You are on page 1of 6

IEEE Transactions on Power Delivery, Vol. 12, No.

4, October 1997 1439

A NON-PILOT PHASE SELECTOR BASED ON SUPERIMPOSED


COMPONENTS FOR PROTECTION OF DOUBLE CIRCUIT LINES

M.S.Jones, D.W. P ,Thomas, Member, IEEE C . Christopoulos, Member IEEE


GEC Alsthom T&D The Electrical and Electronic Engineering Department,
Protection and Control Ltd., The University of Nottingham,
Stafford, UK. Nottingham, UK.

Abstract- This paper gives details of a new phase-selection which is valid throughout the period when superimposed
scheme for simultaneous phase-ground faults on both circuits of components can be obtained.
double circuit EHV transmission lines. Fast phase selection
(within half a cycle) can be achieved by using the information IT. FAULT TRANSIENTS
contained within the fault transients. The theory is presented
along with results obtained through simulations using EMTP. The
The initial magnitudes of the travelling-waves propagating
scheme enables single pole tripping to be employed for
simultaneous faults. The proposed scheme does not require
communication between the two ends of the line. Limitations due
to the low bandwidth of CVT’s have not caused problems and the
method has shown immunity to system noise. Circuit 1

I. INTRODUCTION
4
W l6VA
Fast and accurate phase selection can greatly improve distance
protection and system stability [ 11. Where a double circuit line Circuit 2
is used to connect two areas, then it is feasible to maintain a 3
phase link between the two ends when simultaneous phase-
ground faults occur on both circuits (figure 1) by employing
selective pole tripping. With non-unit (non-pilot) distance Figure 1 Single line diagram of system under study
protection of the types presently in use, such a fault
combination will cause the relays to initiate three pole tripping
of both circuits at one or both ends of the protected zone [2]. away from the fault are dependant upon the system voltage at
the instant the fault occurs. For any particular single circuit
When a fault occurs on a transmission-line it causes a sudden fault, a fault conductance matrix [Y,] can be derived [5].
change in the voltage at the fault location. This change causes Then, knowing the surge impedance of the line under study
travelling-waves, in voltage and current, to propagate away [Z,],it is possible to derive the fault reflection coefficient [k,,]
from the fault location [3], and these are superimposed on the as [51
power frequency signal. Each particular type of fault produces
its own characteristic set of superimposed signals which
provide the information necessary for phase selection [4]. It
will be shown that a phase selection criterion can be derived

where [U] is the unit matrix


PE-268-PWRD-0-11-1996 A paper recommended and approved
by the IEEE Power System Relaying Committee of the IEEE Power
Engineering Society for publication in the IEEE Transactions on If the voltage just prior to fault inception is [V,], it is possible
Power Delivery. Manuscript submitted July 2 2, 1996; made to show that the initial travelling voltage waves [V,] are
available for printing November 25, 1996.
V,I = rqrvfl (2)

On a single-circuit three-phase transmission line, the transient


travelling waves can be considered to propagate as three
independent modes [3]. To a good approximation, the three
independent modes are those of a fully transposed line and are

0885-8977/97/$10.00 0 1997 IEEE


1440
comprised of a ground mode or common mode and two aerial cover faults occurring on one circuit only of a double circuit
modes [ 5 ] . The aerial modes (modes 1 and 2) propagate at line. In this paper we will extend further the scheme to cover
approximately the velocity of light but the ground mode (mode simultaneous faults on both circuits of a double circuit line.
0) propagation can not be easily predicted and is dependant on
factors such as earth resistivity. Therefore, in most schemes, the 111. SIMULTANEOUS DOUBLE CIRCUIT PHASE-
ground mode is subtracted to leave the aerial modes only. GROUND FAULTS

These transients are superimposed on the system voltages and If a double circuit line is considered as a 6-phase system, then
currents. They can be found by filtering out the power system the travelling wave equation of (2) can be used with all
components from the relaying transducer signals to leave the quantities in terms of 6 phases rather than the usual 3. Note that
incremental or superimposed voltages [AV] and currents [AI]. it has been assumed that both circuits are fully transposed and
From [AV] and [AI] the voltage amplitude of the incident each phase is connected to its corresponding phase on the other
travelling waves at the relaying point can be found from [4 ,6] circuit at the busbars. There will now be six modes of
propagation and the modal reflections at the busbars will be
independent of each other if the double circuit line is
connecting balanced systems. The resultant 6-phase
equivalent fault reflection coefficient matrix for a fblly
The incident voltage amplitudes [VI] are then compared with transposed line is.
the predicted voltage amplitudes given by (2) to implement
phase selection [4] and [7].
a O O O b O
It should be noted that the relay transducers will distort the 1 , 0 0 0 . , 1
waveforms that are observed by the relay. Typical transducer
x o o o x o
bandwidths of voltage transformers are less than 600Hz. This [kV3 =
means that individual travelling-waves can not be resolved. x o o o x o
However a general solution of the superimposed transients c O O O d O
incident at the relay has the form [7]
x o o o x o

where the values of the constants x,a,b,c, and d are given in the
appendix.

