S 20478 1 RevA Design Calculations
S 20478 1 RevA Design Calculations
Sheet No.
TYPICAL UNDERHUNG SCAFFOLD ALONG
8.0M WIDE PIPERACK AT
VARIOUS ELEVATIONS
Drawing No.: Prepared
By: Checked By: Date: 1 of 15
Saudi Arabia S/20478/1 RevA RHS
EMK 16-Oct-17
Scaffold Design Calculations
Calculation Cover
Sheet
Objective
To provide analysis & calculations for the design of Typical Slung Scaffold
along Pipe Rack at Various Elevations
Calculation Method
Scaffold Design calculations shall be as per the Criteria laid down in Saudi
Aramco CSM II - 2 Scaffolding (October 2011)
All calculations are done in SI metric Units.
Design Criteria
Planks shall be checked for permitted spans as per manufacturer's
recommendation
Board Bearers shall be checked for Max. Bending & deflection caused due to
Load combination (DL+4LL)
Runners shall be checked for Max. Bending & deflection caused due to Load
combination (DL+4LL)
Hnager Tubes shall be checked for Max. Tensile caused due to Load combination
(4DL+4LL)
Plan Bracing
Couplers shall be checked
connecting for Max.
the various Axial forces
members caused
of the due to
scaffold Wind
shall beLoad
only. a Safety Factor 4.0 shall be considered on the SWL
checked,
of the couplers for Gravity Load Analysis & a Safety Factor of 1.6 shall be
considered for Wind Load Analysis of Bracing & Tie
members
Assumptions
* Steel Scaffold Tube of 48.3mm Outer diameter with 4mm wall thickness
conforming to EN 39 shall be used for all framing members of
Scaffold. The Minimum yield strength of the tube shall be 235 N/mm² with a
modulus of elasticity of 210,000 Mpa.
The maximum available length of the Scaffold Tube is 6.4m and is available in
different shorter lengths as per the job requirements.
A strength increase factor of 1.10 is considered over the minimum yield
strength of 235N/mm² for tubes, since the value of Minimum
Yield strength of the tube as per attached vendor test report and test
conducted by Independent testing company are greater than
430N/mm² í.e 82% higher (Refer to sheet no. X of the attached Material
datasheet and Test results).
* Scaffold Planks shall be LVL Laminated Veneer Lumber, 230mm wide and 38mm
thick.
The Safe Bending Capacity of Planks is 1.03 kN.m & EI = 15kNm as per the
manufacturer's datasheet determined in accordance with
ANSI A10.8 - 2001 (App C) (Refer to sheet no. X of the attached Material
datasheet and Test results).
* The scaffolding shall be checked for wind loading, in accordance with ASCE 7-
05 and the Saudi Aramco Scaffold Safety Handbook.
* The 3-second gust Basic Wind Speed as specified in SAES -A-112 for site
location for 10 year mean recurrence interval per ASCE 7-05
(Table C6-3) shall be considered.
* An Importance factor of 1.0 and Directionality factor of 0.95 shall be used.
* All Tributary wind areas shall be increased an additional 5% to allow for
fittings & overlaps.
* The wind load analysis shall be done for the worst case directions with the
largest projected area. The wind forces without any
shielding shall be applied to the entire Scaffold Structure including the
Toeboards, Handrails, Bracings, Ladder accesses etc.
* The worst case have been considered of wind direction during wind load
analysis.
O
í.e Wind direction 90 on the largest projected area í.e on section of
scaffold.
Design Parameters:-
Load Rating of scaffold = 1.2 kN/m²
Light Duty Scaffold
4
Radius of Gyration =
(OD² +ID²) = 15.73 mm
4
Scaffold Fittings: Conforming to EN 74
2
Weight = 0.06 kN/m
or 0.25 kN/m
W kN/m
A 1.444 B
Mf = SIF
x Fy x Z
The Values of Yield strength of the tubes as per vendor test report and test
where, SIF = Strength Increase Factor
= 1.1 conducted by Independent testing company are in excess of
430N/mm² which
is 82% higher than the minimum specified value hence a SIF of 1.1 is
considered.
