MANUAL
Control Panel
SETRONIK1
INTRODUCTION
Our compliments for choosing the SETRONIK1 controller as the controller for your lift.
Please carefully read this booklet so that you will be able to understand all the qualities of
this device and its potential.
Warning
Since our products are in constant evolution, all information contained in this manual can
be modified by SEA SYSTEMS without notice.
In the case of special lifts, any accessory documentation relating to additional or modified
functions is provided.
SETRONIK1 Pagina 2 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
TABLE OF CONTENTS
SETRONIK1 Pagina 3 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
5. MAINTENANCE ................................................................................ 52
5.1. BATTERY REPLACEMENT.............................................................................................52
5.2. SHAFT SENSORS ........................................................................................................52
5.3. STK1-B BASIC ELECTRONIC BOARD REPLACEMENT .....................................................53
5.4. CS1 SAFETY CIRCUIT REPLACEMENT ..........................................................................54
6. BASIC TROUBLESHOOTING PROCEDURES .................................. 55
6.1. ALARMED CARD (ALL LED ON)....................................................................................55
6.2. ERRONEUS READOUT OF THE SHAFT SENSORS .............................................................55
7. TECHNICAL DATA ............................................................................. 56
SETRONIK1 Pagina 4 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1.FUNCTIONAL CHARACTERISTICS
LIFT TYPES - ROPE 1 - 2 SPEEDS , ACVV , VVVF
- HYDRAULIC : DIRECT , STAR DELTA , SOFT STARTER , SOFT STOP, SCC,
ELECTRONIC VALVES
SETRONIK1 Pagina 5 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
2.INSTALLATION
2.1.GENERAL NOTES
NOTE
Carefully read any warning information in the present operating instructions as
holding important safety, operating and service instructions.
SETRONIK1 Pagina 6 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
2.2.SAFETY RULES
•The unit can only be installed by qualified and authorised personnel, who is liable for the
specific compliance to standards according to the technical best practice available.
•Before any cleaning or serve, cut the unit from the power supply by means of the
installation cut-out switch.
• Always wear the demanded personal protections (fig. 2.1),and more precisely:
- Cask.
- Gloves.
- Overall, closed at the wrist level.
- Protective shoes.
- Safety belts.
- Headphones.
• Never wear loose objects and/or clothing (necklaces, watches, ties), avoid long hair.
• Never store cutting or pointed objects (screwdriver, scissors …) in the shirt pocket.
• Never tamper, wear or hide warning signs or labels. When wore and demanded,
immediately replace the.
• In order to lift heavy loads, always used suitable tools, thus avoiding any damage to the
spine cord depending on the unit manual handling.
2.3.GLOSSARY
NOTE
It provides personnel with specific and valuable information.
WARNING
It provides personnel with information which, when not complied with, can lead to
light people or installation damages
CAUTION
It provides personnel with information on a specific operation, which, if not taken
into account in compliance with safety regulations in force, can lead to possible
severe physical damages.
SETRONIK1 Pagina 7 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
2.4.PRELIMINARY OPERATIONS
Before starting the installation, check what follows:
C)SCAFFOLDING
When setting the unit up, use standard scaffolding, exhibiting operating floors at any stop,
at about 0.5 meter lower than the stop.
CAUTION
Scaffolding completely or partially in metal, to be connected to a suitable
grounding, in compliance with safety regulations in force.
SETRONIK1 Pagina 8 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
HIGHLIGHT
Should the control panel be secured on premises other than the standard
machine room (ex: local cabinet, Pit, Shaft,...), the above procedure may be
inappropriate. In this case, follow the instructions specified for the system.
4. Make sure that the QM master switch is set to OFF (DOWN position);
5. Connect the appliances to the control panel as per the installation diagrams in the
paragraph 2.8
SETRONIK1 Pagina 9 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
Diagram for sensor and magnet disposition Æ See diagram See diagram See diagram
CVIA CVIA CVIC
HIGHLIGHT
We recommend that you choose A System or C System for the installation of
magnets. The system ensures tighter fastening of the magnets, a better magnetic
field, less exposure to various bodies (grease, iron fillings….)
With the B System, the magnets without bracket have to be fixed directly on the
guide.