where [SI is the modal transformation matrix and [A,] and [BA
are diagonal matrices with diagonal elements given by

A l l = ( e (Ylx> P,,e ( - Ylx>> -


+ (5)

I
v WI 25-May-94 14.00.43
400

phase-b
,-./ I ,;Z
cb_I
3z+- '/,-
200
,-A' phase-c

-200 j IIn
pzl and plj are the mode i reflection coefficients at busbars 2
and 1 respectively, yi are the mode i propagation constants, L
is the total line length and i are the modes 0, 1 and 2.
400

400 uyLJ
0.64ms phase-a

In [7] a phase selection scheme was developed that is consistent


with both (2) and (4) to provide correct phase selection for
faults on single circuit lines [7]. The method was shown to have
a general solution valid for the total period when superimposed
! Incident travelling voltage waves due to the aerial modes as seen
quantities were available. This can be directly extended to location x on circuit 1.
1441
The deduced incident waves due to the aerial modes arriving at phase-a on circuit 1 just prior to fault inception can be given as
relay location x on circuit 1 are shown in figure 2. From (7) it
is expected that the incident aerial voltage waves on the
unfaulted phases should be equal in magnitude. This is only
true for the very first incident wave as other incident waves are
present after a short period (0.64 ms.) thus preventing this
equality from being a suitable selection criterion. Therefore
some means is necessary of decomposing the total waves where %, is the phase-a fault resistance and
arriving at each relay into the components due to the two faults. Via(wx)= Incident aerial voltage wave on phase-w, circuit
x of the single circuit systems
VJyz) = Initial amplitude of the phase voltages at the fault
location on phase-y, circuit z.

A similar expression for the voltage waves due to the b'-g fault
is given from (2) and hence the voltage on phase-b on circuit 2
just before fault inception is given by

where Kbis the phase-b resistance to ground

igure 3 Wave propagation due to a simultaneous phase-ground, phase If the fault resistances are assumed to be zero (L= Kb=0) then
ground fault on a double circuit line
the unknown initial phase voltage amplitudes Vdal) and V b 2 )
can be substituted from (9) and (IO) into (8). The total incident
First, consider separately the incident travelling-waves due to travelling voltage wave on circuit 1 is then defined in terms of
the aerial modes for the two simultaneous faults. If the double the initial voltage waves on phase-a propagating away from the
circuit line is initially treated as two separate single circuit a-g fault and the initial waves on phase-b propagating away
lines, with the fault reflection coefficient matrix for the aerial from the b'-g fault giving
mode phase voltages due to the a-g fault is [k,fa(a)] and the
fault reflection coefficient for the b'-g fault is [k,"(b')] ,equation
r 1
(2) gives two expressions for each set of travelling-waves
present on the lines. Consider now the relay shown at point x
in figure 3 on circuit 1 and assume none of the travelling waves
are reflected from the load busbar. The incident waves on
circuit 2 at w will be transmitted onto circuit I at v and travel - V:(a I) ( 5 zdd+zee)Vi"(b 2 )
towards location x as shown in figure 3. Ignoring any 2 'dd
secondary reflections, the incident waves at the relay location
x are due to the transients instigated by the fault on circuit 1
and those instigated by the fault on circuit 2 that have 3zdd ]
propagated through the load bus onto circuit 1 and through the
circuit 1 fault and are given by

For the relaying location x on circuit 1 (1 1) can be solved for


the initial voltage waves on phase-a due to the a-g fault and the
initial voltage waves on phase-b due to the b'-g fault which
gives

where [Vdcct l)] and [Vdcct 2)] are the prefault voltages at the
fault locations for circuit 1 and circuit 2 respectively.

