The document describes 15 interlock logic conditions for opening and closing dampers and bypass dampers on boilers AQC, PH1, and PH2. The interlocks are triggered based on parameters like drum level, inlet gas temperature, hopper levels, and damper positions. For example, the AQC inlet damper will open if the drum level is between 10-90%, inlet temp is below 520°C, and the main bypass damper is 100% open. The AQC outlet damper will close if the bypass opens due to high or low drum level, high inlet gas temperature, or high hopper levels.
The document describes 15 interlock logic conditions for opening and closing dampers and bypass dampers on boilers AQC, PH1, and PH2. The interlocks are triggered based on parameters like drum level, inlet gas temperature, hopper levels, and damper positions. For example, the AQC inlet damper will open if the drum level is between 10-90%, inlet temp is below 520°C, and the main bypass damper is 100% open. The AQC outlet damper will close if the bypass opens due to high or low drum level, high inlet gas temperature, or high hopper levels.
The document describes 15 interlock logic conditions for opening and closing dampers and bypass dampers on boilers AQC, PH1, and PH2. The interlocks are triggered based on parameters like drum level, inlet gas temperature, hopper levels, and damper positions. For example, the AQC inlet damper will open if the drum level is between 10-90%, inlet temp is below 520°C, and the main bypass damper is 100% open. The AQC outlet damper will close if the bypass opens due to high or low drum level, high inlet gas temperature, or high hopper levels.
For 1 AQC Inlet Damper Open 1. All the RAV and DCF are in run condition 2. Boiler Drum level healthy if >10% & < 90% 3. Inlet Temp < 520°C 4. Main By-pass damper 100% Open 5. 2/3 the Hopper levels HI-HI in healthy 2 AQC Outlet Damper Open 1. Inlet Damper 100% open Feedback 3 PH1 Inlet Damper 1. All the RAV and DCF in run condition 2. Boiler Drum level healthy if >10% & < 90% 3. Inlet Temp < 420°C 4. Main By-pass damper 100% Open 5. 1/2 the Hopper levels HI-HI in healthy 4 PH1 Outlet Damper Open 1. Inlet Damper 100% open Feedback 5 PH1 Inlet Damper Open 1. All the RAV and DCF in run condition 2. Boiler Drum level healthy >10% & < 90% 3. Inlet Temp < 420°C 4. Main By-pass damper 100% Open 5. 1/2the Hopper levels HI-HI in healthy
6 PH1 Outlet Damper Open 1. Inlet Damper 100% open Feedback
7 PH1 By-pass Damper Open 1. Inlet gas temp above 420°C for 120 sec 2. Drum level above 90% for 120 sec 3.Drum level below 10% for 120 sec 4. Main steam temp above 395°C for 120 sec 5. One of two Hopper HI-HI for 300 sec 8 PH2 By-pass Damper Open 1. Inlet gas temp above 420°C for 120 sec 2. Drum level above 90% for 120 sec 3.Drum level below 10% for 120 sec 4. Main steam temp above 395°C for 120 sec 5. One of two Hopper HI-HI for 300 sec 9 AQC By-pass Damper Open 1. Inlet gas temp above 420°C for 120 sec 2. Drum level above 90% for 120 sec 3.Drum level below 10% for 120 sec 4. 2/3 Hopper HI-HI for 300 sec 10 AQC Outlet Damper Close 1. By-pass will open 100% if any of a) Drum Level High 90% for 120 Sec b) Drum Level low 10% for 120 Sec c) Inlet Gas temp high 540°C for 300 sec. d) 2/3 Hopper HI-HI for 300 se 11 AQC Inlet Damper Close 1. Outlet Damper 100% Close Feedback S. No Boiler Equipment Logic Interlocks For 12 PH1 Outlet Damper Close 1. By-pass will open 100% if any of a) Drum Level High 90% for 120 Sec b) Drum Level low 10% for 120 Sec c) Inlet Gas tem high 420°C for 300 sec d) 1/2 Hopper HI-HI for 300 sec 13 PH1 Inlet Damper Close 1. Outlet Damper 100% Close Feedback 14 PH2 Outlet Damper Close 1. By-pass will open 100% if any of a) Drum Level High 90% for 120 Sec b) Drum Level low 10% for 120 Sec c) Inlet Gas tem high 420°C for 300 sec d) 1/2 Hopper HI-HI for 300 sec 15 PH2 Inlet Damper Close 1. Outlet Damper 100% Close Feedback