= 7871.29 mm³
Therefore Moment = Mf =
1.1 x 235 x 7871.29
Mf =
2034729.33 Nmm = 2.03 kNm ---------------- Result I
SAFE
Design Check: Board Bearers (Walkway)
See sketh on sheet no. 3.
Maximum Span of Bearer =
1.000 m
Maximum Tributary Width of Bearer =
1.388 m
W kN/m
A 1.000
B
SAFE
Title
Sheet No.
TYPICAL UNDERHUNG SCAFFOLD
ALONG 8.0M WIDE PIPERACK AT
VARIOUS ELEVATIONS
Drawing No.:
Prepared By: Checked By: Date: 5 of 15
Saudi Arabia S/20478/1 RevA
RHS EMK 16-Oct-17
Scaffold Design Calculations
1.220
SAFE
5.22 m
x
0.043 kN/m Weight of scaffold tube per meter
0.22 kN
Allowing 5% extra for Tube over hang, Laps & fittings
Total Load of Tubes & fitting = 0.22 kN x
1.050 = 0.24 kN ------------------ D
2
Tributary area = 1.22 m x 1.45 m x
= 1.77 m
Weight of the Planks = Tributary area x Self weight of the Planks
= 1.77 m² x 0.25 kN/m²
= 0.44 kN ------------------ E
Live Load
Load Rating = 1.2 kN/m²
Total Live Load per Lift = Tributary area x Live Load
per m²
2
= 1.77 m² x 1.2
kN/m = 2.12 kN
The Runner is connected to the Post using a Right Angle Coupler Class B
SWL in Slip of 90O Coupler Class B = 9.4 kN (SWL as per Table 2.1 shall
be reduced to 40% to ensure a safety factor of 4.0)
Therefore, SWL in Slip of a Right Angle Coupler Class B =
9.4 x 0.4 = 3.76 kN
No. of Couplers available = 1
SWL of the connection in slip = 3.76 kN
x 1 = 3.76 kN with Safety factor of 4.0
P
Design Check: Rakers
Total Load (P) acting on the Raker = Self wt. of Tubes, Boards + Live Load
Self weight of Tubes
Tubes length Nos.
Total
Rakers 1.20 m x
1 nos. = 1.20 m
Runners 1.22 m x
1 nos. = 1.22 m
Board Bearers 0.50 m x
2 nos. = 1.00 m
Lacing Tubes 0.50 m x
2 nos. = 1.00 m
4.42 m
(Weight of scaffold tube per meter)
x 0.043 kN/m
0.19 kN
2
Tributary area per Raker = 1.22 m x 0.50 m
= 0.61 m
Load due to Planks on boarded Lift = Tributary area x Self
weight of the Boards x No. of Lifts
= 0.61 m² x
0.25 kN/m² x 1 = 0.15 kN ------------------ G
Live Load
Live load on Planks on Fully planked levels: Access
Loading = 1.2 kN/m²
2
Tributary working lift area per Raker = 2.75 m x
0.34 m = 0.94 m
Total Live Load per Lift = Tributary area x Live Load per m² x
No. of working Lifts
2
= 0.94 m² x 1.2 kN/m x
1 no. = 1.12 kN
Load in raker =
P = 1.47 = 2.08 kN
sin
45o sin 45o
Title
Sheet No.
