Professional Documents
Culture Documents
The Pressure - Enthalpy Chart: by Dave Demma, Senior Application Engineer - Supermarket Refrigeration
The Pressure - Enthalpy Chart: by Dave Demma, Senior Application Engineer - Supermarket Refrigeration
How often have you heard the statement “it isn’t cooling?” Ton of Refrigeration - The amount of cooling required to
Well it may seem a bit picky, but it is not entirely accurate to change (freeze) 1 ton of water at 32ºF into ice at 32ºF, in a 24
say the refrigeration system “cools”. If the system is operating hour period.
properly, the refrigerated space should be “cooler” than its sur-
roundings, but it is the result of a heat transfer process. Heat is Btu - British Thermal Unit: The amount of heat required to
transferred from the refrigerated space to the refrigerant, and raise 1 lb. of water 1ºF.
ultimately from the refrigerant to the ambient (at the condens-
er). A lower temperature in the refrigerated space is the 1 Ton - 12,000 Btu/hr
byproduct of this heat transfer process. Perhaps this is a minor
shift in thinking, but in viewing the refrigeration system for Fig. 1 illustrates some of these definitions, using water as the
what it is…a heat transfer process…a more fundamental medium experiencing a heat transfer process. This graph plots
approach for diagnosis may be obtained. the water temperature vs. the enthalpy of the water (heat content
in Btu/lb). We all know that water boils at 212ºF (atmospheric
In an effort to gain a better understanding of the various heat pressure at sea level). By definition, water at atmospheric pres-
transfer processes occurring in a refrigeration system, the pres- sure, at a temperature lower than 212ºF, is subcooled. So, we
sure-enthalpy chart can be of great use. Additionally, once start with subcooled water at 42ºF, and begin transferring heat to
understood, “the chart” can be a tremendous benefit in analyz- it. Assuming we are working with 1 lb. of water, for every Btu
ing the relative health of a refrigeration system. Let’s follow added, a corresponding temperature increase of 1ºF will be
the refrigerant on a quick journey through a refrigeration sys- achieved (the definition for one Btu). It we continue to add heat,
tem to see what it experiences, and plot it on “the chart” as we eventually the water’s temperature will increase to 212ºF (the
go. Before we start, a few technical definitions are in order: saturation temperature at atmospheric pressure). At this point,
the water begins to change states from a liquid to a vapor (boil).
Refrigeration - The achievement of a temperature below that As noted on the graph, the water will experience no further tem-
of the immediate surroundings. perature increase…for a given pressure, the saturation (boiling)
temperature is the highest temperature a liquid can ever achieve.
Latent Heat of Fusion - The quantity of heat (Btu/lb) required Increasing the amount of heat transferred to the water simply
to change 1 lb. of material from the solid phase into the liquid increases the rate at which the water boils. If the temperature of
phase. the vapor were to be measured, we’d find it to be 212ºF (saturat-
ed vapor). Once the vapor has separated from the liquid, addi-
Latent Heat of Vaporization - The quantity of heat (Btu/lb) tional heat transferred to it will result in a temperature increase.
required to change 1 lb. of material from the liquid phase into By definition, the vapor at 232ºF (20º above the saturation tem-
the vapor phase. perature), is superheated.
Sensible Heat - Heat that is absorbed/rejected by a material, It is interesting to note that while it takes only 1 Btu to raise 1
resulting in a change of temperature. lb. of water 1ºF, it takes almost 1000 times that amount (966.6
Btu) for the 1 lb. mass of water to change states from liquid to
Latent Heat - Heat that is absorbed/rejected by a material vapor. A boiling liquid will always absorb more heat than a
resulting in a change of physical state (occurring at constant vapor experiencing a temperature increase (per unit of mass).
temperature). Understanding this principle explains why the evaporator in a
refrigeration system should always be nearly filled with liquid
Saturation Temperature - That temperature at which a liquid refrigerant. Otherwise, its full potential as a heat transfer
starts to boil (or vapor starts to condense). The saturation tem- device will not be utilized.
perature (boiling temperature) is constant at a given pressure,*
and increases as the pressure increases. A liquid cannot be The pressure-enthalpy chart, as shown in Fig. 2, displays all
raised above its saturation temperature. Whenever the refriger- the pertinent properties for a given refrigerant (in this example
ant is present in two states (liquid and vapor) the refrigerant R22). The bubble to the left is the portion of the diagram where
mixture will be at the saturation temperature. the refrigerant is in the saturated condition. The blue line on
the left of the bubble represents the 100% saturated liquid line,
Superheat - At a given pressure, the difference between a the thin dashed line on the right represents the 100% saturated
vapor’s temperature and its saturation temperature. vapor line, and anywhere inside the bubble represents the
refrigerant as a mixture of saturated liquid and saturated vapor.
