (Ground area: 5.40 m²)

Page 11
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Store (West) / Summary

2.85 m

120
140
140
120
140
140
1.66

140 140 120


120
100 1.19
140
120 140
140
120
100

0.00
0.00 0.99 2.00 2.99 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:37
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 129 91 160 0.703
Floor 20 78 65 89 0.825
Ceiling 50 49 35 60 0.719
Walls (4) 40 124 36 433 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.145, Ceiling / Working Plane: 0.377.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174377 SCUBA PC 1/35W T16 EVG V2A [STD] (1.000) 3300 38.5
Total: 3300 38.5

Specific connected load: 9.55 W/m² = 7.38 W/m²/100 lx (Ground area: 4.03 m²)

Page 12
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Landlords Store (West) / Summary

3.17 m
100
120

140 120
140

140 120
140 100

120 140 140 120 1.55

140
120 140
140

120

0.00
0.00 1.34 1.87 3.21 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:41
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 126 91 151 0.719
Floor 20 79 65 88 0.819
Ceiling 50 46 35 75 0.761
Walls (4) 40 109 37 281 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.006, Ceiling / Working Plane: 0.363.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174377 SCUBA PC 1/35W T16 EVG V2A [STD] (1.000) 3300 38.5
Total: 3300 38.5

Specific connected load: 7.54 W/m² = 5.98 W/m²/100 lx (Ground area: 5.10 m²)

Page 13
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Store adjacent to Air Supply Riser (West) / Summary

5.52 m

240

280
280 280
3.96
240
280
280
320 3.10
280
320 2.59
280
240
1.99
240 280 1.52
280
240

0.00
0.00 2.04 2.90 3.52 5.00 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:71
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 265 172 325 0.649
Floor 20 197 141 234 0.717
Ceiling 50 220 96 641 0.435
Walls (8) 40 230 57 745 /

Workplane:
Height: 0.800 m
Grid: 32 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.999, Ceiling / Working Plane: 0.830.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 17.56 W/m² = 6.63 W/m²/100 lx (Ground area: 12.19 m²)

Page 14
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Landlords Store (East) / Summary

4.50 m

150

180 180
180
150 180
210 180 2.70
210
180
210 210 180 150

180 1.80
180 180
180

150
150

0.00
0.00 1.26 3.85 5.11 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:58
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 167 109 214 0.654
Floor 20 119 90 140 0.759
Ceiling 50 69 43 120 0.625
Walls (4) 40 127 46 389 /

Workplane:
Height: 0.800 m
Grid: 32 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.868, Ceiling / Working Plane: 0.415.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174377 SCUBA PC 1/35W T16 EVG V2A [STD] (1.000) 3300 38.5
Total: 6600 77.0

Specific connected load: 7.45 W/m² = 4.47 W/m²/100 lx (Ground area: 10.34 m²)

Page 15
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Elec Room (East) / Summary

2.83 m

240

280

280 320 320


320 320
240
280 280
320
320 240
1.39
320 320
280 280
320 320
320 280
280
240

0.00
0.00 0.98 2.05 3.02 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:37
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 285 203 357 0.715
Floor 20 176 144 203 0.817
Ceiling 50 82 59 98 0.723
Walls (4) 40 221 65 694 /

Workplane:
Height: 0.800 m
Grid: 16 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.903, Ceiling / Working Plane: 0.288.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 18.00 W/m² = 6.33 W/m²/100 lx (Ground area: 4.25 m²)

Page 16
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Comms Room (East) / Summary

3.60 m

200
240
240
280 280
240 280
200 240
2.05
240 280 280 200
320
280 280 240
1.55
200
240
280 280 240

240 200

0.00
0.00 1.44 2.21 3.65 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:47
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 243 155 321 0.639
Floor 20 161 125 189 0.781
Ceiling 50 65 51 99 0.775
Walls (4) 40 165 53 391 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.755, Ceiling / Working Plane: 0.269.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 11.33 W/m² = 4.66 W/m²/100 lx (Ground area: 6.75 m²)

Page 17
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Emerg Elec Room (East) / Summary

3.60 m

200
240
240 280
280 240
240 280 200
280 2.05
200 320
280
280 240
240 1.55
280
240
280 280
240 200
240
200

0.00
0.00 1.44 2.21 3.65 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:47
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 243 156 321 0.640
Floor 20 161 126 188 0.784
Ceiling 50 66 51 103 0.775
Walls (4) 40 165 52 390 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.753, Ceiling / Working Plane: 0.270.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 11.33 W/m² = 4.66 W/m²/100 lx (Ground area: 6.75 m²)

Page 18
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Store (East) / Summary

2.21 m

140

160 160
140

160
160 140
140
160
160 1.06

160 160 140


160 160
140
140

0.00
0.00 0.75 1.64 2.38 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:29
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 147 114 172 0.778
Floor 20 84 75 91 0.889
Ceiling 50 63 43 76 0.680
Walls (4) 40 163 39 556 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.346, Ceiling / Working Plane: 0.429.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174377 SCUBA PC 1/35W T16 EVG V2A [STD] (1.000) 3300 38.5
Total: 3300 38.5

Specific connected load: 14.80 W/m² = 10.07 W/m²/100 lx (Ground area: 2.60 m²)

Page 19
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Stair Lobby (West) / Summary

5.22 m

90

120
120
90
120 120
90 2.91
2.56
120
2.16
90 120 1.90
120 90
1.47

90

0.00
0.00 1.78 3.14 3.70 4.40 5.61 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:67
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 105 36 140 0.339
Floor 20 105 38 140 0.360
Ceiling 70 108 32 613 0.293
Walls (8) 50 108 23 885 /

Workplane:
Height: 0.000 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.019, Ceiling / Working Plane: 1.034.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 5.82 W/m² = 5.54 W/m²/100 lx (Ground area: 13.15 m²)

Page 21
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Stair Lobby (East) / Summary

5.37 m

100

120 100
120
3.76
120

120
120

100 120
120 1.61
100
100

0.00
0.00 2.29 4.94 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:69
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 114 84 140 0.739
Floor 20 114 86 140 0.749
Ceiling 70 112 41 580 0.366
Walls (4) 50 119 54 350 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 19 15
Grid: 32 x 32 Points Lower Wall 19 15
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.042, Ceiling / Working Plane: 0.985.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 5.94 W/m² = 5.20 W/m²/100 lx (Ground area: 12.88 m²)

Page 22
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Typical Ramp / Summary

15.04 m

480 12.97
540
540

540 600
600
600
600
600 540
540
540

420 2.08

0.00
0.00 2.50 10.63 13.23 m

Height of Room: 3.200 m, Mounting Height: 3.200 m, Maintenance factor: Values in Lux, Scale 1:194
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 512 328 621 0.640
Floor 20 512 319 623 0.624
Ceiling 50 302 142 711 0.471
Walls (4) 40 407 218 1045 /

Workplane:
Height: 0.000 m
Grid: 64 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.794, Ceiling / Working Plane: 0.590.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 11 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 114400 1177.0

Specific connected load: 21.29 W/m² = 4.16 W/m²/100 lx (Ground area: 55.27 m²)

Page 25
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Plant Access (East) / Summary

9.52 m
8.82
8.13
160 80
7.51
200 200
160
200 200
200

200 200
3.67
200
200 200
120
160 1.91
120

0.53
0.00
0.00 2.72 3.79 5.29 6.33 8.05 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:123
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 162 33 227 0.204
Floor 20 129 37 162 0.283
Ceiling 50 93 27 579 0.293
Walls (11) 40 112 21 302 /

Workplane:
Height: 0.800 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.759, Ceiling / Working Plane: 0.578.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 6.79 W/m² = 4.20 W/m²/100 lx (Ground area: 31.53 m²)

Page 26
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Store (West) / Summary

5.06 m

4.56
120
150
120 150
180
150 180 180
3.20
120 150
180 180
150
180 2.24
180 150
180 180
150
150

120

0.00
0.00 2.25 3.13 5.36 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:65
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 150 86 203 0.574
Floor 20 112 79 137 0.705
Ceiling 50 98 34 575 0.346
Walls (6) 40 113 48 295 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.836, Ceiling / Working Plane: 0.656.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 7.53 W/m² = 5.04 W/m²/100 lx (Ground area: 14.21 m²)

Page 28
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Tx and RMU Room / Summary

20.18 m

300

300
13.19
240
300
360
360 240 9.79
360 360
8.27
360 7.05
360

3.99

0.00
0.00 7.49 9.47 11.60 16.66 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:260
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 311 133 394 0.429
Floor 20 270 58 340 0.217
Ceiling 50 95 54 149 0.574
Walls (6) 40 215 70 935 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.716, Ceiling / Working Plane: 0.305.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 16 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 166400 1712.0

Specific connected load: 9.92 W/m² = 3.19 W/m²/100 lx (Ground area: 172.55 m²)

Page 1
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

LV Switchroom 1 / Summary

14.25 m
13.54

280 280 280


280
280 280 8.42
280
280 280
280
5.50
280 280 240
280 280
240
240

0.70
0.00
0.00 4.29 11.69 15.76 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:183
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 263 160 313 0.607
Floor 20 219 124 270 0.567
Ceiling 50 73 50 90 0.688
Walls (4) 40 166 59 341 /

Workplane:
Height: 0.750 m
Grid: 64 x 32 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.638, Ceiling / Working Plane: 0.276.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 8 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 83200 856.0

Specific connected load: 8.39 W/m² = 3.19 W/m²/100 lx (Ground area: 102.01 m²)

Page 2
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Generator Room / Summary

14.58 m
13.89
300 13.07
300

300
300 300 10.48

300 9.15
300
8.04
300 300
300 6.75
300
300
300 5.09
300

240
2.43

0.00
0.00 2.28 9.62 12.69 14.87 16.62 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:188
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 280 72 355 0.256
Floor 20 236 25 300 0.105
Ceiling 50 83 29 126 0.345
Walls (10) 40 194 18 1666 /

Workplane:
Height: 0.750 m
Grid: 64 x 16 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.727, Ceiling / Working Plane: 0.298.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 9 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 93600 963.0

Specific connected load: 11.81 W/m² = 4.22 W/m²/100 lx (Ground area: 81.52 m²)

Page 3
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

MTR / Summary

6.25 m

5.55

480

480 520

520 520 3.37

520 440 2.76

480
520

440

0.70

0.00
0.00 0.70 2.23 4.50 5.95 6.64 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:81
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 506 398 561 0.786
Floor 20 348 258 408 0.742
Ceiling 70 152 116 178 0.761
Walls (4) 50 323 126 1053 /

Workplane:
Height: 1.000 m
Grid: 32 x 32 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.682, Ceiling / Working Plane: 0.300.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 4 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 41600 428.0

Specific connected load: 21.09 W/m² = 4.17 W/m²/100 lx (Ground area: 20.30 m²)

Page 4
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

MV Switchroom / Summary

5.17 m

4.46

280
300 280
300
300 280
260
300 2.66
280 280
300 2.42
280 300
280

260

0.70

0.00
0.00 0.70 2.13 3.15 4.53 5.22 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:67
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 284 232 320 0.818
Floor 20 195 150 229 0.771
Ceiling 50 70 53 83 0.757
Walls (4) 40 181 57 679 /

Workplane:
Height: 0.750 m
Grid: 16 x 16 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.667, Ceiling / Working Plane: 0.246.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 15.52 W/m² = 5.46 W/m²/100 lx (Ground area: 13.79 m²)