SETRONIK1 Pagina 10 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
CVIA SHAFT SENSORS PLACING FOR HYDRAULIC LIFT WITH A OR B SHAFT SENSOR KIT
HIGHLIGHT
With the B System, the magnets without bracket have to be fixed directly on the
guide.
SLOWING DISTANCE K
SPEED K
0.2 m/s 20cm
0.4 m/s 40 cm
0.6 m/s 60 cm
0.8 m/s 80 cm
SETRONIK1 Pagina 11 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
CVIC SHAFT SENSORS PLACING FOR HYDRAULIC LIFT WITH C SHAFT SENSOR KIT
SLOWING DISTANCE K
SPEED K
0.2 m/s 20cm
0.4 m/s 40 cm
0.6 m/s 60 cm
0.8 m/s 80 cm
SETRONIK1 Pagina 12 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
SETRONIK1 Pagina 13 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1. Move the sensor IS toward the centre of a length equal to the space of relevelling
zone required.
2. Gradually increase the value of timer 4.12 so that, when upward runs are repeated,
the car stops aligned with the floor sill.
The timer value depends on the required speed and Relevelling Zone.
3. Move the sensor ID toward the centre so that, in coming down to the landing, the car
stops aligned with the sill.
WARNING
The relevelling control with open doors is permitted by the safety circuit (CS1
device and C, D sensors).
When the led C and D of the CS1 device are on, the relevelling control is
permitted; if one or both of the leds are off the relevelling control with open doors
is interrupted.
SETRONIK1 Pagina 14 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
Diagram for sensor and magnet disposition Æ See diagram See diagram
CVFA CVFA
HIGHLIGHT
We recommend that you choose A System for the installation of magnets. The
system ensures tighter fastening of the magnets, a better magnetic field, less
exposure to various bodies (grease, iron fillings….)
With the B System, the magnets without bracket have to be fixed directly on the
guide.
SETRONIK1 Pagina 15 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
CVFA SHAFT SENSORS PLACING FOR ELECTRIC LIFT WITH A SHAFT SENSOR KIT
HIGHLIGHT
With the B System, the magnets without bracket have to be fixed directly on the
guide.
SLOWING DISTANCE K
SPEED K
0.6 m/s 60cm
0.8 m/s 80 cm
1 m/s 120 cm
1.2 m/s 140 cm
SETRONIK1 Pagina 16 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
SETRONIK1 Pagina 17 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
2.8.INSTALLATION DIAGRAMS
S01CONNECTIONS BETWEEN PANEL AND USERS IN THE MACHINE ROOM: WIRING DIAGRAM
SETRONIK1 Pagina 18 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
SETRONIK1 Pagina 19 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
SETRONIK1 Pagina 20 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
SETRONIK1 Pagina 21 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
S04CALLING PUSH BUTTONS AND BOOKING SIGNALINGS IN THE CAR AND AT THE FLOORS IN UP
AND DOWN COLLECTIVE WITH 1 ACCESS: WIRING DIAGRAM (*).
DOWN FLOOR
UP FLOOR
CAR
NOTE (*)
refer to Paragraph 2.5
SETRONIK1 Pagina 22 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
SETRONIK1 Pagina 23 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
CODE DESCRIPTION
IS, ID Stop, door opening-closing and up and down speed-change sensors
LV Overspeed governor
MA Maintenance stop
MB Low speed push-button being serviced
MC Exchange motor
MG Motor for Electric lift
MN Maintenance switch
MP 1st operator door motor
MP1 2nd operator door motor
MPR Preferred operation contact
MR Restricted operation contact
PA Alarm push-button
PAP1 2nd operator opening push-button
PC 1st operator car door contact
PC1 2nd operator car door contact
PCP, PAP 1st operator closing push-button; 1st operator opening push-button
PT Devices to prevent falls
QF Light switch
QM Master switch
RT Drive thermistor
SP; SP1 Minimum pressure switch; maximum pressure switch
SR, DR Up and down phase shifting sensors
STO Oil temperature thermal contact
XS1 Pit plug
XS2 Car plug
YBR Brake
YCT Electrical sliding block
YVD Down electric valve
YVL Levelling electric valve
YVP Y/∆ switching start electric valve
HIGHLIGHT (*)
For further information on how to connect ringing keys and calling signals, refer to
Paragraph 2.5.
