FSV VRF SYSTEMS

2018 / 2019

We face a time in which “quality air” differentiates business. It’s a time for Panasonic to fully display
its strengths. Our ability to assemble and build superior systems isn’t just due to the rich resources
we have as a comprehensive electronics manufacturer, but also to Panasonic’s 100 years of
tradition, where each person thinks and acts on their own initiative while working in a team to reach
further heights. We do not compromise. Each of our independent selves is a one stop solution. We
face our customers’ challenges together with our customers and do all that we can to build effective
systems. As a true partner for our customers, we strive to always be at the forefront of business.

Please read the Installation Instructions carefully before installing the unit,
and the Operating Instructions before using it. Authorised Dealer
Specifications are subject to change without prior notice.
The contents of this catalogue are accurate as of JULY 2018.
Due to printing considerations, the actual colours may vary slightly
from those shown.
All graphics are provided merely for the purpose of illustrating a point.
Residential & Light Commercial Use
Commercial Use
Do not add or replace refrigerant other than the specified type.
Manufacturer is not responsible for the damage and
deterioration in safety due to usage of other refrigerant.

FSV Mini FSV ID, TH, OM, JM_JULY 2018

Panasonic Global Air Conditioner


Global Site : aircon.panasonic.com
PROClub : panasonicproclub.global

airconpanasonicglobal

180730_FSV_ASIA_D_2.indd 4-5 2018/10/12 14:37:28


THE
GAME
CHANGER

VRF with Extraordinary Energy-Saving


Performance and Powerful Operation
EER 5.3 (U-8ME2H7)
A game-changing VRF system delivering energy-saving performance, In the case of U-8ME 2H7
powerful operation, reliability and comfort surpassing
anything previously possible. CONTENTS
It represents a true paradigm shift in air conditioning solutions.
02 FSV-EX Introduction 54 FSV Indoor Units Range 94 VRF Smart Connectivity+
Taking quality to the extreme — that's the Panasonic challenge. 04 Mini-FSV Introduction 56 F2 Type / Mid Static Ducted 102 FSV Controllers
06 FSV-EX Advantages 60 M1 Type / Slim Low Static Ducted 104 Individual Control Systems
08 FSV-EX Series / Exclusive Feature 1 62 Z1 Type / Slim Low Static Ducted Twenty Series 107 Timer Operation
Extended Operation Range 64 E2 Type / High Static Ducted 108 Centralised Control Systems
10 FSV-EX Series / Exclusive Feature 2 66 E2 Type / Energy Saving High Fresh Air Ducted 112 P-AIMS
Energy-Saving Performance 68 E1 Type / High Static Ducted 114 T10 Terminal for External Control
12 FSV-EX Series / Exclusive Feature 3 70 H1 Type / High-Fresh Air Ducted 115 Interfaces for External Control
Oil Management System 72 K2 Type / Wall Mounted 116 Serial Interface for 3rd Party External Controller
14 ECONAVI 76 U2 Type / 4-WAY Cassette 117 Serial Interface for LonWorks Network
16 Exclusive Feature / High-spec Wired Remote Controller 80 Y2 Type / 4-WAY Mini Cassette 118 FSV Controller External Dimensions
20 Exclusive Feature / Air Handling Unit Kit 82 L1 Type / 2-WAY Cassette 120 VRF Renewal
24 Exclusive Feature / Design Support Software for FSV 84 D1 Type / 1-WAY Cassette 124 A Globally Trusted Air Conditioning Brand
26 FSV Systems 86 T2 Type / Ceiling Mounted 126 Reliability and Durability
28 2-WAY FSV-EX ME2 Series 88 P1 Type / Floor Standing 128 Global Networking of Air Conditioning Solutions
44 2-WAY Mini-FSV LE Series 90 R1 Type / Concealed Floor Standing 130 Panasonic VRF Global Project References
Multiple large-capacity Enlarged heat Newly designed curved
all inverter compressors exchanger surface air discharge bell mouth 52 Indoor Units 92 Remark for High Static Ducted Series
(more than 14HP) area with triple surface for better aerodynamics
* For 8 & 10HP unit, the heat exchanger
is 2 row design.
2 3

180730_FSV_ASIA_D_2.indd 2-3 2018/10/12 14:37:29


MINI
4.20
LE1 Series
*

GAME EER

CHANGER
* In the case of 8HP

Mini VRF LE Series


Cooling & Heating Type 8/10 HP [LE1] 4/5/6 HP [LE2]
Mini-FSV with Extraordinary Energy-Saving Performance and High
External Static Pressure(35Pa)

High External Static Compact Design Long Piping Design


Pressure 35Pa Length forGreater
Design Flexibility

5.08
LE2 Series
*
Actual piping
length 150m Height
[ LE 1 ] (equivalent piping difference
1,330mm length 175m) 50m*1
[ LE 2 ]
996mm
Level difference
between indoor
units 15m
980mm 370mm
LE1 Max. total piping length: 300m
LE2 Max. total piping length: 180m
*1: 40m if the outdoor unit is below the indoor unit. EER
* In the case of 4HP

4 5

180730_FSV_ASIA_D_2.indd 4-5 2018/10/12 14:37:43


FSV-EX Advantages

The most efficient, powerful and quiet system in Panasonic's history.


There has never been a VRF system like it.
It’s the story of a true game changer.

Low-Noise Operation
Numerous technological FSV-EX (ME2)
63.0 FSV (ME1)
innovations, including an
Extraordinary
62.0
61.0
improved compressor and a 60.0

newly designed bell mouth and 59.0

Energy-Saving larger fan, have dramatically


58.0
57.0
56.0
reduced the outdoor noise
Performance
55.0
54.0
level. The result is an even 53.0

more comfortable building


The FSV-EX marks a revolutionary step forward in VRF environment.
efficiency. A look at the incredible EER value clearly
indicates that. What's more, this high EER value is
achieved even during part load operation.
This shows the extraordinary energy-saving performance

Multiple large-capacity
the FSV-EX is capable of providing.

COOLING
6.0 all inverter compressors
5.5 5.30 (more than 14HP)
5.03
5.0 4.73
4.56 Two independently controlled
4.5
4.04 4.13 4.10 inverter compressors achieve
4.0 3.76 high efficiency. Redesigned
3.60 3.61 3.60 3.50
3.5 3.36 3.33 components in the body provide
3.0 performance improvement
8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP
especially in the rated cooling
FSV-EX ME2 series FSV ME1 series
condition and EER performance.

Enlarged heat exchanger surface area


Extended Operation Range Up to 52°C
The FSV-EX can provide cooling even when the outside
with triple surface*
Outside air temperature ˚C (DB)
temperature reaches a maximum of about 52°C. -10 0 10 20 30 40 46 50 The new heat exchanger features a triple-surface construction.
52˚C
And amazingly, it can still operate at 100% capacity when Compared to the divided dual-surface construction in current
the outside temperature is as high as 43°C. FSV-EX (ME2) models, there is no division of space and the area for heat exchange
This high power capability enables reliable operation even is larger. Also, highly efficient piping pattern increases heat exchange
FSV (ME1)
under extremely high temperature conditions. performance by 5%.

* For 8 & 10HP unit, the heat exchanger is 2 row design.

6 7

180730_FSV_ASIA_D_2.indd 6-7 2018/10/12 14:37:48


FSV-EX Series Exclusive Feature 1

Extended Operation Range


up to 52˚C

High reliability even under high temperature conditions Full-capacity Operation up to 43°C
Designed to be durable enough to withstand extreme heat, FSV EX ensures reliable cooling operation The FSV-EX can provide cooling even when the outside temperature reaches a maximum of about 52°C.
over an extended operation range up to 52˚C. And amazingly, it can still operate at 100% capacity when the outside temperature is as high as 43°C.
This high power capability enables reliable operation even under extremely high temperature conditions.

OPERATING RANGE CAPACITY RATIO (COOLING) FSV-EX (ME2)


Competitor A
100% capacity up to 43˚C
Cooling
52˚C 100

Cooling Capacity Ratio (%)


-10 0 10 20 30 40 46 50

85% capacity at 46˚C


80
FSV-EX (ME2)
60
FSV (ME1)
40
Outside air temperature ˚C (DB)

20
Heating -25 -20 -15 -10 -5 0 5 10 15 18˚C
-25˚C FSV-EX (ME2) 18˚C
30 35 40 43 45 50 52˚C 55
Outside air temperature ˚C (DB)
-25˚C FSV (ME1) 15˚C

Outside air temperature ˚C ( WB) <Test Condition> 12HP model, IU/OU capacity ratio:100%, Indoor Condition:27oC[DB]/19oC[WB]
Competitor A spec is from technical data book.

8 9

180730_FSV_ASIA_D_2.indd 8-9 2018/10/12 14:37:49


FSV-EX Series Exclusive Feature 2

Extraordinary Energy-Saving
Performance

Practical Design for Actual Operation 1. Set temperature is rapidly attained; full-load operating time is kept to a minimum.

Panasonic builds air conditioning systems not only with a high EER for rated operation, but also 2. The frequency of forced oil recovery is minimised. The volume of oil within the compressors is
with Seasonal-EER appropriate to the customer’s actual environment of use. For instance, with rated monitored precisely by sensors, so forced oil recovery under full-load operation is conducted
operation, outdoor temperature is constant at 35oC, but in reality the outdoor temperature is continuously only when necessary. Since this suppresses noise due to oil recovery, comfort is maintained.
changing. Consequently, required air conditioning performance also changes. That’s why Panasonic 3. Panasonic pursues a high EER, of course, as well as high EER in part load, for energy saving
implements the following kind of proprietary control. performance under a broad range of loads.
Panasonic’s design concept contributes to substantial energy cost reductions.

Rapidly reaches set temperature


full-load operation duration minimised

Set temperature maintained


with minimum load operation

Thanks to superior oil


management, oil recovery is
minimised, contributing to
reduced energy use and
costs

Load increased as required for a given


outdoor temperature increase to
maintain the set temperature

Actual performance data of When outdoor temperature


drops, operation is
Panasonic FSV installed in Asia immediately stopped
Simulated conditions
Location: Panasonic building in Malaysia System: One 16HP outdoor unit, 4 cassette-type indoor units

10 11

180730_FSV_ASIA_D_2.indd 10-11 2018/10/12 14:37:53


FSV-EX Series Exclusive Feature 3

Intelligent 3-stage
Oil Management System

In a VRF system, where lengthy piping and a large number of indoor units need to be controlled collectively, Features of 3-stage oil recovery design
the key to maintaining the system’s reliability is to ensure an appropriate amount of oil is secured in the
compressors. In order to avoid oil shortage in the compressor, maximum operation is normally forcibly
conducted at regular intervals to recover oil from indoor units. This method, typically employed in a standard Oil sensors installed in each compressor
VRF, causes the system to overheat or overcool and thus waste energy. 1 Oil sensors installed in each Panasonic compressor precisely monitor oil levels, eliminating
In Panasonic VRF systems, a sensor for detecting oil levels is mounted in each compressor. In installations unnecessary oil recovery.
with multiple outdoor units, a shortage of oil in one compressor can be compensated for by recovering oil
either from another compressor in the same unit, from a compressor in an adjacent outdoor unit, or from a
connected indoor unit. Panasonic VRF systems provide users with a comfortable environment whilst saving
In Panasonic VRF systems, a
energy.
sensor for detecting oil levels is
installed in each compressor.
The Panasonic system efficiently manages oil recovery in three stages; minimising
the frequency of forced oil recovery while reducing energy cost and maintaining comfort.