For the a-g fault and from (2) an expression for the voltage on
1442

1
V,'(bZ) = ---[Vp(la) + 2V,"(lb)] (13)
3

where V,a(la) andV,"(lb) are the total incident aerial voltages where VIa(2a)and V,a(2b) are the total incident aerial voltages
on circuit 1 phase-a and phase-b repectively. on circuit 2 phase-a and phase-b repectively

In the initial derivation the losses at the far busbar and the
attenuation along the transmission line are neglected. In the
physical system, these losses are significant. Therefore, if an a-
26-May-94 10.37.57 g fault occurs on circuit 1, the travelling wave component on
circuit 1 due to this fault (12) will be greater than the
corresponding component on circuit 2 (15) due to attenuation
0
and reflection. Similarly, the b'-g components given by (13)
and (16) will be of differing magnitudes.
-200

If the simultaneous faults occur at approximately the same


-400
location along the transmission line, then (1 1) to (16) are also
valid for the general solution for the superimposed modal
-600
transients given by (4). Thus (1 1) to (1 6 ) provide a powerful
1
measure of simultaneous single phase faults which are valid for
-800
I8 19 20 21 22 23 24 25 all the superimposed transients.
t [msl
IV. SIMULATION RESULTS

Figure 4 shows the two a-g fault travelling wave components


of the transients given in figure 2. A1 represents the component
Figure 4 Travelling wave components on circuits 1 and 2 due to the a-g fault.
on the a-phase given by (12) as seen by the relay at x on circuit
1. A2 being the same component given by (15) as seen by relay
Similarly, for the relay location y on circuit 2 the total incident y on circuit 2. The a-g fault occurs at simulation time t=20ms
aerial voltage on circuit 2 is

Fvl 26-May-94 10.46.53


200

-200
I I B2
-400 1-
0.64ms

-600

-BOO
18 19 20 27 22 23 24 25

Equation (14) can be rearranged to give t tmsl

V,"(al) = -[2v;(2a)
2 + VJ24 (15)
3

igure 5 Travelling wave components on circuits 1 and 2 due to the b'-g fault.
1443
on circuit 1 simultaneously with the b'-g fault on circuit 2. Note 50Hz cycle and filtered by a 600Hz low pass filter. By using
that A2 has a 0.64 ms delay compared with AI as it propagates the following criteria (17) correct phase selection can be made.
an extra 200 km. These detailed features will not normally be
resolved. The important feature is the relative amplitudes of A1 There is a simultaneous a'-g and b'-g fault if
and A2 which will be observed in all conditions.
A1 > A2 and 8 2 > B1 (17)
Figure 5 shows the b'-g fault travelling wave components. B 1
is the component due to the b'-g fault calculated using (1 3) and
the waves incident at relay x on circuit 1 . B2 being the same Averaging the decision of the complete half cycle ensures
wave derived from (16) and the incident waves arriving at correct phase selection even when the travelling wave
relay y on circuit 2. Here again there is a clear distinction in components are small.
the relative amplitudes of B 1 and B2.
Similar phase selection criteria for the other possible
The delay between the two wavefionts of each pair of waves in
figures 4 and 5 demonstrate the correct decomposition of the
incident travelling voltage waves. Owing to reflections and

Figure 7 Travelling wave components on circuits 1 and 2 due to the b'-g fault
(filtered to 600Hz and sampled at 72 samples per cycle).

simultaneous phase to ground faults ensure correct phase


igure 6 Travelling wave components on circuits 1 and 2 due to the a-g faul selection for all fault combinations. Phase selection then takes
(filtered to 600Hz and sampled at 72 samples per cycle).
the following form. First, the two faulted phases are identified
from the fault current levels. The possibility of simultaneous
losses, the wave component for the particular fault is greatest phase-ground faults on each circuit is then checked using a
on the circuit on which it occurs. In this case A1>A2 and decision process as given for an a-g and b'-g fault in (1 7). If a
B2>B 1 indicates the fault is a simultaneous a-g, b'-g fault. In simultaneous fault is identified, then single pole trip on the
reality, due to the limitations of present hardware, all the faulted phases, otherwise three pole trip. Though this promises
information in figures 4 and 5 cannot be utilized. The low to be a very powerful technique, simultaneous faults close to
sampling rate eliminates the ability to accurately time the two the remote busbar are difficult to resolve as ultimately the faults
wavefronts arriving at each relay. The low bandwidth of CVT's look like a busbar fault affecting both circuits.
also results in a distortion of the wavefronts. However, by using
the magnitude comparison of the two travelling wave Only a representative case is shown here, but the scheme has
components successful phase selection can still be achieved. been extensively tested on a wide range of faults and power
Figures 6 and 7 show the transients sampled at 72 samples per system conditions. The precise limitations of the scheme
1444
depend on the transmission line length and the source short travelling wave based fault location schemes." Proc. IEE, Vol.
circuit capacity. The scheme has been found to be capable of 139, NO.4, July 1992, ~ ~ 3 3 2 - 3 4 2 .
operating on 400 kV line faults at least within the first 80% of
the transmission line length for lines as short as a 10.0 km and [6] D W P THOMAS, "Protection of major transmission lines
source capacities as low as 2.0 GVA. using travelling-waves." Ph.D. Thesis, University of
Nottingham, May 1990, pp 101-104.
V. CONCLUSIONS
[7] D W P THOMAS, M S JOHNS and C CHNSTOPOULOS,
In this paper a new method of phase selection for simultaneous "Phase selection based on superimposed components." Proc.
phase-ground faults occurring on both circuits of a double IEE, Gen. Transm. Distrib., Vo1143 (3) May 1996 pp 295-299
circuit line was presented. The scheme uses superimposed
components to provide a fast and accurate decision within half VIII. APPENDIX
a power frequency cycle. Though the relays at one end of the
transmission line have to communicate, the scheme is The fault reflection coefficient matrix [k",,] for a simultaneous
essentially a non-unit scheme as information from the remote a-g, b'-g fault for a double circuit line is given by (8) where [4]
end is not required. The algorithm has been developed to be
useable with protection equipment in current use, has been
tested on a variety of system configurations, and shown to be
valid over the usual distance protection scheme's zone 1 range.

