AC STARTUP READINGS

DAFNA STUDY ROOM


DAFNA BEACH PALACE
Building Type: Residential Report Date 28/Jul/2021 Pages 1
:
System Type: DAIKIN PACKAGE & SPLIT UNITS Comm.Date 27/Jul/2021 Revision 0
:
Serial Curren Voltage Current Running Thermostat Reading Actual Room Discharge Suction
Number t Rating Temperature Pressure Pressure
Set Temp Room Temp
SL.No Unit model Location Rating Remarks
(V
(A) (A) (°C) (°C) (°C) (PSI) (PSI)
)

1 UATQ90C6XY1 KIDS PLAY AREA K000479 19 415 16.41/15.21/14.8 17 17 18 440 130

2 UATQ150C6XY1 KIDS STUDY AREA K000274 34 415 28.5/26.5/26.7 17 18 18 440 / 440 128 / 130

3 RR25AV1K ENTRANCE K013889 15 220 9.6 17 18 18 _ 125

4 RR30AV1K KIDS GYM ROOM K012703 18 220 11.7 17 18 18 410 120

5 RR30AV1K TEACHERS ROOM K014235 18 220 11.9 17 18 18 415 120

6 RN20V1K9 ELEC ROOM K000979 7 220 6.1 17 _ 18 _ 120

7 RN20V1K9 PANTRY K001731 7 220 6.3 17 _ 18 _ 110

8 RN20V1K9 DATA ROOM K000978 7 220 6.1 17 _ 18 _ 120

Note:
Reviewed and Acceptance by:

For Engineer Mep Contractor Main Contractor


Date 28/Jul/2021

Name & Signature