Page 5
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

SEC Room / Summary

5.17 m

4.46

260
280 260

280 260
300
280 300 280
260 2.66
300 2.42
260
280
260 280 280
260

0.70

0.00
0.00 0.70 2.13 3.15 4.53 5.22 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:67
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 273 227 305 0.831
Floor 20 189 147 222 0.776
Ceiling 50 72 54 87 0.749
Walls (4) 40 181 57 946 /

Workplane:
Height: 0.750 m
Grid: 16 x 16 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.701, Ceiling / Working Plane: 0.264.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 15.52 W/m² = 5.69 W/m²/100 lx (Ground area: 13.79 m²)

Page 6
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Mechanical Plant Room / Summary

20.74 m
19.39

17.42
300 300 15.84
300 240
300 13.69

300 300 11.84


300 240 10.80

240
8.04

240 5.85
300
300 4.36
300
240 2.46

0.00
0.00 2.49 4.86 6.92 9.88 13.37 19.31 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:267
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 272 83 362 0.306
Floor 20 250 45 328 0.182
Ceiling 50 83 46 106 0.547
Walls (22) 40 161 59 990 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.592, Ceiling / Working Plane: 0.306.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 17 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 176800 1819.0

Specific connected load: 7.70 W/m² = 2.84 W/m²/100 lx (Ground area: 236.23 m²)

Page 7
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

LV Switchroom 2 / Summary

15.08 m
240

300
300
240 300
300 10.72
300
300
240 8.21
300 360
120
360 7.01
300
180 5.88
300 5.06
300 300 4.30

300 300

1.65

0.00
0.00 3.34 4.88 6.55 9.43 13.86 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:194
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 281 92 365 0.328
Floor 20 251 95 320 0.380
Ceiling 50 86 48 103 0.557
Walls (14) 40 184 31 1077 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.669, Ceiling / Working Plane: 0.308.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 10 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 104000 1070.0

Specific connected load: 9.62 W/m² = 3.43 W/m²/100 lx (Ground area: 111.25 m²)

Page 8
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Central Battery Room / Summary

5.11 m

4.46

180 220

220 3.21
200 2.91
2.56

220 2.06
220 180

0.65

0.00
0.00 0.65 1.29 3.89 5.52 6.10 6.74 7.39 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:66
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 208 148 236 0.711
Floor 20 145 98 199 0.673
Ceiling 50 47 33 94 0.698
Walls (8) 40 136 30 720 /

Workplane:
Height: 0.750 m
Grid: 16 x 32 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.691, Ceiling / Working Plane: 0.224.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 11.86 W/m² = 5.70 W/m²/100 lx (Ground area: 18.04 m²)

Page 9
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Cycle Store / Summary

24.72 m

80
120

120 18.92
120 100
120 17.08
120

13.50
120 12.35
120

120
7.65
120
5.39
120

0.00
0.00 4.49 6.89 9.61 13.00 19.06 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:318
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 111 46 140 0.414
Floor 20 97 41 126 0.425
Ceiling 50 40 20 61 0.492
Walls (16) 40 76 24 284 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.705, Ceiling / Working Plane: 0.362.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 12 Zumtobel 42174402 SCUBA PC 1/58W T26 EVG V2A [STD] (1.000) 5200 54.0
Total: 62400 648.0

Specific connected load: 2.96 W/m² = 2.66 W/m²/100 lx (Ground area: 218.75 m²)

Page 10
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Drivers Lounge / Summary

5.99 m

5.29

140 4.55

160 4.00
180
180 180 3.33
180 2.88
180 180

180

0.70

0.00
0.00 0.70 1.55 2.69 3.43 4.07 6.06 6.76 m

Height of Room: 3.000 m, Mounting Height: 3.100 m, Maintenance factor: Values in Lux, Scale 1:77
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 167 102 191 0.608
Floor 20 125 59 159 0.472
Ceiling 70 31 19 53 0.630
Walls (8) 50 70 20 266 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.435, Ceiling / Working Plane: 0.185.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 5 Zumtobel 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH [STD] (1.000) 1800 28.5
Total: 9000 142.5

Specific connected load: 6.94 W/m² = 4.15 W/m²/100 lx (Ground area: 20.53 m²)

Page 11
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Typical Shower / Summary

1.89 m

60 55

65 60
65
1.20
70 70
65 65 60
70
70
65
60
0.69
55 65
65
60

55

0.00
0.00 0.57 1.44 2.02 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:25
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 61 50 72 0.818
Floor 20 38 34 42 0.886
Ceiling 70 31 20 60 0.645
Walls (4) 50 45 14 211 /

Workplane:
Height: 0.750 m
Grid: 32 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.898, Ceiling / Working Plane: 0.510.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810062 PANOS LG 1/18W TC-TEL EVG 175 WH +
1 1 1200 20.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 1200 20.5

Specific connected load: 12.15 W/m² = 19.77 W/m²/100 lx (Ground area: 1.69 m²)

Page 12
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Typical WC / Summary

1.60 m

65
65

70 65
70
70
70 0.90
70 65
70
65 70 0.69
70
70 70

65
65

0.00
0.00 0.57 1.09 1.67 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:21
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 67 58 75 0.876
Floor 20 40 37 44 0.927
Ceiling 70 41 27 54 0.655
Walls (4) 50 55 14 220 /

Workplane:
Height: 0.750 m
Grid: 16 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.033, Ceiling / Working Plane: 0.612.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810062 PANOS LG 1/18W TC-TEL EVG 175 WH +
1 1 1200 20.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 1200 20.5

Specific connected load: 16.06 W/m² = 24.06 W/m²/100 lx (Ground area: 1.28 m²)

Page 13
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Changing Room 1 / Summary

8.70 m

7.89
7.29
6.71
250
150 250
150 5.07
100

100
3.90
100
3.18
2.60
2.18
1.66

0.69
0.00
0.00 1.43 2.53 3.51 4.74 5.59 6.54 8.34 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:112
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 108 44 271 0.409
Floor 20 85 32 180 0.371
Ceiling 70 23 12 124 0.499
Walls (16) 50 50 13 405 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.503, Ceiling / Working Plane: 0.217.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH +
1 10 1800 28.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 18000 285.0

Specific connected load: 8.11 W/m² = 7.48 W/m²/100 lx (Ground area: 35.15 m²)

Page 14
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Changing Room 1 Lobby / Summary

2.88 m

2.18

65
65
70
65 65 60
70 1.44
65
60 1.16

0.91
0.70

0.00
0.00 0.70 1.58 1.89 2.18 2.74 3.44 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:38
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 62 47 72 0.754
Floor 20 36 27 45 0.740
Ceiling 70 11 7.44 16 0.658
Walls (6) 50 24 10 68 /

Workplane:
Height: 0.750 m
Grid: 32 x 32 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.426, Ceiling / Working Plane: 0.183.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH +
1 1 1800 28.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 1800 28.5

Specific connected load: 5.56 W/m² = 9.00 W/m²/100 lx (Ground area: 5.12 m²)

Page 15
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Changing Room 2 / Summary

9.11 m
8.40
7.80
7.26

6.20
5.59
5.01
100 4.30
100 100 3.66
100
200 150 2.87

250 150 2.21


1.47

0.70
0.00
0.00 1.22 2.27 5.07 6.18 7.23 8.47 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:117
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 100 33 261 0.335
Floor 20 79 14 175 0.179
Ceiling 70 21 8.80 92 0.419
Walls (16) 50 46 8.53 308 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.494, Ceiling / Working Plane: 0.210.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH +
1 10 1800 28.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 18000 285.0

Specific connected load: 7.16 W/m² = 7.17 W/m²/100 lx (Ground area: 39.81 m²)

Page 16
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Changing Room 2 Lobby / Summary

3.89 m

3.18
2.90

60
2.37

60 60
60 60 60 1.64

50

0.70

0.00
0.00 0.70 1.55 2.07 2.47 3.41 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:50
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 56 33 69 0.599
Floor 20 33 21 43 0.636
Ceiling 70 8.82 5.56 11 0.630
Walls (6) 50 19 7.25 51 /

Workplane:
Height: 0.750 m
Grid: 32 x 32 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.360, Ceiling / Working Plane: 0.158.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH +
1 1 1800 28.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 1800 28.5

Specific connected load: 4.15 W/m² = 7.46 W/m²/100 lx (Ground area: 6.86 m²)

Page 17
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Corridor to Retail Spaces / Summary

34.41 m

27.73

24.78
22.86

5.38
2.68
0.00
0.00 4.99 9.63 15.18 26.18 30.64 m

Height of Room: 2.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:442

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 161 21 246 0.128
Floor 20 117 22 160 0.190
Ceiling 70 25 12 39 0.462
Walls (14) 50 60 15 198 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.343, Ceiling / Working Plane: 0.155.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42177422 SLOT2 1x1/28W LRO LDE IP40 [STD] (1.000) 2600 30.5
Zumtobel 60810092 PANOS LM 1/26W TC-TEL EVG 200 WH [STD]
2 19 1800 28.5
(1.000)
Total: 39400 602.5

Specific connected load: 5.35 W/m² = 3.31 W/m²/100 lx (Ground area: 112.67 m²)

Page 18
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Loading Bay / Summary

28.28 m

23.76
210 210 22.35
21.06
210 210 210 19.65

210 210 17.32

210
13.55
210
12.09
210 10.10
210 180
210
7.96
150 6.35

0.00
0.00 3.71 6.79 12.87 17.50 21.37 25.72 m

Height of Room: 5.150 m, Mounting Height: 5.150 m, Maintenance factor: Values in Lux, Scale 1:364
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 193 98 223 0.505
Floor 20 174 44 213 0.253
Ceiling 70 90 39 591 0.440
Walls (15) 50 135 48 527 /

Workplane:
Height: 0.750 m
Grid: 64 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.720, Ceiling / Working Plane: 0.464.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 17 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 176800 1819.0

Specific connected load: 5.28 W/m² = 2.73 W/m²/100 lx (Ground area: 344.42 m²)

Page 19
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Generator Foam Suppression Room / Summary

3.52 m

180

160 200
180 220
220 220
2.03
220 220
200 200
220 220
1.50
220 160
220
200
1.02
200 180
160

0.28
0.00
0.00 1.05 2.89 3.42 3.94 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:46
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 191 136 233 0.713
Floor 20 137 112 156 0.813
Ceiling 70 67 51 81 0.751
Walls (7) 50 165 40 704 /

Workplane:
Height: 0.750 m
Grid: 32 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.939, Ceiling / Working Plane: 0.353.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 16.80 W/m² = 8.78 W/m²/100 lx (Ground area: 6.37 m²)

Page 20
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Inergen Room / Summary

3.65 m

2.94

230 220
230 2.34
240

240 240
230
220
1.27
220

0.70

0.00
0.00 0.70 1.51 1.87 2.67 3.36 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:47
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 228 208 241 0.912
Floor 20 145 119 164 0.817
Ceiling 70 73 54 87 0.737
Walls (4) 50 179 57 639 /

Workplane:
Height: 0.750 m
Grid: 16 x 8 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.852, Ceiling / Working Plane: 0.320.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 17.67 W/m² = 7.76 W/m²/100 lx (Ground area: 6.06 m²)

Page 21
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Service Lift Lobby / Summary