STAGE-1
Panasonic compressors are equipped with
sensors which monitor oil levels precisely
at all times. If oil levels fall, oil can be
transferred from other compressors within
Minimum oil level
the same outdoor unit.
(surface of rotary cylinder)

Highly functional oil separator


STAGE-2 2 Thanks to extended separate piping, oil recovery efficiency reaches 90%,
minimising the oil to be discharged from the compressor.
If oil levels in all compressors within the
outdoor unit fall, oil can be replenished
from adjacent outdoor units.

STAGE-3
Forced oil recovery is implemented only
if oil levels become insufficient in spite of
above measures. The Panasonic system’s
design concept is radically different from
conventional oil systems.

12 13

180730_FSV_ASIA_D_2.indd 12-13 2018/10/12 14:37:54


ECONAVI Detects Inefficiencies
and Saves Energy

Remote ECONAVI sensor allows 4-Way Cassette

optimum energy operation Twenty Duct

Pillars, walls, cabinets and other fittings obstruct the sensor, Mini Cassette
reducing the area of detection and lowering the energy-saving
Thorough cooling
effect. Taking into consideration blind spots, Panasonic
in areas of high activity
enables the optimum layout for sensors in any office. Mid Static Duct
Wall-Mounted
1m 3m 5m 7m
Wide detection area
-60° 60°
Ceiling
40°
-40°

-20° 20° ECONAVI sensor



Wide 120° CZ-CENSC1
Panasonic enables use with various types

2.5m
Gentle cooling in areas of indoor units
of low activity Detection area
Approx 1m Providing outstanding energy-saving performance,
Panasonic's inverter VRF System can be connected to
Dead Zone
7m ECONAVI to detect when energy is being wasted. ECONAVI
senses the presence or absence of people and the level of
A sensor is remotely set to maximise the detection area. activity in each area of an office. When unnecessary heating
or cooling is detected, indoor units are individually controlled
Installation flexibility ready for indoor unit replacement to match office conditions for energy-saving operation.
and layout changes.

Detection of the level of


activity enables precise ECONAVI VRF Field Test
power saving.
Presence or absence of people at their desks and Indoor units (12)
7F
the level of activity in the office are detected in real In the morning In the afternoon At night Sensors (12)
time. Set temperature is automatically adjusted to Thorough cooling when Reduced cooling when Automatic Thermo Off DOCUMENT DOCUMENT
RM.4 RM.3 Trial term: 11 Apr - 16 May 2014
there is a high level of there are fewer people depending on
DOCUMENT DOCUMENT
RM.2 RM.1
Location: Panasonic Malaysia Building
optimise the lower power consumption. activity conditions at the end of Office floor: Cooling capacity 112kW
the day* 1 MEETING ROOM 4
Testing conditions:
2 ・Remote controller setting temperature 23˚C
3 ・Setting time AM7:00~PM21:00
Units used Panasonic Malaysia Building Outdoor units on the roof

Human activity and presence detection System Outdoor unit Indoor unit
SALES DIRECTOR 1 S-106MU1E5
1 2 S-106MU1E5
Activity detection Presence detection CU-L7-6
U-20ME1E8
3 S-106MU1E5
4 S-106MU1E5
5 S-56MU1E5
HIGHER ACTIVITY LOWER ACTIVITY After 20 mins absence After 3 hours absence 6 S-106MU1E5
2
U-20ME1E8 7 S-106MU1E5
CU-L7-7
8 S-56MU1E5
Cooling Set Temp. +/-0°C Cooling Set Temp. +1°C Cooling Set Temp. +2°C Cooling Thermo OFF* 9 S-106MU1E5 Sensor
MANAGER 6 10 S-106MU1E5 installation example
3
U-14ME1E8 Interior of the office
GENERAL MANAGER 2
11 S-56MU1E5
CU-L7-7
12 S-106MU1E5
Heating Set Temp. -1°C Heating Set Temp. +/-0 °C Heating Set Temp. -2°C Heating Thermo OFF*

Every 2 min Every 2 min After 3 hours the setting can change to Stop

15%
or Temperature Shift Power consumption Without ECONAVI
Up to Energy-saving effect
energy saving tested and verified
With ECONAVI by Field test
*Depending on conditions, the setting can change to Switch Off After 3 Hours, Thermo Off or Temperature Shift.

14 15

180730_FSV_ASIA_D_2.indd 14-15 2018/10/12 14:38:00


Exclusive Feature

High-spec Wired
Remote Controller

Multiple control settings to meet a wide range of air conditioning needs

Temperature Auto Return


Even if you change the temperature setting, after a set time it
automatically returns to the original temperature setting. You can set
temperature auto return time in 10-minute intervals within a period of 4
hours.

Temperature Setting Range


You can set the upper and lower temperature limits. Doing this helps
reduce power consumption due to over cooling or heating. Setting is
possible in the Cooling, Heating and Dry modes.

Auto Shutoff
Air conditioning automatically stops after a set time, so you don’t have
to worry about forgetting to switch the unit off. Even if you manually
switch the unit back on after it has stopped, it automatically switches
off again after the set time.

Wide range of controls for extra convenience

CZ-RTC5B Actual size Individual Louver Control


(Lock individual flap only for 4-way cassette U1 type)
Each of the 4-directional outlets can be selected and locked to provide
efficient air distribution that matches the indoor unit layout. Indoor units
can be set individually.

Weekly Timer
Large 3.5" Full-dot LCD with Stylish, Easy-to-use This lets you specify 8 Start/Stop times and temperature presets for
each day of the week.
White LED Backlight Touch Key Design
Characters and icons are The elegant, flat design
clearly displayed for features large touch keys in
improved visibility. The a simple layout enabling
display is also large enough easy, intuitive operation. Service Contact Address
to provide a wide range of
Once you have register service contact details, they are automatically
information for easy
displayed if a problem with the air conditioner occurs. This helps you
confirmation of operation
quickly deal with the situation.
conditions.

16 17

180730_FSV_ASIA_D_2.indd 16-17 2018/10/12 14:38:03


Convenient Controls Function List

Operation Lock Maintenance Function


Controllability
To prevent operation by anyone Display of outdoor malfunction Control Item
”A-B”model Non”A-B”model
other than the supervisor, data, service contact details,
operation keys can be locked. filter cleaning remaining time and Basic instructions
This prevents unauthorized other data enables at-a-glance FLAP
personnel from changing verification of maintenance
information with the remote Individual louver control (Lock individual flap only for 4-way cassette U2 type)
temperature settings, airflow
rate, airflow direction and other controller. ON/ OFF timer
settings. Weekly timer
Filter information
Menu items
Repeat OFF Timer Outing function
Filter Information
You can stop the operation after
Quiet operation mode
Filter information is indicated for
cleaning after a set time of a certain period of time each Energy saving
operation period has past. The time operation is performed. Initial settings
number of hours can be
Ventilation
adjusted.
Temperature auto return
Temperature setting range
Quiet Operation Mode Setting Lists Auto shutoff
Energy Saving
There’s a Quiet mode that Information concerning Schedule peak cut
reduces the outdoor unit’s current settings is displayed
Repeat off timer
operating noise. The mode can in the remote controller’s LCD
be switched On/ Off and Start/ for easy confirmation. ECONAVI on/ off
End times can be set. Outdoor unit error data
Service Contact address
RC setting mode
Maintenance Test Run
Function Sensor Information
Service check
Simple/ Detailed Settings
Auto address

18 19

180730_FSV_ASIA_D_2.indd 18-19 2018/10/12 14:38:04


Exclusive Feature

Air Handling Unit Kit


AHU Kit connects FSV-EX and FSV outdoor units to Air Handling Units System

AIR HANDLING UNIT Kit to connect to your ventilation system

AHU Connection Kit


PCB, Power trans, Remote control can be Expansion Thermistor x2 Thermistor x2
Terminal block easily installed on the valve (Refrigerant: E1, E3) (x1 in PACi) (Air: Tf, Tb)
AHU Kit box.
(Remote control must be
purchase separately.)

If you require this


fresh air solution,
please contact an
Optional Remote controller
authorized Panasonic
distributor. Timer remote controller.
CZ-RTC4

Connect Air Handling Unit to your FSV-EX and FSV systems


for a high efficiency operation. Optional parts: Following functions are available by
Application: Hotels, offices, server rooms or all large buildings where air quality
control such as humidity control and fresh air are needed.
using different type of control accessories:

CZ-RTC4 Wired remote controller Technical Zoom


• Operation-ON/OFF • Max. piping length: 100m (actual)/ 120m (equivalent)
• Mode select • Difference between longest and shortest piping from first
• Temperature setting branch: 10m
* Fan operation signal can be taken from the PCB. • Max. length of branch tubing: 12m
* Other conditions to be referred the standard piping design
T10 terminal regulations.
• Input signal= Operation ON/OFF • Available temperature range in Heating: -20 °C (WB)~15 °C
• Remote controller prohibition (WB)
Fan operation signal • Output signal= Operating-ON status • Available temperature range for the suction air at AHU Kit:
• Alarm output (by DC12 V) Cool: 18~32 °C / Heat: 16~30 °C
OPTION terminal, DC12V outlet CZ-280MAH1 // CZ-560MAH1
Gas temperature • Output signal= Cool / Heat/Fan status • The system controlled by the suction air (or return air from
28 kW • Defrost room) temperature as same as standard indoor unit.
H/E Fan motor
Liquid temperature control PCB
• Thermostat-ON (Selectable mode: Automatic / Cooling / Heating / Fan / Dry
CZ-280MAH1 CZ-CAPBC2 Seri-para I/O unit for each indoor unit (but same as Cool)
MOV 56 kW • Temperature setting by 0-10 V or 0-140 Ω input signal • The discharge air temperature is also controlled to prevent
H/E
• Room (inlet air) temp outlet by 4-20 mA too-low air discharge in Cooling or too-high air discharge in
• Mode select or/and ON/OFF control Heating. (in case of VRF system)
CZ-560MAH1
• Fan operation control • Demand control (Forcible thermostat-OFF control by
14 HP 16 HP 18 HP
56 kW
H/E • Operation status output/ Alarm output operating current)
Inlet temperature • Defrost operation signal, Thermo-ON/OFF states output
Gas tube CZ-560MAH1
• External target temperature setting via Indoor/Outdoor signal
Outlet temperature interface is available with CZ-CAPBC2. (Ex. 0 – 10 V)
O_U / I_U communication • Connectable with P-LINK system
Liquid tube

