This document summarizes the analysis of foundation bolts for an SRP skid support. It finds that the skid experiences no tension or shear loads based on STAAD analysis. As such, no anchor bolts are technically required. However, two bolts are being provided given the large size of the skid. Design codes, bolt properties, material properties, and capacity calculations are presented and confirm the bolts are safe without loads.
This document summarizes the analysis of foundation bolts for an SRP skid support. It finds that the skid experiences no tension or shear loads based on STAAD analysis. As such, no anchor bolts are technically required. However, two bolts are being provided given the large size of the skid. Design codes, bolt properties, material properties, and capacity calculations are presented and confirm the bolts are safe without loads.
This document summarizes the analysis of foundation bolts for an SRP skid support. It finds that the skid experiences no tension or shear loads based on STAAD analysis. As such, no anchor bolts are technically required. However, two bolts are being provided given the large size of the skid. Design codes, bolt properties, material properties, and capacity calculations are presented and confirm the bolts are safe without loads.
Node No - 3656 UNIT Reference Bolt size = M20 Area of bolt, Ab = 169 mm² Tensile force, Fy = 18 KN STAAD analysis Shear force, Fx = 0 KN STAAD analysis Shear force, Fz = 0 KN STAAD analysis Resultant Shear force, V = 0.00 KN Tensile force, T = 18.00 KN No of bolt, n = 2 Material = Gr 8.8 Yield strength, Fy = 640 N/mm² futa = min(fu, 1.9*fy, 125 [ksi]) Sec. D.5.1.2 futa = 800 N/mm² Tensile Strength, Fu = 800 N/mm² Shear Capacity, Vc = n x Φ x Ab x 0.5 x Fu Eq. D-20 Vc = 101.4 KN Utility Ratio = 0.00 HENCE SAFE = V < Vc Tensile Capacity, Tc = n x Φ x Ab x 0.75 x Futa Eq. D-3 Tc = 152.10 KN Utility Ratio = 0.12 HENCE SAFE = T < Tc Combined Ratio V/Vc+T/Tc = 0.12 < 1.4 = HENCE SAFE
AS THERE IS NO TESNSION OR SHEAR LOAD ACTION AT THE SUPPORT LOCATION,
NO ANCHOR BOLTS ARE REQUIRED. BUT CONSIDERING LARGE SKID SIZE, TWO BOLTS ARE PROVIDED.