6.94 m
60 6.49

90 5.81

120 5.33
120
4.35

120 150
150
150 120 2.86
120 150
150
2.11
150
120
1.32
0.76

0.00
0.00 2.60 3.56 4.24 4.90 6.37 m

Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:90
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 122 39 162 0.323
Floor 20 95 44 119 0.459
Ceiling 70 81 18 630 0.217
Walls (12) 50 80 18 217 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.717, Ceiling / Working Plane: 0.668.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174377 SCUBA PC 1/35W T16 EVG V2A [STD] (1.000) 3300 38.5
Total: 6600 77.0

Specific connected load: 3.62 W/m² = 2.97 W/m²/100 lx (Ground area: 21.24 m²)

Page 22
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Air extract fan chamber / Summary

14.35 m

120
120

120

8.87
90 150 120
150 8.03
150
150
5.96
120

150 4.51

150 3.43
150

120 1.63
120

0.00
0.00 3.21 6.17 7.62 10.28 12.10 15.55 m

Height of Room: 5.000 m, Mounting Height: 5.000 m, Maintenance factor: Values in Lux, Scale 1:185
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 118 13 157 0.112
Floor 20 105 15 138 0.141
Ceiling 50 72 5.66 580 0.079
Walls (12) 40 87 4.19 767 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.790, Ceiling / Working Plane: 0.611.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 5 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 52000 535.0

Specific connected load: 5.24 W/m² = 4.45 W/m²/100 lx (Ground area: 102.06 m²)

Page 23
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Waste room / Summary

11.24 m
10.53
110
120
130 120
130 130 110
130 130 6.81
140
120 140 130
130
120 130 4.82
130
130
120
120
110

0.72
0.00
0.00 4.62 7.70 11.34 m

Height of Room: 5.000 m, Mounting Height: 5.000 m, Maintenance factor: Values in Lux, Scale 1:145
0.50

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 123 92 141 0.750
Floor 20 102 73 121 0.721
Ceiling 50 78 35 344 0.444
Walls (4) 40 100 52 215 /

Workplane:
Height: 0.750 m
Grid: 32 x 32 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.863, Ceiling / Working Plane: 0.637.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 6 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 39600 459.0

Specific connected load: 7.56 W/m² = 6.16 W/m²/100 lx (Ground area: 60.72 m²)

Page 24
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
10.01.2011

Operator
Telephone
Fax
e-Mail

Waste room2 / Summary

4.60 m

3.90

75
80
80
75 2.65
80 80

75 80 1.86
80
75

0.68

0.00
0.00 0.73 1.85 3.22 4.26 4.96 m

Height of Room: 5.000 m, Mounting Height: 5.000 m, Maintenance factor: Values in Lux, Scale 1:60
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 78 70 83 0.897
Floor 20 56 48 62 0.855
Ceiling 50 101 31 538 0.309
Walls (4) 40 85 24 398 /

Workplane:
Height: 0.750 m
Grid: 32 x 16 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.222, Ceiling / Working Plane: 1.309.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 7.01 W/m² = 9.04 W/m²/100 lx (Ground area: 10.91 m²)

Page 25
Project 1
10.01.2011

Operator
Telephone
Fax
e-Mail

Wadi entrance lobby - BH layout / Normal Lighting / Summary

14.05 m

12.37

550 550 10.07


550 550
550
550

550 550
550
550
550 550 550 550
550 550 550
550
550 550
550 1.39
0.00
0.00 18.34 20.49 26.86 33.44 m

Height of Room: 6.100 m, Maintenance factor: 0.80 Values in Lux, Scale 1:240

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 246 30 2724 0.120
Floor 20 254 28 2266 0.110
Ceiling 70 55 21 169 0.383
Walls (12) 50 118 24 4884 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.490, Ceiling / Working Plane: 0.223.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 14 iGuzzini 2680 Deep Minimal 2x75W (1.000) 2186 150.0
2 9 iGuzzini 2682 Deep Minimal 2x35W (1.000) 2800 70.0
3 26 iGuzzini 8466 Family SHUTTLE 1x70W (1.000) 6600 83.0
Total: 227404 4888.0

Specific connected load: 13.67 W/m² = 5.55 W/m²/100 lx (Ground area: 357.59 m²)

Page 1
KAFD Parcel 3.09 Basement 3 Water Tanks
19.01.2011

Operator
Telephone
Fax
e-Mail

Water Tank Room / Single Sheet Output

25.60 m
23.61

20.60
18.70
17.00
15.77

12.92
10.97
9.74

6.65
5.42

3.19
1.96
0.00
0.00 2.45 4.85 10.94 18.30 23.24 26.51 31.04 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:329
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 188 71 250 0.378
Floor 20 74 0.17 241 0.002
Ceiling 50 133 34 647 0.253
Walls (29) 40 226 28 1144 /

Workplane:
Height: 0.000 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.186, Ceiling / Working Plane: 0.706.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 22 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 228800 2354.0

Specific connected load: 8.38 W/m² = 4.45 W/m²/100 lx (Ground area: 280.83 m²)

Page 1
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Water feature treatment room / Single Sheet Output

15.35 m
240
240 280 240
240 240 11.72
240
200 240
9.17
240

7.21
6.00

1.49

0.00
0.00 4.22 7.36 12.42 17.00 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:198
0.50

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 207 138 295 0.668
Floor 20 88 0.20 233 0.002
Ceiling 50 124 54 473 0.434
Walls (4) 40 204 52 1089 /

Workplane:
Height: 0.800 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.112, Ceiling / Working Plane: 0.592.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 14 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 145600 1498.0

Specific connected load: 12.76 W/m² = 6.16 W/m²/100 lx (Ground area: 117.38 m²)

Page 1
Level B4
19.01.2011

Operator
Telephone
Fax
e-Mail

Oil Tank Room / Single Sheet Output

17.53 m

240
14.73
240
180
12.45
240 11.61
240
300 9.62

7.96
180

240 180
180 240
3.56
2.23
1.12
0.00
0.00 3.00 5.07 7.04 9.81 13.55 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:226
0.85

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 199 28 304 0.143
Floor 20 164 23 238 0.141
Ceiling 50 93 16 590 0.168
Walls (6) 40 118 19 422 /

Workplane:
Height: 0.800 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.627, Ceiling / Working Plane: 0.467.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 5 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 52000 535.0

Specific connected load: 6.59 W/m² = 3.32 W/m²/100 lx (Ground area: 81.24 m²)

Page 1
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Water Tank Room / Single Sheet Output

70.64 m
320
63.39
59.40
55.84
400 52.54
49.21
44.78
41.52
36.39
32.62
29.39
24.22
18.58
13.87
10.41
6.62
3.39
0.00
0.00 7.17 13.84 23.13 32.02 41.33 50.54 58.72 67.07 75.27 89.36 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:907
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 255 47 417 0.186
Floor 20 147 0.01 413 0.000
Ceiling 50 135 22 641 0.161
Walls (81) 40 239 18 2788 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.964, Ceiling / Working Plane: 0.529.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 77 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 800800 8239.0

Specific connected load: 8.63 W/m² = 3.39 W/m²/100 lx (Ground area: 955.08 m²)

Page 1
Buro Happold

5.2 Substructure Package Emergency


Lighting Calculations

KAFD Plot 3.09 Report Revision 0


3.09 KAFD Core Areas (B1 West) - Emergency
17.01.2011

Operator
Telephone
Fax
e-Mail

Office Lobby (West) / Emergency / Summary

11.93 m
11.22
60 10.12
30

8.30
30 60
30
60 120 6.67
6.12
90 30
5.27
30 4.62

30
3.03
90
1.99

0.71
0.00
0.00 1.62 4.04 5.41 6.61 7.78 9.29 11.52 m

Height of Room: 2.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:154

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 50 6.06 139 0.121
Floor 20 44 1.13 139 0.026
Ceiling 70 0.00 0.00 0.00 0.000
Walls (24) 50 14 0.00 176 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.285, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 ERCO 83260000 Compact 100 Downlight 2xTC-DEL 13W (1.000) 1800 26.0
2 2 Zumtobel 42177422 SLOT2 1x1/28W LRO LDE IP40 [STD] (1.000) 2600 30.5
Total: 8800 113.0

Specific connected load: 2.34 W/m² = 4.69 W/m²/100 lx (Ground area: 48.26 m²)

Page 1
3.09 KAFD Core Areas (B1 West) - Emergency
17.01.2011

Operator
Telephone
Fax
e-Mail

Residential Lobby (West) / Emergency / Summary

15.14 m
14.43

90 13.12
30
11.75
60
9.94
8.99
90 60 60
90 8.28
60
90 60
60 30 6.42
60
30 60
60 30 4.74
60 60

60
60

0.70
0.00
0.00 2.29 4.41 5.91 7.38 10.18 14.05 m

Height of Room: 2.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:195

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 52 4.44 114 0.085
Floor 20 46 0.86 114 0.019
Ceiling 70 0.00 0.00 0.00 0.000
Walls (20) 50 7.21 0.00 48 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.138, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 Zumtobel 42177422 SLOT2 1x1/28W LRO LDE IP40 [STD] (1.000) 2600 30.5
Zumtobel 60811226 PANOS Q HM 1/26W TC-TELI EVG 250 TI [STD]
2 2 1800 28.5
(1.000)
Total: 11400 148.5

Specific connected load: 1.72 W/m² = 3.30 W/m²/100 lx (Ground area: 86.12 m²)

Page 2
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
17.01.2011

Operator
Telephone
Fax
e-Mail

Retail Lobby (West) / Emergency / Summary

13.76 m

12.64
11.64

30
9.95
30 90 9.24
8.45
30 90 90 30
30 7.47
30
30 30 60 90
60
30 6.12
90 5.45
30 30
30 30 4.45
90 30
90
3.30
90
30

0.70
0.00
0.00 4.87 6.31 7.64 9.02 10.86 13.55 m

Height of Room: 2.300 m, Mounting Height: 2.410 m, Maintenance factor: Values in Lux, Scale 1:177
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 35 0.00 111 0.000
Floor 20 27 0.00 111 0.000
Ceiling 70 0.00 0.00 0.00 0.000
Walls (4) 50 5.56 0.00 88 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.158, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 Zumtobel 42177424 SLOT2 1x1/35W LRO LDE IP40 [STD] (1.000) 3300 38.6
Total: 9900 115.8

Specific connected load: 1.24 W/m² = 3.51 W/m²/100 lx (Ground area: 93.49 m²)

Page 1
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
17.01.2011

Operator
Telephone
Fax
e-Mail

Office Lobby (West) / Emergency / Summary

14.06 m
13.05

10.89
10.11
30

60 8.30
60
120 6.77
6.10
90
5.31
30
4.57
30
2.98
90
1.98

0.70
0.00
0.00 1.60 4.02 5.36 6.72 8.54 11.50 m

Height of Room: 2.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:181

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 59 5.61 142 0.096
Floor 20 51 1.56 142 0.031
Ceiling 70 0.00 0.00 0.00 0.000
Walls (26) 50 15 0.00 130 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.253, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 ERCO 83260000 Compact 100 Downlight 2xTC-DEL 13W (1.000) 1800 26.0
2 2 Zumtobel 42177422 SLOT2 1x1/28W LRO LDE IP40 [STD] (1.000) 2600 30.5
Total: 10600 139.0

Specific connected load: 2.66 W/m² = 4.55 W/m²/100 lx (Ground area: 52.24 m²)

