Professional Documents
Culture Documents
INSTRUCTIONS
CURRENT
BALANCE RELAYS
Types
!iC52A and IJCS2B
CK
INNER BL
1
COVER BLOCK 1
CAS E—
CRADLE
OUTER BLOCK
INNER BLOCK
RESET BUTN
PLUGS
led
Fig. 1 (8007843) The Type IJC52A Relay Disassemb
2
CURRENT BALANCE RELAYS
TYPES IJC52A AND IJC52B
INTRODUCTION is first
relays are used To draw out the relay unit the cover are
The types IJC52A and IJC52B drawn out. Shortin g bars
of regulat ing trans removed, and the plug
windin g t transform
to protect the exciting provided in the case to short the curren
d, and the
fo rmers. er circuits. The latches are then release replace the
be easily drawn out. To
three mech relay unit can
The type 1JC52 relays consist of
‘.
.r.--: T:
50 :
.
—
I — — — — — — — —
..—‘
-
—
Ar :: 0
U, ‘+
eyçz
—
—
r4 —
w hen c u rrq,nt IS r— ‘.
-*-—
—‘
-‘----
inthisare
‘1 — —
-÷ - -
40 - — - - • - —
.- Lr
.,
c3 I.
.-- - -
L
o3 S
S
E 5
---— L5__ —r -r- 1
r -- ‘— ‘—-
— — — — —
— — — —
— —
30—----
..‘
-- - -- .-
— —
C — — - - - - --
L — — —
25
—
.,•
,. — — —
— ‘-
0 —
—
—
_—
f
—
:;:
—
::•. :
4)
L
1 5 -;;.
:::_::::z::::z:
0 —.• •.:
0
10
5
—
20 25 30 35 40
00 5 10 15
current (Ampere s)
Restraining
-
and
and lJC52 Relays With I2O Slope
Fig. 2 Characteristic Curve of the IJC52A
3 Amperes Minimum Pick—up
4
Current Balance Relays Types IJC GEI-Th375
Each unit closes its contacts after a time de on the sr al-in element is determined by the current
lay which is dependent both on the ratio and the drawn by the trip coil.
magnitudes of the currents and also on the time The 0.2—ampere tap is for use with trip coils
lever setting. The time decreases with an increase that operate on currents ranging from 0.2 up to 2.0
of both currents or an increase of the ratio of oper amperes at the minimum control voltage. If this
atiii to restraint current. The time lever controls tap is used with trip coils requiring more than 2
the (ontact travel. A lower time lever setting de— amperes, there is a possibility that the 7-ohm re
crc ises the cotitact travel and the time. sistance will reduce the current to so low a value
RATINGS that the breaker willnot be tripped.
Pr ‘n ‘:aiable ratings are .7 amperes nor— The 2-ampere tap should be used with trip coils
ma (urrent 25—60 ccles 3 amp minimum pick that take 2 amperes or more at minimum control
reeiO
up, with 12 ( )C slope. voltage, provided the tripping current does not cx
reed 30 amperes at the maximum control voltage.
P ioing rating of the contacts is
—
If the tripping current exceeds 30 amperes an aux
30 ;m :‘e. :oltages not exceeding 250 volts. iliary relay should be used, the connections being
Thi rur eit—carr ing ratings are affected by the such that the tripping current does not pass through
selc tioi of the iap n the target and seal—in coil the contacts or the target and seal-in coils of the
as mdicater in the following table: protective relay.
BURDENS
Ameres AC or DC
2-Amp ap 10.2 Amp T The burdens in oseci on the current transform
ers by each operating and restraining coil at 5 anrs
-
Ffbtb0n
T ripping Duty 30 are as follows:
Carry Continuously 4 08
j j
The 2-ampere tap has a d-c resistance of 0.13
ohms a d a 60 cycle impedance of 0.53 ohms while
the 0.2-ampere tap has a 7 ohm d-c resistance and
a 52 ohm 60 cycle impedance. The tap setting used
INSTALLATION
When the exciting winding of the transformer
LOCATION ‘s connected in grounded wye the secondaries of
The location should be clean and dry, free from the current transformers in series with this wind
dust and excessive vibration, and well lighted to ing should be delta-connected to avoid tripping on
facilitate inspection and testing. external giound faults.
INSPECTION
CONNECTIONS At the time of installation, the relay should be
Internal connections are shown in Figs. 7 and 8. inspected for tarnished contacts, loose screws, or
other imperfections. If any trouble is found, it
Typical external connections for the IJC52A should be corrected in the manner described under
relay, are shown in Fig. 6. MAINTENANCE.