20 21

180730_FSV_ASIA_D_2.indd 20-21 2018/10/12 14:38:07


System and regulations. System overview Project References

A: A  HU Kit controller box (with control PCB) Office Residential + Commercial


B: AHU equipment (Field supplied) Hong Kong Red Cross Headquaters Malaysia Utropolis, Glenmarie
C: Remote controller (option parts)
D: Outdoor unit
E : Gas piping (Field supplied)
F : Liquid piping (Field supplied)
G: Electronic expansion valve
H: Thermistor for Gas pipe (E3)
I : Thermistor for Liquid pipe (E1)
J : Thermistor for Suction air (TA)
K : Thermistor for Discharge air (BL)
L : Inter unit wiring
M: Magnetic relay for operating the blower
(Field supplied)
Air Conditioning System: Air Conditioning System:
VRF 2-way FSV ME1 series: VRF 2-way FSV ME1 series:
2 systems 29 systems
Indoor Units: 2 units Indoor Units: 168 units
AHU Kit: 6 units AHU Kit: 9 units
Cooling Capacity: 28O kW / 80 USRT Cooling Capacity: 3,077 kW / 875 USRT

AHU Connection Kit / System Combination AHU Connection Kit / System Combination
Capacity (HP) Outdoor unit combination AHU kit combination
22.4 kW (8 HP) U-8ME2H7 CZ-280MAH1
28.0 kW (10 HP) U-10ME2H7 CZ-280MAH1
33.5 kW (12 HP) U-12ME2H7 CZ-560MAH1
40.0 kW (14 HP) U-14ME2H7 CZ-560MAH1
45.0 kW (16 HP) U-16ME2H7 CZ-560MAH1
50.0 kW (18 HP) U-18ME2H7 CZ-560MAH1
56.0 kW (20 HP) U-20ME2H7 CZ-560MAH1
61.5 kW (22 HP) U-10ME2H7 U-12ME2H7 CZ-560MAH1 CZ-280MAH1
68.0 kW (24 HP) U-12ME2H7 U-12ME2H7 CZ-560MAH1 CZ-280MAH1
73.0 kW (26 HP) U-10ME2H7 U-16ME2H7 CZ-560MAH1 CZ-280MAH1
78.5 kW (28 HP) U-12ME2H7 U-16ME2H7 CZ-560MAH1 CZ-280MAH1
85.0 kW (30 HP) U-14ME2H7 U-16ME2H7 CZ-560MAH1 CZ-280MAH1
90.0 kW (32 HP) U-16ME2H7 U-16ME2H7 CZ-560MAH1 CZ-560MAH1
96.0 kW (34 HP) U-14ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1
101.0 kW (36 HP) U-16ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1
107.0 kW (38 HP) U-18ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1
113.0 kW (40 HP) U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1
118.0 kW (42 HP) U-10ME2H7 U-16ME2H7 U-16ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
2-WAY FSV-EX ME2 Series
124.0 kW (44 HP) U-12ME2H7 U-16ME2H7 U-16ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
(Space-saving Combination)*
130.0 kW (46 HP) U-14ME2H7 U-16ME2H7 U-16ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
135.0 kW (48 HP) U-16ME2H7 U-16ME2H7 U-16ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
140.0 kW (50 HP) U-14ME2H7 U-16ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
145.0 kW (52 HP) U-16ME2H7 U-16ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
151.0 kW (54 HP) U-14ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
156.0 kW (56 HP) U-16ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
162.0 kW (58 HP) U-18ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
168.0 kW (60 HP) U-20ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
174.0 kW (62 HP) U-14ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
180.0 kW (64 HP) U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
185.0 kW (66 HP) U-10ME2H7 U-16ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
190.0 kW (68 HP) U-12ME2H7 U-16ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
196.0 kW (70 HP) U-10ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1
202.0 kW (72 HP) U-16ME2H7 U-16ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
208.0 kW (74 HP) U-16ME2H7 U-18ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
213.0 kW (76 HP) U-16ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
219.0 kW (78 HP) U-18ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
224.0 kW (80 HP) U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1
*These are combination examples for space-saving combination. These combinations are also compatible for high efficiency models on page 34-35.

22 23

180730_FSV_ASIA_D_2.indd 22-23 2018/10/12 14:38:08


Exclusive Feature

Design Support
Software for FSV

Features the unique Mounting Scheme function providing The Panasonic VRF Designer software can be used
more thorough spec-in and tender quotation support for easier,
for all Panasonic FSV and FSV-EX ranges
faster completion of work.

Panasonic has identified the importance of ever-increasing demands for fast and accurate
responses to customer requests in our industry. More and more emphasis is being placed upon
energy-efficiency in our marketplace. The ability to calculate cooling/heating loads and produce
information of actual design conditions is a major advantage to any architect, consultant,
contractor or end user.
Panasonic understands the time-poor and demanding industry we are in and we are pleased to
announce the launch of the next generation of our system design software program.
The Panasonic VRF Designer software has been customised to make the selection and design
process as quick and easy as possible.
The design package utilises system wizards and import tools to enable both simple and complex
systems to be created. In addition, the system will allow outdoor and indoor units to be dragged
on an interactive desktop. This allows users to create everything from realistic floor plans
with detailed piping and wiring schematics to send out with quotations, through to installation
guidance drawings.

Features include
• Mounting scheme
Design selection from building
floor drawing.
• Any kind of drawing format.
(dxf, jpg, png..etc.)
• Conventional principal scheme.
• Easy to use system wizards.
• Auto piping and wiring
features.
• Converted duties for
conditions and pipework
• Auto(CAD) [dxf], Excel and
PDF export.
• Detailed wiring and pipework
diagrams.
• Automatic price quotation.
• Automatic tender document
assist.

24 25

180730_FSV_ASIA_D_2.indd 24-25 2018/10/12 14:38:10


FSV Systems
FSV systems are designed for energy savings, high efficiency, and high durability with strong
cooling power even operating at high ambient temperature.
Panasonic continuously apply advanced technologies to meet the requirements of diverse
situations and contribute to the creation of comfortable living spaces.

2-WAY FSV-EX ME2 Series 2-WAY Mini-FSV LE2 Series NEW (3-phase)
Extraordinary energy-saving performance and powerful operation For small-scale commercial and residential use

Cooling or Heating Type 1/3-phase 4/5/6 HP


Space-saving Combination Model
• High external static pressure 35Pa
• Wide operation range: Cooling: -10°C to 46°C DB, Heating at: -20°C to 18°C WB
Cooling or Hi-Durability • Refrigerant chargeless up to 50m
Heating Type Model • Extraordinary energy saving: 5.08* EER for 4HP model
• Demand response (Peak cut) by optional parts.
• Wide range of systems from 8HP to 80HP • Maximum number of connectable indoor units : 9*
• Class-leading EER of 5.3 (for 8HP model) • Diversity ratio 50-130%
• Industry-leading low noise of 53.0 DB (8HP model) • DC inverter technology combined with R410A for excellent efficiency
• Cooling operation possible with outdoor temperature as high as 52˚C (DB) • Demand response (Peak cut) by optional parts.
• Long maximum pipe length (up to 1,000 m) • One ampere starting current
• Up to 64 indoor units connectable • Full range of indoor units and control options
• External static pressure of 80 Pa • Auto restart from outdoor unit
• Extended operating range allows heating with outdoor temperatures as low as • Hi-durability outdoor unit model is available.
-25˚C (WB) • Suitable for R22 renewal projects
• Suitable for R22 refurbishing projects
* 6 HP only; 4 HP for 7 units, 5 HP for 8 units.

High Efficiency Combination Model


Cooling or Hi-Durability 2-WAY Mini-FSV LE1 Series
Heating Type Model
For small-scale commercial and residential use
• Wide range of systems from 8HP to 64HP
• Class-leading EER of 5.3 (for 8HP model)
• Higher EER than the Space-saving Combination Model
e.g., a combination of two 10HP units delivering 20HP reduces compressor load.
Cooling or Heating Type 3-phase 8/10 HP

• High external static pressure 35Pa


• Wide operation range: Cooling: -10°C to 46°C DB, Heating at: -20°C to 18°C DB
• Maximum number of connectable indoor units : 13
• Diversity ratio 50-130%
• DC inverter technology combined with R410A for excellent efficiency
• Actual piping length: 150m (Total piping length: 300m)
• System difference of elevation:50m /40m (outdoor above/below)
• Difference in elevation between indoor units:15m
• Demand response (Peak cut) by optional parts.
• One ampere starting current
• Full range of indoor units and control options
• Auto restart from outdoor unit
• Hi-durability outdoor unit model is available.
• Suitable for R22 renewal project

26 27

180730_FSV_ASIA_D_2.indd 26-27 2018/10/12 14:38:17


High-efficiency & Space-saving VRF system

2-WAY FSV-EX ME2

Remarkable improvement on key components Extraordinary energy-saving performance

1 Multiple large-capacity all inverter


compressors (more than 14HP)
4 Flat fan guard
Two independently controlled inverter
compressors achieve high efficiency. Redesigned
components in the body provide performance
3 New curved improvement especially in the rated cooling
bell mouth condition and EER performance.

2 Enlarged heat exchanger


surface area with triple surface*
The new heat exchanger features a triple-surface
construction. Compared to the divided dual-
surface construction in current models, there is
2 Combined no division of space and the area for heat
triple-surface heat exchange is larger.
exchanger Also, highly efficient piping pattern increases heat Conventional model [ME1] New model [ME2]
exchange performance by 5%.
* For 8 & 10HP unit, the heat exchanger is 2 row design.

1 Multiple large-
capacity inverter
Redesigned for smooth and better air discharge
compressor
(More than 14HP)
3 Newly designed curved air
discharge bell mouth
for better aerodynamics
The new curved shape with integrated top and
bottom assure smooth exhaust flow. This gives
more air-volume with same sound level, less Conventional model [ME1] New model [ME2]
power input at same air-volume.

4 Large air discharge area with


new flush surface top panel
To reduce air resistance, instead of a tubular fan
design, a new large flat fan guard design, flush
with the top panel, is employed. This design lead Conventional model [ME1] New model [ME2]
to the improvements in air resistance, but also
contributed to better appearance designing.