Page 2
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
17.01.2011

Operator
Telephone
Fax
e-Mail

Residential Lobby (West) / Emergency / Summary

7.64 m

6.93

90 5.61
90 30
30
30
30
30
90
60 90
2.06

0.71

0.00
0.00 2.30 4.72 7.03 m

Height of Room: 2.300 m, Mounting Height: 2.500 m, Maintenance factor: Values in Lux, Scale 1:99
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 65 7.47 111 0.114
Floor 20 59 4.48 111 0.076
Ceiling 70 0.00 0.00 0.00 0.000
Walls (4) 50 9.57 0.00 47 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 64 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.145, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel 60811226 PANOS Q HM 1/26W TC-TELI EVG 250 TI [STD]
1 2 1800 28.5
(1.000)
Total: 3600 57.0

Specific connected load: 2.52 W/m² = 3.85 W/m²/100 lx (Ground area: 22.61 m²)

Page 3
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
17.01.2011

Operator
Telephone
Fax
e-Mail

Office Lobby (East) / Emergency / Summary

14.12 m
13.43

30 90 11.65

120
90 30
30 8.63
90
60 90 7.96
7.30
90 30 6.59
30 5.90
30 5.01
60 4.11

60

1.51
0.70
0.00
0.00 1.98 7.36 8.80 10.77 12.71 14.74 18.76 m

Height of Room: 2.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:182

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 46 1.83 139 0.039
Floor 20 40 0.54 139 0.014
Ceiling 70 0.00 0.00 0.00 0.000
Walls (26) 50 11 0.00 166 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.235, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 ERCO 83260000 Compact 100 Downlight 2xTC-DEL 13W (1.000) 1800 26.0
2 2 Zumtobel 42177422 SLOT2 1x1/28W LRO LDE IP40 [STD] (1.000) 2600 30.5
Total: 10600 139.0

Specific connected load: 1.95 W/m² = 4.21 W/m²/100 lx (Ground area: 71.24 m²)

Page 4
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
17.01.2011

Operator
Telephone
Fax
e-Mail

Staircases / Emergency light scene 1 / Summary

6.63 m

5.92

5.33
4.89
50 4.55
50
50

40
40

30
1.76

0.71

0.00
0.00 0.70 1.84 2.67 4.13 5.39 6.09 m

Height of Room: 7.000 m, Maintenance factor: 0.50 Values in Lux, Scale 1:86

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 42 27 55 0.653
Floor 20 40 23 55 0.575
Ceiling 70 3.08 0.98 5.79 0.317
Walls (4) 50 39 0.51 548 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 16 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.930, Ceiling / Working Plane: 0.074.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 13200 153.0

Specific connected load: 9.09 W/m² = 21.85 W/m²/100 lx (Ground area: 16.83 m²)

Page 1
3.09 KAFD Core Areas (B4 - B2 West and B4 - B1 East)
17.01.2011

Operator
Telephone
Fax
e-Mail

Staircases / Emergency light scene 1 / False Colour Rendering

0 12.50 25 37.50 50 62.50 75 87.50 100 lx

Page 2
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

B4 Car Park / Emergency / Summary

107.68 m
10
10 100.29
10 93.86
10
88.50
10 83.51
10
10 10 78.39
10 10 73.33
68.36
10 10 10
10 10 62.82
20 57.70
10 10
10 52.53
10 10
10 10 47.35
10 10 42.25
10 10 10 37.07
10
10 10 10 31.90
26.73
10 10 21.43
20 16.25
20 11.11
5.84
0.00
0.00 10.60 23.03 35.45 47.85 61.87 74.41 86.83 100.11 124.05 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:1383
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 12 0.37 43 0.030
Floor 20 12 0.13 43 0.010
Ceiling 50 4.73 0.01 595 0.002
Walls (96) 40 11 0.00 648 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.908, Ceiling / Working Plane: 0.370.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 30 Zumtobel 42174402 SCUBA PC 1/58W T26 EVG V2A [STD] (1.000) 5200 54.0
Total: 156000 1620.0

Specific connected load: 0.38 W/m² = 3.09 W/m²/100 lx (Ground area: 4222.99 m²)

Page 1
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Air Extract Fan Chamber (West) / Emergency / Summary

6.76 m

100
100
120
120 120
100 100
140 140 120
140
80 140 3.56
100 120 140
120 100 3.20
140
140
120
100
120 120

100 100

80

0.00
0.00 2.65 4.30 6.95 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:87
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 110 62 150 0.565
Floor 20 109 62 150 0.566
Ceiling 50 65 1.82 505 0.028
Walls (4) 40 97 26 300 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 32 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.883, Ceiling / Working Plane: 0.590.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 9.24 W/m² = 8.44 W/m²/100 lx (Ground area: 23.16 m²)

Page 3
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Air Supply Fan Chamber (West) / Emergency / Summary

15.86 m

12.93
11.94
30
30
60
30 9.50
30 60
60
90 60 30
90
60 90 6.13
60
90 90 5.00
90
90 3.78
90 2.67
90

0.00
0.00 2.07 4.75 7.57 9.51 12.73 17.29 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:204
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 48 3.34 107 0.070
Floor 20 47 0.00 108 0.000
Ceiling 50 18 0.01 503 0.000
Walls (8) 40 40 0.02 204 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 32 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.834, Ceiling / Working Plane: 0.386.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 31200 321.0

Specific connected load: 2.57 W/m² = 5.40 W/m²/100 lx (Ground area: 124.76 m²)

Page 4
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Air Extract Fan Chamber (East) / Emergency / Summary

6.47 m

60
60

80 80
60
80 40
80 80
80 80 60
3.15
60
40
40 60 2.53
60
60
40

0.00
0.00 2.77 6.16 7.50 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:84
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 53 18 85 0.340
Floor 20 53 18 85 0.334
Ceiling 50 30 0.22 502 0.007
Walls (4) 40 44 3.58 216 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 64 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.830, Ceiling / Working Plane: 0.559.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 4.23 W/m² = 7.92 W/m²/100 lx (Ground area: 25.31 m²)

Page 5
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Comms Room (West) / Emergency / Summary

4.49 m

100
100

100

120 100 2.87


100
80
60
100
100
100
40 80
1.62
60

40

0.00
0.00 1.34 3.47 4.81 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:58
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 84 33 121 0.391
Floor 20 84 33 121 0.391
Ceiling 50 13 0.72 30 0.056
Walls (4) 40 76 0.95 427 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 16 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.912, Ceiling / Working Plane: 0.153.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 8.10 W/m² = 9.61 W/m²/100 lx (Ground area: 9.45 m²)

Page 6
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Elec Room (West) / Emergency / Summary

2.88 m

100

110 100
110 110

110 100
110
120 1.54
110
100 110 1.34
100

110 110
100
110 110
100

0.00
0.00 1.28 1.62 2.89 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:37
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 106 85 121 0.801
Floor 20 106 85 121 0.801
Ceiling 50 3.94 0.72 12 0.184
Walls (4) 40 138 1.03 444 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 16 x 16 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.319, Ceiling / Working Plane: 0.037.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 18.21 W/m² = 17.21 W/m²/100 lx (Ground area: 4.20 m²)

Page 7
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Emerg Elec Room (West) / Emergency / Summary

3.26 m

90

100
90
110
110 110 100

110
100 110 100 90
90 120 1.72
110 1.54

110 110
90
110 110
100
90 100

0.00
0.00 1.27 2.08 3.36 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:42
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 101 74 121 0.733
Floor 20 100 74 121 0.733
Ceiling 50 3.79 0.72 13 0.190
Walls (4) 40 118 1.26 444 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 16 x 16 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.186, Ceiling / Working Plane: 0.038.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 14.17 W/m² = 14.09 W/m²/100 lx (Ground area: 5.40 m²)

Page 8
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Landlords Store (West) / Emergency / Summary

3.17 m

40
45

45 40

45 45
40
1.55
40 45
45

40 45

40

0.00
0.00 1.34 1.87 3.21 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:41
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 43 34 48 0.802
Floor 20 43 34 48 0.803
Ceiling 50 4.01 0.30 21 0.074
Walls (4) 40 67 0.46 225 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 32 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.603, Ceiling / Working Plane: 0.094.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174377 SCUBA PC 1/35W T16 EVG V2A [STD] (1.000) 3300 38.5
Total: 3300 38.5

Specific connected load: 7.54 W/m² = 17.65 W/m²/100 lx (Ground area: 5.10 m²)

Page 10
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Store adjacent to Air Supply Riser (West) / Emergency / Summary

5.52 m

40

3.96
40
60

60 3.10

2.59
80 80
1.99
80 80
80 1.52
80
80 80

0.00
0.00 2.04 2.90 3.52 5.00 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:71
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 58 0.00 85 0.000
Floor 20 58 0.00 85 0.000
Ceiling 50 57 0.00 499 0.000
Walls (8) 40 68 0.00 533 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 16 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.181, Ceiling / Working Plane: 0.982.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 8.78 W/m² = 15.17 W/m²/100 lx (Ground area: 12.19 m²)

Page 11
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Elec Room (East) / Emergency / Summary

2.83 m

90
100

90 100
110
110 110
100
90
110
110 90
100 120 100 1.39
110
110

110 100 90
110
100
90

0.00
0.00 0.98 2.05 3.02 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:37
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 104 80 121 0.772
Floor 20 104 80 121 0.772
Ceiling 50 2.64 0.73 8.41 0.277
Walls (4) 40 135 1.18 564 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 16 x 16 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.324, Ceiling / Working Plane: 0.025.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 18.00 W/m² = 17.38 W/m²/100 lx (Ground area: 4.25 m²)

Page 13
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Comms Room (East) / Emergency / Summary

3.60 m

80

100

100

80
100 100 2.05

100 100 1.55

100
100

0.00
0.00 1.44 2.21 3.65 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:47
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 98 70 121 0.710
Floor 20 98 70 120 0.710
Ceiling 50 6.36 0.72 22 0.114
Walls (4) 40 102 1.27 312 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 16 x 16 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.053, Ceiling / Working Plane: 0.065.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 11.33 W/m² = 11.55 W/m²/100 lx (Ground area: 6.75 m²)

Page 14
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Emerg Elec Room (East) / Emergency / Summary

3.60 m

100
100
100

100 2.05
100
80
100 1.55
100

100
100
80

0.00
0.00 1.44 2.21 3.65 m

Height of Room: 3.550 m, Mounting Height: 2.700 m, Maintenance factor: Values in Lux, Scale 1:47
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 98 70 121 0.710
Floor 20 98 70 120 0.710
Ceiling 50 6.36 0.72 22 0.114
Walls (4) 40 102 1.27 312 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 16 x 16 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.053, Ceiling / Working Plane: 0.065.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 11.33 W/m² = 11.54 W/m²/100 lx (Ground area: 6.75 m²)

Page 15
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Stair Lobby (West) / Emergency Light scene / Summary

5.22 m

40
60
60
60 40
60
60 2.91
40
2.56
40 60
2.16
60 1.90
60
40 1.47

40

0.00
0.00 1.78 3.14 3.70 4.40 5.61 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:67
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 50 5.62 70 0.113
Floor 20 50 5.39 70 0.108
Ceiling 70 47 0.18 488 0.004
Walls (8) 50 53 0.00 722 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 32 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.064, Ceiling / Working Plane: 0.951.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 5.82 W/m² = 11.65 W/m²/100 lx (Ground area: 13.15 m²)