5
Current Balance Relays Types IJC
GEI-16375
ISTIC
TYPICALTIMECHARACTER
OF TYPE IJC52A
RELAY ON #10 TIME
DIAL SETTING
60 CYCLES
8
C),
0
C-)
u-I
(13
0
20 40 60
0
ERES
OPERATINGCURRENT-AMP
6
Current Balance Relays Types LJC GEI-16375
ADJUSTMENTS
TARGET AND SEAL-IN ELEMENT the factory. Pickup, current required to close the
contacts with zero restraint, can be adjusted by
For trip coils operating on currents ranging turning the control spring adjusting ring. This ring
from 0.2 up to 2.0 amperes at the minimum control has slots the proper size to fit most screw driver
voltage, set the target and seal-in tap plug in the blades. By inserting the blade of a screw driver
0.2-ampere tap. into one of the slots, the ring can be turned. If the
ring is turned in the contact opening direction, the
For trip coils operating on currents ranging pickup will be raised. If the ring is turned in the
from 2 to 30 amperes at the minimum control volt contact closing direction, the pickup will be low
age, place the tap plug in the 2-ampere tap. ered.
The tap plug is the screw holding the right-hand TIME SETTING
stationary contact of the seal-in element. To change
the tap setting, first remove the connecting plug. For a given condition, time may be adjusted in
then, take a screw from the left-hand stationary two ways. The time lever setting controls the con
contact and place it in the desired tap. Next remove tact travel, hence the time. The drag magnet may
the screw from the other tap, and place it in the be moved on its shelf away from the disk shaft for
left-hand contact. This procedure is necessary to increased time and toward the disk shaft for de
prevent the right-hand stationary contact from get creased time. The time lever gives the greater
ting out of adjustment. ocrews should not be in both range of adjustment and is more convenient.
taps at the same time as pickup for d-c will be the
higher tap value a.d a-c pickup will be increased. To set the time of a particular unit it is nec
essary to impose the desired conditions on the unit
and measure the time required to close the contacts
PICKUP SETTING with a standard timer. Adjust the time lever and
Pickup of the relay is adjusted before it leaves drag magnet until the desired time is obtained.
OPERATION
Before leaving the factory, the relays were the contacts all the way back to the time lever. This
tested and adjusted for correct operation. The only condition will cause no difficulty, however, because
adjustment which should be necessary is setting the as soon as the relay is energized with balanced
time lever, and if necessary, adjusting the drag currents of applicable magnitude the torque of the
magnet, for the correct time. restraint U—magnet will reset the contacts. As
noted before, the chief function of the spring is to
It may be that the control spring will not reset open the contacts when the relay is de-energized.
MAINTENANCE
The relays are adjusted at the factory and it is polishing action is so delicate that no scratches are
advisable not to disturb the adjustments. If for any left, yet corroded material will be removed rapidly
reason, they have been disturbed, the following and thoroughly. The flexibility of the tool insures
points should be observed in restoring them: the cleaning of the actual points of contact. Some
times an ordinary file cannot reach the actualpoints
DISK AND REARINGS of contact because of some obstruction from some
other part of the relay.
The lower jewel may be tested for cracks by
exploring its surface with the point of a fine needle. Fine silver contacts should not be cleaned with
If it is necessary to replace the jewel a new pivot knives, files, or abrasive paper or cloth. Knives
should be screwed to the bottom of the shaft at or files may leave scratches which increase arcing
the same time. A very small drop of General Elec and deterioration of the contacts. Abrasive paper
tric meter-jewel oil, or fine watch oil, should be or cloth may leave minute particles of insulating
placed on the new jewel before it is inserted. The abrasive material in the contacts and thus prevent
jewel should be turned up until the disk is centered closing.
in the air gaps, after which it should be locked in
this position by the set screw provided for this The buri-iishing tool described above can be
purpose. obtained from the factory.
CONTACT CLEANING CONTACT ADJUSTMENTS
For cleaning fine silver contacts, a flexible With the contacts open the stationary contact
burnishing tool should be used. This consists of a should be engaged with the adjusting screw and should
flexible strip of metal with an etched roughened deflect about 1/32 inch before it is stopped by the back
surface, resembling in effect a superfine file. The stop.