28 29

180730_FSV_ASIA_D_2.indd 28-29 2018/10/12 14:38:21


High-efficiency & Space-saving VRF system

2-WAY FSV-EX ME2

A large number of indoor units can be connected Up to 50m length difference between the longest and the shortest piping from the first branch

Up to 64 indoor units can be connected in a single


system for ultimate design flexibility.
Up to 64 Indoor Units Connectable!*
Flexible piping layout makes it easier to design
systems for locations such as train stations,
L1 = Longest pipe run
L2 = Shortest pipe run
L1 – L2 = Maximum 50m
airports, schools and hospitals.
*Maximum number of indoor units depends on outdoor unit capacity. MAX.
MAX.180 m (ME1)
200 m (ME2)
• Up to 64 units can be connected to one system.
• Difference between maximum and minimum pipe
runs after first branch can be a maximum of 50m.
• Larger pipe runs can be up to 200m. L2 L1

Increased piping length for greater design flexibility


Extended operating range
Adaptable to various building types and sizes
Actual piping length : 200m
Cooling operation range: Outside air temperature (˚C DB)
Max piping length : 1,000m
-10˚C DB to +52˚C DB
*Elevation difference of Max. 90m in case of ODU is higher than IDU FSV-EX ME2
may be allowed following certain conditions. Please consult with
Panasonic sales engineers in case of piping elevation of over 50m
is required. -10 -5 0 5 10 15 20 25 30 35 40
*1: 40 m if the outdoor unit is
below the indoor unit.
200 52
Heating operation range:
Max. total length:1,000m Outside air temperature (˚C WB)
Extended heating operation range enables
heating even when the outdoor temperature is FSV-EX ME2
as low as -25˚C. Using a wired remote control,
Connectable indoor/outdoor unit capacity ratio up to 130% * indoor heating temperature range can be set -25 -20 -15 -10 -5 0 5 10 15 18
from 16˚C to 30˚C*.
FSV systems attain maximum indoor unit connection capacity of up to 130 %* of the unit’s connection range, * Depending on the type of remote controller.

depending on the outdoor and indoor models selected. So for a reasonable investment, FSV systems provide
an ideal air conditioning solution for locations where full cooling/heating are not always required.
Compact design
SYSTEM / HP 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80
MNcIU : 130% 13 16 19 23 26 29 33 36 40 43 46 50 53 56 59 63 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 The new ME2 series has 18-20 HP 8-10 HP
Weight
reduced the installation space 375 kg
MNcIU : Maximum Number of Connectable Indoor Unit
Note: If more than 100% indoor units are operated with a high load, the units may not perform at the rated capacity. required with up to 20 HP
For the details, please consult with an authorised Panasonic dealer
available in a single chassis.

H 1,842
* If the following conditions are satisfied, the effective range is above 130 % up to 200 %. 8 - 10 HP are able to fit
i ) Obey the limited number of connectable indoor units.

1,000
ii ) The lower limit of operating range for heating outdoor temperature is limited to -10°CWB (standard -25°CWB). inside a lift for easy handling
iii ) Simultaneous operation is limited to less than 130 % of connectable indoor units.
on site. D 1,000
D 1,800
1,540 W 770
W 1,640
Excellent energy savings
Required installation space
(Unit: mm)
FSV-EX ME2 series FSV ME1 series FSV-EX ME2 series FSV ME1 series
The operation efficiency has been improved
6.0 5.84
using highly efficient R410A refrigerant, new 5.56 Newly designed fan
DC inverter compressor, and new heat 5.5 5.30 5.38
5.29
5.13 5.05
exchanger design. 5.0
5.03
Optimised air flow Noise reduction
4.73
4.56 4.60
4.5
4.56 Newly designed fan and Turbulence (blue) can be
4.04
4.13 4.10 4.10 4.10
4.21 bell-mouth reduces stress suppressed and the
4.0
3.76 3.85 3.86 3.82 on the fan by dispersing air unwanted noise can be
3.60 3.61 3.60
3.5 3.36
3.50
3.33
quickly. Thus, lower air reduced. Even though a
resistance results in lower high speed fan is utilised,
3.0
8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP energy consumption. the noise level is still very
COOLING HEATING low.

30 31

180730_FSV_ASIA_D_2.indd 30-31 2018/10/12 14:38:26


High-efficiency & Space-saving VRF system

2-WAY FSV-EX ME2

High external static pressure on condensers Demand response

With a newly designed fan, fan guard, motor, and casing, new models can be custom-installed on-site to provide Featuring inverter control technology, all Panasonic
up to 80 Pa of external static pressure. An air discharge duct prevents shortages of air circulation, allowing FSV systems are Demand Response Management DRED
(Demand
outdoor units to be installed on every floor of a building. (DRM) ready. With this control, power consumption controller)
Relay contact
at times of peak load can be set in three steps to point:No
deliver optimum performance. This helps to reduce voltage relay
Current input is
High static annual power consumption with minimal loss in DC 24 V 10 mA
pressure DRM1 DRM2 DRM3 C
comfort.
Terminal block

80 Pa Outdoor unit

Fan Fan Motor and Casing Simple Demand Response with the
CZ-CAPDC4 Demand Response Signal Power Input
DRM 1 0%
Demand control terminal is available to control
DRM 2 50%
Extended compressor life by uniform compressor operation time 0-50-75-100% of capacities.
DRM 3 100%
*CZ-CAPDC4 is required as an option
The total run-time of compressors are monitored by Compressors with histories showing shorter run
a built-in microcomputer, which ensures that times are selected first, ensuring equal wear and tear
Set point Normal operation
operation times of all compressors within the same across all units and extended the working life of the Flexible Demand Response with the Power input
refrigerant circuit are balanced. system. CZ-CAPDC2 *1
Setting is possible as 0% or in the range from 40 to
System example 100% (in steps of 5%). At the time of shipping, Time
[Case1] Load Load Load
increase increase increase setting has been done to the three steps of 0%,
A,B,C,D: DC inverter compressor
A B C D A B C D A B C D A B C D Power input
70% and 100%.
Level 1 100% (Preset)
Possible to change 40-100%
*1 An outdoor Seri-Para l/O unit (CZ-CAPDC2) is required for demand input Level 2 70% (Preset)
* Depend on accumulated operation time of each compressors.
signal.
* Compressor priority has possibility to be changed. Level 3 0% (Always in stop condition)
(e.g) Case1: AgCgBgD, Case2: CgAgDgB, Case3: AgCgDgB, Case4: CgAgBgD

Automatic backup operation in the case of compressor failure or outdoor unit malfunction Hi-durability outdoor unit

Except for 8, 10 & 12 HP Even if a whole outdoor Even if a compressor in a


Corrosion-resistance treated for high resistance to PC board
single unit installation unit fails single system fails rust and salty air to assure long-lasting performance. Electric box

*Backup operation allows uninterrupted Outer body


Note: Selecting this unit does not completely eliminate the possibility of rust
cooling or heating to continue whilst waiting
developing. For details concerning unit installation and maintenance, Accumulator Receiver tank
for service.
please consult an authorised dealer. Oil separator
Users should contact their authorised
Screws
service centre as soon as fault occurs. Heat exchanger
(blue fin condenser)

The other outdoor unit can The other compressor


keep running can keep running

Automatic backup operation.