Page 19
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Stair Lobby (East) / Emergency Light scene / Summary

5.37 m

40
50
50 40
60
60 50 3.76
60
60
60

60
50 60
40 60 60
50 1.61

40 50

40

0.00
0.00 2.29 4.94 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:69
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 53 32 70 0.595
Floor 20 53 32 70 0.595
Ceiling 70 50 0.24 486 0.005
Walls (4) 50 60 3.48 258 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 32 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.132, Ceiling / Working Plane: 0.942.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 5.94 W/m² = 11.19 W/m²/100 lx (Ground area: 12.88 m²)

Page 21
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Typical Ramp / Emergency / Summary

15.04 m
100
80 12.97
80 80
60
80 80
100 100
100 80
80
80
60
80
80
100
100 2.08

0.00
0.00 2.50 10.63 13.23 m

Height of Room: 3.200 m, Mounting Height: 3.200 m, Maintenance factor: Values in Lux, Scale 1:194
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 80 50 115 0.630
Floor 20 80 50 115 0.628
Ceiling 50 39 0.81 489 0.021
Walls (4) 40 74 9.54 642 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 16 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.924, Ceiling / Working Plane: 0.497.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 31200 321.0

Specific connected load: 5.81 W/m² = 7.30 W/m²/100 lx (Ground area: 55.27 m²)

Page 25
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Plant Access (East) / Emergency / Summary

9.52 m
8.82
8.13
7.51

20

40 20
60
60
40
80 80 60
3.67
80 80
60
80
60
60 1.91
60
40
0.53
0.00
0.00 2.72 3.79 5.29 6.33 8.05 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:123
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 41 1.94 85 0.047
Floor 20 41 1.94 85 0.047
Ceiling 50 24 0.01 501 0.000
Walls (11) 40 34 0.00 228 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 32 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.819, Ceiling / Working Plane: 0.571.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 3.39 W/m² = 8.23 W/m²/100 lx (Ground area: 31.53 m²)

Page 26
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Oil Tank Room / Emergency / Summary

17.53 m

120 90
14.73
90
120
12.45
120 11.61
90
9.62
90 90
90 7.96
90
90
90
90
90
120 3.56
2.23
1.12
0.00
0.00 3.00 5.07 7.04 9.81 13.55 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:226
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 93 1.60 145 0.017
Floor 20 90 0.00 145 0.000
Ceiling 50 38 0.02 503 0.001
Walls (6) 40 60 0.00 242 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 32 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.647, Ceiling / Working Plane: 0.412.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 4 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 41600 428.0

Specific connected load: 5.27 W/m² = 5.69 W/m²/100 lx (Ground area: 81.24 m²)

Page 27
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Tx and RMU Room / Emergency / Summary

20.18 m

120 60
60 60

60
60
13.19
30 60
60
60 120 120
30 60 60 90
9.79
90 60
120 60 8.27
60 60 7.05
60
90 60
90 3.99
30

0.00
0.00 7.49 9.47 11.60 16.66 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:260
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 61 7.44 149 0.122
Floor 20 52 7.07 99 0.137
Ceiling 50 6.74 0.26 18 0.038
Walls (6) 40 38 1.01 781 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 64 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.662, Ceiling / Working Plane: 0.111.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 4 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 41600 428.0

Specific connected load: 2.48 W/m² = 4.06 W/m²/100 lx (Ground area: 172.55 m²)

Page 1
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

LV Switchroom 1 / Emergency / Summary

14.25 m
13.54

120
90 90
120
60 60 30
60
30 30
30 8.42

30 30
30 60 60 30 5.50
30 60
90 120

120

0.70
0.00
0.00 4.29 11.69 15.76 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:183
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 47 7.85 141 0.168
Floor 20 37 10 88 0.270
Ceiling 50 3.74 0.34 13 0.090
Walls (4) 40 30 0.62 194 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 64 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.666, Ceiling / Working Plane: 0.080.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 2.10 W/m² = 4.49 W/m²/100 lx (Ground area: 102.01 m²)

Page 2
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Generator Room / Emergency / Summary

14.58 m
13.89
13.07
60
60
30
120
60
60 10.48
120
60
60 90 9.15
120
60 120 8.04
60
60 6.75
60 60
5.09
30 90
60
120 90
2.43
90

0.00
0.00 2.28 9.62 12.69 14.87 16.62 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:188
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 67 0.80 144 0.012
Floor 20 54 0.93 92 0.017
Ceiling 50 3.87 0.05 13 0.013
Walls (10) 40 47 0.00 966 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 32 Points are ignored.
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.747, Ceiling / Working Plane: 0.058.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 31200 321.0

Specific connected load: 3.94 W/m² = 5.87 W/m²/100 lx (Ground area: 81.52 m²)

Page 3
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

MTR / Emergency / Summary

6.25 m

5.55

320
360
360
320 360

320 360
3.37
360 2.76
360 280

360 360
280

280

0.70

0.00
0.00 0.70 2.23 4.50 5.95 6.64 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:81
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 335 227 390 0.678
Floor 20 202 125 253 0.616
Ceiling 70 13 3.58 21 0.272
Walls (4) 50 184 6.64 906 /

Workplane: Emergency lighting scene (EN 1838):


Height: 1.000 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 32 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.606, Ceiling / Working Plane: 0.039.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 4 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 41600 428.0

Specific connected load: 21.09 W/m² = 6.29 W/m²/100 lx (Ground area: 20.30 m²)

Page 4
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

MV Switchroom / Emergency / Summary

5.17 m

4.46

120
120
100
120
80
120 100 2.66
120 120 2.42
100 80
100
80

0.70

0.00
0.00 0.70 2.13 3.15 4.53 5.22 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:67
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 103 54 141 0.523
Floor 20 65 33 87 0.514
Ceiling 50 4.53 0.32 13 0.070
Walls (4) 40 59 0.41 543 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 16 x 16 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.612, Ceiling / Working Plane: 0.044.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 7.76 W/m² = 7.50 W/m²/100 lx (Ground area: 13.79 m²)

Page 5
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

SEC Room / Emergency / Summary

5.17 m

4.46

120
100
120
80
100
120 60 2.66
120 120
2.42
100 80
100
80

60

0.70

0.00
0.00 0.70 2.13 3.15 4.53 5.22 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:67
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 98 47 141 0.484
Floor 20 62 30 87 0.482
Ceiling 50 5.06 0.32 13 0.063
Walls (4) 40 59 0.30 824 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 16 x 16 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.656, Ceiling / Working Plane: 0.052.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 7.76 W/m² = 7.95 W/m²/100 lx (Ground area: 13.79 m²)

Page 6
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Mechanical Plant Room / Emergency / Summary

20.74 m
90 19.39

90 90 17.42
30
30 60 30 15.84
30 30
13.69
30
60 30
60 11.84
120 90 60 90 10.80
60 30 60
60 120
60 90 120
60 8.04
60
60 60 60 60
60 30 5.85
60
60 120
60 4.36
120 60
30 2.46

0.00
0.00 2.49 4.86 6.92 9.88 13.37 19.31 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:267
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 49 1.18 146 0.024
Floor 20 43 1.73 95 0.040
Ceiling 50 5.79 0.39 16 0.068
Walls (22) 40 30 0.12 956 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.624, Ceiling / Working Plane: 0.118.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 4 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 41600 428.0

Specific connected load: 1.81 W/m² = 3.70 W/m²/100 lx (Ground area: 236.23 m²)

Page 7
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

LV Switchroom 2 / Emergency / Summary

15.08 m

30
60 30 60
90 60
60 120 10.72
120 60
60 120
90 120 120 60 60
30 8.21
60
60 60
60
7.01
30 30
5.88
60 60 5.06
60 4.30
60 120
60
90 1.65

0.00
0.00 3.34 4.88 6.55 9.43 13.86 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:194
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 56 6.11 144 0.109
Floor 20 48 3.60 92 0.075
Ceiling 50 5.85 0.38 15 0.065
Walls (14) 40 43 0.00 942 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 64 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.814, Ceiling / Working Plane: 0.105.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 31200 321.0

Specific connected load: 2.89 W/m² = 5.16 W/m²/100 lx (Ground area: 111.25 m²)

Page 8
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Central Battery Room / Emergency / Summary

5.11 m

4.46

120
120
120
120 90 3.21
120 2.91
120 90
2.56
60
90 30 2.06
60

0.65

0.00
0.00 0.65 1.29 3.89 5.52 6.10 6.74 7.39 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:66
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 79 10 141 0.130
Floor 20 50 0.00 87 0.000
Ceiling 50 0.82 0.00 4.98 0.000
Walls (8) 40 45 0.00 335 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 16 x 32 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.613, Ceiling / Working Plane: 0.010.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 5.93 W/m² = 7.55 W/m²/100 lx (Ground area: 18.04 m²)

Page 9
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Cycle Store / Emergency / Summary

24.72 m

20
20
20 60 40
18.92
20 40
20 60
17.08
60 20
40
40
20 13.50
20
12.35
20
20
20 40

40 20 7.65
60
5.39
20

0.00
0.00 4.49 6.89 9.61 13.00 19.06 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:318
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 22 1.82 69 0.083
Floor 20 18 1.29 44 0.071
Ceiling 50 3.89 0.13 15 0.033
Walls (16) 40 13 0.21 234 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.609, Ceiling / Working Plane: 0.177.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 Zumtobel 42174402 SCUBA PC 1/58W T26 EVG V2A [STD] (1.000) 5200 54.0
Total: 15600 162.0

Specific connected load: 0.74 W/m² = 3.37 W/m²/100 lx (Ground area: 218.75 m²)

Page 10
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Drivers Lounge / Emergency / Summary

5.99 m

5.29

4.55
20
80
40 4.00
80 60
40 60
40 80 3.33
40
60
80 2.88
40 60
20
20

0.70

0.00
0.00 0.70 1.55 2.69 3.43 4.07 6.06 6.76 m

Height of Room: 3.000 m, Mounting Height: 3.100 m, Maintenance factor: Values in Lux, Scale 1:77
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 41 6.23 91 0.151
Floor 20 31 5.27 53 0.168
Ceiling 70 0.00 0.00 0.00 0.000
Walls (8) 50 18 0.00 236 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 64 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.501, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH [STD] (1.000) 1800 28.5
Total: 3600 57.0

Specific connected load: 2.78 W/m² = 6.73 W/m²/100 lx (Ground area: 20.53 m²)

Page 11
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Typical WC / Summary

1.60 m

65
65

70 65
70
70
70 0.90
70 65
70
65 70 0.69
70
70 70

65
65

0.00
0.00 0.57 1.09 1.67 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:21
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 67 58 75 0.876
Floor 20 40 37 44 0.927
Ceiling 70 41 27 54 0.655
Walls (4) 50 55 14 220 /

Workplane:
Height: 0.750 m
Grid: 16 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.033, Ceiling / Working Plane: 0.612.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810062 PANOS LG 1/18W TC-TEL EVG 175 WH +
1 1 1200 20.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 1200 20.5

Specific connected load: 16.06 W/m² = 24.06 W/m²/100 lx (Ground area: 1.28 m²)

Page 13
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Changing Room 1 / Emergency / Summary

