Analysis of Power System Harmonics Using Singular

Value Decomposition, Least Square Estimation and FFT


Bilawal Rehman1, Masood Ahmad2, Jawad Hussain3
SST-UMT1, CIIT-LHR2, EED-UET3
Lahore Pakistan
eer.cbr@gmail.com1, masoodjaffar@gmail.com2, jawwd-hussain@hotmail.com3

Abstract — This research work will examine singular frequency drive shares the AC power supply with
value decomposition (SVD), Fast Fourier Transform touchy electronic equipment, for example, computers,
(FFT) and least square technique for the estimation of telecommunications networks, lighting and clocks.
harmonics in power system. Harmonics in power system Delicate equipment build significantly at exploration
disturbs the quality of energy supplied to load,
focuses, healing centres and so forth. A conceivable
increased energy losses and reduce the reliability of the
power system. In some cases, the large power converter concern in such situations could be harmonic twisting
systems produce not only typical harmonics but also a on the AC power line created by the adjustable
significant amount of inter harmonics which can frequency drive and other electrical equipment [2].
significantly deteriorate the quality of power supply Most flexible frequency drives operate by utilizing a
voltage. Inter harmonics are those components of bridge rectifier to change the incoming AC voltage to
current or voltage waveform which are not integer DC voltage. Inverter is then used to convert this DC
multiple of fundamental frequency component. Since voltage into an exact output AC voltage and
poor power quality cause losses in power system that’s frequency to control the speed of the motor [3].
why researchers are working to find techniques to
estimate and control the harmonics in power system.
During rectification current can't spill out of the
Singular value decomposition approach is an ideal rectifier into the DC bus until the input voltage is
technique to estimate harmonics in power system more prominent than the DC bus voltage. This only
located far away. Since in most of the cases, power happens for a very short period of time for each phase.
system produce over determine equations which can This causes a non-sinusoidal current flow produce by
easily be solved using SVD for optimal solution. drive. Keeping in mind the end goal to exchange the
Singular vector decomposition, SVD is really a energy needed by the motor in short period of time,
mathematical method to lessen a dataset containing an the crest current must be high. It comprises of two
extensive number of qualities to a dataset containing discrete pulses per half-period. Since the current
fundamentally less values, yet which still contains a
huge portion of the variability introduce in the first
pulses are focused in the voltage period. The result is
information. SVD investigation brings about a more that such a current waveform has an abnormal state of
reduced representation of correlations, particularly harmonic distortion.
with multivariate datasets and can give knowledge into
spatial and temporal variations exhibited in the fields of Harmonics are actually distortion of supply
data being analysed under different circumstance. waveform form ideal sinusoidal waveform. These are
Similarly traditional least square method is also one of due to the interaction between distorting customer
the most prominent method to estimate the line of best loads and impedance of the supply network. Its major
fit. This research work will show the analysis of said
disadvantageous effects are induction motors,
techniques to find the optimal approximation of noisy
and distorted wave form. To investigate effectiveness of transformers and capacitors’ heating and the
said techniques; simulations will be carried out in overloading neutrals.
MATLAB with same parameters. Harmonic distortion is not generally due to the
operation of the power system. It is always be due to
Key Word: Singular Value Decomposition, Least non-linear load which draw non-sinusoidal current.
square estimation, Harmonics, Power System
Various electronic equipment behaves differently
I. INTRODUCTION depending on their method of operation. Equipment
Variable frequency drives have become a standard having large THD factor are not affected adversely
technique to control ventilation, heat, industrial but equipment with low THD factor are severely
machines due to accurate control and momentous damaged. In most of the cases harmonics cause
energy savings. Converters have been used in overheating which results increased degradation of
industrial application for years to control process [1]. insulation and could cause damage to life. Also
In most HVAC installations, the customizable
harmonics cause malfunctioning of sensitive data’s substructure more clearly and orders it from
electronic equipment. higher variation to the lower.