Subcooling - At a given pressure, the difference between a liq-
uid’s temperature and its saturation temperature. To the left of the saturated liquid line is the area where the
* Except for zeotrope refrigerants refrigerant can exist at a temperature lower than the saturated
Page 2 / FORM 5-200
condition; subcooled liquid. To the right of the saturated vapor Specific volume is expressed in cu.ft/lb. (see orange line).
line is the area where the refrigerant can exist at a temperature
higher than the saturated condition; superheated vapor. The Entropy - Entropy is the mathematical relationship between
critical point is the highest temperature that the refrigerant can heat and temperature, and relates to the availability of energy.
experience, and remain in the liquid form. If the temperature These lines extend at an angle from the saturated vapor line.
exceeds the critical point, regardless of pressure, the refriger- Their presence on the chart is relevant in that vapor compres-
ant can only exist in the vapor state. sion (in the ideal cycle) occurs at constant entropy (see dark
blue line).
All of the relevant properties are shown in Fig. 2:
Quality - Lines of constant quality appear vertically, and only
Pressure - The vertical axis of the chart, in psia (see pink line). within the saturation bubble. The refrigerant within the bubble
To obtain gauge pressure, subtract atmospheric pressure. is a mixture of liquid and vapor at saturation, and the quality is
the percentage of the mixture which is in the vapor state (see
Enthalpy - The horizontal axis of the chart shows the heat con- green line).
tent of the refrigerant in Btu/lb.
The ultimate goal of the refrigeration system is to get the
Temperature - Constant temperature lines generally run in a verti- refrigerant into a condition where it can be useful as a medium
cal direction in the superheated vapor & sub-cooled liquid portion to transfer heat from the refrigerated space. If the system
of the chart. In the saturated bubble, the constant temperature line design requires a -10ºF space temperature, you would expect
is along the horizontal, illustrating that the saturation temperature the refrigerant temperature in the evaporator to be somewhat
is constant at a given pressure (see black line). lower…say -20ºF (a 10º temperature difference). This allows
the relatively warmer air (something above the design of -
Specific Volume - Constant volume lines extend from the red 10ºF) to be blown across the evaporator, flowing relatively
line saturated vapor line out into the superheated vapor-por- cooler refrigerant (-20ºF). The result is the transfer of heat
tion of the chart at a slight angle from the horizontal axis. from the warmer air to the cooler refrigerant.
Refrigeration
Water at Atmospheric Pressure
(14.7 psia pressure)
Boiling at constant pressure and temperature
Saturation 20° Superheat (232°– 212°= 20°)
Superheated
Temperature 232 Vapor
212
Temperature (°F)
In the ideal cycle, the condenser serves as a two-fold compo- So, in order to reduce the temperature, the pressure has to be
nent. Before any condensation occurs, the high pressure vapor reduced, and some sort of restriction is required for this to
must first be brought to a saturated condition (de-superheated). occur. It would be preferable if the restriction could regulate
SCALE CHANGE
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
14 15 16 17 18 19 20 21 22 23
12
13
0. 0. 0. 0. 4
0. 6 0. 0. 0. 0. 0. 0.2
0.
0.
5000
0.01 0.018 0.020 0.022 5000
0.017 0.2
5
4000 0.025 6
4000
3000
REFRIGERANT 22 0.03 60
0.2
0 7
3000
58 0.2
0.04 56 0
2000 54 0 2000
0.05
200
52 0
8
50 0 0.2
180
py
48
160°F
0
tro
46
0.10 1000
1000
Critical Point
0
44
800 n 800
0
tE 42
0.14
200 –
0
40
600 n 600
ta
0
180 –
38
180 0.2
s
0
36
on
160 – 160 –
0
34
400 400
C 0.3
0
140 – 140 –
Constant Pressure
320
300 300
0.4
30 0
120 – 120 –
280
0.5
e
100 – 100 –
e
200
r Lin
200
260
Lin
80 – 80 – 0.7
240
140 140
Pressure (psia)
uid
220
o
60 – 60 – 1.0
Vap
200
100
Liq
100
e
Constant Volum
180
80 40 – 40 – 1.4 80
ted
ted
160
60 20 – 20 – 2.0 60
140
ura
ura
120
40 0– 0– 3.0 40
Sat
Sat
100
60
20 20
7.0
40
-40 – -40 –
14 14
20
10.0
uality
10
0
-60 – -60 – 14
8.0 8.0
-20
6.0 F ) 20 6.0
-°
-40
ant Q
-80 – -80 – / lb
tu
-60
4.0 (B 4.0
30
py
ro
-80
Const
3.0
3.0 nt 40
-100 – -100 – tE
t an
2.0 ns 50 Specific Volume (ft3/lb) 2.0
Co
7 38 0.
39 .40
.3
6
0.
3 0. 0
1.4
1.4 35 0 70
0.
34
33
0.
2
-120 – -120 –
0.