32 33

180730_FSV_ASIA_D_2.indd 32-33 2018/10/12 14:38:30


FSV-EX ME2 Series FSV-EX ME2 Series

U-12ME2H7

2-WAY FSV-EX ME2 Series HIGH EFFICIENCY COMBINATION MODEL U-8ME2H7


U-10ME2H7
U-14ME2H7
U-16ME2H7

Appearance

18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
HP 8 10 12 14 16
U-18ME2H7HE U-20ME2H7HE U-22ME2H7 U-24ME2H7 U-26ME2H7 U-28ME2H7 U-30ME2H7 U-32ME2H7 U-34ME2H7HE U-36ME2H7HE U-38ME2H7HE U-40ME2H7HE U-42ME2H7 U-44ME2H7 U-46ME2H7 U-48ME2H7 U-50ME2H7HE U-52ME2H7HE U-54ME2H7HE
U-10ME2H7 U-12ME2H7 U-10ME2H7 U-12ME2H7 U-10ME2H7 U-12ME2H7 U-14ME2H7 U-16ME2H7 U-10ME2H7 U-12ME2H7 U-10ME2H7
U-8ME2H7 U-10ME2H7 U-10ME2H7 U-12ME2H7 U-10ME2H7 U-12ME2H7 U-14ME2H7 U-16ME2H7 U-12ME2H7 U-12ME2H7 U-12ME2H7
Model name U-8ME2H7 U-10ME2H7 U-12ME2H7 U-14ME2H7 U-16ME2H7 U-12ME2H7 U-12ME2H7 U-12ME2H7 U-12ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7
U-10ME2H7 U-10ME2H7 U-12ME2H7 U-12ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-12ME2H7 U-12ME2H7 U-16ME2H7
U-12ME2H7 U-12ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7
380/400/415V/3-phase/50Hz 380/400/415V/3-phase/50Hz
Power supply
380/400V/3-phase/60Hz 380/400V/3-phase/60Hz
kW 22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 68.0 73.0 78.5 85.0 90.0 96.0 101.0 107.0 113.0 118.0 124.0 130.0 135.0 140.0 145.0 151.0
Cooling
BTU/h 76,500 95,600 114,300 136,500 153,600 170,600 191,100 209,900 232,100 249,100 267,900 290,100 307,200 327,600 344,700 365,200 385,700 402,700 423,200 443,700 460,800 477,800 494,900 515,400
Capacity
kW 25.0 31.5 37.5 45.0 50.0 56.0 63.0 69.0 76.5 81.5 87.5 95.0 100.0 108.0 113.0 119.0 127.0 132.0 138.0 145.0 150.0 155.0 160.0 169.0
Heating
BTU/h 85,300 107,500 128,000 153,600 170,600 191,100 215,000 235,500 261,100 278,200 298,600 324,200 341,300 368,600 385,700 406,100 433,400 450,500 471,000 494,900 511,900 529,000 546,100 576,800
Cooling W/W 5.30 5.03 4.73 4.56 4.13 5.15 5.05 4.84 4.69 4.42 4.36 4.31 4.13 4.80 4.72 4.51 4.45 4.31 4.26 4.25 4.13 4.58 4.53 4.40
EER / COP
Heating W/W 5.84 5.56 5.38 5.29 5.13 5.71 5.58 5.48 5.31 5.29 5.24 5.19 5.13 5.40 5.38 5.31 5.23 5.22 5.19 5.18 5.12 5.36 5.33 5.26
1,842 x 770 x 1,842 x 770 x 1,842 x 1,180 x 1,842 x 1,180 x 1,842 x 1,180 x 1,842 x 1,600 x 1,842 x 1,600 x 1,842 x 2,010 x 1,842 x 2,420 x 1,842 x 2,010 x 1,842 x 2,420 x 1,842 x 2,420 x 1,842 x 2,420 x 1,842 x 3,250 x 1,842 x 3,660 x 1,842 x 3,250 x 1,842 x 3,660 x 1,842 x 3,250 x 1,842 x 3,660 x 1,842 x 3,660 x 1,842 x 3,660 x 1,842 x 4,490 x 1,842 x 4,900 x 1,842 x 4,490 x
Dimensions HxWxD mm
1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
Net weight kg 210 210 270 315 315 420 420 480 540 525 585 630 630 750 810 795 855 840 900 945 945 1,065 1,125 1,110
Running current A 7.1 / 6.8 / 6.5 9.6 / 9.1 / 8.8 11.8 / 11.2 / 10.8 15.3 / 14.5 / 14.0 18.4 / 17.5 / 16.8 16.6 / 15.7 / 15.2 19.2 / 18.2 / 17.5 21.4 / 20.4 / 19.6 24.2 / 23.0 / 22.2 28.2 / 26.8 / 25.8 30.4 / 28.9 / 27.8 33.6 / 31.9 / 30.8 36.8 / 35.0 / 33.7 33.8 / 32.1 / 30.9 35.7 / 33.9 / 32.7 40.0 / 38.0 / 36.6 42.4 / 40.3 / 38.8 46.3 / 43.9 / 42.4 49.1 / 46.7 / 45.0 52.2 / 49.6 / 47.8 55.2 / 52.4 / 50.5 51.7 / 49.1 / 47.3 53.4 / 50.8 / 48.9 57.9 / 55.0 / 53.0
Cooling
Power input kW 4.23 5.57 7.08 8.77 10.9 9.70 11.1 12.7 14.5 16.5 18.0 19.7 21.8 20.0 21.4 23.7 25.4 27.4 29.1 30.6 32.7 30.6 32.0 34.3
Electrical ratings
Running current A 7.1 / 6.8 / 6.5 9.6 / 9.2 / 8.8 11.6 / 11.1 / 10.7 14.9 / 14.1 / 13.6 16.6 / 15.8 / 15.2 16.5 / 15.7 / 15.1 19.3 / 18.3 / 17.7 21.3 / 20.2 / 19.5 24.0 / 22.8 / 22.0 26.3 / 25.0 / 24.1 28.2 / 26.8 / 25.8 31.6 / 30.0 / 28.9 33.3 / 31.6 / 30.5 33.8 / 32.1 / 30.9 35.1 / 33.3 / 32.1 37.8 / 35.9 / 34.6 41.0 / 39.0 / 37.6 43.2 / 41.0 / 39.5 44.9 / 42.7 / 41.1 48.3 / 45.9 / 44.3 50.0 / 47.5 / 45.8 48.8 / 46.3 / 44.7 50.6 / 48.1 / 46.4 54.8 / 52.1 / 50.2
Heating
Power input kW 4.28 5.67 6.97 8.51 9.75 9.80 11.3 12.6 14.4 15.4 16.7 18.3 19.5 20.0 21.0 22.4 24.3 25.3 26.6 28.0 29.3 28.9 30.0 32.1
Starting current A 1 1 1 2 2 2 2 2 2 3 3 4 4 3 3 4 4 5 5 6 6 5 5 6
m³/h 13,440 13,440 13,920 13,920 13,920 26,880 26,880 27,360 27,840 27,360 27,840 27,840 27,840 41,280 41,760 41,280 41,760 41,280 41,760 41,760 41,760 55,200 55,680 55,200
Air flow rate
L/s 3,733 3,733 3,866 3,866 3,866 7,466 7,466 7,600 7,733 7,600 7,733 7,733 7,733 11,466 11,600 11,466 11,600 11,416 11,600 11,600 11,600 15,333 15,460 15,333
Refrigerant amount at shipment kg 5.6 5.6 8.3 8.3 8.3 11.2 11.2 13.9 16.6 13.9 16.6 16.6 16.6 22.2 24.9 22.2 24.9 22.2 24.9 24.9 24.9 30.5 33.2 30.5
External static pressure Pa 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
Gas pipe mm (inches) Ø19.05 (Ø3/4) Ø22.22 (Ø7/8) Ø25.40 (Ø1) Ø25.40 (Ø1) Ø28.58 (Ø1-1/8) Ø28.58 (Ø1-1/8) Ø28.58 (Ø1-1/8) Ø28.58 (Ø1-1/8) Ø28.58 (Ø1-1/8) Ø31.75 (Ø1-1/4) Ø31.75 (Ø1-1/4) Ø31.75 (Ø1-1/4) Ø31.75 (Ø1-1/4) Ø31.75 (Ø1-1/4) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2)
Piping
Liquid pipe mm (inches) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø12.70 (Ø1/2) Ø12.70 (Ø1/2) Ø12.70 (Ø1/2) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4)
connections
Balance pipe mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4)
Ambient temperature operating range Cooling: -10˚C (DB)~ +52˚C (DB). Heating: -25˚C (WB)~ +18˚C (WB) Cooling: -10˚C (DB)~ +52˚C (DB). Heating: -25˚C (WB)~ +18˚C (WB)
Sound Normal mode dB (A) 53.0 56.0 57.0 58.0 61.0 58.0 59.0 59.5 60.0 62.5 62.5 63.0 64.0 61.5 62.0 63.5 63.5 65.0 65.0 65.0 66.0 64.5 64.5 65.5
pressure level Silent mode (2) dB (A) 48.0 51.0 52.0 53.0 56.0 53.0 54.0 54.5 55.0 57.5 57.5 58.0 59.0 56.5 57.0 58.5 58.5 60.0 60.0 60.0 61.0 59.5 59.5 60.5
Sound power level Normal mode dB 74.0 77.0 78.0 79.0 82.0 79.0 80.0 80.5 81.0 83.5 83.5 84.0 85.0 82.5 83.0 84.5 84.5 86.0 86.0 86.0 87.0 85.5 85.5 86.5

GLOBALREMARKS
Rated conditions: Cooling Heating
8 / 10 HP 12 / 14 / 16 HP
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
Appearance
Outdoor air temperature 35˚C DB 7˚C DB / 6˚C WB
According to the installation site, you may choose the setting According to the installation site, you may choose the setting
These specifications are subject to change without notice.
56 58 60 62 64 position in the depth direction of the anchor bolt from A, B or C. position in the depth direction of the anchor bolt from A, B or C.
HP
U-56ME2H7HE U-58ME2H7HE U-60ME2H7HE U-62ME2H7 U-64ME2H7
U-12ME2H7 U-10ME2H7 U-12ME2H7 U-14ME2H7 U-16ME2H7
A: (Installation hole pitch) For removing tube forward A: (Installation hole pitch) For removing tube forward
U-12ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 B: (Installation hole pitch) For removing the downward B: (Installation hole pitch) For removing the downward
Model name U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 C: (Installation hole pitch) C: (Installation hole pitch)
U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7
380/400/415V/3-phase/50Hz
Power supply
380/400/3-phase/60Hz
Top view Front view Top view Front view
kW 156.0 162.0 168.0 174.0 180.0
Cooling Air outlet Air outlet
BTU/h 532,400 552,900 573,400 593,300 614,300
Capacity Installation anchor hole
kW 175.0 182.0 189.0 195.0 201.0
Heating 8-15×21 elongated holes Installation anchor hole
BTU/h 597,300 621,200 645,100 665,300 685,800
Air intake 8-15×21 elongated holes
Cooling W/W 4.38 4.27 4.24 4.23 4.13 Air intake
EER / COP
Heating W/W 5.24 5.19 5.15 5.16 5.11
1,842 x 4,900 x 1,842 x 4,490 x 1,842 x 4,900 x 1,842 x 4,900 x 1,842 x 4,900 x
Dimensions HxWxD mm
1,000 1,000 1,000 1,000 1,000

A:964
1000
Net weight kg 1,170 1,155 1,215 1,260 1,260

1842

A:964

1842
1000
Running current A 60.1 / 57.1 / 55.0 64.0 / 60.8 / 58.6 66.9 / 63.5 / 61.2 70.2 / 66.7 / 64.2 73.6 / 69.9 / 67.4

Air intake

Air intake
Air intake

Air intake
Cooling
Power input kW 35.6 37.9 39.6 41.1 43.6
Electrical ratings

953
Running current A 56.4 / 53.6 / 51.6 59.9 / 56.9 / 54.9 62.7 / 59.5 / 57.4 64.5 / 61.3 / 59.1 67.1 / 63.7 / 61.4

953
Heating

18
B:730
C:730
Power input kW 33.4 35.1 36.7 37.8 39.3

18
B:730
C:730
15 740 15 1150
Starting current A 6 7 7 8 8 770 1180

m³/h 55,680 55,200 55,680 55,680 55,680


Air flow rate
L/s 15,466 15,333 15,466 15,466 15,466
unit: mm unit: mm
Refrigerant amount at shipment kg 33.2 30.5 33.2 33.2 33.2
External static pressure Pa 80 80 80 80 80
Gas pipe mm (inches) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø41.28 (Ø1-5/8) Ø41.28 (Ø1-5/8)
Piping
Liquid pipe mm (inches) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4)
connections
Balance pipe mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4)
Ambient temperature operating range Cooling: -10˚C (DB)~ +52˚C (DB). Heating: -25˚C (WB)~ +18˚C (WB)
Sound Normal mode dB (A) 65.5 66.5 66.5 66.5 67.0
pressure level Silent mode dB (A) 60.5 61.5 61.5 61.5 62.0
Sound power level Normal mode dB 86.5 87.5 87.5 87.5 88.0

34 35

180730_FSV_ASIA_D_2.indd 34-35 2018/10/12 14:38:34


FSV-EX ME2 Series FSV-EX ME2 Series

U-12ME2H7
2-WAY FSV-EX ME2 Series SPACE SAVING COMBINATION MODEL U-8ME2H7
U-10ME2H7
U-14ME2H7
U-16ME2H7
U-18ME2H7
U-20ME2H7

