TECHNICAL QUERY SHEET

CONTRACTOR REFERENCE Offshore PRP7-RT Pipeline Replacement Project


ITEM Clean Agent System
VENDOR NAME SHM
VENDOR OFFER REFERENCE SHM/FSD/LTHE/PRPVII/21-22/227R1

BIIDDER'S OFFER BIDDER'S RESPONSES BIDDER'S RESPONSES


Sl. No. CLARIFICATION/ CONFIRMATION REQUIRED FROM BIDDER LTHE Response REMARK
REFERENCE TQ-1 RESPONSE TQ-2 RESPONSE
MECHANICAL
Technical Proposal
1 Design Calculation sheet Update area as per addendum 1. Bidder to confirm. Noted, please refer attached revised offer Noted.

2 Technical Offer Bidder to submit sign and stamped IRT for clean agent system. Enclosed. Noted.

Noted , NTE weight and dimension noted.


Bidder to ensure and confirm the weight and dimension of clean Cabinet dimension configuartion (Single
3 Technical Offer Noted, please refer attached revised offer Noted.
agent cabinet is Not to exceed. cylinder row or 2 cylinder row) will be decided
during Post order stage.

We have not received Forms along


Bidder to confirm compliance to code and standards and bid Confirm, offered system is inline with past Noted.Bidder to submit FORM-B with NIL
4 Technical Offer with tender document, please provide
specifications for clean agent system. NLRNC & NWISR project DEVIATION,
Form B
Scope of supply shall be inline with scope split of NLRNC (past
5 Technical Offer Confirm. Noted.
project supply.
Please note piping MTO is based on
the cylinder location, hydraulic
Noted. NLRNC piping MTO referred for similar
calculations & pipe routing. The
Bidder to provide preliminary Piping MTO for extended Switchgear room configuration for MTO consideration.
6 Technical Offer Piping MTO shall be provided post order piping MTO may or may not be
room. Bidder to ensure no change on the Piping
similar for same room configuration
MTO post order.
as cylinder location & pipe route will
not be exactly samilar.

TQ-2
Bidder to cosnider all spares, consumables,
7 Revised Technical Offer Intial fill and special tools and tackles required Noted & Considered.
under base scope.
Bidder to cionfirm the Electrical and Confirm. Offered clean agent system
8 Revised Technical Offer instrumentaion area classification as per is same as that of supplied for
Specification requirement. NWISR & HRPIII project

Please note cylinder painting shall be


Cylinder painting shall be as per ONGC spec as per manufacturer standard. Same
9 Revised Technical Offer
2005. is been followed in HRPIII & NWISR
project & accepted by ONGC