Professional Documents
Culture Documents
Section 11 Boiler Control Philosophy R01
Section 11 Boiler Control Philosophy R01
- Graphical mimic with dynamic FAN Inlet Guide Vanes (IGV) opening /
animation VFD speed as per the deviation from
- Data storage and retrieval set point.
- On demand/ shift/ daily /weekly
reports Control action of this controller is Direct
- Extensive alarm management i.e. if draft value increases the opening
- Event storage of IGV/speed command to VFD also
- Engineering software function increases and vice versa.
-Tuning of control parameters IGV and VFD is controlled by separate
-Changing of alarm controllers and at a time only one
controller will be in auto mode and the
Signal using for realising close loop other one, which will be in manual,
control and data acquisition: should be given 100% command. Ratio
factor is provided to balance the load on
-Transmitter signal: 4 to 20 mA parallel fans as per the site condition.
-Thermocouple signal: mV Initially the ratio is kept 1.
-RTD signal : Resistance
2. STEAM TEMPERATURE:
This loop maintains a constant
Major Control Loops of the boiler
temperature of steam at final super
heater outlet. The outlet steam
- Furnace Draft Control
temperature is sensed using
- Steam Temp Control temperature sensors.
- Drum Level Control A cascade control strategy is followed to
take care of final super heater response
- Combustion Control
to the spray water control provided
- Deaerator level control between stages of the superheaters.
The master controller takes the input of
- Deaerator Pressure Control main steam temperature and generates
- CBD Tank level control controller output used as set point to
slave controller. The slave controller
- Start Up Vent Control gets process value of steam temperature
- BFP Discharge Header Pressure after attemperator and regulates the
Control attemperator valve.
- Soot Blower Pressure Control For better control, in addition to this, a
part of feed forward signal of furnace
temperature difference with respect to
1. FURNACE DRAFT CONTROL: time is added with the slave controller
Typically the boiler flue gas system output.
comprises two Induced draft (ID) alias
flue gas fans with inlet vanes or inlet 3. DRUM LEVEL CONTROL:
damper, and the dampers after the A. Drum level is measured using drum
fan. Alternatively the control vanes level transmitters. The final output is
can be replaced with Variable compensated for drum pressure. As the
frequency Drives as speed controller characteristics of Drum pressure Vs
for Fans. Drum level is non-linear, the
Furnace pressure transmitters are compensated signal is to be generated
located at the same elevation in upper in DCS.
section of the furnace. The furnace B. Main Steam Flow
pressure (Draft) is one of the boiler
interlock signals. Main Steam flow is measured with the
help of steam flow transmitters. These
In this control loop, Furnace pressure transmitters output is compensated for
is controlled by ID fan Inlet Guide main steam pressure and main steam
Vanes/ VFD. Furnace pressure signal temperature.
is fed to furnace draft controller which
controls the furnace pressure by ID
1 X 80 TPH CFBC Boiler Section 11, Page 2
M/s. PT Tereos FKS, Indonesia
Comm/ JB No 0993/C11
Rev 00 01/ 06.07.13
Isgec Heavy Engineering Ltd
This compensated flow is computed in additional two parameters i.e. total feed
flow computing circuit where water flow and compensated main
averaging of compensated steam flow steam flow.
signal is generated as per following
In this control loop, 100% feed water
formula
control valve is controlled. In this
control we first take the difference of
QC=Q x √ (Pa+1.033) x (Td+273)
compensated main steam flow and total
(Pd+1.033) x (Ta+273)
feed water flow. Then this difference is
Where
QC=Compensated Steam Flow
re-ranged from +100 to -100 with
Q=Un-compensated Steam Flow from FT respect to +feed water flow range to –
Pa=Process Value of Main Steam Pressure feed water flow range. This value is then
Ta=Process Value of Main steam temp. multiplied with a factor called Steam
Pd=Design Pressure Load Factor (initially kept 0.3, which is
Td=Design Temperature. finally adjusted during the
Note: Pd and Td are the values on commissioning of Boiler). This value is
which DP calculations are done by passed through a selector switch which
nozzle supplier. All pressures are in passes 0 when single element is
Kg/Cm2 and Temperatures are in selected and passes the previously
DegC. calculated value when three element is
selected. Output of selector switch is
C. Feed Water Flow directly added to the output of PID
block which gives the output by
Feed Water Flow is measured with the
help of flow transmitter. The output of considering the drum level.
these transmitters is used in three Now if the selector switch is in single
element control. element position, selector switch passes
0 and then drum level control is
Note: If spray water tapping is taken
before feed water nozzle, Spray flow is considering the drum level only and if
to be added with Feed water flow to the selector switch is in three element
calculate total water consumption. position, selector switch passes the
calculated value generated by the
Control Loop difference of compensated main steam
flow and total feed water flow which is
Drum Level Control for 30%
added in the output of PID block
Control Valve:
considering drum level. In three element
The compensated drum level signal is control, a feed forward signal of the
compared with the set point in the difference in steam and feed water flow
primary level controller and the is utilized to compensate the water fed
output of the control controller is to the drum in fluctuating conditions of
used to regulate the 30% control load to make the control more effective.
valve.
