Fire Fighting Drawing: Blow Film Building Compliance
Fire Fighting Drawing: Blow Film Building Compliance
TOTAL: 4 SHEETS
PROJECT NAME : TPE LG3 Blow Film Building Compliance Project ( Including Cover )
PROJECT NO. : -
LOCATION : SCG Chemical Site #3 (TPE)
DISTRIBUTION
Master File
Client
Maintenance
Procurement
ENG. DESIGN
PE
PIP
IE
MES
MER
EE
CE
IC
IA
CONSTRUCTION
PM
CE
ME
PIP
I&E
Contractor REPCO Doc. No. TITLE IFS IFI/ IFR IFA IfC P A B C 0 1 2 3 4
Doc. No.
Contractor 0
0 17-Sep-20 IFC = Issue for Construction PB WB JG TPE-BFB-PIP-CAL-0001-00
Doc. No.
C 27-Aug-20 IFR = Issue for Review PB WB JG
B 11-Aug-20 IFR = Issue for Review PB WB JG
A 27-Jul-20 IFR = Issue for Review PB WB RC SHEET NO. 3 OF 4
REV. DATE DESCRIPTION BY CHKD APPD
Client THAI POLYETHYLENE CO.,LTD.
SUBJECT HYDRAULIC CALCULATION REPORT
PROJECT TPE_LG3 BLOW FILM BUILDING REV DATE ORIGINATOR CHECKER APPROVER
CONTRACT No. B 11-Aug-20 CA PB WB
DOCUMENT No. TPE-BFB-PIP-CAL-0001-00 C 27-Aug-20 CA PB WB
0 17-Sep-20 CA PB WB
Assumptions:
1/2" 1. The Firewater flow rate for existing transformer 371 l/min (22.26 m3/h)
1/2"
Firewater flow rate is based on K-factor 17.3 lpm/m2 (Metric)
U4 U8 U7 U6 Assumed inlet water spray nozzles pressure at least 2.0 barg (Recommend)
1/2" 1/2" .: Total fire water flow rate is 391 l/min (23 m3/h)
2. The sizing is based on 110% margin of flow rate
3. The Fluid properties are assumed at 30°C
UPPER 4. Piping size 2" tie-in from the existing pipe 6"
U3 U5 5. Fire water pressure at tie-in point 9 kg/cm2g
1/2" 1/2" 6. Total equipvalent line length based on pipe and fitting as per isometric drawing.
A
2 EL+3000 mm 7. The criteria of liquid transfer, SCG practice for allpwable velocity is not more than 6 m/s.
8. Deluge valve can reduce pressure to 1.4 - 4.1 barg
A1 2" EL+2929 mm
U2 U1 U B
1/2" 1/2"
1 1/2" 1 EL+2700 mm
2"x1 Results:
1. All line sizes are adequate with process conditions and capacity.
2. Set pressure after deluge valve least 2.75 barg, the fire water pressure inlet water spray nozzles on fire water upper ring are
1/2" 1/2"
2.0 kg/cm2g and pressure inlet water spray nozzles on fire water lower ring are 2.1 kg/cm2g
L4 L8 L7 L6
1/2" 1/2"
1 1/2"
LOWER RING
L3 L5
1/2" 1/2"
L2 L1 L
1/2" 1/2"
1 1 EL+1200 mm
Total Eq length m 23.5 24.6 2.7 1.8 1.87 3.96 2.15 2.15 2.15 3.96 1.9 2.62 1.8 1.87 3.96 2.15 2.15 2.15 3.96 1.9
dP / 100 m kg/cm2 2.085 2.085 1.932 0.516 0.299 0.141 0.040 0.516 0.299 0.141 0.040 1.932 0.516 0.299 0.141 0.040 0.516 0.299 0.141 0.040
Line loss kg/cm2 0.490 0.513 0.052 0.009 0.006 0.006 0.001 0.011 0.006 0.006 0.001 0.051 0.009 0.006 0.006 0.001 0.011 0.006 0.006 0.001
Upstream EL mm 2929 1244 2700 1200 1200 1200 1200 1200 1200 1200 1200 2700 2700 2700 2700 2700 2700 2700 2700 2700
Downstream EL mm 1244 2700 1200 1200 1200 1200 1200 1200 1200 1200 1200 2700 2700 2700 2700 2700 2700 2700 2700 2700
Elevation change m -1.685 1.456 -1.5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Static pressure kg/cm2 -0.168 0.145 -0.149 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
dP / section kg/cm2 0.322 0.658 -0.097 0.009 0.006 0.006 0.001 0.011 0.006 0.006 0.001 0.051 0.009 0.006 0.006 0.001 0.011 0.006 0.006 0.001
Inlet pressure kg/cm2g 9.0 2.750 2.092 2.189 2.180 2.174 2.169 2.189 2.178 2.172 2.166 2.092 2.041 2.032 2.027 2.021 2.041 2.030 2.024 2.018
Outlet pressure kg/cm2g 8.678 2.092 2.189 2.180 2.174 2.169 2.168 2.178 2.172 2.166 2.166 2.041 2.032 2.027 2.021 2.020 2.030 2.024 2.018 2.018
Velocity m/s 3.24 3.24 2.66 1.33 1.00 0.67 0.33 1.33 1.00 0.67 0.33 2.66 1.33 1.00 0.67 0.33 1.33 1.00 0.67 0.33