8.70 m

7.89

20 7.29
40 6.71
20

20
20 5.07
40 40

40 3.90
40
20 40 3.18
20 2.60
2.18
1.66

0.69
0.00
0.00 1.43 2.53 3.51 4.74 5.59 6.54 8.34 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:112
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 23 1.36 60 0.059
Floor 20 16 1.36 34 0.087
Ceiling 70 0.00 0.00 0.00 0.000
Walls (16) 50 4.90 0.03 66 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 64 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.225, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH +
1 2 1800 28.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 3600 57.0

Specific connected load: 1.62 W/m² = 7.10 W/m²/100 lx (Ground area: 35.15 m²)

Page 14
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Changing Room 1 Lobby / Emergency / Summary

2.88 m

2.18

50
55 55 50
55
50 45 1.44
55
1.16
45
0.91
0.70

0.00
0.00 0.70 1.58 1.89 2.18 2.74 3.44 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:38
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 49 35 59 0.708
Floor 20 25 16 34 0.620
Ceiling 70 0.00 0.00 0.00 0.000
Walls (6) 50 14 0.84 57 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 32 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.315, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH +
1 1 1800 28.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 1800 28.5

Specific connected load: 5.56 W/m² = 11.32 W/m²/100 lx (Ground area: 5.12 m²)

Page 15
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Changing Room 2 / Emergency / Summary

9.11 m
8.40
7.80
40 7.26

20
20 20 6.20
20 5.59
40 40 5.01
20
40 4.30
40
20 3.66
40 40 20
20 2.87
2.21
1.47

0.70
0.00
0.00 1.22 2.27 5.07 6.18 7.23 8.47 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:117
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 21 1.02 60 0.049
Floor 20 14 0.54 34 0.037
Ceiling 70 0.00 0.00 0.00 0.000
Walls (16) 50 4.38 0.00 194 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.227, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH +
1 2 1800 28.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 3600 57.0

Specific connected load: 1.43 W/m² = 6.91 W/m²/100 lx (Ground area: 39.81 m²)

Page 16
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Changing Room 2 Lobby / Emergency / Summary

3.89 m

3.18
2.90

50
2.37

50
50
50 50 1.64

40

0.70

0.00
0.00 0.70 1.55 2.07 2.47 3.41 m

Height of Room: 2.800 m, Mounting Height: 2.900 m, Maintenance factor: Values in Lux, Scale 1:50
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 46 25 60 0.540
Floor 20 24 12 34 0.510
Ceiling 70 0.00 0.00 0.00 0.000
Walls (6) 50 11 0.32 42 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 32 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.252, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


Zumtobel Set 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH +
1 1 1800 28.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 1800 28.5

Specific connected load: 4.15 W/m² = 9.04 W/m²/100 lx (Ground area: 6.86 m²)

Page 17
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Corridor to Retail Spaces / Emergency / Summary

34.41 m

27.73

24.78
22.86

5.38
40
2.68
0.00
0.00 4.99 9.63 15.18 26.18 30.64 m

Height of Room: 2.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:442

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 42 0.13 199 0.003
Floor 20 27 0.82 96 0.030
Ceiling 70 0.00 0.00 0.27 0.000
Walls (14) 50 9.48 0.02 174 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.209, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42177422 SLOT2 1x1/28W LRO LDE IP40 [STD] (1.000) 2600 30.5
Zumtobel 60810092 PANOS LM 1/26W TC-TEL EVG 200 WH [STD]
2 5 1800 28.5
(1.000)
Total: 11600 173.0

Specific connected load: 1.54 W/m² = 3.63 W/m²/100 lx (Ground area: 112.67 m²)

Page 18
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Loading Bay / Emergency / Summary

28.28 m

20
40 23.76
20 22.35
40 40 21.06
20
20 19.65
20
17.32

20 20
40 13.55
20
40 12.09
40 10.10
40 40
40 7.96
40
20 6.35

0.00
0.00 3.71 6.79 12.87 17.50 21.37 25.72 m

Height of Room: 5.150 m, Mounting Height: 5.150 m, Maintenance factor: Values in Lux, Scale 1:364
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 22 1.73 59 0.077
Floor 20 20 0.86 45 0.043
Ceiling 70 6.87 0.03 500 0.005
Walls (15) 50 16 0.00 354 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.748, Ceiling / Working Plane: 0.307.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 31200 321.0

Specific connected load: 0.93 W/m² = 4.15 W/m²/100 lx (Ground area: 344.42 m²)

Page 19
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Generator Foam Suppression Room / Emergency / Summary

3.52 m

100
80
120
100
120
2.03
140
120 120
100
1.50
120
100 1.02
120

80

0.28
0.00
0.00 1.05 2.89 3.42 3.94 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:46
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 110 68 141 0.622
Floor 20 74 54 87 0.727
Ceiling 70 0.46 0.31 0.86 0.688
Walls (7) 50 90 0.03 595 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 32 x 16 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.911, Ceiling / Working Plane: 0.004.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 16.80 W/m² = 15.29 W/m²/100 lx (Ground area: 6.37 m²)

Page 20
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Inergen Room / Emergency / Summary

3.65 m

2.94
120
130
2.34
130
140

120 130 1.27


120

0.70

0.00
0.00 0.70 1.51 1.87 2.67 3.36 m

Height of Room: 5.000 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:47
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 129 110 141 0.858
Floor 20 76 60 87 0.787
Ceiling 70 0.54 0.34 1.49 0.618
Walls (4) 50 97 0.37 532 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 16 x 8 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.837, Ceiling / Working Plane: 0.004.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 10400 107.0

Specific connected load: 17.67 W/m² = 13.74 W/m²/100 lx (Ground area: 6.06 m²)

Page 21
KAFD Parcel 3.09 Basement 1 (Revised Room layouts)
17.01.2011

Operator
Telephone
Fax
e-Mail

Service Lift Lobby / Emergency / Summary

6.94 m
6.49

5.81
5.33
80 80

80 120 120 4.35

160
80 120 80
160
160 120
2.86
120 160
120
80 80
120 120 40 2.11

80 1.32
80
0.76

0.00
0.00 2.60 3.56 4.24 4.90 6.37 m

Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:90
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 85 6.15 172 0.072
Floor 20 61 7.10 98 0.116
Ceiling 70 32 0.00 489 0.000
Walls (12) 50 38 0.00 176 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 64 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.480, Ceiling / Working Plane: 0.376.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 1 Zumtobel 42174382 SCUBA PC 2/35W T16 EVG V2A [STD] (1.000) 6600 76.5
Total: 6600 76.5

Specific connected load: 3.60 W/m² = 4.24 W/m²/100 lx (Ground area: 21.24 m²)

Page 22
Project 1
17.01.2011

Operator
Telephone
Fax
e-Mail

Wadi entrance lobby - BH layout / EMERGENCY Light scene / Summary

14.05 m

12.37

90 90 10.07
90 90
90 90
90

90 90 90 90
90 90 90 90
90 90

1.39
0.00
0.00 18.34 20.49 26.86 33.44 m

Height of Room: 6.100 m, Maintenance factor: 0.80 Values in Lux, Scale 1:240

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 16 0.32 433 0.020
Floor 20 14 0.14 364 0.010
Ceiling 70 0.00 0.00 0.00 0.000
Walls (12) 50 1.50 0.09 7.00 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.094, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 14 iGuzzini 2680 Deep Minimal 2x75W (1.000) 1093 75.0
Total: 15302 1050.0

Specific connected load: 2.94 W/m² = 18.76 W/m²/100 lx (Ground area: 357.59 m²)

Page 1
KAFD Parcel 3.09 Basement 3 Water Tanks
19.01.2011

Operator
Telephone
Fax
e-Mail

Water Tank Room / Emergency / Summary

25.60 m
23.61

20.60
80
18.70
17.00
15.77

12.92
10.97
80 9.74

6.65
5.42

3.19
60 1.96
0.00
0.00 2.45 4.85 10.94 18.30 23.24 26.51 31.04 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:329
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 48 0.35 90 0.007
Floor 20 19 0.00 89 0.000
Ceiling 50 20 0.14 500 0.007
Walls (29) 40 63 0.01 1007 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 64 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.286, Ceiling / Working Plane: 0.424.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 8 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 83200 856.0

Specific connected load: 3.05 W/m² = 6.33 W/m²/100 lx (Ground area: 280.83 m²)

Page 1
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Oil Tank Room / Emergency / Summary

17.53 m

80
80
60 14.73
80
60 40
40 40 12.45
11.61

40 40 9.62
60
60 7.96
80
80
80 60
40
60
40 40
40 3.56
20 2.23
1.12
0.00
0.00 3.00 5.07 7.04 9.81 13.55 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:226
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 47 0.22 87 0.005
Floor 20 46 0.00 87 0.000
Ceiling 50 19 0.01 500 0.000
Walls (6) 40 30 0.00 168 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 64 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.640, Ceiling / Working Plane: 0.405.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 20800 214.0

Specific connected load: 2.63 W/m² = 5.57 W/m²/100 lx (Ground area: 81.24 m²)

Page 1
Level B4
20.01.2011

Operator
Telephone
Fax
e-Mail

Water Tank Room / Emergency / Summary

70.64 m

40
63.39
59.40
40
55.84
20 52.54
49.21
44.78
41.52
40
36.39
40 32.62
29.39
24.22
18.58
13.87
10.41
6.62
3.39
0.00
0.00 7.17 13.84 23.13 32.02 41.33 50.54 58.72 67.07 75.27 89.36 m

Height of Room: 3.550 m, Mounting Height: 3.550 m, Maintenance factor: Values in Lux, Scale 1:907
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 37 0.00 89 0.000
Floor 20 22 0.00 87 0.000
Ceiling 50 15 0.06 503 0.004
Walls (81) 40 45 0.00 2699 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.000 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.242, Ceiling / Working Plane: 0.396.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 19 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 197600 2033.0

Specific connected load: 2.13 W/m² = 5.76 W/m²/100 lx (Ground area: 955.08 m²)

Page 2
Buro Happold

5.3 Superstructure Package Normal


Lighting Calculations

KAFD Plot 3.09 Report Revision 0


PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

Office PGL lobby - BH layout / Normal Light Scene / Summary

26.68 m
450
450 450 450
450 450 22.09
450 450 450 450 450
18.38
450
450 16.05
450 450 450
450 450 450 450 13.92
900 450 450 450
450 450 10.21
450
450
6.39

2.83
0.00
0.00 17.32 24.56 39.74 46.35 52.58 67.15 m

Height of Room: 6.100 m, Mounting Height: 6.100 m, Maintenance factor: Values in Lux, Scale 1:481
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 337 25 2166 0.073
Floor 20 313 24 1731 0.077
Ceiling 70 49 16 97 0.324
Walls (18) 50 60 15 2454 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.173, Ceiling / Working Plane: 0.146.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


ERCO 46450000 Quintessence Directional luminaire 1xHIT-TC-CE 35W
1 24 3400 35.0
(1.000)
2 52 iGuzzini 2682 Deep Minimal 105W (1.000) 4250 105.0
Total: 302600 6300.0

Specific connected load: 9.46 W/m² = 2.81 W/m²/100 lx (Ground area: 665.78 m²)

Page 1
KAFD Parcel 3.09 Level PGL
21.01.2011

Operator
Telephone
Fax
e-Mail

Post room / Summary

6.11 m

5.41

4.54
280

360
320 360
360
320 2.97
360 360
320
320

0.70

0.00
0.00 0.70 1.81 3.79 5.41 6.62 7.32 m

Height of Room: 3.000 m, Mounting Height: 3.092 m, Maintenance factor: Values in Lux, Scale 1:79
0.67