SETRONIK1 Pagina 24 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
2.9.INSULATION TEST
Before carrying out the flash tests reported in the following table, perform the following
operations:
1 Bring the car out of the landing zone;
2 De-energise QM master switch and QF light switch;
3 Pull out and insulate the ground cables that reach the panel;
4 Unplug the phone line from the dialling key.
Master Safety dev., Three-phase Car d.c. Motor, Signals
Switch, Brake, Motor, Doors Lighting Doors OCC,FD,FS,
TO Motors Retractable MP,MP,MP, L1,L,N +,-,30,32, PS1,PS2…
R,S,T, Sliding MP1,MP1,MP1 MP,MP
FROM U,V,W, block
U1,V1,W1 1..10, F+,F-,
U2,V2,W2 PR+,PR-
GROUND
_____
___
U U U U U U
_
Master Switch,
Motors
R,S,T, U,V,W,
U1,V1,W1
U2,V2,W2
NO U U U U U
Safety dev.,
Brake,
Retractable
Sliding block
1..10, F+,F-,
U NO U U NO U
PR+,PR-
Alarm
AL+, AL-, AL U NO U U NO U
Car Lighting
L1,L,N U U U NO U U
Signals
OCC,FD,FS,PS1 U U U U U NO
Safety Circuit
DI,XC2,CI,XC1 U NO U U NO U
U = Insulation test to be carried out.
SETRONIK1 Pagina 25 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
2.10.SYSTEM COMMISSIONING
1. Make sure that the maintenance push-button panel switch placed on the car roof is set
to NORMAL;
2. Turn ON the control panel and ascertain that the following leds are switched ON:
1, 2, 8, 10, CM, 01, +5 (in case of Hydraulic lift also TC and PST);
3. Should any problems arise (ex: alarmed card: ALL leds ON), refer to Paragraph 6:
Basic Troubleshooting Procedures.
SETRONIK1 Pagina 26 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
3.PROGRAMMING
3.1PROGRAMMER CONNECTION (STK2-PM)
1. Check that the ON\OFF switch of the Keyboard is in the OFF position.
2. Insert the connection cable in connector FC3 on the STK1-B board.
3. Bring the ON\OFF switch in the ON position.
4. All the 7 displays show the number 8 for about 2”: this function is used to check that
all displays are working correctly.
5. After the 2”, the displays show 0.00.XXXX (X indicates any number), or 0.00.0000
with the last four digits flashing. In this second case it means that an access code
has been stored and that it is therefore necessary to enter the digits of the access
code in the last 4 displays (DG3..DG6) and then to press .
ab
d ef g c
a= Displays indicating the Parameter Code, marked as DG0, DG1 and DG2.
b= Displays indicating the Parameter Value, marked DG3, DG4, DG5, DG6.
c= DIN guide release
d= ON\OFF switch.
e= Connection cable to connector FC3 on the STK1-B board.
f= Pushbutton to select the display from DG0 to DG6, scrolling from left to right
whenever it is pressed. The selected display flashes.
g= Pushbuttons , to modify the number of the display previously selected.
(Please refer to ‘Example of programmer use’ Par. 3.2)
SETRONIK1 Pagina 27 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
DG0 flashes
DG0 flashes
4
1.3. Select DG1 and DG2, by pressing the pushbutton once
(DG1 and DG2 flash):
DG0 DG1 DG2 DG3 DG4 DG5 DG6
DG3..DG6 flash
4 0 2
DG3..DG6 flash
4 0 2 0 0 8 0
NOTA
The value set is operational by pressing once, but it is not stored.
For the storing please refer to paragraph 3.4_Parameters Storing..
SETRONIK1 Pagina 28 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
0 1 0
ACCESS CODE
The old access code stored is displayed. If no code has been entered, value 0000 is
displayed.
Enter the new access code on displays DG3..DG6.
(Value 0000 removes the access code)
0 1 1
ACCESS CODE
Enter the same access code entered in point 2 on displays DG3..DG6. If the code is
different, the same is not accepted, therefore the old code previously stored, if any, is
valid.
(Value 0000 removes the access code)
SETRONIK1 Pagina 29 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
3.4.PARAMETERS STORING.
This parameter execute the command for the permanent storing of the parameters
modified. If this operation is not performed, any modifications made remain valid until the
power supply to the STK1_B boards is cut off.