7
GEI-16375 Current Balance Relays Types JJC
TIME DIAL
SEAL- IN ELLM F NT
STETIONAI1Y
CONTACT LEFT- —
- CONTROL SPRING
SEAL-IN ELEMENT
STATIONAR1’ DISK
cONTAcT RI’HT
-
MAIN STATIONARY
DRAG MAGNET CONTACT ADJUSTING
SCREW
SEAL-IN ELEMENT
MOVING CONTACT /
ASSEMBLY - -
TOP PIVOT
CONTROL SPRING
ADJUSTING RING
MAIN STATIONA
BRUSH AND CONTACT
ASSEMBLY .—‘
-,
LOWEll JEWEL
RESTRAINING—
U-MAGNET
OPERATING
U-MAGNET
H
._OPERAT1NG
RESTRAINING —
COIL
COIL_
Front View
Fig. 5 (8007844) The Type IJC52A Relay Removed from the Case,
8
Current Balance Relays Types IJC GEI-16375
RENEWAL PARTS
It is recommended that sufficient quantity of est tales Office of the General Electric Company,
renewal parts be carried in stock to enable the specify quantity required, name of part wanted, and
prompt replacement of any that are worn, broken, give complete nameplate data, including serial num
or damaged. ber. If possible, give the General Electric Company
requisition number on which the relay was furnish
When ordering renewal parts, address the near- ed.
) I
4’
t1’
t -
LU
L.
T
jTp
i
S2-
rfr ti
-iinr i
51 I’OSL1 Ir1RIIU
0 flIMSRY -
3HFPl<I H
i’ (ONLJSLI.
II 1i
T
(,I C ORAL NI IIRLANCL ‘1
‘Ly IICS2A
, CL taTI%r RH - rrCI<OUT It LI-H. FIAIID RLSFI
ILLS 1111”’ C)1AC CLOSEt)
WHI N )LIRUII HAl AILL IF 5 1
f
II IRS IL
*SNDI’LS CLOI;lI)
N HURL AILS CONIALLI CLO.I I) 1LEL
L%SIN CIlFLr)JI I 11)11 HAt I) 1 (rIP S
I RIP COIL
I
IN rERNAL CONNEC lIONS (FRONT VIEW) = SHORT FINGER
T’PICAL €lERFLRL CtFItESIICFS
Fig. 6 (K-6154233-3) Typical External Connections Fig. 7 (K—6209675—2) Internal Connections for the
for the Type IJC52A Relay Type IJC52A Relay, Front View
INucTlOr
ELEMENT
0
P
‘1? 0
Al
TL
N
G
2
SHORT FINGER
INTERNAL CONNECTIONS (FRONT VIEW) =
View
Fig. 8 (K-6305896-J.) Internal Connections for the Type IJC52B Relay, Front
9
_
___
__
___
STUD
NUMBER I NO
20 312 p—--(6) 10—32 X 3/8
/ MTG, SCREWS
516MM
9753
0000 0
VI 00000 4
10 8 6 2
BACK VIEW
CUTOUTS MAY REPLACE
DRILLED HOLES
6 HOLES
6MM
— —
— —
14 CU TtIU T
500
12MM
(TYPICAL)
PANEL DRILLING
FOR SURFACE MOUNTING
PANEL DRILLING FRONT VIEW
FOR SEMI-FLUSH MOUNTING
FRONT VIEW
5/16—18 STUD
TYPICAL DIM,
INCHES VIEW
MM FOR
10
Current Balance Relays Types IJC GEl-i 6375
PANEL LOCATION
SEMI-FLUSH SURFACE (2) 5/16-18 STUDS
FOR SURFACE MTG,
:fI
8.375
- 212MM
2.2MM
:25 H (.1)
MTC
10—32
SCREWS
3/8 =- :i STUD
i- 10-32 NUMEER INC
i STUDS
V
97531
L_) )
10 2 C 4 3
125 BACK V2E
25MM MM
7
187
HL.L 157MM -— 76MM
MM -
5/8 DRILL
CUTOUT MA’ REPLACE
2 HOLES
DRILLED HOLES
I
2 87 .406 256
12MM 29MM
56MM
L
I
l72MMl .500
‘H 12MM
5.687 (TYPICAL)
144MM 3/4 DRILL
PANEL DRILLING 10 HOLES
FOR SEMI-FLUSH MOUNTING 19MM PANEL DRILLING
FRONT VIEW FOR SURFACE MOUNTING
FRONT VIEW
Fig. 10 (K—6?09271 181) Outline and Panel Drilling for the Type IJC52B Relay
11
GE Power Management
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222
Fax: (905) 201-2098
www.ge.comlindsyslpm