Appearance

22 24 26 28 30 32 34 36 38 40 42 44 46 48
HP 8 10 12 14 16 18 20
U-22ME2H7 U-24ME2H7 U-26ME2H7 U-28ME2H7 U-30ME2H7 U-32ME2H7 U-34ME2H7SP U-36ME2H7SP U-38ME2H7SP U-40ME2H7SP U-42ME2H7 U-44ME2H7 U-46ME2H7 U-48ME2H7
U-10ME2H7 U-12ME2H7 U-14ME2H7 U-16ME2H7
U-10ME2H7 U-12ME2H7 U-10ME2H7 U-12ME2H7 U-14ME2H7 U-16ME2H7 U-14ME2H7 U-16ME2H7 U-18ME2H7 U-20ME2H7
Model name U-8ME2H7 U-10ME2H7 U-12ME2H7 U-14ME2H7 U-16ME2H7 U-18ME2H7 U-20ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7
U-12ME2H7 U-12ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7
U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7
380/400/415V/3-phase/50Hz 380/400/415V/3-phase/50Hz
Power supply
380/400V/3-phase/60Hz 380/400V/3-phase/60Hz
kW 22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 68.0 73.0 78.5 85.0 90.0 96.0 101.0 107.0 113.0 118.0 124.0 130.0 135.0
Cooling
BTU/h 76,500 95,600 114,300 136,500 153,600 170,600 191,100 209,900 232,100 249,100 267,900 290,100 307,200 327,600 344,700 365,200 385,700 402,700 423,200 443,700 460,800
Capacity
kW 25.0 31.5 37.5 45.0 50.0 56.0 63.0 69.0 76.5 81.5 87.5 95.0 100.0 108.0 113.0 119.0 127.0 132.0 138.0 145.0 150.0
Heating
BTU/h 85,300 107,500 128,000 153,600 170,600 191,100 215,000 235,500 261,100 278,200 298,600 324,200 341,300 368,600 385,700 406,100 433,400 450,500 471,000 494,900 511,900
Cooling W/W 5.30 5.03 4.73 4.56 4.13 4.10 3.76 4.84 4.69 4.42 4.36 4.31 4.13 4.05 3.91 3.89 3.74 4.31 4.26 4.25 4.13
EER / COP
Heating W/W 5.84 5.56 5.38 5.29 5.13 5.05 4.60 5.48 5.31 5.29 5.24 5.19 5.13 4.86 4.81 4.80 4.58 5.22 5.19 5.18 5.12
1,842 x 770 x 1,842 x 770 x 1,842 x 1,180 x 1,842 x 1,180 x 1,842 x 1,180 x 1,842 x 1,540 x 1,842 x 1,540 x 1,842 x 2,010 x 1,842 x 2,420 x 1,842 x 2,010 x 1,842 x 2,420 x 1,842 x 2,420 x 1,842 x 2,420 x 1,842 x 2,780 x 1,842 x 2,780 x 1,842 x 3,140 x 1,842 x 3,140 x 1,842 x 3,250 x 1,842 x 3,660 x 1,842 x 3,660 x 1,842 x 3,660 x
Dimensions HxWxD mm
1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
Net weight kg 210 210 270 315 315 375 375 480 540 525 585 630 630 690 690 750 750 840 900 945 945
Running current A 7.1 / 6.8 / 6.5 9.6 / 9.1 / 8.8 11.8 / 11.2 / 10.8 15.3 / 14.5 / 14.0 18.4 / 17.5 / 16.8 20.6 / 19.6 / 18.9 24.6 / 23.4 / 22.5 21.4 / 20.4 / 19.6 24.2 / 23.0 / 22.2 28.2 / 26.8 / 25.8 30.4 / 28.9 / 27.8 33.6 / 31.9 / 30.8 36.8 / 35.0 / 33.7 40.0 / 38.0 / 36.6 43.1 / 40.9 / 39.4 45.9 / 43.6 / 42.0 49.9 / 47.4 / 45.7 46.3 / 43.9 / 42.4 49.1 / 46.7 / 45.0 52.2 / 49.6 / 47.8 55.2 / 52.4 / 50.5
Cooling
Power input kW 4.23 5.57 7.08 8.77 10.9 12.2 14.9 12.7 14.5 16.5 18.0 19.7 21.8 23.7 25.8 27.5 30.2 27.4 29.1 30.6 32.7
Electrical ratings
Running current A 7.1 / 6.8 / 6.5 9.6 / 9.2 / 8.8 11.6 / 11.1 / 10.7 14.9 / 14.1 / 13.6 16.6 / 15.8 / 15.2 18.9 / 18.0 / 17.4 22.9 / 21.7 / 20.9 21.3 / 20.2 / 19.5 24.0 / 22.8 / 22.0 26.3 / 25.0 / 24.1 28.2 / 26.8 / 25.8 31.6 / 30.0 / 28.9 33.3 / 31.6 / 30.5 37.9 / 36.0 / 34.7 39.7 / 37.7 / 36.3 41.9 / 39.8 / 38.3 46.2 / 43.9 / 42.3 43.2 / 41.0 / 39.5 44.9 / 42.7 / 41.1 48.3 / 45.9 / 44.3 50.0 / 47.5 / 45.8
Heating
Power input kW 4.28 5.67 6.97 8.51 9.75 11.1 13.7 12.6 14.4 15.4 16.7 18.3 19.5 22.2 23.5 24.8 27.7 25.3 26.6 28.0 29.3
Starting current A 1 1 1 2 2 2 2 2 2 3 3 4 4 4 4 4 4 5 5 6 6
m³/h 13,440 13,440 13,920 13,920 13,920 24,300 24,300 27,360 27,840 27,360 27,840 27,840 27,840 38,220 38,220 48,600 48,600 41,280 41,760 41,760 41,760
Air flow rate
L/s 3,733 3,733 3,866 3,866 3,866 6,758 6,758 7,600 7,733 7,600 7,733 7,733 7,733 10,616 10,616 13,500 13,500 11,466 11,600 11,600 11,600
Refrigerant amount at shipment kg 5.6 5.6 8.3 8.3 8.3 9.5 9.5 13.9 16.6 13.9 16.6 16.6 16.6 17.8 17.8 19.0 19.0 22.2 24.9 24.9 24.9
External static pressure Pa 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
Gas pipe mm (inches) Ø19.05 (Ø3/4) Ø22.22 (Ø7/8) Ø25.40 (Ø1) Ø25.40 (Ø1) Ø28.58 (Ø1-1/8) Ø28.58 (Ø1-1/8) Ø28.58 (Ø1-1/8) Ø28.58 (Ø1-1/8) Ø28.58 (Ø1-1/8) Ø31.75 (Ø1-1/4) Ø31.75 (Ø1-1/4) Ø31.75 (Ø1-1/4) Ø31.75 (Ø1-1/4) Ø31.75 (Ø1-1/4) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2)
Piping
Liquid pipe mm (inches) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø12.70 (Ø1/2) Ø12.70 (Ø1/2) Ø12.70 (Ø1/2) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4)
connections
Balance pipe mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4)
Ambient temperature operating range Cooling: -10˚C (DB)~ +52˚C (DB). Heating: -25˚C (WB)~ +18˚C (WB) Cooling: -10˚C (DB)~ +52˚C (DB). Heating: -25˚C (WB)~ +18˚C (WB)
Sound Normal mode dB (A) 53.0 56.0 57.0 58.0 61.0 59.0 59.0 59.5 60.0 62.5 62.5 63.0 64.0 61.5 63.5 62.0 62.0 65.0 65.0 65.0 66.0
pressure level Silent mode (2) dB (A) 48.0 51.0 52.0 53.0 56.0 54.0 54.0 54.5 55.0 57.5 57.5 58.0 59.0 56.5 58.5 57.0 57.0 60.0 60.0 60.0 61.0
Sound power level Normal mode dB 74.0 77.0 78.0 79.0 82.0 80.0 80.0 80.5 81.0 83.5 83.5 84.0 85.0 82.5 84.5 83.0 83.0 86.0 86.0 86.0 87.0

GLOBALREMARKS
Rated conditions: Cooling Heating
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
Appearance
Outdoor air temperature 35˚C DB 7˚C DB / 6˚C WB
These specifications are subject to change without notice.
50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80
HP
U-50ME2H7SP U-52ME2H7SP U-54ME2H7SP U-56ME2H7SP U-58ME2H7SP U-60ME2H7SP U-62ME2H7 U-64ME2H7 U-66ME2H7SP U-68ME2H7SP U-70ME2H7SP U-72ME2H7SP U-74ME2H7SP U-76ME2H7SP U-78ME2H7SP U-80ME2H7SP
U-14ME2H7 U-16ME2H7 U-10ME2H7 U-12ME2H7 U-10ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-18ME2H7 U-20ME2H7
U-14ME2H7 U-16ME2H7 U-14ME2H7 U-16ME2H7 U-18ME2H7 U-20ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7 U-20ME2H7 U-16ME2H7 U-18ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7
Model name U-16ME2H7 U-16ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-16ME2H7 U-16ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7
U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-16ME2H7 U-16ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7
380/400/415V/3-phase/50Hz 380/400/415V/3-phase/50Hz
Power supply
380/400/3-phase/60Hz 380/400/3-phase/60Hz
kW 140.0 145.0 151.0 156.0 162.0 168.0 174.0 180.0 185.0 190.0 196.0 202.0 208.0 213.0 219.0 224.0
Cooling
BTU/h 477,800 494,900 515,400 532,400 552,900 573,400 593,900 614,300 631,400 648,500 668,900 689,400 709,900 727,000 747,400 764,500
Capacity
kW 155.0 160.0 169.0 175.0 182.0 189.0 195.0 201.0 207.0 213.0 219.0 226.0 233.0 239.0 245.0 252.0
Heating
BTU/h 529,000 546,100 576,800 597,300 621,200 645,100 665,500 686,000 706,500 727,000 747,400 771,300 795,200 815,700 836,200 860,100
Cooling W/W 4.09 3.99 3.95 3.87 3.86 3.76 4.23 4.13 4.00 3.99 3.90 3.91 3.90 3.83 3.82 3.76
EER / COP
Heating W/W 5.00 4.95 4.79 4.76 4.73 4.60 5.16 5.11 4.85 4.84 4.73 4.82 4.79 4.70 4.69 4.60
1,842 x 4,020 x 1,842 x 4,020 x 1,842 x 4,380 x 1,842 x 4,380 x 1,842 x 4,740 x 1,842 x 4,740 x 1,842 x 4,900 x 1,842 x 4,900 x 1,842 x 5,210 x 1,842 x 5,620 x 1,842 x 5,570 x 1,842 x 5,620 x 1,842 x 5,980 x 1,842 x 5,980 x 1,842 x 6,340 x 1,842 x 6,340 x
Dimensions HxWxD mm
1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
Net weight kg 1,005 1,005 1,065 1,065 1,125 1,125 1,260 1,260 1,275 1,335 1,335 1,380 1,440 1,440 1,500 1,500
Running current A 57.7 / 54.8 / 52.9 60.6 / 57.6 / 55.5 63.8 / 60.6 / 58.4 67.3 / 63.9 / 61.6 70.1 / 66.6 / 64.2 73.8 / 70.1 / 67.6 70.2 / 66.7 / 64.2 73.6 / 69.9 / 67.4 77.3 / 73.4 / 70.8 79.5 / 75.5 / 72.8 84.0 / 79.8 / 76.9 86.2 / 81.8 / 78.9 89.0 / 84.5 / 81.5 91.8 / 87.2 / 84.1 94.6 / 89.9 / 86.6 98.4 / 93.5 / 90.1
Cooling
Power input kW 34.2 36.3 38.2 40.3 42.0 44.7 41.1 43.6 46.3 47.6 50.3 51.6 53.3 55.6 57.3 59.6
Electrical ratings
Running current A 52.9 / 50.3 / 48.5 54.5 / 51.8 / 49.9 59.6 / 56.6 / 54.6 62.1 / 59.0 / 56.9 65.0 / 61.7 / 59.5 68.6 / 65.2 / 62.8 64.5 / 61.3 / 59.1 67.1 / 63.7 / 61.4 72.1 / 68.5 / 66.0 73.5 / 69.8 / 67.3 77.3 / 73.4 / 70.8 79.2 / 75.2 / 72.5 82.0 / 77.9 / 75.1 85.0 / 80.7 / 77.8 87.2 / 82.8 / 79.8 91.5 / 86.9 / 83.8
Heating
Power input kW 31.0 32.3 35.3 36.8 38.5 41.1 37.8 39.3 42.7 44.0 46.3 46.9 48.6 50.9 52.2 54.8
Starting current A 6 6 6 6 6 6 8 8 7 7 7 8 8 8 8 8
m³/h 52,140 52,140 62,520 62,520 72,900 72,900 55,680 55,680 75,960 76,440 86,340 76,440 86,820 86,820 97,200 97,200
Air flow rate
L/s 14,483 14,483 17,366 17,366 20,250 20,250 15,466 15,466 21,100 21,233 23,983 21,233 24,116 24,116 27,000 27,000
Refrigerant amount at shipment kg 26.1 26.1 27.3 27.3 28.5 28.5 33.2 33.2 32.9 35.6 34.1 35.6 36.8 36.8 38.0 38.0
External static pressure Pa 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
Gas pipe mm (inches) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø38.10 (Ø1-1/2) Ø41.28 (Ø1-5/8) Ø41.28 (Ø1-5/8) Ø41.28 (Ø1-5/8) Ø41.28 (Ø1-5/8) Ø41.28 (Ø1-5/8) Ø44.45 (Ø1-3/4) Ø44.45 (Ø1-3/4) Ø44.45 (Ø1-3/4) Ø44.45 (Ø1-3/4) Ø44.45 (Ø1-3/4)
Piping
Liquid pipe mm (inches) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø19.05 (Ø3/4) Ø22.22 (Ø7/8) Ø22.22 (Ø7/8) Ø22.22 (Ø7/8) Ø22.22 (Ø7/8) Ø22.22 (Ø7/8) Ø22.22 (Ø7/8) Ø22.22 (Ø7/8)
connections
Balance pipe mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4)
Ambient temperature operating range Cooling: -10˚C (DB)~ +52˚C (DB). Heating: -25˚C (WB)~ +18˚C (WB) Cooling: -10˚C (DB)~ +52˚C (DB). Heating: -25˚C (WB)~ +18˚C (WB)
Sound Normal mode dB (A) 64.5 65.5 63.5 64.5 64.0 64.0 66.5 67.0 65.5 65.5 64.5 66.5 66.0 66.0 65.0 65.0
pressure level Silent mode dB (A) 59.5 60.5 58.5 59.5 59.0 59.0 61.5 62.0 60.5 60.5 59.5 61.5 61.0 61.0 60.0 60.0
Sound power level Normal mode dB 85.5 86.5 84.5 85.5 85.0 85.0 87.5 88.0 86.5 86.5 85.5 87.5 87.0 87.0 86.0 86.0

