SM6 Switchgears

 The SM6 range is made up of modular


units containing fixed or withdrawable
metal-enclosed SF6 switchgear, including:
switch-disconnectors;
Fluarc SF1 or SFset circuit breakers;
Rollarc 400 or 400D contactors;
disconnectors.

 SM6 units are used for the MV section in


MV/LV transformer substations in public
distribution systems and MV consumer or
distribution substations up to 24 kV.

 SM6 units are designed for indoor


installation (IP2XC).

SM6 The secondary distribution solution

standards
• recommendations: IEC 298,
265 129
265, 129, 694
694, 420
420, 56
56;
• UTE standards: NFC 13.100,
13.200, 64.130, 64.160;
• EDF specifications: HN 64-S-
41, 64-S-43.

secondary distribution

BMTBD-TSN training-nxcuong-8.04 2

4.2 Máy ngắt SM6


SM6 The modular SF6 solution: equipment for MV/LV
substations

 Factory built assemblies

 SF6 switchgear

 Protection and control/


monitoring functions

24 KV - 630 A ou 1250 A - 20 KA / 1s
12 KV - 630 A ou 1250 A - 25 KA / 1s

BMTBD-TSN training-nxcuong-8.04 3

SM6

industrial
distribution
substations

BMTBD-TSN training-nxcuong-8.04 4

4.2 Máy ngắt SM6


SM6 Optimum performance
rated voltage (KV) 7,2 12 17,5 24

50 Hz / 1 min. (KV rms) insulation 20 28 38 50


isolation 23 32 45 60

1,2 / 50 µs (KV peak) insulation 60 75 95 125


isolation 70 85 110 145

breaking capacity, transformer off load (A) 16 16 16 16

breaking capacity, cables off load (A) 25 25 25 25

short-time withstand in 630/1250 A 25 25 20 20


current (kA / 1 s) in 400/630/1250 A 12,5 12,5 12,5 12,5

BMTBD-TSN training-nxcuong-8.04 5

SM6 Compartmented factory built cubicles


2
 Switch cubicles

1 1. switchgear
4 2. busbars
3. operating mechanism
3
4. low voltage
5. connection

BMTBD-TSN training-nxcuong-8.04 6

4.2 Máy ngắt SM6


SM6 Compartmented factory built cubicles

2
 Circuit breaker cubicles

5
1 1. switchgear
3 2. busbars
3. operating mechanism
4. connection and circuit breaker
5. low voltage

3
4

BMTBD-TSN training-nxcuong-8.04 7

SM6 Factory built cubicles

 Switchgear (switch and disconnector)


compartment

 0,4 bar relative pressure

 Sealed pressure system

 safety membrane

 switch-diconnector
switch diconnector

 Earthing switch

BMTBD-TSN training-nxcuong-8.04 8

4.2 Máy ngắt SM6


switch and disconnector compartment
SM6

1 enclosure
2 cover
3 operating shaft
4 fixed contact
5 moving contact
6 seall

BMTBD-TSN training-nxcuong-8.04 9

SM6 SF6 switchgear

 3-position switch
 Isolation
 M ki capacity
Making it off earthing
thi switch
it h
 Optimized breaking technique

closed open earthed

BMTBD-TSN training-nxcuong-8.04 10

4.2 Máy ngắt SM6


SM6 Factory built cubicles

 Busbar compartment

 Connection in horizontal plane


 Field distributors
 Insulated busbars
 No risk of error

BMTBD-TSN training-nxcuong-8.04 11

SM6 Factory built cubicles

 Connection and switchgear (circuit


breaker) compartment
 All ttypes off cables
bl
 up to 240 mm2 - 630 A and
 up to 630 mm2 - 1250 A

 Single-handed connection

 Field distributors

 Fluarc SF1 or SFset circuit breakers

BMTBD-TSN training-nxcuong-8.04 12

4.2 Máy ngắt SM6


SM6 SF6 circuit breaker

 SF1 circuit breaker: 630 or 1250 A

 combined
bi d with
ith an electronic
l t i relay
l and
d standard
t d d sensors

 auxiliary power supply

BMTBD-TSN training-nxcuong-8.04 13

SM6 SF6 circuit breaker

 SFset enhanced circuit breaker - 630 A

 special sensors
 dedicated electronic relays
 no auxiliary power supply

BMTBD-TSN training-nxcuong-8.04 14

4.2 Máy ngắt SM6


Fluarc SFset or SF1 circuit breaker
SM6

1 enclosure
2 bottom cover
3 operating shaft
4 main moving contact
5 moving arcing contact
6 fixed arcing contact
7 sealing system
8 compression chamber
9 moving piston
10 valves
11 insulating nozzle

BMTBD-TSN training-nxcuong-8.04 15

SM6 breaking principle

BMTBD-TSN training-nxcuong-8.04 16

4.2 Máy ngắt SM6


SM6 Factory built cubicles

 Operating mechanism compartment


 optional motorized operation
 low
l maintenance
i t
 clear, animated mimic panels
 accessible with busbars energized

