HYDROSPLIT m3

Thermal energy calculator split version


(The HYDROSPLIT-M3 is a separate thermal energy computer that measures the amount of energy used to heat
or cool the water supplied to piping systems, including large calibers, that do not allow the installation of the
compact version. It connects to the pulse output of a meter to measure the volume of water used. The processing
of the data regarding the difference between the temperature of the thermal agent at flow and return, as well as
the data regarding the volume of water used by each user, allows the calculation of the amount of energy actually
consumed. )
Separate heat/BTU calculator for measuring the amount of energy used for heating
and/or cooling. Easily connectable to flow meters equipped with pulse output and
used in systems with pipes larger than DN20 – ¾ “.
The processing of the data on the difference between the temperature of the thermo-
vector fluid supply and the return one (DT), combined with the data on the volume of
the thermo-vector fluid used, allows accurate calculation of the amount of energy
consumed.
Approved according to the MID 2004/22/CE MI004 and the EN1434 standard.
Technical Features

Environmental class A (E1; M1)


Temperature measuring range (Heating) 5 – 180 °C
Temperature difference range (Heating) 3 – 150 K
Temperature measuring range (cooling) 2 – 24 °C
Calibration temperature 3 – 20 K
Maximum measurable power 99 MW
Temperature sensor PT 1000
Cable length for the temperature sensor 3 m / 10 m
Power supply Litium battery / external power supply
Max. Battery life (basic version) 10+1 years
Protection degree IP52
Display level 6
Display LCD 8 digits + icons
Energy load indicator MWh (GJ on request)
Maximum cable length pulse emitter 2m
0.1 – 0.25 – 1.0 – 2.5 – 10 – 25 – 100 – 250
Input pulse rate
litres
1 dedicated for the heating/cooling circuit
Pulse input
meter
Class IA (default): Open Collector or reed
Pulse input class
contact, max 5Hz
Display Pulse input maximum frequency
5Hz
(MID approved)
Installation site of flowmeter (Flow in) Return pipe (default), Supply pipe (optional)
Supported vector fluid Water
The most important indications of the Hydrosplit M3 heat meter are:

 Current readout of heat consumption in GJ;


 Current amount of heat / cooling energy consumed;
 26-month indications of consumption of heat / cooling and C1 and C2 water meters with dates;
 Instantaneous flow of the heating medium;
 Cumulative volume of flow;
 Flow / return temperature and temperature difference
 Instantaneous energy consumption in kW;
 Operating hours of the device since the issuance of the conformity assessment;
 Indications of C1 and C2 water meters.