3.3.2 MCCB-áp D NG
3.3.2 MCCB-áp D NG
APPLICATION
Current Limiting
3
nxcuong-BMTBD-Version
current limiting
Example 1
current limiting curves What is the real value of a 150 kA rms
The current limiting capacity of a CB is expressed by two prospective short-time (i. e. 330 kA peak) limited
curves which give, as a function of the prospective short by an NS250L upstream?
circuit current:
1. the actual peak current (limited current);
2. the thermal stress (A2s), i. e. the energy dissipated by the Example 2
short-circuit in a conductor with a resistance of 1 Ω . Is an Cu/PVC cable with a cross-section of
10 mm2 adequately protected by an
maximum permissible cable stress NS160N?
The table below indicates the maximum permissible thermal
stresses for cables depending on their insulation, material
(Cu or Al) and CSA. CSA values are given in mm2 and thermal
stresses in A2s.
4
nxcuong-BMTBD-Version
peak current
5
nxcuong-BMTBD-Version
Limited energy
6
nxcuong-BMTBD-Version
Examplep 1
What is the real value of a 150 kA rms prospective short-
time (i. e. 330 kA peak) limited by an NSX250L upstream?
Answer: 30 kA peak.
Example 2
Is an Cu/PVC cable with a cross-section of 10 mm2
adequately protected by an NSX160F?
Answer:
A
The permissible stress is 1.32 106 A2s.
All short-circuit currents at the point where an NSX160F (Icu = 35 kA) is installed
are limited with a thermal stress less than 6 105 A2s.
Cable protection is ensured up to the limit of the breaking capacity of the CB.
7
nxcuong-BMTBD-Version
APPLICATION
Discrimination
9
nxcuong-BMTBD-Version
10
nxcuong-BMTBD-Version
11
nxcuong-BMTBD-Version
Compact NSX
12
nxcuong-BMTBD-Version
13
nxcuong-BMTBD-Version
Compact NSX
14
nxcuong-BMTBD-Version
Total Discrimination
NSX160NTM160D
C60N C50
15
nxcuong-BMTBD-Version
Example
NSX100N TM100D
C60N C32
Partial Discrimination
Isc3=900A
16
nxcuong-BMTBD-Version
Cascading
cascading
what is cascading?
cascading tables
Cascading is the use of the current limiting capacity of circuit
breakers at a g given p
point to ppermit downstream installation of
M li G
Merlin Gerin
i cascading
di ttables
bl are:
lower-rated breaking capacity (than the prospective short-
circuit at their point of installation) circuit breakers.
• drawn up on the basis of calculations
Since the current is limited throughout the circuit controlled by
(comparison between the energy limited
the limiting circuit breaker, cascading applies to all switchgear
by the upstream device and the
downstream. It is not restricted to two consecutive devices.
maximum permissible thermal stress for
The characteristics of the two devices must be coordinated in
the downstream device);
such a way that the energy let through by the upstream device
is not more than that which can be withstood by the
• verified experimentally in accordance
downstream device and the cables protected by these devices
with IEC standard 947-2.
without damage.
For distribution systems with 220/240V,
Cascading can only be checked by laboratory tests and the
400/415 V and 440 V between phases,
possible combinations can be specified only by the circuit
the tables of the following pages
breaker manufacturer.
indicate cascading possibilities between
upstream CB and downstream CB.
18
nxcuong-BMTBD-Version
19
nxcuong-BMTBD-Version
20
nxcuong-BMTBD-Version
21
nxcuong-BMTBD-Version
22
nxcuong-BMTBD-Version
In a table, a box containing two equal values indicates that discrimination is provided up to
the reinforced breaking capacity of the downstream device.
These tables apply only to cases with combined discrimination and cascading between two
devices. For all other cases, refer to the normal cascading and discrimination tables.
23
nxcuong-BMTBD-Version
24
nxcuong-BMTBD-Version
25
nxcuong-BMTBD-Version
APPLICATION
28
nxcuong-BMTBD-Version
30
nxcuong-BMTBD-Version
32
nxcuong-BMTBD-Version
APPLICATION
Connection
36
nxcuong-BMTBD-Version
APPLICATION
Environmental Conditions
Temperature derating
Compact NSX100 to 250 TMD
40
nxcuong-BMTBD-Version
41
nxcuong-BMTBD-Version
42
nxcuong-BMTBD-Version
altitude derating
44
nxcuong-BMTBD-Version