0 1 2 0 0 0 0
0 1 2 0 0 0 0
3. Press for one second, then displays DG3..DG6 indicate the following result of the
operation:
DG0 DG1 DG2 DG3 DG4 DG5 DG6
Or
DG0 DG1 DG2 DG3 DG4 DG5 DG6
STORING INCORRECT.
0 1 2 0 0 0 3 Repeat the command or replace the board.
SETRONIK1 Pagina 30 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1 0 0
MASTER / SLAVE
0= Single Lift
1= Master control panel for Duplo with two signalings
‘Coming’
2= Master control panel for Duplo with one signaling
‘Coming’
3= Slave control panel for Duplo
4= Not used
SELECTOR TYPE
0= Shaft with magnetic switches without safety circuit
(CS1)
1= Shaft with magnetic switches with safety circuit
(CS1)
OPERATION TYPE
0= APB
1= Not enabled
2= Down collective
3= Up and down Collective
4= Pick-Up
LIFT TYPE
0= 1 speed Electric lift
1= 2 speed Electric lift
2= 2 speed Electric lift with ACVV
3= Electric lift for Inverter without encoder
4= Electric lift for Inverter with encoder
5= Hydraulic lift
1 0 1
NUMBER OF SERVICES
NUMBER OF STOPS
SETRONIK1 Pagina 31 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1 0 2
MAIN FLOOR
1 0 3
FIREMAN FLOOR #2
(Input Function 9)
FIREMAN FLOOR #1
(Input Function 8 o 22)
1 0 4
NUMBER OF DUPLO VERTICAL RISE FLOORS
(to be programmed on the panel of the lower lift)
NOTA
Floors numbering starts from number 1 corresponding to the lower external floor
SETRONIK1 Pagina 32 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1 0 5
OPERATOR B
See Operator A
OPERATOR A:
(1) = Set the timer 4.04 (for Operator A) end/or the timer 4.05 (for operator B) twice the
door closing time;
(Limit switches are controlled: see error codes from 76 to 79)
(2) Set the timer 4.04 (for Operator A) end/or the timer 4.05 (for operator B) equal to the
door closing time;
(3) = The door opening/closing signal is turned off when the set with the timer 4.04
end/or 4.05 is over;
(4) = Set the timer 4.06 (for both operators A and B) to delay the door ri-opening after
the photocell activation (with 4.06.0000 = immediate ri-opening)
Operators with Motor power supplied during the run with closing limit switch:
In case of operators that need to be power supplied during le lift run, it is necessary to use
the input programmable functions 30 and 31 (see par. 3.14)
SETRONIK1 Pagina 33 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1 0 6
SETRONIK1 Pagina 34 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1 0 7
GONG ACTIVATION
0= Upon speed change only for external calls
1= On floor only for external calls
2= Upon speed change for internal or external calls
3= On floor for internal or external calls
SETRONIK1 Pagina 35 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1 0 8
OVERLOAD CONTACT (INPUT CE)
0=Contact NO;
1=Contact NC
SETRONIK1 Pagina 36 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
3.11.PROGRAMMING OF SERVICES.
In order to modify the parameters values, it is necessary to disconnect the FA automatic
valve while, to only display the same, this is not necessary.
2
TYPE OF OPENING AND
DOOR STATUS IN PARKING FOR B ACCESS:
See Type of Opening and Door status in parking for A
Access
B ACCESS TYPE:
See A access Type
A ACCESS TYPE:
0= There is no service
1= Simplex Access (*)
2= Duplo Access (*)
STOP
01= Stop1
02= Stop2
03= Stop3
04= Stop4
.
.
.
12= Stop12
(*) Simplex / Duplo Access= The Access has to be programmed Simplex if the relative
stop is served by only one lift (in this case the Simplex access has to be
programmed on this lift);
The access has to be programmed Duplo if the relative stop is served by both the
lifts (in this case the Duplo Access has to be programmed on both the lifts).
SETRONIK1 Pagina 37 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
3.12.SHAFT PROGRAMMING:
In order to modify the parameters values, it is necessary to disconnect the FA automatic
valve while, to only display the same, this is not necessary.
