Professional Documents
Culture Documents
Abstract- This paper gives details of a new phase-selection which is valid throughout the period when superimposed
scheme for simultaneous phase-ground faults on both circuits of components can be obtained.
double circuit EHV transmission lines. Fast phase selection
(within half a cycle) can be achieved by using the information IT. FAULT TRANSIENTS
contained within the fault transients. The theory is presented
along with results obtained through simulations using EMTP. The
The initial magnitudes of the travelling-waves propagating
scheme enables single pole tripping to be employed for
simultaneous faults. The proposed scheme does not require
communication between the two ends of the line. Limitations due
to the low bandwidth of CVT’s have not caused problems and the
method has shown immunity to system noise. Circuit 1
I. INTRODUCTION
4
W l6VA
Fast and accurate phase selection can greatly improve distance
protection and system stability [ 11. Where a double circuit line Circuit 2
is used to connect two areas, then it is feasible to maintain a 3
phase link between the two ends when simultaneous phase-
ground faults occur on both circuits (figure 1) by employing
selective pole tripping. With non-unit (non-pilot) distance Figure 1 Single line diagram of system under study
protection of the types presently in use, such a fault
combination will cause the relays to initiate three pole tripping
of both circuits at one or both ends of the protected zone [2]. away from the fault are dependant upon the system voltage at
the instant the fault occurs. For any particular single circuit
When a fault occurs on a transmission-line it causes a sudden fault, a fault conductance matrix [Y,] can be derived [5].
change in the voltage at the fault location. This change causes Then, knowing the surge impedance of the line under study
travelling-waves, in voltage and current, to propagate away [Z,],it is possible to derive the fault reflection coefficient [k,,]
from the fault location [3], and these are superimposed on the as [51
power frequency signal. Each particular type of fault produces
its own characteristic set of superimposed signals which
provide the information necessary for phase selection [4]. It
will be shown that a phase selection criterion can be derived
These transients are superimposed on the system voltages and If a double circuit line is considered as a 6-phase system, then
currents. They can be found by filtering out the power system the travelling wave equation of (2) can be used with all
components from the relaying transducer signals to leave the quantities in terms of 6 phases rather than the usual 3. Note that
incremental or superimposed voltages [AV] and currents [AI]. it has been assumed that both circuits are fully transposed and
From [AV] and [AI] the voltage amplitude of the incident each phase is connected to its corresponding phase on the other
travelling waves at the relaying point can be found from [4 ,6] circuit at the busbars. There will now be six modes of
propagation and the modal reflections at the busbars will be
independent of each other if the double circuit line is
connecting balanced systems. The resultant 6-phase
equivalent fault reflection coefficient matrix for a fblly
The incident voltage amplitudes [VI] are then compared with transposed line is.
the predicted voltage amplitudes given by (2) to implement
phase selection [4] and [7].
a O O O b O
It should be noted that the relay transducers will distort the 1 , 0 0 0 . , 1
waveforms that are observed by the relay. Typical transducer
x o o o x o
bandwidths of voltage transformers are less than 600Hz. This [kV3 =
means that individual travelling-waves can not be resolved. x o o o x o
However a general solution of the superimposed transients c O O O d O
incident at the relay has the form [7]
x o o o x o
where the values of the constants x,a,b,c, and d are given in the
appendix.
where [SI is the modal transformation matrix and [A,] and [BA
are diagonal matrices with diagonal elements given by
I
v WI 25-May-94 14.00.43
400
phase-b
,-./ I ,;Z
cb_I
3z+- '/,-
200
,-A' phase-c
-200 j IIn
pzl and plj are the mode i reflection coefficients at busbars 2
and 1 respectively, yi are the mode i propagation constants, L
is the total line length and i are the modes 0, 1 and 2.