Quite a large number of single-phase distorting The most notable point of singular value
loads causes harmonics which may extend to three decomposition is that we can simply ignore variation
phases, for example, happens in high-rise office below a certain threshold which reduces our data
buildings; harmonics can cause neutral currents which massively but we have to make sure that the actual
can surpass dynamic line current. At the point where relationship of interest should be preserved.
the harmonics are truant, the neutral carries a little
current; this thing has been in practice that the neutral We can drive singular value decomposition
is rated for full or at-least major part of the live line theorem using simple algebraic concepts which states
current which is not less then half. With unnecessary that an ordinary rectangular matrix ‫ܣ‬can be expressed
harmonics’ level caused by loads in single phase, as the product of three matrices.
there is the danger of overloading of neutral with ܷis orthogonal matrix (ܷ ் ܷ ൌ ‫)ܫ‬
these two conceivable results: ‫ ܦ‬is diagonal matrix
ܸ ் is transpose U, the orthogonal matrix (ܸ ் ܸ ൌ
Overheating of the neutral wire which leads to the ‫)ܫ‬
loss of conductor’s life and conceivable danger of fire. SVD is normally expressed by following equation
There are few claims which state that the huge
neutral- earth voltages can influence the modern ‫ܣ‬௠௡ ൌ ܷ௠௠ ‫ܦ‬௠௡ ܸ௡௡ ்
digital equipment if earthing system’s design is not
good. Orthogonal eigenvalues of ‫ ்ܣܣ‬and ‫ ܣ ்ܣ‬are the
Transformers and PFI (Power Factor column vectors ofܷ and ܸ respectively, whereas ‫ ܦ‬is
Improvement) capacitors are highly affected by a diagonal matrix having the square roots of
harmonics that came with supply in power system eigenvalues from ܷ or ܸ in descending order. By
substations. Transformer are affected by un-even applying Gram-Schmidt orthonormalization method
current waveform that leads to extra heating and we can convert a matrix into an orthogonal matrix.
causes the reduction of their service life. The applied
voltage waveform affects the capacitor which leads to
In order to estimate a noisy signal using SVD
the overheating of dielectric and it increases the
technique we have to apply above equation on
explosion risk. So harmonic effect leads to the over-
characteristic equation of signal. Consider a noisy
heating of equipment, minimizes service life to as low
signal
as half and risk of life and property that results in
considerable losses in terms of economy.
‫ݔ‬ሺ‫ݐ‬ሻ ൌ ͷͲ …‘•ሺʹߨͷͲ‫ݐ‬ሻ ൅ ͺͲ …‘•ሺʹߨʹ͹ͷ‫ݐ‬ሻ
In this research work a noisy power signal will be
൅ ͳͲͲ…‘•ሺʹߨͳʹͷ‫ݐ‬ሻ
examined using singular value decomposition (SVD),
reduced SVD, Fast Fourier Transform (FFT) and least
square technique for the estimation of harmonics in Shown in figure 1.
power system. Graphical results will be shown to
verify the accuracy of techniques.

II.SINGULAR VALUE DECOMPOSITION

Singular value decomposition is a technique in


mathematics to transform correlated variable into
uncorrelated set of variables which expose original
behaviour, to identify set of data points which exhibits
most variation and to approximate original data into
fewer dimensions [8].

The basic idea behind the singular value


decomposition is transformation of a high
dimensional, largely variable set of data points into a Figure 1
lower dimensional space that exposes the original
The signal contains basic frequency component of
50 Hz, higher frequency 275 Hz and inter harmonics
of 125 Hz. Applying SVD technique to ‫ݔ‬ሺ‫ݐ‬ሻ we get

Figure 4

Many more simulations have been taken into


account and results are shown in figure 5.

Figure 2

Figure 2 follows that Singular value


decomposition is a suitable approach to estimate a
signal. Applying Chirp Z-Transform to SVD signal
we can estimate signal frequency and higher
harmonics.