DG0 DG1 DG2 DG3 DG4 DG5 DG6
3 0 0
INTER-FLOOR TYPE (*)
00= Normal Floors
(Interfloor > 2K)
01= Short Floors
(Interfloor < 2K and > 1K)
02= Close Floors
(Interfloor < 1K and > 2 brackets)
03= Very Close Floors
(Interfloor < 2 brackets: a second bracket is
required)
INTER-FLOOR SELECTION
01= Inter-floor between floor 1 and 2
02= Inter-floor between floor 2 and 3
03= Inter-floor between floor 3 and 4
04= Inter-floor between floor 4 and 5
05= Inter-floor between floor 5 and 6
06= Inter-floor between floor 6 and 7
07= Inter-floor between floor 7 and 8
08= Inter-floor between floor 8 and 9
09= Inter-floor between floor 9 and 10
10= Inter-floor between floor 10 and 11
11= Inter-floor between floor 11 and 12
(*) = K is the slowing distance: see the layout L01 and L02
SETRONIK1 Pagina 38 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
3.13.PROGRAMMING OF TIMERS:
4
TIME
Expressed in tenths of a second
(i.e. 0080 = 8 seconds)
TIMER
00= Max duration of the inter-floor run
01= Max duration run in low speed (if 4.01=0000 Æ the timer is not enabled)
02= Floor parking duration (occupied)
03= Floor parking reduced duration after photocell activation
04= Max duration of the stage side A lift doors opening/closing
(See error codes from 76 to 77)
05= Max duration of the stage side B lift doors opening/closing
(See error codes from 78 to 79)
06= doors opening delay after stop or door re-opening delay with operator 09
07= Max time at start (after the drop out of closing / opening contactors)
08= despatch delay to parking floor
(if 4.08=0000 Æ the timer is not enabled)
09= despatch delay to lower outmost floor (for hydraulic lifts)
(if 4.09=0000 Æ the timer is not enabled)
10= combinable with output functions to be programmed
11= combinable with output functions to be programmed
12= Stop delay to adjust the relevelling space
(see paragraph 2.6.3_‘Relevelling space adjustment’)
13= Max time of the call holding with still car
14= contactors excitation delay at start (this is used to avoid false excitations of operating
contactors due to safety contacts bouncing)
15= doors opening delay due to the activation of the safety circuit (used with door opening
in advance)
SETRONIK1 Pagina 39 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
3.14.INPUT PROGRAMMING:
5 0 0
INPUT FUNCTION
00 None
INPUTS: 01 - Safety photocells (With operators in 02 type);
- Door opening extralimit switch of the 1° and 2° operator (with
operator different from 02 type) (NC contact)
Led Term. 02 Oil thermal sensor (NC contact)
00 03 Low point pressure switch (NC contact)
01 X1 X1 04 Peak point pressure switch (NC contact)
02 (*) X2 X2 05 Landing operation stop control (for ACVV or 3VF with old interface)
03 (*) X3 X3 06 Operator A sticking contactor control
04 (*) X4 X4 07 Operator B sticking contactor control
05 (*) X5 X5 08 Fire-fighting operation with despatch to the fire-fighting floor #1
06 X6 J8.4 09 Fire-fighting operation with despatch to the fire-fighting floor #2
07 (*) X7 J9.4 10 Preferential operation
08 X8 J2.4 11 Safety circuit control (err 19, 20)
09 X9 J2.5 12 Very close landings control (with Additional ID switch)
10 X10 J2.6 13 Very close landings control (with Additional IS switch)
11 X11 J2.7 14 High/low speed Maintenance
12 FG FG 16 Full load
13 MR MR 17 Alarm with 0094 error, Out-of-service on landing
14 TC TC 18 Additional extralimit switch in the top_Contact monitoring and 0095
error signalling
15 PST PST 19 Alarm with 0096 error, immediate out-of-service
16 MP MP 20 Alarm with 0097 error, Failed start (3VF)
21 Reserved operation
22 Hong Kong Firemen operation
23 Photocell of the operator A independent of the opening push button
(used with selective opening)
(*) = Leds and 24 Photocell of the operator B independent of the opening push button
terminals are on the (used with selective opening)
expansion card 25 Out-of-service with despatch to the programmed parking floor with
STK1-E signalling of error 098
26 BA1 input (NA) for panels without board STK1-E
28 Emergency operation (not with board B12E)
29 CM1 input (NC) for panels without board STK1-E
30 Doors closing limit switch for operator A (NC contact for lifts with
motors powered during the run)
31 Doors closing limit switch for operator B (NC contact for lifts with
motors powered during the run)
32 Low and peak point pressure switch (PST) (NC contact; it can be
used only on inputs X6, X9, FG, PST)
SETRONIK1 Pagina 40 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
3.15.OUTPUT PROGRAMMING:
5 0 0
NOTE: Functions 0016, 0017, 0018 are obsolete with diagrams based on Eprom 4.00 or
later types.