BMTBD-TSN training-nxcuong-8.04 17

SM6 Positive break

 Position indicator on operating shaft

 Direct
Di t and
d reliable
li bl transmission
t i i mechanism
h i

 Natural interlocking

Closed Open Earthed

BMTBD-TSN training-nxcuong-8.04 18

4.2 Máy ngắt SM6


SM6 Factory built cubicles

 For protection and control/monitoring systems


 Accessible with cables and busbars energized

BMTBD-TSN training-nxcuong-8.04 19

SM6 Protection and control monitoring functions

Network Coupling Transfo. Motor

SEPAM
1000 and 2000

STATIMAX

BMTBD-TSN training-nxcuong-8.04 20

4.2 Máy ngắt SM6


SM6 Protection and control monitoring functions

 Sepam 1000 series

 protection
t ti

 measurements

 auxiliary source

BMTBD-TSN training-nxcuong-8.04 21

SM6 Protection and control monitoring functions

 Sepam 2000 series

 Remote communication

 Protection

 Measurements

 Automatic control functions

 Adjustable
j p
parameters

 Self-test

 Auxiliary source

BMTBD-TSN training-nxcuong-8.04 22

4.2 Máy ngắt SM6


SM6 Connection to networks

 Incoming or outgoing unit  Outgoing unit,


right or left

IM 375 IMC 500 IMB 375

BMTBD-TSN training-nxcuong-8.04 23

SM6 Protection

 Fuses-switch  Fuses-switch
unit combination unit

PM 375 QM 375

BMTBD-TSN training-nxcuong-8.04 24

4.2 Máy ngắt SM6


SM6 Protection

 Fuses-switch  Fuses-switch
combination unit combination unit,
right or left outgoing line

QMC 625 QMB 375

BMTBD-TSN training-nxcuong-8.04 25

SM6 Protection

 Contactor unit  Fused-contactor unit

CRM 750 CRM 750

BMTBD-TSN training-nxcuong-8.04 26

4.2 Máy ngắt SM6


SM6 Protection

 Single-isolation circuit
 Single-isolation
breaker unit right or
circuit breaker unit
left outgoing line

DM1 - A 750 DM1 - D 750

BMTBD-TSN training-nxcuong-8.04 27

SM6 Protection

 Double-isolation circuit breaker unit,


right or left outgoing line

DM2 750

BMTBD-TSN training-nxcuong-8.04 28

4.2 Máy ngắt SM6


SM6 Protection

 Withdrawable  Withdrawable single-isolation


single-isolation circuit circuit breaker unit, right or
breaker unit left outgoing line

DM1 - W 750 DM1 - Z 750

BMTBD-TSN training-nxcuong-8.04 29

SM6 MV metering

 Voltage transformers  Voltage transformers for mains


for mains with earthed with insulated neutral system
neutral system

CM 375 CM2 500

BMTBD-TSN training-nxcuong-8.04 30

4.2 Máy ngắt SM6


SM6 MV metering

 Current and/or voltage  Current and/or voltage


measurement unit, right measurement unit
or left outgoing line

GBC - A 750 GBC - B 750

BMTBD-TSN training-nxcuong-8.04 31

SM6 Functions required by private networks

 Intermediate  Extension unit  Connection unit


bus unit VM6/SM6 right/left outgoing line

GIM 125 GEM 125 GBM 375

BMTBD-TSN training-nxcuong-8.04 32

4.2 Máy ngắt SM6


SM6 Functions required by private networks

 Incoming  Incoming
cable-connection unit cable-connection unit

GAM 2 375 GAM 500

BMTBD-TSN training-nxcuong-8.04 33

SM6 Functions required by private networks

 Disconnector unit  MV/LV transformer


unit for auxiliaries

SM 375 TM 375

BMTBD-TSN training-nxcuong-8.04 34

4.2 Máy ngắt SM6


SM6 Functions required by private networks

 Busbars power supply for main incoming line on right or left


and cables for stanby line

NSM-barres 375 NSM-cables 375

BMTBD-TSN training-nxcuong-8.04 35

SM6 Optimum characteristics

rated voltage (KV) 7,2 12 17,5 24

IM, IMB, IMC, NSM-cables, 630 A 630 A 630 A 630 A


NSM-busbars
PM, QM, QMC, QMB 25 KA 25 KA 20 KA 20KA

CRM 10 KA 8 KA

CRM with fuses 25 KA 12,5 KA

DM1 - A, DM1 - D, DM1 - W, 25 KA 25 KA 20 KA 20 KA


DM1 - Z
DM2 20 KA 20 KA 20 KA 16KA

BMTBD-TSN training-nxcuong-8.04 36

4.2 Máy ngắt SM6


SM6 Optimum characteristics

Mechanical endurance electrical endurance


IM, IMC, IMB, CEI 265 CEI 265
PM 1000 100 breaks
QM, QMC, QMB operations at In, cos  = 0,7
NSM-cables, NSM-busbar
CRM CEI 56 CEI 56
300 000 100 000 breaks
operations at 320 A
300 000 breaks
at 250 A
DM1 - A, DM1 - D, CEI 56 CEI 56
DM1 - W, DM1 - Z, DM2 10 000 40 breaks
operations at 12,5KA
10 000 breaks
at In, cos  = 0,7

BMTBD-TSN training-nxcuong-8.04 37

SM6 Easy installation

 Simplified civil works

 Symmetric cable connection

 Identical cubicle heights and


floor-level depths

BMTBD-TSN training-nxcuong-8.04 38

4.2 Máy ngắt SM6


SM6 Overall quality

 Routine tests

 Inspections
I ti
EDF/SEPIA
 mechanical quality audit
 operating times
 seal Annual production
 Dielectric line sampling

 Measurements Production sites


with ISO 9002
 operating stresses certification by AFAQ
 voltage drop

BMTBD-TSN training-nxcuong-8.04 39