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 316 221 375 0.699
Floor 20 233 141 308 0.606
Ceiling 70 71 53 99 0.744
Walls (6) 50 159 67 366 /

Workplane:
Height: 0.750 m
Grid: 32 x 32 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.546, Ceiling / Working Plane: 0.223.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 5 Zumtobel 42174795 ML4 B EM 2/24W T16 M600 KA [STD] (1.000) 3500 48.5
Total: 17500 242.5

Specific connected load: 11.35 W/m² = 3.59 W/m²/100 lx (Ground area: 21.37 m²)

Page 1
KAFD Parcel 3.09 Level PGL
21.01.2011

Operator
Telephone
Fax
e-Mail

Smoking room / Summary

7.11 m

6.42

90 5.86
100

110

110
3.54
110
100 110
110 100 2.65
2.18
100

0.70

0.00
0.00 0.70 2.54 3.40 4.20 5.19 m

Height of Room: 3.000 m, Mounting Height: 3.092 m, Maintenance factor: Values in Lux, Scale 1:92
0.67

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 101 77 118 0.757
Floor 20 74 49 97 0.656
Ceiling 70 21 18 31 0.879
Walls (6) 50 45 23 100 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.477, Ceiling / Working Plane: 0.205.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


Zumtobel Set 60810070 PANOS LG 1/26W TC-TEL EVG 175 WH +
1 6 1800 28.5
60800031 PANOS IP54 GLAS STRUKT E175 WH [STD] (1.000)
Total: 10800 171.0

Specific connected load: 9.57 W/m² = 9.44 W/m²/100 lx (Ground area: 17.86 m²)

Page 2
KAFD 3.09 PGL level
21.01.2011

Operator
Telephone
Fax
e-Mail

Wadi entrance lobby - BH layout / Normal Light scene / Summary

10.81 m
10.07
9.35
1100

7.13
1100

1100 1100 1100


1100 1100 1100 1100
1100 1100

1100 1.42

0.00
0.00 11.10 12.96 19.28 23.56 m

Height of Room: 5.300 m, Mounting Height: 5.300 m, Maintenance factor: Values in Lux, Scale 1:169
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 343 38 5041 0.111
Floor 20 336 37 4209 0.109
Ceiling 70 60 33 104 0.545
Walls (10) 50 112 40 959 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.335, Ceiling / Working Plane: 0.176.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 4 iGuzzini 2680 Deep Minimal 2x75W (1.000) 2186 150.0
2 15 iGuzzini 2682 Deep Minimal 2x35W (1.000) 2800 70.0
3 14 iGuzzini 8466 Family SHUTTLE 1x70W (1.000) 6600 83.0
Total: 143144 2812.0

Specific connected load: 13.40 W/m² = 3.90 W/m²/100 lx (Ground area: 209.87 m²)

Page 1
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L01 Central lobby pt1 - BH layout / Normal Light scene / Summary

50.21 m

32.03
950 29.35
950
23.81
21.23
950 950 17.96
950
950
950 14.30
950 950
11.26
950 950
950

2.38
0.00
0.00 5.28 14.46 22.41 33.02 38.85 54.96 69.05 83.97 m

Height of Room: 5.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:645

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 290 17 4596 0.059
Floor 20 250 1.99 3695 0.008
Ceiling 70 42 18 132 0.432
Walls (22) 50 69 20 5667 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.242, Ceiling / Working Plane: 0.146.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 28 iGuzzini 2680 Deep Minimal 2x75W (1.000) 2186 150.0
2 69 iGuzzini 2682 Deep Minimal 2x35W (1.000) 2800 70.0
3 25 iGuzzini 8466 Family SHUTTLE 1x70W (1.000) 6600 83.0
Total: 419408 11105.0

Specific connected load: 11.90 W/m² = 4.10 W/m²/100 lx (Ground area: 933.07 m²)

Page 2
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L01 Office lift lobby - BH layout / Normal Light scene / Summary

3.19 m

300 2.68
200 250 300 200
250 300 200 200
300
250 250 300 200
250 250 250
200 200 200 300
250 300 250 300
300 250 200
300 250
200 300 300 200 200 250
300 250
250
300 300 200
250 300 150
0.50

0.00
0.00 0.51 7.68 8.18 m

Height of Room: 5.300 m, Mounting Height: 5.300 m, Maintenance factor: Values in Lux, Scale 1:59
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 244 117 345 0.481
Floor 20 204 65 289 0.319
Ceiling 70 31 18 61 0.576
Walls (4) 50 59 18 606 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.243, Ceiling / Working Plane: 0.129.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 iGuzzini 2661 Deep Minimal 1x35W (1.000) 2006 39.0
2 2 iGuzzini 2661 Deep Minimal 1x35W (Type 2)* (1.000) 2006 39.0
*Modified Technical Specifications Total: 10030 195.0

Specific connected load: 7.57 W/m² = 3.11 W/m²/100 lx (Ground area: 25.77 m²)

Page 4
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L01 Central lobby pt2- BH layout / Normal Light scene / Summary

19.02 m
17.51

15.13

9.51
1000
1000 7.39
1000
1000
1000 1000 1000 4.64
3.73
1000 1000
1000 1000
1000 1000

0.00
0.00 2.07 8.88 11.77 19.00 22.60 29.10 m

Height of Room: 5.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:245

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 397 46 4831 0.117
Floor 20 349 52 4067 0.149
Ceiling 70 57 26 95 0.462
Walls (16) 50 100 30 422 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.240, Ceiling / Working Plane: 0.144.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 7 iGuzzini 2680 Deep Minimal 2x75W (1.000) 2186 150.0
2 19 iGuzzini 2682 Deep Minimal 2x35W (1.000) 2800 70.0
3 30 iGuzzini 8466 Family SHUTTLE 1x70W (1.000) 6600 83.0
Total: 266502 4870.0

Specific connected load: 13.27 W/m² = 3.34 W/m²/100 lx (Ground area: 367.06 m²)

Page 7
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L01 Office lift lobby - BH layout / Normal Light scene / Summary

6.69 m
6.08

450
450
3.76
450
450
450 450 450
2.92
450 450
450
450 450

0.61
0.00
0.00 1.33 12.24 13.49 m

Height of Room: 5.300 m, Mounting Height: 5.300 m, Maintenance factor: Values in Lux, Scale 1:97
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 266 26 2063 0.097
Floor 20 208 21 1570 0.103
Ceiling 70 27 13 47 0.497
Walls (4) 50 46 12 245 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.174, Ceiling / Working Plane: 0.100.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 iGuzzini 2661 Deep Minimal 1x35W (1.000) 2006 39.0
2 2 iGuzzini 2661 Deep Minimal 1x35W (Type 2)* (1.000) 2006 39.0
3 1 iGuzzini 2680 Deep Minimal 2x75W (1.000) 2186 150.0
4 2 iGuzzini 2682 Deep Minimal 2x35W (1.000) 2800 70.0
*Modified Technical Specifications Total: 15810 446.0

Specific connected load: 10.07 W/m² = 3.79 W/m²/100 lx (Ground area: 44.27 m²)

Page 9
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L03 Office lift lobby - BH layout / Normal Light scene / Summary

3.25 m

450 450 2.67


450
450
900 450 900 450 900
450 450 450

0.50
0.00
0.00 15.76 m

Height of Room: 5.300 m, Mounting Height: 5.300 m, Maintenance factor: Values in Lux, Scale 1:113
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 276 22 2022 0.078
Floor 20 210 18 1539 0.084
Ceiling 70 25 13 95 0.492
Walls (4) 50 42 11 941 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.152, Ceiling / Working Plane: 0.092.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 iGuzzini 2661 Deep Minimal 1x35W (1.000) 2006 39.0
2 2 iGuzzini 2661 Deep Minimal 1x35W (Type 2)* (1.000) 2006 39.0
3 3 iGuzzini 2682 Deep Minimal 2x35W (1.000) 2800 70.0
*Modified Technical Specifications Total: 16424 366.0

Specific connected load: 7.32 W/m² = 2.65 W/m²/100 lx (Ground area: 49.97 m²)

Page 11
KAFD Parcel 3.09 Level 02
21.01.2011

Operator
Telephone
Fax
e-Mail

Mechanical Plantroom / Single Sheet Output

100.37 m
94.25
88.34
83.30
280
78.56
71.60

61.73
350 57.10
350 51.00
45.11
37.89
30.60
23.49
18.15
12.44
7.27
0.00
0.00 9.81 19.58 31.88 43.67 58.47 70.32 91.13 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:1289
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 267 50 387 0.187
Floor 20 210 4.79 348 0.023
Ceiling 50 57 4.57 94 0.080
Walls (56) 40 151 30 1441 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.556, Ceiling / Working Plane: 0.215.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 133 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 1383200 14231.0

Specific connected load: 6.57 W/m² = 2.46 W/m²/100 lx (Ground area: 2166.59 m²)

Page 1
KAFD Parcel 3.09 Level 10
21.01.2011

Operator
Telephone
Fax
e-Mail

Tx & RMU Room / Summary

15.04 m
14.19
13.50
350
350
350
350 420 420 9.93
420 350 8.87
420 420 8.14
350 420
420 7.08
420 6.34
420 420 420 350
280 350

350 350
3.18
280
1.58
0.70
0.00
0.00 2.46 4.15 5.98 8.81 10.98 14.50 18.18 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:194
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 352 109 439 0.309
Floor 20 295 74 394 0.250
Ceiling 50 73 42 99 0.578
Walls (20) 40 157 28 589 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.442, Ceiling / Working Plane: 0.208.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 14 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 145600 1498.0

Specific connected load: 10.18 W/m² = 2.90 W/m²/100 lx (Ground area: 147.08 m²)

Page 1
KAFD Parcel 3.09 Level 10
21.01.2011

Operator
Telephone
Fax
e-Mail

LV Switchroom / Summary

15.95 m
210

280
13.17
350 350 12.28
280
11.52
350
280
350 420
280 8.45
7.70
350 350
6.24
210 350 350
350
210
280

0.00
0.00 4.70 6.50 10.05 15.96 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:205
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 311 81 421 0.261
Floor 20 280 61 378 0.219
Ceiling 50 69 50 83 0.729
Walls (16) 40 159 20 1070 /

Workplane:
Height: 0.750 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.502, Ceiling / Working Plane: 0.222.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 12 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 124800 1284.0

Specific connected load: 10.01 W/m² = 3.22 W/m²/100 lx (Ground area: 128.23 m²)

Page 2
KAFD Parcel 3.09 Level 10
21.01.2011

Operator
Telephone
Fax
e-Mail

Mechanical Plantroom / Summary

48.54 m

350 350 42.68

350 350
350 35.30
32.77
350
350 29.18
350 350 26.74
350
24.37
350 21.92
19.45
350
350
12.35
350 350
350
7.28
280 4.87

0.00
0.00 4.85 9.86 15.94 24.03 30.14 36.31 42.47 49.17 58.19 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:624
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 313 59 385 0.188
Floor 20 290 51 356 0.177
Ceiling 50 82 52 104 0.635
Walls (37) 40 195 24 1317 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.624, Ceiling / Working Plane: 0.262.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 71 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 738400 7597.0

Specific connected load: 9.19 W/m² = 2.94 W/m²/100 lx (Ground area: 826.69 m²)