SETRONIK1 Pagina 41 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
4.DIAGNOSIS
4.1.LIFT STATUS DISPLAY
The parameter value (DG3..DG6) is constantly updated in relation to the current status of
the lift.
If the Car Position is 00 (DG5, DG6), this means that the resetting operation has not been
performed.
0 0 0
CAR POSITION
0= Lift without resetting
n= Actual position ( from 1 to 12)
OPERATION STATUS
0= Floor parking
1= Doors closing for start
2= High speed motion
3= Low speed motion
4= Doors opening
5= Car still off landing
LIFT STATUS
0= Normal operation
1= Firemen operation on
2= Fire-fighting operation on
3= Preferential operation on
4= Reserved operation on
5= Safety photocell action
6= Not used
7= Out-of-service for failures at floor
8= Out-of-service for permanent failures
9= Maintenance operation on
SETRONIK1 Pagina 42 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
0 0 1
FAILURE CODE
If the parameter value (DG3..DG6) is 0000, this means that no failure or malfunction has
occurred.
Set ‘Parameter Code’ 0.02 on displays DG0, DG1, DG2 and press :
DG0 DG1 DG2 DG3 DG4 DG5 DG6
If the parameter value (DG3..DG6) is 0000, this means that no failure/malfunction has
occurred or the end of the failure codes list has been reached.
C).FAILURES CANCELLATION:
1. Set ‘Parameter Code’ 0.03 on displays DG0, DG1, DG2 and press :
DG0 DG1 DG2 DG3 DG4 DG5 DG6
DG3..DG6 FLASH
0 0 3 0 0 0 0
2. Press . The parameter value (DG3..DG6) shows 0001 to indicate that failures have
been deleted:
DG0 DG1 DG2 DG3 DG4 DG5 DG6
FAILURES DELETED
0 0 3 0 0 0 1
SETRONIK1 Pagina 43 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
0 0 0
NUMBER OF TENS OF RUNS
Displays DG3..DG6 show the tens of runs performed. The maximum value which can be
displayed is 9999 corresponding therefore to 99999 maximum runs.
0 0 6 0 0
RUNS NUMBER
0 0 0
NUMBER OF RELEVELLINGS
SETRONIK1 Pagina 44 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
0 0 9
B OPERATOR CLOSING\OPENING OPERATION:
A=Doors opening in progress, or already open.
To perform the closing, select DG6 and press .
C=Doors closing in progress, or already closed.
To perform the opening, select DG6 and press
AUTOMATIC CALLS:
0=Function disabled. The lift works normally.
1=Calls on all floors in automatic mode, it stops if
DG3=0 or if the lift goes Out-of-service.
2=Calls on all floors in automatic mode, it stops if
DG3=0 or if any type of failure occurs.
3=It controls the car motion in low speed.
Position on DG4
Press to go down, to go up.
(For these commands the safety devices must be
closed and the lift must not be in maintenance
condition)
SETRONIK1 Pagina 45 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
SETRONIK1 Pagina 46 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
SETRONIK1 Pagina 47 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
(*) = The programmed function code is specified on the tab TS01, the programmed
function is described at the paragraphs 2.14 and 2.15.