1.0
1
0.3
1.0
0.3
0
0.3
9
0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.8
0.2
0.6 0.6
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
SCALE CHANGE
itself as the system load demands change. This is exactly what Because the refrigerant must conform to its law of existence,
the thermostatic expansion valve does; it is an adjustable when the 210.7 psia (100ºF) liquid experiences the reduction in
restriction which causes a reduction in liquid refrigerant pres- pressure to 24.9 psia, it must drop to the new saturation tem-
sure, yet will modulate in an effort to maintain constant super- perature of -20ºF. Some of the liquid refrigerant is required to
heat at the evaporator outlet. The TEV is a superheat control, boil as a means of removing the heat necessary to achieve this
and will not maintain a constant evaporator pressure. It only lower temperature. Yet another heat transfer process, which
provides the restriction necessary to reduce the pressure to yields a lower liquid temperature. The liquid that is sacrificed
some level, which will be determined by compressor size, TEV in the boiling process explains the increase in refrigerant qual-
size, load demand, and system conditions. If a constant evapo- ity. The greater the difference between the liquid temperature
rator temperature is required, it can be achieved very simply by and evaporator temperature, the more liquid will have to be
maintaining the pressure corresponding to the saturation tem- boiled to achieve the new saturation temperature. This results
perature required. This is accomplished by adding an evapora- in an even higher refrigerant quality.
tor pressure regulating valve to the system.
The final portion of the refrigerant’s journey is as a mixture of
Our ideal cycle has experienced a pressure drop in the TEV, saturated liquid and vapor, traveling though the evaporator tub-
and for the purpose of discussion we are at a constant 24.9 psia ing. Warm air is blown across the evaporator, where its heat
in the evaporator. This is a saturation temperature of -20ºF. You content is transferred to the boiling refrigerant. This is a latent
will notice that the refrigerant quality at the TEV inlet was 0%, heat gain to the refrigerant, causing no temperature increase,
and has increased to 35% at the evaporator inlet. Subcooling or while experiencing a change of state. In the ideal cycle, the last
superheat cannot exist where there is a mixture of liquid and molecule of saturated liquid boils off at the evaporator outlet,
vapor. Therefore, any place in the system where the refrigerant which is connected to the compressor inlet. Hence, the vapor
exists in two states (the receiver, parts of the evaporator and at the inlet of the compressor is saturated.
condenser, the accumulator at times), it will be at the saturation
temperature for its pressure. For example, R22 in a saturated The cycle continues this way until the refrigerated space tem-
state at 24.9 psia (10.2 psig) will always be at -20ºF. perature is satisfied, and the equipment cycles off.
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
14 15 16 17 18 19 20 21 22 23
12
13
0. 0. 0. 0. 4
0. 6 0. 0. 0. 0. 0. 0.2
0.
0.
5000
0.01 0.018 0.020 0.022 5000
0.017 0.2
5
4000 0.025 6
4000
3000
REFRIGERANT 22 0.03 60
0.2
3000
58 0
0 .27
0.04 56 0
2000 54 0 2000
0.05
200
52 0
8
50 0 0.2
180
1400
1400
IDEAL CYCLE 0.07 0
48
0
46
44
800 800
0
42
0.14
200 –
0
40
600 600
0
180 –
Co
38
0.2
180 Desuperheating Line
0
ns
36
160 – 160 –
tan
0
34
400 400
0.3
0
140 – 140 –
t Te
320
mper
120 120 –
280
0.5
100 – 200
ature (
200
260
80 – 80 – 0.7
or
240
140
Vap
140
Pressure (psia)
°F )
220
60 – 60 – 1.0
ted
200
100 100
ura
180
80 40 – 40 – 1.4 80
Sat
160
60 Expansion20Line
– 20 – Compression Line 2.0 60
140
120
40 0– 0– 3.0 40
100
id
30 4.0 30
u
80
Liq
60
20 20
ura
-40 – -40 –
Sat
14 14
20
10.0
10
0
-60 – -60 – 14
8.0 8.0
-20
F ) 6.0
6.0 20
-°
-40
-80 – -80 – / lb
tu
-60
4.0 (B 30
4.0
y
op
-80
3.0 n tr 3.0
tE 40
-100 – -100 –
t an
2.0 ns 50 Specific Volume (ft3/lb) 2.0
Co
37 38 0.
39 .40
5 36 0. 0. 0
1.4
1.4 .3 0. 70
34
0
33
0.
2
-120 – -120 –
0.