36 37

180730_FSV_ASIA_D_2.indd 36-37 2018/10/12 14:38:38


FSV-EX ME2 Series FSV-EX ME2 Series

U-12ME2H7
2-WAY FSV-EX ME2 Series SPACE SAVING COMBINATION MODEL U-8ME2H7
U-10ME2H7
U-14ME2H7
U-16ME2H7
U-18ME2H7
U-20ME2H7

8 / 10 HP 12 / 14 / 16 HP 18 / 20 HP
According to the installation site, you may choose the setting According to the installation site, you may choose the setting According to the installation site, you may choose the setting
position in the depth direction of the anchor bolt from A, B or C. position in the depth direction of the anchor bolt from A, B or C. position in the depth direction of the anchor bolt from A, B or C.

A: (Installation hole pitch) For removing tube forward A: (Installation hole pitch) For removing tube forward A: (Installation hole pitch) For removing tube forward
B: (Installation hole pitch) For removing the downward B: (Installation hole pitch) For removing the downward B: (Installation hole pitch) For removing the downward
C: (Installation hole pitch) C: (Installation hole pitch) C: (Installation hole pitch)

Top view Top view Top view


Installation anchor hole
Installation anchor hole Installation anchor hole
8-15×21 elongated holes 8-15×21 elongated holes
8-15×21 elongated holes
Air intake
Air intake Air intake Air intake
A:964

A:964
A:964
1000

1000
1000

Air intake
Air intake

Air intake
Air intake
Air intake

Air intake

18
18
15

B:730
1510

B:730

C:730
C:730
15
18
B:730
C:730

1150
15 740 1540
1180
770

Front view Front view Air outlet Front view Air outlet
Air outlet
1842

1842
1842
953

953
953

unit: mm unit: mm unit: mm

38 39

180730_FSV_ASIA_D_2.indd 38-39 2018/10/12 14:38:40


Piping Design Necessary amount of additional refrigerant charge per outdoor unit
U-8ME2H7(E) U-10ME2H7(E) U-12ME2H7(E) U-14ME2H7(E) U-16ME2H7(E) U-18ME2H7(E) U-20ME2H7(E)
Select installation locations so that the lengths and sizes of refrigerant 5.5kg 5.5kg 7.0 kg 7.0 kg 7.0 kg 7.0 kg 7.0 kg

piping are within the allowable ranges shown in the figure below.

1. Main tubing length (maximum tubing size) LM = LA + LB … System limitations


2. Main distribution tubes LC – LH are selected according to the capacity after the distribution joint.
3. The outdoor connection main tubing (LO portion) is determined by the total capacity of the Max. No. allowable connected outdoor units 4 *2
outdoor units that are connected to the tube ends.
4. Sizes of indoor unit connection tubing 1 – 64 are determined by the connection tubing sizes Max. capacity allowable connected outdoor units 180 kW (64 HP)
on the indoor units.
Max. connectable indoor units 64 *1
Max. allowable indoor/outdoor capacity ratio 50-130 % *3

L1
H3 *1: In the case of 38 HP or smaller units, the number is limited by the total capacity of the connected indoor units.
L2 *2: Up to 4 units can be connected if the system has been extended.
C
*3: If the following conditions are satisfied, the effective range is above 130 % and below 200 %.
LM i ) Obey the limited number of connectable indoor units.
A
ii ) The lower limit of operating range for heating outdoor temperature is limited to -10°CWB (standard -25°CWB).
LA
Balance tubing B iii ) Simultaneous operation is limited to less than 130 % of connectable indoor units.
(ø 6.35mm)
LO L3
LC
1st distribution joint for outdoor unit
LD
LB H1
R410A distribution joint 4 5 62 63
64
CZ-P680PJ2 (for outdoor unit)
CZ-P1350PJ2 (for outdoor unit)
LF Max. 40cm For Additional refrigerant charge
CZ-P160BK2 (for indoor unit) 1st distribution joint extension
CZ-P680BK2 (for indoor unit)
Liquid tubing size mm (inches) Amount of refrigerant charge/m (g/m)
CZ-P1350BK2 (for indoor unit) For
Explanation of symbols
extension H2 ø6.35 (ø1/4) 26
Max. 40cm
Distribution joint
LH
ø9.52 (ø3/8) 56
(CZ: optional parts)
LG 3 ø12.7 (ø1/2) 128
Ball valve (field supply) 1 2
T-joint (field supply) ø15.88 (ø5/8) 185
L4
Solidly welded shut ø19.05 (ø3/4) 259
(pinch weld)

Note: Be sure to use special R410A distribution joints (CZ: optional parts) for outdoor unit connections and tubing branches. ø22.22 (ø7/8) 366
ø25.4 (ø1) 490

Refrigerant piping (Existing piping can be used.)


Ranges that apply to refrigerant piping lengths and Tubing size (mm)
to differences in installation heights Material Temper - O Material Temper - 1/2 H, H
ø6.35 t 0.8 ø22.22 t 1.0
Items Mark Contents Length (m) ø9.52 t 0.8 ø25.4 t 1.0
Actual length ≤200*2 ø12.7 t 0.8 ø28.58 t 1.0
L1 Max. tubing length
Equivalent length ≤210*2 ø15.88 t 1.0 ø31.75 t 1.1
∆ L (L2-L4) Difference between max. length and min. length from the 1st distribution joint ≤50*5 ø19.05 t 1.2 ø38.1 over t 1.35
* When bending the tubes, use a bending radius that is at
Max. length of main tubing (at maximum size) ø41.28 over t 1.45 least 4 times the outer diameter of the tubes. In addition, take
Allowable tubing LM -*3
* Even after 1st distribution joint, LM is allowed if at maximum tubing length. sufficient care to avoid crushing or damaging the tubes when
length ø44.45 over t1.55
ℓ1, ℓ2~ ℓ64 Max. length of each distribution tube ≤50*7 bending them.

L1+ ℓ1+ ℓ2~ ℓ63+


Total max. tubing length including length of each distribution tube (only liquid tubing) ≤1000
ℓA+ ℓB+LF+LG+LH

ℓA, ℓB+LO, ℓC+LO Maximum tubing length from outdoor’s 1st distribution joint to each outdoor unit ≤10
When outdoor unit is installed higher than indoor unit ≤50
H1
Allowable elevation When outdoor unit is installed lower than indoor unit ≤40
difference H2 Max. difference between indoor units ≤15*6
H3 Max. difference between outdoor units ≤4

Allowable length T-joint tubing (field-supply); Max. tubing length between the first T-joint and solidly
L3 ≤2
of joint tubing welded-shut end point
L = Length, H = Height

NOTE
1: The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
2: If the longest tubing length (L1) exceeds 90 m (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for gas tubes
and liquid tubes. Use a field supply reducer. Select the tube size from the table of main tubing sizes (Table 3) and from the table of refrigerant tubing sizes (Table 8) on the
second following page.
3: If the longest main tubing length (LM) exceeds 50 m, increase the main tubing size at the portion before 50 m by 1 rank for the gas tubes. Use a field supply reducer.
Determine the length less than the limitation of allowable maximum tubing length. For the portion that exceeds 50 m, set based on the main tubing size (LA) listed in Table 3.
4: If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the size.
* If the existing tubing is used, and the amount of on-site refrigerant charge exceeds the value listed below, then change the size of the tubing to reduce the amount of
refrigerant.
Total amount of refrigerant for the system with 1 outdoor unit: 50 kg
Total amount of refrigerant for the system with 2 outdoor units: 80 kg
Total amount of refrigerant for the system with 3 outdoor units or 4 outdoor units: 105 kg
5: When the tubing length exceeds 40 m, increase a longer liquid or gas tubing by 1 rank. Refer to the Technical Data for the details.
6: If the total distribution tubing length exceeds 500m, maximum allowable elevation difference (H2) between the indoor units is calculated by the following formula. Make
sure the indoor unit’s actual elevation difference should fall within the figure calculated as follows.
Unit of account (meter): 15 x (2 - total tubing length(m) ÷ 500)
7: If any of the tubing length exceeds 30m, increase the size of the liquid and gas tubes by 1 rank.

