Professional Documents
Culture Documents
CRSI ETN B 3 16 Vibration and Sound Control
CRSI ETN B 3 16 Vibration and Sound Control
ETN-B-3-16
Vibration and Sound Control in
Reinforced Concrete Buildings
Technical Note Introduction
Consideration of vibration and sound
within buildings is an important aspect in
Vibration Control
Natural Frequency of Reinforced Concrete
Floor Systems
design. Vibrations may simply be unpleas- One of the fundamental vibration char-
ant or may cause significant difficulties, acteristics of any floor system is its natural
particularly when day-to-day activities of frequency, which is related to the mass and
the occupants, performance of sensitive stiffness of the floor system. Natural fre-
equipment, or important functions are rou- quency is a measure of how a floor system
tinely disrupted. Sounds transmitted from a will respond to the sources that can cause
room or office can have a direct impact on vibration and is directly related to how the
the comfort and productivity of the occu- occupants will perceive such vibrations.
pants in adjacent rooms, especially where
people are trying to rest, sleep, or perform Most commercial computer programs
normal activities. can determine natural frequency and oth-
er pertinent vibration characteristics using
This Technical Note summarizes basic vi- finite element methods. Simplified proce-
bration and sound control characteristics of dures to determine the natural frequency
reinforced concrete. Sources of vibration of reinforced concrete floor systems can
and sound typically encountered in rein- be found in CRSI (2014).
forced concrete buildings are discussed as
are acceptance criteria for both. Guidelines In general, the greater the natural fre-
are provided on how to choose a reinforced quency, the more likely the floor system
concrete floor system based on vibration will be able to satisfy the required vibra-
acceptance criteria. Information is also giv- tion acceptance criteria for human comfort
en on the inherent sound control qualities or sensitive equipment. Because of their
of reinforced concrete and how these quali- inherent mass and stiffness, reinforced
ties meet minimum code requirements for concrete floor systems can readily meet
sound transmission. even the most stringent acceptance crite-
ria. Natural frequencies in the range of 7
to 12 Hz can be achieved by satisfying only
Sources Description
HVAC equipment
(ACI 2014). Larger natural frequencies are also easily at- Unacceptable Zone:
tainable. Many economical reinforced concrete options Areas above the curves
are available to satisfy essentially any prescribed accep- for each structure type
tance criteria.
Sources of Vibration 10
Rhythmic
Vibration of floor systems in buildings can be caused Activities
by a variety of sources, including the ones identified in
Shopping
Table 1. Sources that occur inside of or that are attached
Peak Acceleration %g
Malls,Dining
to a building are categorized as internal sources and and Dancing
those that are not are classified as external sources. The
1
items in the Table, which are not meant to be compre- Offices/
hensive, are sources that can typically have an impact on Residential
vibration design of a floor system.
(c) (d)
(e)
Figure 2 – Reinforced Concrete Floor Systems: (a) wide-module joist (b) flat plate (c) flat plate voided concrete slab
(d) two-way joist (e) grillage.
Table 2 – Initial Selection Guide for Reinforced Concrete Floor Systems Based on Vibration Acceptance Criteria
Wide-module joist X
Flat plate X
Two-way joist X X X
Grillage X X X
Wood stud wall (2 × 4 in. studs spaced at 16 in. on center with ½ in. gypsum board on each face screwed
34
to the studs)
Metal stud wall (35/8 in., 25 gauge studs spaced 24 in. on center with a single layer of 5/8 in. gypsum board
39
on each face screwed to the studs)
8 × 8 × 16 in. lightweight CMU (28 lbs/block) 45
While STC and IIC ratings of 50 are the minimum pre- References
scribed by the IBC, it is not uncommon for owners of
ACI (American Concrete Institute). 2014. “Building
high-end properties to stipulate STC and IIC ratings of
Code Requirements for Structural Concrete and
60 or higher. While an STC of 60 is readily achievable, IIC
Commentary.” ACI 318-14, Farmington Hills, Michigan.
values of 60 generally require the use of resilient floor-
ing (vinyl) or carpet and are difficult to attain using hard ASTM (American Society for Testing and
surfacing such as ceramic tile. Materials). 2009. “Standard Test Method for Laboratory
Measurement of Airborne Sound Transmission Loss of
Advantages of Reinforced Concrete with Respect to
Building Partitions and Elements.” ASTM E90 – 09, West
Sound Control
Conshohocken, Pennsylvania.
Reinforced concrete has many inherent characteristics
that make it ideal for attenuating sounds: ASTM (American Society for Testing and Materials).
2012. “Standard Classification for Determination of
•
Due to its greater mass, reinforced concrete has
Impact Insulation Class (IIC).” ASTM E989 – 12, West
higher STC ratings and can block low frequency
Conshohocken, Pennsylvania.
sounds better than wood or steel.
ASTM (American Society for Testing and Materials).
• Due to mainly flat floor and roof surfaces, it is easier
2016a. “Standard Test Method for Laboratory
to avoid flanking paths in reinforced concrete struc-
Measurement of Impact Sound Transmission Through
tures compared to structures of other materials.
Floor-Ceiling Assemblies Using the Tapping Machine.”
• Low frequency thumping sounds of foot traffic are ASTM E492 – 16, West Conshohocken, Pennsylvania.
better attenuated by reinforced concrete floor sys-
ASTM (American Society for Testing and Materials).
tems than floor systems of wood or steel.
2016b. “Classification for Rating Sound Insulation.”
• Exterior walls of reinforced concrete attenuate out- ASTM E413 – 16, West Conshohocken, Pennsylvania.
side noise sources (which tend to be low frequencies
CRSI (Concrete Reinforcing Steel Institute). 2014.
below 125 Hz) significantly better than other materi-
Design Guide for Vibrations of Reinforced Concrete
als; this is especially beneficial for schools, hospitals,
Floor Systems, Schaumburg, IL.
and residences, or where buildings are located near
an airport or other loud sound sources.
Contributors: The primary contributors to this publication are: David A. Fanella, Ph.D., P.E., S.E.,
F.ACI, F.ASCE and David B. McDonald, Ph.D., P.E., F.ACI, F.ASCE
Keywords: acoustic rating, IIC (impact insulation class), natural frequency, noise, reinforced concrete,
sound, STC (sound transmission class), vibration.
Reference: Concrete Reinforcing Steel Institute – CRSI [2016], “Vibration and Sound Control in 933 North Plum Grove Rd.
Reinforced Concrete Buildings,” CRSI Technical Note ETN-B-3-16, Schaumburg, Illinois, 8 pp.
Schaumburg, IL 60173-4758
Historical: None p. 847-517-1200 • f. 847-517-1206
www.crsi.org
Note: This publication is intended for the use of professionals competent to evaluate the significance
and limitations of its contents and who will accept responsibility for the application of the material it Regional Offices Nationwide
contains. The Concrete Reinforcing Steel Institute reports the foregoing material as a matter of infor-
mation and, therefore, disclaims any and all responsibility for application of the stated principles or for A Service of the Concrete Reinforcing Steel Institute
the accuracy of the sources other than material developed by the Institute. ©2016 This publication, or any part thereof, may not be
reproduced without the expressed written consent of CRSI.