1.0
1
0.3
1.0
0.3
0
0.3
9
0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.8
0.2
0.6 0.6
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
SCALE CHANGE
Once the system has been plotted, various data points can be Heat of Compression (HOC): This is the amount of heat added
read and used for the system design calculations. Admittedly, to the refrigerant from the compression process (represented
this information is not typically something the technician will by H2 minus H1 on the chart).
need for servicing the refrigeration equipment. However, an
understanding of how operating conditions affect system Heat of Rejection (HOR): This is the amount of heat that has
design, efficiency, energy consumption, and particularly com- to be rejected at the condenser…the heat transferred to the
pressor performance, should be of great worth to the technician. refrigerant from the refrigerated space (RE), and the heat trans-
ferred to the refrigerant during compression (HOC). It is this
Data Points and System Design Calculations: value, plus some safety factor, from which the condenser selec-
tion is made (represented by H2 minus H3 on the chart).
Refrigeration Effect (RE): This is the total heat transfer, in
Btu/lb, from the refrigerated space to the refrigerant. H1 minus Refrigerant Circulation Rate (RCR): The amount of refrigerant
H4 (H1 is the enthalpy of the refrigerant at point #1 in Fig. 3, in lbs/min which must circulate in the system to meet the
and so forth). demands of the load.
(200 Btu/min – ton)
Note: For the purpose of this discussion, H1 will be considered the
RE (Btu/lb)
point where the evaporation line intersects with the saturated vapor
line. In the real world, the location of H1 would be to the right of the Compressor Horsepower Required: The horsepower/ton
saturated vapor line, reflecting the superheated vapor at the evapora- requirement to meet the load demand. Contrary to popular
tor outlet. With an expansion valve maintaining a typical amount of belief, 1 horsepower and 1 ton are not necessarily synonymous.
superheat (in the 4° - 6° range for low temperature applications), the
heat transferred to the vapor is minimal (less than 1 Btu/lb). The heat RCR (lb/min-ton) X HOC (Btu/lb) X 778 ft-lb/Btu
transferred to the vapor between the suction piping outside of the 33,000 ft-lb/min-hp
refrigerated space and the compressor cylinder inlet is never consid-
ered as part of the refrigeration effect, as this heat was not trans-
ferred from the refrigerated space.
SCALE CHANGE
14 15 16 17 18 19 20 21 22 23
12
13
0. 0. 0. 0. 4
0. 6 0. 0. 0. 0. 0. 0.2
0.
0.
5000
0.01 0.018 0.020 0.022 5000
0.017 0.2
5
4000 0.025 6
4000
3000
REFRIGERANT 22 0.03 60
0.2
0 7
3000
58 0.2
0.04 56 0
2000 54 0 2000
0.05
TYPICAL CYCLE - 1
200
52 0
8
50 0 0.2
180
48
0
46
1000 0.10 1000
40°F Suction S.H. @ Comp. Inlet
0
44
160F
800 800
0
42
0.14
215°F Discharge Temp. 200 –
0
40
600 600
0
180 –
Co
38
180 0.2
0
ns
36
160 – 160 –
tan
0
34
140 – 140 – t Te
320
m pe r
120 – 120 –
280
0.5
100 – 200
ature (°
200
260
80 – 80 – 0.7
or
240
140
Vap
140
Pressure (psia)
220
F)
60 – 60 – 1.0
ted
200
id
100 100
iq u
ura
180
80 40 – 40 – 1.4 80
dL
Sat
160
ate
60 20 – 20 – 2.0 60
tur
140
Sa
120
40 0– 0– 3.0 40
100
30 4.0 30
80
20 20
7.0
40
-40 – -40 –
14 14
20
10.0
10
0
-60 – -60 – 14
8.0 8.0
-20
) 6.0
6.0 -F 20
-40
Btu -80 – l
u/=
b 3.23 lb
-80 – HOR = 135 – 40 = 95 REF Circulation Rate
Bt
-60
4.0 lb y
( min - ton 30
4.0
op
tr
-80
3.0 n 3.0
Btu tE 2.05 HP 40
-100 – HOC = 27 -100 – COMP HP Req an =
st n 50 Specific Volume (ft3/lb) 2.0
2.0 lb Co
8
ton 9 0
6 37 0.
3 0.
3 0.4
1.4 35 0.
3 0. 70 1.4
Btu . 7.39 CFM
34
0
NRE = 62 COMP VOL Req =
33
0.
2
-120 – -120 –
0.
1.0
1
0.3
1.0 lb ton
0.3
0
0.3
9
0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.8
0.2
0.6 0.6
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
SCALE CHANGE
Compressor Volume Required: The compressor cylinder vol- The suction superheat will insure that the compressor is pro-
ume requirement needed to pump the RCR, in cu ft/ton. The tected from liquid flooding. The cost of this protection comes
vapor specific volume is read on the lines of constant volume. in the form of a larger compressor volume requirement. This is
due to the warmer, thinner suction vapor; at +20ºF the specific
RCR (lb/min-ton) X vapor specific volume (cu ft/lb) volume of the vapor (measured in cu.ft./lb) is greater than it
was at -20ºF. The compressor’s cylinders are a measured vol-
Let’s look at a few typical system scenarios, plot them on the ume...they never change. The density of the refrigerant may
P-H diagram, and then compare the performance measurements. change, and this will affect the pounds per minute of refriger-
ant that the compressor will pump, however the volume
Typical Cycle #1 (Fig. 4): It is neither realistic nor safe to have pumped remains constant. So, because the suction vapor is less
a saturated vapor at the compressor inlet. Because liquid can- dense, we now require more compressor cylinder volume to
not be present with superheated vapor, some amount of pump the same mass flow.