SETRONIK1 Pagina 48 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
CODE DESCRIPTION
001 Run timer action ( Timer 4.00.XXXX )_Immediate Permanent Out of Order
002 Low speed timer action ( Timer 4.01.XXXX )_ Immediate Permanent Out of Order
003 Overload cut-out 1 action (-RT)_Permanent Out of Order at floor
004 Not used
005 The car has performed a number of levellings equal to the value set in Parameter
1.06.XXXX_Permanent Out of Order at floor
006 Run (KM)/ High (KA)/ Low (KB) contactors sticking_ Immediate Permanent Out of
Order
007 Up (KS)/ Star (KY)/ Delta (K∆) contactors sticking_Immediate Permanent Out of Order
008 Down (KD)/ impedance/resistors exclusion (KE) contactors sticking_ Immediate
Permanent Out of Order
009 Lack of or wrong input phases sequence_ Immediate Temporary Out of Order
010 Safety chain Terminal 1 with no voltage_ Immediate Temporary Out of Order
011 Overtravel action (Ex) _ Immediate Permanent Out of Order
012 Pit stop action (AF)/ Maintenance Stop (MA)/ Safety gear (PT)/ Approaches (ACC)/
End of Timer 4.13.XXXX at floor with doors kept open_ Immediate Permanent Out of
Order
013 Not used
014 Safety photocell action (for cars with no doors) _ Immediate Temporary Out of Order
015 Failed excitation of the Run (KM)/ High (KA)/ Low (KB) contactors
016 Failed excitation of the Up (KS)/ Star (KY)/ Delta (K∆) contactors
017 Failed excitation of the Down (KD)/ impedance exclusion (KE) contactors
018 Failed excitation of the resistors exclusion (KEA, KEB) contactors
019 Safety circuit (CS1) active with car off floor (input function 11)_ Immediate Temporary
Out of Order
020 Safety circuit (CS1) not active with car at floor (input function 11)_ Immediate
Temporary Out of Order
021..044 Failed closing of safety contacts PC \ PC1 \ BC..BCn on floor
(Floor number = ‘Error code’ less 20)
045..068 Opening of safety contacts PC \ PC1 \ BC..BCn going to the floor
(Floor number = ‘Error code’ less 44)
069 Opening of the safety contacts PC \ PC1 \ BC..BCn during resetting run
SETRONIK1 Pagina 49 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
CODE DESCRIPTION
070 Failed excitation of door opening minicontactor KAP for 1°operator (if it exists)
071 Failed excitation of door opening minicontactor KAP1 for 2°operator (if it exists)
072 Failed excitation of door closing minicontactor KCP for 1° operator (if it exists)
073 Failed excitation of door closing minicontactor KCP1 for 2° operator (if it exists)
074 Sticking of door opening/closing minicontactor KAP \ KCP for 1°operator (if it exists)
075 Sticking of door opening/closing minicontactor KAP1 \ KCP1 for 2°operator (if it exists)
CODE DESCRIPTION
076 Door opening limit switch FCA did not open after the programmed time (Timer 4.04.)
(if it exists)
077 Door closing limit switch FCC did not open after the programmed time (Timer 4.04) (if
it exists)
078 Door opening limit switch FCA1 (for 2°operator) did not open after the programmed
time (Timer 4.05) (if it exists)
079 Door closing limit switch FCC1 (for 2°operator) did not open after the programmed
time (Timer 4.05) (if it exists)
080 Floating floor off for more than 5 consecutive runs (with programmed parameter 1.07)
090 Oil thermal sensor action (STO) in hydraulic lifts or Motor thermal sensor action (TS1-
TS2) in Electric lifts_ Temporary Out of Order at floor
091 Low and/or peak point pressure switch action (SP, SP1) (standard electrical
configuration)_ Immediate Permanent Out of Order
092 Alarm combined with Function 04 input_ Immediate Permanent Out of Order
093 Not used
094 Alarm combined with Function 17 input_ Temporary/Permanent Out of Order at floor
095 Alarm combined with Function 18 input_ Permanent Out of Order at floor
096 Alarm combined with Function 19 input (e.p. ACVV, VVVF, electronic valve GEV,…)_
Immediate Permanent Out of Order
097 Failed start (Combined with Function 20 input, e.p. VVVF,… )_ Permanent Out of
Order at floor
098 Alarm combined with Function 25 input_ Permanent Out of Order at floor
SETRONIK1 Pagina 50 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
CODE DESCRIPTION
100..123 Sensor IS skipped a Stop plate during the upward run
(skipped floor = ‘Error code’ less 99)
124..147 Sensor ID skipped a Stop plate during the downward run
(skipped floor = ‘Error code’ less 123 )
148..171 Sensor IS skipped a Speed change plate during downward run
(Related floor = ‘Error code’ less 147 )
172..195 Sensor IS skipped a Speed change plate during upward run
(Related floor = ‘Error code’ less 171 )
196..219 Sensor ID skipped a Speed change plate during downward run
(Related floor = ‘Error code’ less 195 )
220..243 Sensor ID skipped a Speed change plate during upward run
(Related floor = ‘Error code’ less 219 )
244 Sensor DR open at the upper floors in run
245 Sensor DR closed with car in floor zone at the upper floor, or
Sensor DR open with car in floor zone at the lower floors
246 Sensor SR closed with car in floor zone at the lower floor, or
Sensor SR open with car in floor zone at the upper floors
247 Sensor SR open at the lower floors at start
248 Sensor DR and SR open simultaneously_ Temporary Out of Order at floor
SETRONIK1 Pagina 51 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
5.MAINTENANCE
Before carrying out any cleaning or maintenance operations, unplug the appliance from
the power supply unit by turning OFF the master switch.
