WHRB Interlocks

S. No Boiler Equipment Logic Interlocks


For
1 AQC Inlet Damper Open 1. All the RAV and DCF are in run condition
2. Boiler Drum level healthy if >10% & < 90%
3. Inlet Temp < 520°C
4. Main By-pass damper 100% Open
5. 2/3 the Hopper levels HI-HI in healthy
2 AQC Outlet Damper Open 1. Inlet Damper 100% open Feedback
3 PH1 Inlet Damper 1. All the RAV and DCF in run condition
2. Boiler Drum level healthy if >10% & < 90%
3. Inlet Temp < 420°C
4. Main By-pass damper 100% Open
5. 1/2 the Hopper levels HI-HI in healthy
4 PH1 Outlet Damper Open 1. Inlet Damper 100% open Feedback
5 PH1 Inlet Damper Open 1. All the RAV and DCF in run condition
2. Boiler Drum level healthy >10% & < 90%
3. Inlet Temp < 420°C
4. Main By-pass damper 100% Open
5. 1/2the Hopper levels HI-HI in healthy

6 PH1 Outlet Damper Open 1. Inlet Damper 100% open Feedback


7 PH1 By-pass Damper Open 1. Inlet gas temp above 420°C for 120 sec
2. Drum level above 90% for 120 sec
3.Drum level below 10% for 120 sec
4. Main steam temp above 395°C for 120 sec
5. One of two Hopper HI-HI for 300 sec
8 PH2 By-pass Damper Open 1. Inlet gas temp above 420°C for 120 sec
2. Drum level above 90% for 120 sec
3.Drum level below 10% for 120 sec
4. Main steam temp above 395°C for 120 sec
5. One of two Hopper HI-HI for 300 sec
9 AQC By-pass Damper Open 1. Inlet gas temp above 420°C for 120 sec
2. Drum level above 90% for 120 sec
3.Drum level below 10% for 120 sec
4. 2/3 Hopper HI-HI for 300 sec
10 AQC Outlet Damper Close 1. By-pass will open 100% if any of
a) Drum Level High 90% for 120 Sec
b) Drum Level low 10% for 120 Sec
c) Inlet Gas temp high 540°C for 300 sec.
d) 2/3 Hopper HI-HI for 300 se
11 AQC Inlet Damper Close 1. Outlet Damper 100% Close Feedback
S. No Boiler Equipment Logic Interlocks
For
12 PH1 Outlet Damper Close 1. By-pass will open 100% if any of
a) Drum Level High 90% for 120 Sec
b) Drum Level low 10% for 120 Sec
c) Inlet Gas tem high 420°C for 300 sec
d) 1/2 Hopper HI-HI for 300 sec
13 PH1 Inlet Damper Close 1. Outlet Damper 100% Close Feedback
14 PH2 Outlet Damper Close 1. By-pass will open 100% if any of
a) Drum Level High 90% for 120 Sec
b) Drum Level low 10% for 120 Sec
c) Inlet Gas tem high 420°C for 300 sec
d) 1/2 Hopper HI-HI for 300 sec
15 PH2 Inlet Damper Close 1. Outlet Damper 100% Close Feedback