superheat at the compressor inlet becomes the margin nec-
essary to insure the safety of the compressor. Here we see While all the various data points and system design calcula-
the suction vapor superheated to +20ºF (40º superheat). This is tions are listed, they will appear in a comparative chart later.
the result of an expansion valve set to maintain some amount
of superheat, plus the temperature increase the refrigerant Typical Cycle #1A (Fig. 5): Using an open drive compressor,
vapor experiences in the suction line. The suction line connect- with a 20ºF vapor temperature at the compressor inlet, we see
ed to the compressor will have some accumulation of frost on the benefit of subcooling the liquid to 50ºF. Note the change in
it. This is the result of the 20°F pipe temperature and mositure refrigerant quality at the TEV outlet. Instead of 65% liquid, we
in the air, NOT the result of floodback. Floodback is not pos- now have 80% liquid. Because the difference between liquid
sible when the vapor’s temperature is 40° above the saturation temperature and evaporator temperature has been reduced,
temperature (40° superheat). Do not confuse frost buildup with there is less refrigerant flashing during the expansion process.
floodback. As a result, the TEV and distributor nozzle (if used) can possi-
bly be downsized.
SCALE CHANGE
14 15 16 17 18 19 20 21 22 23
12
13
0. 0. 0. 0. 4
0. 6 0. 0. 0. 0. 0. 0.2
0.
0.
5000
0.01 0.018 0.020 0.022 5000
0.017 0.2
5
4000 0.025 6
4000
3000
REFRIGERANT 22 0.03 60
0.2
0 7
3000
58 0.2
0.04 56 0
2000 54 0 2000
0.05
200
TYPICAL CYCLE - 1A 50
52
0
0
0.2
8
180
800 800
0
42
0.14
Liquid Subcooled to18050°F
200 –
0
40
600 600
0
–
Co
38
180 0.2
0
ns
36
160 – 160 –
tan
0
34
140 – 140 –
t Te
320
mpe
120 – 120 –
280
0.5
rature
100 – 200
200
260
0.7
or
80 – 80 –
240
140
Vap
140
Pressure (psia)
° F)
220
60 – 60 – 1.0
ted
200
100 100
ura
180
80 40 – 40 – 1.4 80
Sat
160
60 20 – 20 – 2.0 60
140
120
40 0– 0– 3.0 40
100
id
30 4.0 30
u
80
Liq
60
20 20
ura
7.0
40
-40 – -40 –
Sat
14 14
20
10.0
10
0
-60 – -60 – 14
8.0 8.0
-20
) 6.0
6.0 -F 20
-40
Btu / lb 2.5 lb
-80 – HOR = 95 -80 – REF Circulation Rate tu =
-60
3.0 E nt 3.0
Btu nt 1.59 HP 40
-100 – HOC = 27 -100 – COMP HP Req
ns
ta =
50 Specific Volume (ft3/lb) 2.0
2.0 lb Co ton 9
37
8 3 0.
3 .40
5 36 0. 0. 0
1.4
1.4
Btu .3 0. 5.73 CFM 70
34
0
NRE = 80 COMP VOL Req =
33
0.
2
-120 – -120 –
0.
1.0
1
0.3
1.0 lb ton
0.3
0
0.3
9
0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.8
0.2
0.6 0.6
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
SCALE CHANGE
The use of a liquid to suction heat exchanger will yield sub- seals. The disadvantage is that there is now an electric motor in
cooled liquid, but at the expense of higher suction vapor tem- the refrigerant circuit (at least on suction vapor cooled hermet-
peratures. While this method of subcooling will insure vapor ic compressors). In addition to the guaranteed system contam-
free liquid refrigerant at the TEV inlet, it has little effect on ination problem when a hermetic motor burns, you have the
increasing system efficiency. The benefit realized resulting heat from the motor being transferred to the refrigerant vapor.
from subcooling will be offset by the higher suction vapor tem- An approximate 80ºF temperature increase can be expected
peratures, and the volume requirement penalty they impose. In between the vapor entering the compressor service valve, and
this supermarket example the liquid for the low temperature the vapor entering the compressor cylinders. This brings the
rack is subcooled using the medium temperature rack. There is suction vapor temperature up to 100ºF, with a corresponding
no heat gain to the low temperature rack as a byproduct of the increase in discharge temperature…now approaching 300ºF.