VI. ACKNOWLEDGEMENTS

The authors wish to thank the Science and Engineering


Research Council and GEC Measurements T&D Protection and
Control Ltd. for their financial support.

VII. REFERENCES

[l] R 0 BERGLAND, W A MITTELSTADT, M L


SHELTON, P BARKEN, C G DEWEY, and K M
SKREINER, "One cycle fault interruption at 500kV. System
benefits and breaker design." IEEE trans P.A.S., vol. PAS-93, Martin S Jones was born in Preston, UK, on May 16, 1970. He received a
B.Eng in Electrical and Electronic Engineering with French in 1991. From
1974, ~ ~ 1 2 4 0 - 1 2 5 1 .
1991 to 1994 he was in postgraduate research in the Electrical and Electronic
Engineering Department, University of Nottingham. Since 1994 he has been
[2] J ESZTERGALYOS, J ANDRICHAK, D H COLWELL, in Relay Development at GEC ALSTHOM T&D Protection and Control Ltd.
D.C DAWSON, JA JODICE, T J MURRAY, K K
David W P Thomas was born in Padstow, Cornwall, UK on May 5,1959. He
MUSTAPHI, G R NAIL, A POLITIS, J W POPE, G D received a B. Sc. degree in Physics from Imperial College of Science and
ROCKEFELLER, G P STRANNE, D TZIOUVARAS and E 0 Technology, London, M. Phil degree in Space Physics from Sheffield
SCHWEITZER, "Single phase tripping and auto reclosing of University and the Ph.D. degree from Nottingham University, in 1981, 1987,
transmission lines. IEEE committee report" IEEE Trans and 1990 respectively. In 1984 he joined the department of Electrical and
Electronic Engineering at the University of Nottingham where he is now a
PWRD, vol. 7 No. 1, January 1992, pp182-192. Lecturer. His research interests are in Power System Protection,
Electromagnetic Compatibility, and Electrosatic Precipitation.
[3] L M WEDEPOHL, "Application of matrix methods to the
solution of travelling-wave phenomena in polyphase systems" Christos Christopoulos was born in Patras, Greece, on September 17, 1946.
He received the Diploma in Electrical Engineering and Mechanical
Proc. IEE, Prt C, Vol. 110, 1963, pp 2200-2212. Engineering from the National Technical University of Athens in 1969 and
the MSc and DPhil from the University of Sussex in 1970 and 1974
[4] A T JOHNS and M M EL-DIN MAHMOUD, "New respectively. In 1974 he joined the Arc Research Project of the University of
approach to ultra-high-speedphase-selectionin single-pole auto Liverpool and worked on vacuum arcs and breakdown while on attachment
to the UKAEA Culham Laboratories. In 1976 he joined the University of
reclosure schemes." Proc. IEE, Vol 133, Pt. C, No. 4, May Durham as a senior demonstrator in Electrical Engineering Science. In
1986 pp 188-200. October 1978 he joined the Department of Electrical and Electronic
Engineering where he is now a Professor of Electrical Engineering. His
[ 5 ] G B ANCELL and N C PAHALAWATHTHA "Effects of research interests are in Electrical Discharge and Plasmas, Electromagnetic
Compatibility, Electromagnetics, and Protection and Simulation of Power
frequency dependance and line parameters on single ended Networks.

You might also like