This document summarizes the results of a bolt check analysis for the foundation of an SRP skid from STAAD. It examines two load cases:
1) Maximum FX and FY loads of 97kN tension and 29kN shear were found to be safe, with utility ratios of 0.32 and 0.14 for tension and shear below the capacity limits.
2) Maximum FZ and FY loads of 227kN shear and 71kN tension were also found to be safe based on the combined ratio, although the shear load exceeded the shear capacity on its own.
This document summarizes the results of a bolt check analysis for the foundation of an SRP skid from STAAD. It examines two load cases:
1) Maximum FX and FY loads of 97kN tension and 29kN shear were found to be safe, with utility ratios of 0.32 and 0.14 for tension and shear below the capacity limits.
2) Maximum FZ and FY loads of 227kN shear and 71kN tension were also found to be safe based on the combined ratio, although the shear load exceeded the shear capacity on its own.
This document summarizes the results of a bolt check analysis for the foundation of an SRP skid from STAAD. It examines two load cases:
1) Maximum FX and FY loads of 97kN tension and 29kN shear were found to be safe, with utility ratios of 0.32 and 0.14 for tension and shear below the capacity limits.
2) Maximum FZ and FY loads of 227kN shear and 71kN tension were also found to be safe based on the combined ratio, although the shear load exceeded the shear capacity on its own.
Design code - AISC 360-10 Node - 30 UNIT Reference Bolt size = M20 Area of bolt, Ab = 169 mm² Tensile force, Fy = 97 KN STAAD analysis Shear force, Fx = 0 KN STAAD analysis Shear force, Fz = 29 KN STAAD analysis Resultant Shear force, V = 29.00 KN Tensile force, T = 97.00 KN No of bolt, n = 4 Material = Gr 8.8 Yield strength, Fy = 640 N/mm² futa = min(fu, 1.9*fy, 125 [ksi]) Sec. D.5.1.2 futa = 800 N/mm² Tensile Strength, Fu = 800 N/mm² Shear Capacity, Vc = n x Φ x Ab x 0.5 x Fu Eq. D-20 Vc = 202.8 KN Utility Ratio = 0.14 HENCE SAFE = V < Vc Tensile Capacity, Tc = n x Φ x Ab x 0.75 x Futa Eq. D-3 Tc = 304.20 KN Utility Ratio = 0.32 HENCE SAFE = T < Tc Combined Ratio V/Vc+T/Tc = 0.46 < 1.4 = HENCE SAFE SRP SKID - FOUNDATION BOLT CHECK CASE 2 - MAX FZ AND FY Design code - AISC 360-10 Node - 30 UNIT Reference Bolt size = M20 Area of bolt, Ab = 169 mm² Tensile force, Fy = 71 KN STAAD analysis Shear force, Fx = 10 KN STAAD analysis Shear force, Fz = 227 KN STAAD analysis Resultant Shear force, V = 227.22 KN Tensile force, T = 71.00 KN No of bolt, n = 4 Material = Gr 8.8 Yield strength, Fy = 640 N/mm² futa = min(fu, 1.9*fy, 125 [ksi]) Sec. D.5.1.2 futa = 800 N/mm² Tensile Strength, Fu = 800 N/mm² Shear Capacity, Vc = n x Φ x Ab x 0.5 x Fu Eq. D-20 Vc = 202.8 KN Utility Ratio = 1.12 UNSAFE = V < Vc Tensile Capacity, Tc = n x Φ x Ab x 0.75 x Futa Eq. D-3 Tc = 304.20 KN Utility Ratio = 0.23 HENCE SAFE = T < Tc Combined Ratio V/Vc+T/Tc = 1.35 < 1.4 = HENCE SAFE