subcooled liquid. The refrigerant is subcooled on a rack that is This is the upper limit at which most compressor manufacturers
operating between 2 to 2-1/2 horsepower per ton, and the ben- agree shouldn’t be exceeded. The refrigerant vapor at 100ºF
efit is being experienced on a rack that is operating near 5 has a specific volume approximately 20% higher than at 20ºF.
horsepower per ton. This translates into a compressor volume requirement which
will be approximately 20% greater. The higher suction vapor
The comparative chart will show the benefits: reduced refrig- temperature also results in a higher HOC, which raises the
erant circulation rate, reduced horsepower requirement, and horsepower requirement.
reduced compressor volume requirement. If the subcooling can
be accomplished very inexpensively, such as ambient subcool- Typical Cycle #3 (Fig. 7): Now, let’s take a look at the real
ing with a receiver bypass, the energy savings can be enor- world. It is now the dead of summer – the most extreme condi-
mous. For more details on this see Sporlan Form 90-134. tion for the equipment. When the system design and equipment
selection was made, it was this summer weather that was used
Typical Cycle #2 (Fig. 6): The advantage of using a hermetic as the worst case condition of operation. Now, your company
compressor is the elimination of either belts or drive motor was so busy in the winter that the yearly preventative mainte-
couplings which require precise alignment, and crankshaft nance was not done. Or perhaps it’s one of those customers who
SCALE CHANGE
14 15 16 17 18 19 20 21 22 23
12
13
0. 0. 0. 0. 4
0. 6 0. 0. 0. 0. 0. 0.2
0.
0.
5000
0.01 0.018 0.020 0.022 5000
0.017 0.2
5
4000 0.025 6
4000
3000
REFRIGERANT 22 0.03 60
0.2
0 7
3000
58 0.2
0.04 56 0
2000 54 0 2000
TYPICAL CYCLE - 2 0.05
200
52 0
8
50 0 0.2
180
48
160F
0
46
0.10 1000
1000
40°F Suction S.H. @ Comp. Inlet
0
44
800 800
0
42
0.14
295°F Discharge Temp. 200 – 0
40
600 600
Co
0
180 –
38
180 0.2
ns
0
36
400 t Te
0.3 400
0
140 – 140 –
320
300 300
mpe
0.4
30 0
120 – 120 –
280
0.5
rature
100 – 200
200
260
0.7
or
80 – 80 –
240
140
Vap
140
°F)
Pressure (psia)
220
60 – 60 – 1.0
ted
200
id
100 100
iq u
ura
180
80 40 – 40 – 1.4 80
dL
Sat
160
ate
60 20 – 20 – 2.0 60
tur
140
Sa
120
40 0– 0– 3.0 40
100
30 4.0 30
80
20 20
7.0
40
-40 – -40 –
14 14
120°F Suction Superheat
20
10.0
10 80°F-60Vapor Temperature increase from hermetic motor windings
0
-60 – – 14
8.0 8.0
-20
) 6.0
6.0 -F 20
-40
lb
-80 – Btu-80 – t u/ 3.23 lb
HOR = 152 - 40 = 112 REF Circulation Rate
(B =
-60
4.0 4.0
lb ro
py min - ton 30
-80
3.0 t 3.0
t En 40
-100 – Btu
-100 – an 2.36 HP
HOC = 152 - 121 = 31 COMP HP Reqst = 50 Specific Volume (ft3/lb)
2.0 on C
2.0
lb .3
8 ton.39 .40
36 37 0 0 0
1.4 3 5 0. 0. 70 1.4
0.
34
0.
2
1.0
1
0.3
1.0
0.3
0
lb ton
0.3
9
0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.8
0.2
0.6 0.6
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
SCALE CHANGE
never wants to spend money on prevention…the one you tell for the vapor trapped in the clearance volume. It too is at the
“you can either pay me a little now, or you can pay me a lot discharge pressure. Before any suction vapor can re-enter the
more, later”. In either case, the condenser is dirty, and the bot- cylinders, the clearance volume vapor must experience a reduc-
tom line is that the condensing temperature has increased; from tion in pressure to a level slightly below that of the suction pres-
100ºF to 120ºF. sure. Otherwise, there would be no flow into the cylinder. It is
piston travel, which increases the cylinder volume, that reduces
With the higher discharge pressure, the compression ratio has this clearance volume pressure. This portion of the piston trav-
increased from 8.5:1 to 11:1. This higher pressure that the el, which is entirely dedicated to lowering the clearance volume
compressor is pumping against has a twofold negative impact. pressure, performs no useful work at all. In fact, it is advanta-
First, the motor amperage will be higher. Secondly, the volu- geous to keep this to a minimum. The higher the clearance vol-
metric efficiency of the compressor will be reduced. ume pressure is above the suction pressure, the more of this
wasted piston travel will be required. Simply put, this is the def-
There is a pocket of vapor between the bottom of the valve inition of a high compression ratio (substituting discharge pres-
plate, and the top of the piston, called the clearance volume. It sure for clearance volume pressure, as they are one and the
is there to insure that the piston does not run into the valve same).
