You are on page 1of 2

SRP SKID - FOUNDATION BOLT CHECK

MAX LOADS FROM STAAD ANALYSIS

CASE 1 - MAX FX AND FY


Design code - AISC 360-10
Node - 30 UNIT Reference
Bolt size = M20
Area of bolt, Ab = 169 mm²
Tensile force, Fy = 97 KN STAAD analysis
Shear force, Fx = 0 KN STAAD analysis
Shear force, Fz = 29 KN STAAD analysis
Resultant Shear force, V = 29.00 KN
Tensile force, T = 97.00 KN
No of bolt, n = 4
Material = Gr 8.8
Yield strength, Fy = 640 N/mm²
futa = min(fu, 1.9*fy, 125 [ksi]) Sec. D.5.1.2
futa = 800 N/mm²
Tensile Strength, Fu = 800 N/mm²
Shear Capacity, Vc = n x Φ x Ab x 0.5 x Fu Eq. D-20
Vc = 202.8 KN
Utility Ratio = 0.14
HENCE SAFE
= V < Vc
Tensile Capacity, Tc = n x Φ x Ab x 0.75 x Futa Eq. D-3
Tc = 304.20 KN
Utility Ratio = 0.32
HENCE SAFE
= T < Tc
Combined Ratio V/Vc+T/Tc = 0.46 < 1.4
= HENCE SAFE
SRP SKID - FOUNDATION BOLT CHECK
CASE 2 - MAX FZ AND FY
Design code - AISC 360-10
Node - 30 UNIT Reference
Bolt size = M20
Area of bolt, Ab = 169 mm²
Tensile force, Fy = 71 KN STAAD analysis
Shear force, Fx = 10 KN STAAD analysis
Shear force, Fz = 227 KN STAAD analysis
Resultant Shear force, V = 227.22 KN
Tensile force, T = 71.00 KN
No of bolt, n = 4
Material = Gr 8.8
Yield strength, Fy = 640 N/mm²
futa = min(fu, 1.9*fy, 125 [ksi]) Sec. D.5.1.2
futa = 800 N/mm²
Tensile Strength, Fu = 800 N/mm²
Shear Capacity, Vc = n x Φ x Ab x 0.5 x Fu Eq. D-20
Vc = 202.8 KN
Utility Ratio = 1.12
UNSAFE
= V < Vc
Tensile Capacity, Tc = n x Φ x Ab x 0.75 x Futa Eq. D-3
Tc = 304.20 KN
Utility Ratio = 0.23
HENCE SAFE
= T < Tc
Combined Ratio V/Vc+T/Tc = 1.35 < 1.4
= HENCE SAFE

You might also like