4. COMBUSTION CONTROL:
30% feed water flow control valve is
working only in Single element drum A. Combustion Air Control
level control loop and take care of
This control loop controls the air supply
boiler feed water demand at start-up
to the boiler thru various fans and
duration and at lower load.
controls the fuel feeding depending on
the boiler load and maintains the boiler
Drum Level Control for 100%
pressure and excess air levels in the
Control Valve:
boiler.
100% feed water flow control valve is
Required combustion air quantity of
having option to control water flow in
solid fuel is determined based on air
boiler in Single element drum level
requirement at various loads. This is
control and Three element drum level
compensated based on excess oxygen
control.
level to increase or decrease the air flow
Three element drum level control loop to maintain the required conditions.
take care of sufficient water flow by
considering the drum level with
1 X 80 TPH CFBC Boiler Section 11, Page 3
M/s. PT Tereos FKS, Indonesia
Comm/ JB No 0993/C11
Rev 00 01/ 06.07.13
Isgec Heavy Engineering Ltd
The fuel supply to the boiler shall O2) is detected. Fuel feeding should be
depend on the boiler load and the immediately stopped if such condition
pressure of the boiler. arises.
Control Loop: Control Loop:
This loop maintains required air flow Oxygen trimming controller is giving the
in boiler as per the load v/s air flow O/P which is scaled between 0.9 to 1.1
curve. In this control loop, PA and SA and the same is multiplied and send to
air flow is controlled by fan Inlet the air flow controller as a remote set
Guide Vanes / VFD. point.
PA fan air flow signal with density Control action of this controller is
correction is fed to PA air flow Reverse i.e. if flow value increases the
controller which controls the PA fan output of controller decreases and vice
air flow as per the deviation from the versa.
remote set point generated out of the
C. Main Steam Pressure Control
curve depending on the load on the
boiler. The objective is to match the boiler’s
steam production to the steam demand
The total air required by the boiler is
of the process. To accomplish this
controlled using the control of air thru
objective the system must be designed
the upper and lower SA nozzles. These
to maintain a constant steam pressure
nozzles dampers are regulated based
and generate a demand for fuel to the
on a load Vs Total air curve for the
boiler.
boiler. Depending on the deviation of
actual measured total air flow and the The plant load change cause the steam
value generated out of the curve at flow to change which in turn causes a
the load of the boiler, the dampers of change in the main steam pressure.
upper and lower SA nozzles are Main steam pressure controller adjusts
controlled. the demand to the fuel which eliminates
deviation between the pressure set point
Control action of this controller is
and the steam pressure measurement.
Reverse i.e. if flow value increases the
output of controller decreases and The Boiler Masters output sets the
vice versa. demand to the boilers fuel which in turn
respond accordingly to both satisfy the
B. Oxygen Trim Control
steam flow demanded by the process
The oxygen trim controller is and eliminate any deviation between the
responsible for controlling the boiler’s main steam pressure and the pressure
excess air by trimming the air flow set point.
based on the oxygen content
Control loop:
measured in the flue gas. The
controller compares the oxygen The main steam pressure control of the
content of the flue gas to the operator boiler depends on the steam demand
adjustable set point and accordingly from the system. If the steam demand
generates an output that will cause from the system is high, then high
an adjustment to the set point of the amount of fuel shall be required to
air flow controller. The adjustment is maintain the pressure and vice versa. In
limited to ±10% of the required order to maintain a constant pressure,
airflow. the steam generation shall be increased
by increasing the fuel flow. Main Steam
It should be noted that oxygen
Pressure is considered as a major
content in flue gas is one of the most
parameters for combustion control.
important variables to be monitored
during the operation of the boiler. A The measured value is compared with
low content is indicative of fuel main steam pressure set point meant
overfeeding into the combustion for fuel flow and combustion air flow
chamber, and an alarm will be control logic system. The master
initiated to warn the operators when a pressure controller will generate the
low oxygen condition (typically<1% demand signal for fuel.