plate during the operation of the compressor. The vapor in this
pocket requires re-expansion to a lower pressure before any Note the higher HOC. Referring to the system design calcula-
new suction vapor can enter the compressor’s cylinders. tions reveals that more horsepower will be required. In addi-
tion, the quality of the saturated liquid/vapor mixture at the
Let’s take a look at the compression cycle. It begins when suc- TEV outlet has further deteriorated, resulting in a lower RE.
tion vapor enters a cylinder as its piston is traveling down. As Referring again to the system design calculations will reveal
the piston starts to travel back up, reducing the volume of the that the lower the RE is, the higher the RCR has to be. This, in
cylinder, the vapor pressure increases. When the piston reaches turn, will require more cylinder volume to meet the demand of
the top of its stroke, the entire volume of compressed vapor will an increased RCR. In a typical supermarket there are backup
have exited the cylinder through the discharge valves EXCEPT compressors that only operate under high load conditions, so
SCALE CHANGE
14 15 16 17 18 19 20 21 22 23
12
13
0. 0. 0. 0. 4
0. 6 0. 0. 0. 0. 0. 0.2
0.
0.
5000
0.01 0.018 0.020 0.022 5000
0.017 0.2
5
4000 0.0 25 4000
6
3000
REFRIGERANT 22 0.03 60
0.2
0 7
3000
58 0.2
0.04 56 0
2000 54 0 2000
0.05
200
TYPICAL CYCLE - 3 50
52
0
0
0.2
8
180
800 800
0
42
0.14
120°F S.H. @ Cylinder Inlet
200 –
0
40
600 600
0
180 –
Co
38
180 0.2
0
ns
36
160 – 160 –
tan
0
34
140 – 140 –
t Te
320
m pe
120 – 120 –
280
0.5
100 –
295°F Discharge Temp.
rature
200 200
260
0.7
or
80 – 80 –
240
140
Vap
140
Pressure (psia)
°F)
220
60 – 60 – 1.0
ted
200
100 100
ura
180
80 40 – 40 – 1.4 80
Sat
160
60 20 – 20 – 2.0 60
140
120
40 0– 0– 3.0 40
100
id
30 4.0 30
u
80
Liq
60
20 20
ura
7.0
40
-40 – -40 –
Sat
14 14
20
10.0
10
0
-60 – -60 – 14
8.0 8.0
HOR @ 100°F = 112 Btu HOR @ 120°F = 110 Btu 3.5 lb
-20
REF Circulation
F)
Rate = 6.0
6.0 lb lb - min - ton 20
-40
lb
-80 – -80 – u/
Bt
-60
( 4.0
HOC @ 100°F = 31 Btu HOC @ 120°F = 34 Btu Req = 2.81 HP
4.0
py
COMPtroHP 30
-80
0.
2
-120 – -120 –
0.
1.0
1
0.3
1.0
0.3
0
0.3
9
0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.8
0.2
0.6 0.6
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
SCALE CHANGE
extra capacity is not a problem. For the store owner, paying for So, this makes sense…if a lower discharge air temperature is
the additional electricity to operate the extra compressor(s) required, what easier way is there to accomplish it? By reduc-
might be a major problem. ing the refrigerant pressure in the evaporator, the saturation
temperature will be reduced. This allows for a higher tempera-
Finally, the discharge temperature has increased to 320ºF. At ture difference between the air entering the evaporator and the
this elevated temperature the mineral oil’s lubrication qualities heat transfer medium (the refrigerant), resulting in a higher rate
will be diminished. Additionally, at 320ºF mineral oil will most of heat transfer…or in simple terms a lower discharge air tem-
certainly start to decompose. Under certain circumstances, the perature. There is only one problem. The EPR is already wide
refrigerant (R22) may start to decompose as well. All of this open. Hey…how about lowering the set point for the common
spells a short destructive life for the compressor. suction pressure on the rack’s energy management control sys-
tem. There’s plenty of extra horsepower in the form of idle
Typical Cycle #4 (Fig. 8): Now for the double whammy. Not compressors, so capacity isn’t an issue…just bring another
only is the condenser filthy, but the TEV’s were never adjust- compressor on.
ed. They are operating at abnormally high superheats, which in
effect have reduced the size of the evaporators. As a result, the With a simple adjustment, the fixture lineup’s discharge air
discharge air temperature in the glass door frozen food display temperature can be brought in line. The pressure set point is
cases is too high, causing the frozen juice to melt. lowered to 20 psia (-29ºF). Simple…yes…but there’s a doozy
of a problem with this approach.