400
400 uyLJ
0.64ms phase-a
A similar expression for the voltage waves due to the b'-g fault
is given from (2) and hence the voltage on phase-b on circuit 2
just before fault inception is given by
igure 3 Wave propagation due to a simultaneous phase-ground, phase If the fault resistances are assumed to be zero (L= Kb=0) then
ground fault on a double circuit line
the unknown initial phase voltage amplitudes Vdal) and V b 2 )
can be substituted from (9) and (IO) into (8). The total incident
First, consider separately the incident travelling-waves due to travelling voltage wave on circuit 1 is then defined in terms of
the aerial modes for the two simultaneous faults. If the double the initial voltage waves on phase-a propagating away from the
circuit line is initially treated as two separate single circuit a-g fault and the initial waves on phase-b propagating away
lines, with the fault reflection coefficient matrix for the aerial from the b'-g fault giving
mode phase voltages due to the a-g fault is [k,fa(a)] and the
fault reflection coefficient for the b'-g fault is [k,"(b')] ,equation
r 1
(2) gives two expressions for each set of travelling-waves
present on the lines. Consider now the relay shown at point x
in figure 3 on circuit 1 and assume none of the travelling waves
are reflected from the load busbar. The incident waves on
circuit 2 at w will be transmitted onto circuit I at v and travel - V:(a I) ( 5 zdd+zee)Vi"(b 2 )
towards location x as shown in figure 3. Ignoring any 2 'dd
secondary reflections, the incident waves at the relay location
x are due to the transients instigated by the fault on circuit 1
and those instigated by the fault on circuit 2 that have 3zdd ]
propagated through the load bus onto circuit 1 and through the
circuit 1 fault and are given by
where [Vdcct l)] and [Vdcct 2)] are the prefault voltages at the
fault locations for circuit 1 and circuit 2 respectively.
For the a-g fault and from (2) an expression for the voltage on
1442
1
V,'(bZ) = ---[Vp(la) + 2V,"(lb)] (13)
3
where V,a(la) andV,"(lb) are the total incident aerial voltages where VIa(2a)and V,a(2b) are the total incident aerial voltages
on circuit 1 phase-a and phase-b repectively. on circuit 2 phase-a and phase-b repectively
In the initial derivation the losses at the far busbar and the
attenuation along the transmission line are neglected. In the
physical system, these losses are significant. Therefore, if an a-
26-May-94 10.37.57 g fault occurs on circuit 1, the travelling wave component on
circuit 1 due to this fault (12) will be greater than the
corresponding component on circuit 2 (15) due to attenuation
0
and reflection. Similarly, the b'-g components given by (13)
and (16) will be of differing magnitudes.
-200
-200
I I B2
-400 1-
0.64ms
-600
-BOO
18 19 20 27 22 23 24 25
V,"(al) = -[2v;(2a)
2 + VJ24 (15)
3
igure 5 Travelling wave components on circuits 1 and 2 due to the b'-g fault.
1443
on circuit 1 simultaneously with the b'-g fault on circuit 2. Note 50Hz cycle and filtered by a 600Hz low pass filter. By using
that A2 has a 0.64 ms delay compared with AI as it propagates the following criteria (17) correct phase selection can be made.
an extra 200 km. These detailed features will not normally be
resolved. The important feature is the relative amplitudes of A1 There is a simultaneous a'-g and b'-g fault if
and A2 which will be observed in all conditions.
A1 > A2 and 8 2 > B1 (17)
Figure 5 shows the b'-g fault travelling wave components. B 1
is the component due to the b'-g fault calculated using (1 3) and
the waves incident at relay x on circuit 1 . B2 being the same Averaging the decision of the complete half cycle ensures
wave derived from (16) and the incident waves arriving at correct phase selection even when the travelling wave
relay y on circuit 2. Here again there is a clear distinction in components are small.
the relative amplitudes of B 1 and B2.
Similar phase selection criteria for the other possible
The delay between the two wavefionts of each pair of waves in
figures 4 and 5 demonstrate the correct decomposition of the
incident travelling voltage waves. Owing to reflections and
Figure 7 Travelling wave components on circuits 1 and 2 due to the b'-g fault
(filtered to 600Hz and sampled at 72 samples per cycle).
VI. ACKNOWLEDGEMENTS
VII. REFERENCES