TYPICAL UNDERHUNG
SCAFFOLD ALONG 8.0M WIDE PIPERACK AT
VARIOUS ELEVATIONS
Drawing No.:
Prepared By: Checked By: Date: 7
of 15
Saudi Arabia S/20478/1 RevA
RHS EMK 16-Oct-17
Scaffold Design Calculations
=
0.01573
2
where, E = Modulus of Elasticity
= 210,000 N/mm
2 Properties of EN 39 tubes
Fy = Minimum Yield Strength
= 235 N/mm
SIF = Strength increase factor
= 1.1 The Values of Yield strength of the tubes as per vendor test
KL
for < CC
r
Fa = (1- (KL/r)2 ) x
Fy x SIF -------- Equation 1
2(CC)2
KL
for > CC
r
Fa = (3.142)2 E
-------- Equation 2
(KL/r)2
(KL/r)2
2
= 3.142
x 210000 = 128.242 N/mm2
127.15 2
Ag= Cross sectional Area of Scaffold Tube
= 556.7624 mm2 for scaffold tube
with 4.0mm wall thickness & 48.3 mm OD
Axial compressive Pf = Ag x Fa
2
capacity of Tube = 556.76 mm
x 128.242 N/mm2
= 71400.13 N
= 71.40 kN
Factored Capacity Pf 4 4 =
71.40 kN = 17.85 kN ---------------- Result II
of 2.0 m Tube
4 with safety factor 4.0
Center Point Load, SWL (for 6.1m Span Ladder Beam) as per page X of
Manufacturer Data Sheets & Test Certs. = 10.36 kN
Allowed Maximum Deflection shall not exeed 1/60 of the span length (as per
CSM II-2, section 2.5.1 I).
SAFE
Title
Sheet No.
TYPICAL UNDERHUNG SCAFFOLD
ALONG 8.0M WIDE PIPERACK AT
VARIOUS ELEVATIONS
Drawing No.:
Prepared By: Checked By: Date: 11 of 15
Saudi Arabia S/20478/1 RevA
RHS EMK 16-Oct-17
Scaffold Design Calculations
Maximum Capacity BM at the joint is limited by the tension in the bottom boom
mm
Max.
Permissible Tensile Load in
Max. Load in Hanger tube
Scaffold Tube
16.40 kN <
78.50 kN Therefore Hanger Tubes are
With Safety Factor 4.0
SAFE
Design Check: Hanger Tube Connection to Horizontal Tube
Load (P) acting on the Short Tubes = End reaction from the Horizontal Tubes =
16.40 kN
SAFE
Title
Sheet No.
TYPICAL UNDERHUNG SCAFFOLD
ALONG 8.0M WIDE PIPERACK AT
VARIOUS ELEVATIONS
Drawing No.:
Prepared By: Checked By: Date: 13 of
15
Saudi Arabia S/20478/1 RevA
RHS EMK 16-Oct-17
Scaffold Design Calculations
The short Tubes are connected to the Steel Beam Using a pair of Girder
Couplers
Calculation of Wind
Loads for Bracing.
All the Bracing shall be designed purely for Wind Load only.
Assumption:
1) The scaffold is completely unsheeted.The wind pressure on the scaffold shall
be in accordance with ASCE 7-05
2) The worst case for wind analysis is assumed to be when the direction of wind
incident normal to the maximum projected area of the
scaffold with no wind shielding considered.
3) It is assumed that no gravity loads are transmitted through the bracing hence
we shall design Bracing purely for Wind Loads only
4) Tributary Area shall be increased by 5% for fittings & overlaps etc.
Calculations:-
V= Basic Wind Speed = 165 kph = 45.83
m/s (Jizan Area)
As per the revised recommendations of CSM II-2 Scaffolding, the wind speed
for 10 years MRI as per ASCE 7-05 can be used.
Conversion factor for 10 years MRI as per ASCE 7 -05 (Table C6-3) =
0.84
Hence, Wind Velocity = 45.83 m/s
x 0.84 = 38.50 m/s
2
Kz at 24.4.m from grd = 1.210 24.4
1.210 1.0 0.95 38.50 1.0 1.044
kN/m²
9.03 m²
Ladder Beam length Qty
Dia Area
Chords/Booms 6.00 x 10 x
0.0483 = 2.90 m²
Rungs/Steps 0.305 x 100 x
0.0483 = 1.47 m²
4.37 m²
5.03 kN
Max Axial load in each Transverse Brace = 5.03 kN 4 Sin
42O
= 7.52 kN
Plan Brace
Factored Capacity of 2.0m Tube = 17.85 kN
P < Pf / 4
42O
7.52 kN < 17.85 kN Therefore the Plan Bracing
are
SAFE
SAFE