Page 3
KAFD Parcel 3.09 Level 27
21.01.2011

Operator
Telephone
Fax
e-Mail

Mechanical Plantroom / Single Sheet Output

46.41 m
210
41.19
38.73
210 350
350 34.94
32.77
29.96
350 27.63
350 350 24.86
350 21.51
350 19.17
280
16.92
280 14.39
11.76
8.77
6.15

0.00
0.00 5.03 10.54 16.04 21.34 27.08 32.50 38.04 43.76 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:596
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 275 43 371 0.157
Floor 20 202 3.85 336 0.019
Ceiling 50 55 3.03 102 0.055
Walls (60) 40 141 25 1562 /

Workplane:
Height: 0.750 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.503, Ceiling / Working Plane: 0.200.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 61 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 634400 6527.0

Specific connected load: 6.35 W/m² = 2.31 W/m²/100 lx (Ground area: 1028.46 m²)

Page 1
Buro Happold

5.4 Superstructure Package Emergency


Lighting Calculations

KAFD Plot 3.09 Report Revision 0


PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L01 Central lobby pt1 - BH layout / Emergency Light scene / Summary

50.21 m

32.03
29.35

23.81
21.23
17.96
14.30
11.26

2.38
0.00
0.00 5.28 14.46 22.41 33.02 38.85 54.96 69.05 83.97 m

Height of Room: 5.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:645

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 13 1.19 595 0.095
Floor 20 10 0.98 330 0.093
Ceiling 70 0.01 0.00 45 0.000
Walls (22) 50 1.28 0.06 85 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.102, Ceiling / Working Plane: 0.001.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 28 iGuzzini 2680 Deep Minimal 2x75W (1.000) 1093 75.0
Total: 30604 2100.0

Specific connected load: 2.25 W/m² = 17.97 W/m²/100 lx (Ground area: 933.07 m²)

Page 1
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L01 Office lift lobby - BH layout / Emergency Light scene / Summary

3.19 m

50 2.68
150 250 200 150 150 150
200
100 150 150 150
100 100 150 250
250
150 250
100 100 100 100 250
200 150 150
150 100 200 250 200
250
250 150 100 100
150 250 50 50 150
0.50

0.00
0.00 0.51 7.68 8.18 m

Height of Room: 5.300 m, Mounting Height: 5.300 m, Maintenance factor: Values in Lux, Scale 1:59
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 132 24 273 0.183
Floor 20 107 13 209 0.119
Ceiling 70 0.00 0.00 0.00 0.000
Walls (4) 50 17 0.04 495 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.129, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 iGuzzini 2661 Deep Minimal 1x35W (1.000) 2006 39.0
Total: 6018 117.0

Specific connected load: 4.54 W/m² = 3.43 W/m²/100 lx (Ground area: 25.77 m²)

Page 3
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L01 Office corridor - BH layout / Emergency Light scene / Summary

9.15 m
180 60 8.65
8.09

60 60

180
240 240
180

60 60

0.51
0.00
0.00 3.55 5.54 m

Height of Room: 5.300 m, Mounting Height: 5.300 m, Maintenance factor: Values in Lux, Scale 1:118
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 83 1.54 267 0.019
Floor 20 64 1.26 197 0.020
Ceiling 70 0.00 0.00 0.00 0.000
Walls (6) 50 9.26 0.00 80 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.111, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 iGuzzini 2661 Deep Minimal 1x35W (1.000) 2006 39.0
Total: 4012 78.0

Specific connected load: 2.85 W/m² = 3.44 W/m²/100 lx (Ground area: 27.36 m²)

Page 5
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L01 Central lobby pt2- BH layout / Energency Light scene / Summary

19.02 m
17.51

15.13

9.51
80
80 80
7.39

80 80 4.64
3.73
80
80 80 80 80 80

0.00
0.00 2.07 8.88 11.77 19.00 22.60 29.10 m

Height of Room: 5.300 m, Maintenance factor: 0.80 Values in Lux, Scale 1:245

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 11 0.89 357 0.078
Floor 20 9.81 0.93 265 0.095
Ceiling 70 0.39 0.00 241 0.000
Walls (16) 50 2.23 0.01 117 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.205, Ceiling / Working Plane: 0.033.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 7 iGuzzini 2680 Deep Minimal 2x75W (1.000) 1093 75.0
Thorn 96004128 VOYAGER TWINSPOT 2x20w E3NM IP20 LI [STD]
2 12 320 40.0
(1.000)
Total: 11491 1005.0

Specific connected load: 2.74 W/m² = 24.00 W/m²/100 lx (Ground area: 367.06 m²)

Page 6
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L01 Office lift lobby - BH layout / Emergency Light scene / Summary

6.69 m
6.08

120 60
240 240
60 120 120
120 120
60 120 240 180
60 60 3.76

2.92

0.61
0.00
0.00 1.33 12.24 13.49 m

Height of Room: 5.300 m, Mounting Height: 5.300 m, Maintenance factor: Values in Lux, Scale 1:97
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 45 0.19 271 0.004
Floor 20 41 0.20 202 0.005
Ceiling 70 0.00 0.00 0.00 0.000
Walls (4) 50 7.83 0.00 195 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.177, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 iGuzzini 2661 Deep Minimal 1x35W (1.000) 2006 39.0
Total: 4012 78.0

Specific connected load: 1.76 W/m² = 3.88 W/m²/100 lx (Ground area: 44.27 m²)

Page 8
PGL Lobby
21.01.2011

Operator
Telephone
Fax
e-Mail

L03 Office lift lobby - BH layout / Emergency Light scene / Summary

3.25 m
120 180 2.67
120 120 60
120 60
240 120 60
180 120
0.50
0.00
0.00 15.76 m

Height of Room: 5.300 m, Mounting Height: 5.300 m, Maintenance factor: Values in Lux, Scale 1:113
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 39 0.08 271 0.002
Floor 20 35 0.08 202 0.002
Ceiling 70 0.00 0.00 0.00 0.000
Walls (4) 50 7.06 0.00 659 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.190, Ceiling / Working Plane: 0.000.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 2 iGuzzini 2661 Deep Minimal 1x35W (1.000) 2006 39.0
Total: 4012 78.0

Specific connected load: 1.56 W/m² = 4.02 W/m²/100 lx (Ground area: 49.97 m²)

Page 10
KAFD Parcel 3.09 Level 02
21.01.2011

Operator
Telephone
Fax
e-Mail

Mechanical Plantroom / EMERGENCY / Summary

100.37 m
40 94.25
88.34
83.30
40 78.56
71.60
80
80 80 61.73
57.10
80 51.00
80 45.11
80 80
40 37.89
80 40
30.60
40 80
23.49
80
18.15
40 12.44
80
80 7.27
0.00
0.00 9.81 19.58 31.88 43.67 58.47 70.32 91.13 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:1289
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 59 3.51 154 0.060
Floor 20 45 0.00 109 0.000
Ceiling 50 3.23 0.00 10 0.000
Walls (56) 40 29 0.02 1350 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.486, Ceiling / Working Plane: 0.055.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 36 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 374400 3852.0

Specific connected load: 1.78 W/m² = 3.02 W/m²/100 lx (Ground area: 2166.59 m²)

Page 1
KAFD Parcel 3.09 Level 10
21.01.2011

Operator
Telephone
Fax
e-Mail

Tx & RMU Room / EMERGENCY / Summary

15.04 m
14.19
120 13.50
120
120
80
120 120 9.93

40 8.87
80 120 8.14
40
80 120 7.08
40 80 80
6.34
80 120 80 80
80
120 120
120
80 80 120 3.18

1.58
0.70
0.00
0.00 2.46 4.15 5.98 8.81 10.98 14.50 18.18 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:194
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 78 4.41 158 0.057
Floor 20 63 3.94 109 0.063
Ceiling 50 3.96 0.13 6.92 0.033
Walls (20) 40 32 0.02 308 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 64 Points are ignored.
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.408, Ceiling / Working Plane: 0.051.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 4 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 41600 428.0

Specific connected load: 2.91 W/m² = 3.75 W/m²/100 lx (Ground area: 147.08 m²)

Page 1
KAFD Parcel 3.09 Level 10
21.01.2011

Operator
Telephone
Fax
e-Mail

LV Switchroom / EMERGENCY / Summary

15.95 m

30
60
13.17
90
60 12.28
120 90 11.52
60 60
120
30 60 90
90 60 60
60 8.45
90 60 60 7.70
90
120 90
90 90 60
60 90 6.24
60 120 90
60
30 120
60
30

0.00
0.00 4.70 6.50 10.05 15.96 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:205
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 63 7.44 150 0.118
Floor 20 54 2.86 99 0.053
Ceiling 50 2.77 0.30 4.83 0.107
Walls (16) 40 27 0.00 280 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 64 x 64 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.424, Ceiling / Working Plane: 0.044.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 3 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 31200 321.0

Specific connected load: 2.50 W/m² = 3.98 W/m²/100 lx (Ground area: 128.23 m²)

Page 2
KAFD Parcel 3.09 Level 10
21.01.2011

Operator
Telephone
Fax
e-Mail

Mechanical Plantroom / EMERGENCY / Summary

48.54 m
80
40 42.68
80
80
80
80
35.30
80 32.77
80
80
80 29.18
80 80 26.74
80 80 80
80 120 24.37
80 21.92
80
80 19.45
80 80
40
40
80
80 80 80 12.35
40
40 40
80 40 7.28
4.87

0.00
0.00 4.85 9.86 15.94 24.03 30.14 36.31 42.47 49.17 58.19 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:624
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 63 0.30 159 0.005
Floor 20 57 0.23 111 0.004
Ceiling 50 4.36 0.34 9.48 0.078
Walls (37) 40 36 0.00 934 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.578, Ceiling / Working Plane: 0.069.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 18 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 187200 1926.0

Specific connected load: 2.33 W/m² = 3.68 W/m²/100 lx (Ground area: 826.69 m²)

Page 3
KAFD Parcel 3.09 Level 27 - Emergency
21.01.2011

Operator
Telephone
Fax
e-Mail

Mechanical Plantroom / EMERGENCY / Summary

46.41 m
80

80 80 80 41.19
80 38.73
80 80 40 40
80
34.94
40 80 40 40
32.77
80 40 29.96
80
40
40 27.63
120 40 80 24.86
40 40
80 80 21.51
80
40 19.17
40 40 80 80 16.92
40 14.39
40 40 80 11.76
80
8.77
40 40
6.15

0.00
0.00 5.03 10.54 16.04 21.34 27.08 32.50 38.04 43.76 m

Height of Room: 6.400 m, Mounting Height: 3.500 m, Maintenance factor: Values in Lux, Scale 1:596
0.80

Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 53 0.52 154 0.010
Floor 20 38 0.00 105 0.000
Ceiling 50 2.82 0.00 9.49 0.000
Walls (60) 40 24 0.00 323 /

Workplane: Emergency lighting scene (EN 1838):


Height: 0.750 m Only direct light is calculated. Contributions of reflected light
Grid: 128 x 128 Points are ignored.
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.444, Ceiling / Working Plane: 0.053.

Luminaire Parts List

No. Pieces Designation (Correction Factor) Φ [lm] P [W]


1 14 Zumtobel 42174424 SCUBA PC 2/58W T26 EVG V2A [STD] (1.000) 10400 107.0
Total: 145600 1498.0

Specific connected load: 1.46 W/m² = 2.73 W/m²/100 lx (Ground area: 1028.46 m²)