‫ܪ‬ሺ‫ݖ‬ሻ ൌ ͳ െ ෍ ݄௜ ‫ି ݖ‬௜
௜ୀଵ
Here ݄௜ is the sampled signal of SVD estimation.

Figure 5

III. FAST FOURIER TRANSFORM


Fast Fourier Transform (FFT) is a type of Fourier
Transform that deals in the transformation of time
data points’ block. It speaks to the frequency
composition of the time signal. Fourier series is
actually gives an alternative way to represent the data.
We can represent a signal by the amount of
information at different frequencies instead of
expressing the signal as function of amplitude and
Figure 3 time. Fast Fourier Transform (FFT) is the most
Figure 3 follows the frequency spectrum of commonly used systems in the field of Electrical
estimated signal. Taking positive values of frequency Engineering to analyse the frequency behaviour of
spectrum we can illustrate the frequency components different signals. On other hand Fourier series states
of power signal as shown in figure 4. that a signal can be represented by infinite series
expressing sum of •‹‡•and …‘•‹‡•of different
frequencies
correct amplitude of frequency components in noisy

signal.
݂ሺ‫ݐ‬ሻ ൌ ܽ௢ ൅ ෍ሺܽ௡ •‹ሺʹߨ݊‫ݐ‬ሻ ൅ ܾ௡ …‘•ሺʹߨ݊‫ݐ‬ሻሻ
௡ୀଵ
IV. LEAST SQUARE ESTIMATION
Least square estimation is a traditional technique
݂ሺ‫ݐ‬ሻ represents the signal in time domain, and ܽ௡ about estimating parameters by minimizing the
and ܾ௡ are unknown coefficients of the series. squared differences between actual value and
Figure 6 follows the Fourier transform of above observed value of data under consideration. The least
mentioned signal. We can easily see that singular squares technique is actually a computationally
value decomposition is effective technique to estimate convenient measure of best fit. It corresponds to
frequency component of noisy signal. The error maximum possibility estimation when the noise is
between singular value decomposition and Fourier normally distributed over the signal. Figure 8 shows
transform is show in figure 7. the least square estimation of above mention signal
[8].

Figure 8
Figure 6 Figure 9 indicates the moving average estimation
of above signal with lower noise.

Figure 7
Figure 9
Figure 7 clearly explains the accuracy of singular Fourier transform of estimated moving average
value decomposition technique to estimate harmonics signal can be seen in figure 10.
in power systems while FFT fails to calculate the
VI. REFERENCES

[1] Integral energy, “Harmonic distortion in the electric


supply system”- 2000
[2] “Preliminary Study of a New Approach to NMF Based
Text Summarization Fused with Anaphora Resolution”,
TICKDD -2010
[3] “Harmonic Distortion of the AC Power Line” by
danfoss-2011
[4] Kirk Baker, “Singular Value Decomposition Tutorial”,
2005
[5] Carbone D. Menniti, N. Sorrentino A. Testa, “Iterative
Harmonic and Interharmonic Analysis in Multiconverter
Industrial Systems”
[6] T. Lobos, T. Kozina , H.-J. Koglin ,“Power System
Harmonics Estimation Using Linear Least Squares Method
and SVD”
Figure 10 [7] T. Lobos and J. Rezmer ,Real-Time Determination of
We can see form figure 10 that moving average Power System Frequency”, IEEE Trans., Instrument. And
fails to determine all frequency components of power Measurement, February 1991.
signal. However singular value decomposition [8] Sara A. Van De Geer, “Least Squares Estimation” 2005
efficiently point out the all frequency components of
signal.
V. CONCLUSION
In this research work various mathematical
techniques to estimate harmonics of power signal
have been analysed. All the simulations have been
carried out in MATLAB with a same signal. Results
show that all techniques have their own features but it
has been clear from results that singular value
decomposition technique to estimate harmonics in
power signal is more efficient as compared to other
presented techniques in literature.