Because it is the dead of summer, and the service call log is
overflowing, a quick solution to this problem would be great. Lowering the suction pressure will increase the compression
So, in order to compensate for the high discharge air tempera- ratio: in this example from 11:1 to 13.6:1…an approximate
tures in the fixture lineup mentioned above, the service techni- 20% increase over the compression ratio in Typical Cycle #3.
cian decides to lower the EPR setting. It doesn’t occur to him This further reduces the compressor volumetric efficiency, and
that a -20ºF saturated suction temperature should be low increases the horsepower requirement.
enough to achieve a -10ºF discharge air temperature.
SCALE CHANGE
14 15 16 17 18 19 20 21 22 23
12
13
0. 0. 0. 0. 4
0. 6 0. 0. 0. 0. 0. 0.2
0.
0.
5000
0.01 0.018 0.020 0.022 5000
0.017 0.2
5
4000 0.025 6
4000
3000
REFRIGERANT 22 0.03 60
0.2
0 7
3000
58 0.2
0.04 56 0
54 0 2000
2000
TYPICAL CYCLE - 4 0.05
200
52 0
8
50 0 0.2
180
0.07 1400
1400
Dirty Condenser - 120°F Cond. Temp 0
48
0
Hermetic Compressor
46
1000 0.10 1000
0
44
160F
800 800
0
130°F S.H. @ Cylinder Inlet
200 –
42
0
0.14
40
600 600
0
180 0.2
0
ns
36
160 – 160 –
tan
0
34
140 – 140 –
t Te
320
m pe r
120 – 120 –
280
0.5
100 – 100 – 200
ature (
200
260
0.7
por
80 – 80 –
240
140 140
Pressure (psia)
°F)
220
Va
60 – 60 – 1.0
ted
200
100 100
ura
180
80 40 – 40 – 1.4 80
Sat
160
60 20 – 20 – 2.0 60
140
120
40 0– 0– 3.0 40
100
id
30 4.0 30
u
80
Liq
60
20 20
ura
7.0
40
-40 – -40 –
Sat
14 14
20
10.0
10
0
-60 – -60 – 14
8.0 8.0
-20
) 6.0
6.0 -F 20
-40
Btu l
u/=
b 3.51 lb
-80 – HOR = 120 -80 – REF Circulation Rate
Bt
-60
3.0 t 3.0
En
Btu an =
t 3.4 HP 40
-100 – HOC = 41 -100 – COMP HP Req
st 50 Specific Volume (ft3/lb)
2.0 lb C on ton 9 2.0
37 38
0.
3 .40
3 6
0. 0. 0
1.4
1.4
Btu . 35 0. 70
12.42 CFM
34
0
NRE = 57 COMP VOL Req =
33
0.
2
-120 – -120 –
0.
1.0
1
0.3
1.0 lb ton
0.3
0
0.3
9
0.8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.8
0.2
0.6 0.6
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
SCALE CHANGE
Refrigeration
Compression
Compressor
REFRIGERANT 22
Circulation
Evaporator
Condenser
Superheat
Discharge
Discharge
Superheat
Rejection
Spec Vol
HP Reqd
Suction
Suction
Vol Req
Heat of
Heat of
Effect
Vapor
Comp
Comp
Comparative Data
Temp
Temp
Temp
Temp
Ratio
Rate
COP
REF
with Varying Conditions (°F) (°F) (°F) (°F) (°F) (°F) Btu/lb Btu/lb Btu/lb lb/min-ton hp/ton cu ft/lb cfm/ton
Ideal Cycle -20 -20 0 100 180 8.5 80 27 89 62 2.30 3.23 2.05 2.07 6.68
Typical Cycle - 1
Open Drive Compressor -20 20 40 100 215 8.5 115 27 95 62 2.30 3.23 2.05 2.29 7.39
(40°F Suction S.H.)
Typical Cycle - 1A
Open Drive Compressor -20 20 40 100 215 8.5 115 27 95 80 2.96 2.50 1.59 2.29 5.73
(40°F Suction S.H.)
Liquid subcooled to 50°F
Typical Cycle - 2
Hermetic Compressor (add 80°F S.H.) -20 100 120 100 295 8.5 195 31 112 62 2.00 3.23 2.36 2.72 8.77
120°F S.H. vapor entering cylinders
Typical Cycle - 3
Hermetic Compressor (add 80°F S.H.) -20 100 120 120 320 11.1 200 34 110 57 1.68 3.51 2.81 2.72 9.54
120°F S.H. vapor entering cylinders
Dirty Condenser (120°F Cond. Temp)
Typical Cycle - 4
Hermetic Compressor (add 80°F S.H.)
120°F S.H. vapor entering cylinders -30 100 130 120 365 13.9 245 41 120 57 1.39 3.51 3.39 3.54 12.42
Dirty Condenser - 120°F Cond. Temp
Suction pressure lowered to
compensate for starving TEV's