Professional Documents
Culture Documents
FACULTY OF ENGINEERING
LABORATORY REPORT
2
NO - LOAD OPEARTION OF A SINGLE-PHASE TRANSFORMER
OBJECTIVE
Analyzing no-load operation of a transformer, finding losses at no-load operation, finding turns
ratio and getting experience about the subject.[1]
A single-phase transformer if connected through one of its terminals to a voltage source while is
second is made open is said to operate in a no-load condition and as a result, current flows only
through the terminals connected to the voltage source. It should be emphasized that also the open
terminal has no current flowing through it, there is an induced emf through it terminals.
Because no current flows through the opened terminal, the power loss at that terminal is equal to
zero since
S = VI
Where S is the apparent power and I is the total current made up of the active current in
responsible for power losses and magnetizing current responsible for maintaining any flux
generation in the circuit.
If I = 0
The measurable S is equal to zero hence the active power is equal to zero.
3
This shows that power losses occur only in the terminal connected to a voltage source either due
to the resistive nature of the winding or eddy current and hysteresis.
EXPERIMENT
PROCEDURE
DATA TABLES
Table 1.2: Experimental values gotten of the transformer parameters
U1 I1 U2 Energy Analyzer Explanation
(V) (A) (V) U (V) I (A) CosØ W VA VAR
4.1 0.1 0.6 4.1 0 1 0 0 0 No Power loss
24.7 0.1 4.1 24.7 0 1 0 0 0 No Power loss
53.4 0.1 8.4 53.5 0 1 0 0 0 No Power loss
73.9 0.1 12.35 74.2 0 1 0 0 0 No Power loss
93.8 0.1 15.65 94.1 0 1 0 0 0 No Power loss
113.9 0.1 19.04 114 0 1 0 0 0 No Power loss
133.9 0.1 22.3 133 0 1 0 0 0 No Power loss
152.7 0.1 25.43 152 0 1 0 0 0 No Power loss
172.1 0.1 29.03 174 0 1 0 0 0 No Power loss
193.8 0.1 32.3 194 0.08 0.66 8.8 13.6 9.6 Little Power loss
QUESTIONS/ANSWERS
1. What is the power observed in the energy analyzer when the rated voltage U1 was applied to
the primary of the transformer and there is no load at the secondary?
ANS: It was observed that due to the absence of current measured by the energy analyzer, the
power loss recorded was zero till the voltage at the primary reached an appreciable value of
0.08A as observed from the analyzer and this is consistent with the fact that for a no load
operation state since there is no load at the secondary, the current drawn is very low at about 2-
10% of a loaded transformer and as such a very high voltage is needed for an appreciable current
to flow through the primary.
2. Find the transformation ratio of the transformer using the values U1, U2 recorded in the
experiment
ANS: The transformation ratio is
4
𝑁2 𝐸2 32.3 1 1
= = = ≅
𝑁1 𝐸1 198.8 6.15 6
3. Sketch the no-load operation graph of the transformer using the values U1, I2 and the values
read in the energy analyzer.
Figure 1.1
REFERENCES
5
[1] Electric Machines Lab Manual.