While maintenance procedures are in progress, refer to the safety regulations set out in
paragraph 2.
In no event shall SEA SYSTEMS Srl be liable for any damages whatsoever arising out of
the inability to comply with the above instructions and of any improvements as regards
configuration, fastening and connections in the originally supplied apparatus.
5.1.BATTERY REPLACEMENT
The control panel is fitted with the following batteries:
• 12v 2Ah. or
• 12v 7.5Ahif an emergency descent is provided for
5.2.SHAFT SENSORS
Shaft indicators are formed by monostable and/or bistable sensors and their
corresponding magnets to enable switching.
In order to ensure that sensors switch over properly when placed opposite their
corresponding magnets, check out on a yearly basis that:
- The distance between the sensor and its corresponding magnet is kept 1 cm apart,
including during machining stress;
- Sensors travel the same axis as the magnets;
- Magnets have no metal bodies attached;
- The brackets for both the sensors and magnets are steadily fastened to the car roof
and the guides.
SETRONIK1 Pagina 52 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1. Before carrying out any operations, make sure that the control panel is de-energised;
2. Visually check that the supporting structure and the card are in suitable conditions,
i.e., that they show no dents that could result in short-circuits;
3. To secure the card and prevent it from being damaged, use M3X8 type of screws only
and a suitable cross tip screwdriver;
4. Engage all the retaining screws for the card to be tightly anchored to the frame;
5. Insert all the connectors retrieved from the control panel wiring board;
6. When peeling the wires for connection purposes, turn them towards the outside of the
cabinet to avoid ejecting copper wires towards the card;
7. Visually check the card and make sure that there are no foreign bodies, such as
flakes of dry plaster, pieces of electric wire or conduction material;
8. While tightening the removable jumpers screws on the lower side of the card, use an
appropriate screwdriver to avoid card damage in the process.
SETRONIK1 Pagina 53 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
1. Before carrying out any operations, make sure that the control panel is de-energised.
2. The CS1 safety circuit is anchored to a DIN guide, driven into the control panel; to
remove the device from the DIN guide, use an appropriate screwdriver to loosen the
upper tab of the device.
WARNING
Do not open the casing covering the CS1 device.
4. Visually inspect the circuit and look out for possible short-circuits between the jumpers.
SETRONIK1 Pagina 54 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
SETRONIK1 Pagina 55 di 56
INSTALLATION AND USE MANUAL MSTK11-GB
CONTROL PANEL STK1 Rev.01
SEA SYSTEMS For Electric and Hydraulic Lifts 30/12/05
7.TECHNICAL DATA
Input voltages 110 to 440 Vac (Single-phase and Three-phase)
Operating voltage 48 Vdc
Cam, electro-valves, operators ON DEMAND
voltages
Position, arrows, out-of-service 24 Vdc – 4.5W Max. Each
signalling outputs (With upper power see NOTE 1)
Coming, booking, Gong, Overload 24 Vdc – 2.4W Max. Each
signalling outputs (With upper power see NOTE 2 and 3)
Occupied signalling outputs 24 Vdc – 36W Max.
Safety devices inputs OPTO-ISOLATED (Conforming with EN 81
ED.98)
Operating temperature 0 ÷ 40 °C
Logic type MICROPROCESSOR CONTROLLED
Data storage PERMANENT
Re-chargeable battery 12vdc, 2 ÷ 7.5 ah (3 years life if constantly under
charge)
NOTE 1:
If the Position and Arrow signallings require a power upper than that specified upon, it’s
necessary use STK1-RO card;
NOTE 2:
If the Position Arrow and Booking signallings require a power upper than that specified upon,
it’s necessary use STK1-RV card;