40 41

180730_FSV_ASIA_D_2.indd 40-41 2018/10/12 14:38:41


FSV-EX ME2 Series FSV-EX ME2 Series

Refrigerant Branch Pipes (optional accessories) 3. CZ-P160BK2

for 2-WAY ME2 Series


Use: For indoor unit (Capacity after distribution joint is 22.4 kW or less.)*

GAS TUBING LIQUID TUBING


110 110 110 110
97 97 97 97
C C
Optional Distribution Joint Kits Model name Cooling capacity after distribution Remarks
AB
B
B
B
D C D
C
C
C
D E D E

72

72
72
A

72
1. CZ-P680PJ2 68.0 kW or less For outdoor unit B Distribution B A A Insulation Distribution Joint C C
See the installation instructions packaged with the 2. CZ-P1350PJ2 more than 68.0 kW For outdoor unit
Insulation Joint
D D
distribution joint kit for the installation procedure. 3. CZ-P160BK2 22.4 kW or less * For indoor unit EUnit: mm
C C E
* In case the total capacity of indoor units connected after distribution 4. CZ-P680BK2 68.0 kW or less * For indoor unit
exceeds the total capacity of the outdoor units, select the distribution tubing 5. CZ-P1350BK2 more than 68.0 kW * For indoor unit
size for the total capacity of the outdoor units. Size of connection point on each part (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E
(mm) Ø19.05 Ø15.88 Ø12.70 Ø9.52 Ø6.35
Dimension
(inches) Ø3/4 Ø5/8 Ø1/2 Ø3/8 Ø1/4

Tubing size (with thermal insulation)


4. CZ-P680BK2
1. CZ-P680PJ2 Use: For indoor unit (Capacity after distribution joint is more than 22.4 kW and no more than 68.0 kW.)*
For outdoor unit (Capacity after distribution joint is 68.0 kW or less.)
GAS TUBING LIQUID TUBING
GAS TUBING LIQUID TUBING
175 175 110 110
175 175 110 110
A A 135 135 97 97
G H G H
135 135 97 97
B B E E F F A A B C BD C ED F E F E E
D C BD C B A A G F G F E E F G HF G H

114

114

72

72
B B C D E C D E D FE F E E

72
C

72
C D E E E
114
114

A A
Distribution Distribution
F F Joint
H G H G Joint
B B
Distribution F F
G G B B
Joint G G
Distribution Joint H H C C
C C H H
D D Reducing Joints
D D Reducing Joints
E E Insulation Insulation
Reducing Joints E E
Insulation Unit: mm
F F
Reducing Joints Insulation
Unit: mm

Size of connection point on each part (Shown are inside diameters of tubing) Size of connection point on each part (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E Part F Part G Part H Size Part A Part B Part C Part D Part E Part F Part G Part H
(mm) ø31.75 ø28.58 ø25.40 ø22.22 ø19.05 ø15.88 ø12.70 ø9.52 (mm) Ø28.58 Ø25.40 Ø22.22 Ø19.05 Ø15.88 Ø12.70 Ø9.52 Ø6.35
Dimension Dimension
(inches) Ø1-1/4 Ø1-1/8 Ø1 Ø7/8 Ø3/4 Ø5/8 Ø1/2 Ø3/8 (inches) Ø1-1/8 Ø1 Ø7/8 Ø3/4 Ø5/8 Ø1/2 Ø3/8 Ø1/4

5. CZ-P1350BK2
2. CZ-P1350PJ2 Use: For indoor unit (Capacity after distribution joint is more than 68.0 kW.)*
For outdoor unit (Capacity after distribution joint is more than 68.0 kW.)

GAS TUBING 175 175 LIQUID TUBING 110 110 GAS TUBING 175 LIQUID TUBING 110
175135 110 97
H I H I A
135 135 97 97 135 A F 97 F
A A B F F
A A B B F F G G G
B B B G H

72
A B C D G

114
F F B G H

72
E FG G C D G
72

72

E F A

114
114

114

C D C D B
Distribution G
G G Joint B Distribution
I H I H D C
BDistribution B D C
Joint
Distribution H
Joint H H C
Joint I
I I C D H
I J
D J
C E C E E
Insulation
D D E F Insulation
Reducing Joints
F F F Reducing Joints
Insulation G Reducing Joints
Reducing Joints H
G Unit: mm
Insulation Unit: mm H

Size of connection point on each part (Shown are inside diameters of tubing) Size of connection point on each part (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E Part F Part G Part H Part I Size Part A Part B Part C Part D Part E Part F Part G Part H Part I Part J
(mm) ø38.10 ø31.75 ø28.58 ø25.40 ø22.22 ø19.05 ø15.88 ø12.70 ø9.52 (mm) Ø38.10 Ø31.75 Ø28.58 Ø25.40 Ø22.22 Ø19.05 Ø15.88 Ø12.70 Ø9.52 Ø6.35
Dimension Dimension
(inches) Ø1-1/2 Ø1-1/4 Ø1-1/8 Ø1 Ø7/8 Ø3/4 Ø5/8 Ø1/2 Ø3/8 (inches) Ø1-1/2 Ø1-1/4 Ø1-1/8 Ø1 Ø7/8 Ø3/4 Ø5/8 Ø1/2 Ø3/8 Ø1/4
* If the tube diameter is more than ø38.1, use field-supply reducer. *If the tube diameter is more than ø38.1, use field-supply reducer.
42 * In case the total capacity of indoor units connected after distribution exceeds the total capacity of the outdoor units, 43
select the distribution tubing size for the total capacity of the outdoor units.

180730_FSV_ASIA_D_2.indd 42-43 2018/10/12 14:38:43


Mini-FSV LE Series Mini-FSV LE Series

2-WAY Mini-FSV LE Series Long piping design length for greater design flexibility LE1 LE2

High External
Adaptable to various
building types and sizes

Static Pressure Actual piping length 150m


(equivalent piping length 175m)
Height
difference
50m*1
Actual piping length 150m
(equivalent piping length 175m)
Height
difference
50m*1

35Pa Max. total piping length:300m

LE 1
Level difference
between indoor
units 15m Max. total piping length:180m

LE 2
Level difference
between indoor
units 15m

*1: 40m if the outdoor unit is below the indoor unit.

Refrigerant chargeless up to 50m LE2

Up to 50m of piping without additional gas charging


makes installation flexible, easy and hassle-free. [ Sample piping lay-out ]
Chargeless
A 50m pipe length is sufficient for most residential and small business
buildings. When total piping length exceeds 50m, additional refrigerant
Max. total piping length: 50m
charge is required. Charge
Max. total piping length: 180m
(Actual length: 150m)

High external static pressure 35Pa LE1 LE2 Compact design LE1 LE2

When unit is installed on a narrow balcony and exposed to the sun, the fence at the front side would restrict Also, since Mini VRF LE Series is a single
hot air from being discharged. Heat accumulated in an enclosure can cause over-heating. This could unit, it is possible to install the unit in more
potentially result in damage or shorten the product’s life span. A high external static pressure sends the air various places compared to the Single
further away from the outdoor unit and through the fence. This provides better air circulation and distribution. Split system.

Single Split Mini-FSV

Previous model - Low pressure LE series - High pressure Short height of 996mm LE2 [ LE 2 ]
When the pressure is low, hot air will accumulate in the unit thus But with a high pressure of 35Pa, hot air is sent further away Short
In addition to raising efficiency, we have [ LE 1 ]
affecting its work performance and of the unit above it as well. preventing overheating inside the outdoor unit enclosure.
made the outdoor unit more compact. It Height 1330mm
996mm
can now be installed in places that were
996mm
previously too small.
Can be installed in the small space
980mm 370mm

Heat discharged
35
Pa
Up to 13 indoor units connectable LE1 LE2
Heat accumulated

An expansion from Panasonic VRF line up, the mini FSV is compatible with the same indoor units and controls as
the rest of the FSV range.

35
LE1 Up to 13 (LE1) / 9* (LE2) indoor units
Pa

Previous fan LE series fan


LE2
High electrostatic pressure The new LE Series fan has ribs extending
disrupted the airflow of the near the blade tips, in a structure that resists
previous fan, lowering the air deformation. During high electrostatic Refrigerant pipe Control line
pressure and preventing hot pressure, this blade shape suppresses
air from being discharged far disruptions in the airflow, and a high air
enough. pressure of 35 Pa discharges the hot air a * Use any of the 22 type indoor models. Depending on the size or type of indoor unit, tubing size shall be changed. Please refer manuals for details.
sufficient distance. * Diversity ration 50-130%
* 6 HP only; 4 HP for 7 units, 5 HP for 8 units.

44 45

180730_FSV_ASIA_D_2.indd 44-45 2018/10/12 14:39:02


Mini-FSV LE Series Mini-FSV LE Series

COOLING FSV HEATING FSV


5.5 5.5

2-WAY Mini-FSV LE Series


5.0
4.50
5.0
5.19

4.60
4.5 4.5 4.27
4.06 4.02 3.93
4.0 3.73 3.80 4.0

3.5 3.31 3.5

3.0 3.0

2.5 2.5
High efficiency LE1 LE2 Wide operating range LE1 LE2
4 HP 5 HP 6 HP 8 HP 10 HP 4 HP 5 HP 6 HP 8 HP 10 HP
LE 2 LE 1 LE 2 LE 1
The operation efficiency has been improved using highly efficient R410A refrigerant, a DC Inverter compressor, • Cooling operation is possible even when outdoor
DC motor and a heat exchanger design. temperature is as low as -10°C DB.
• Cooling operation is possible even when outdoor
COOLING FSV FS Multi HEATING FSV FS Multi
temperature is as high as 46°C DB.
5.5 5.5 5.43
5.25
5.08 5.08 • Heating operation is possible even when outdoor
5.0 5.0
4.61 4.52 4.55 temperature is as low as -20°C WB.
4.5 4.27 4.5
4.20 4.10
4.01 Cooling: -10°C DB ~ 46°C DB Heating: -20°C WB ~ 18°C WB
4.0 4.0 The remote controller temperature can be set from
3.70
3.59 * For further information please refer to the capacity tables in the Technical Data Book.
3.5 3.37 3.5 18°C up to 30°C (Cooling), 16°C up to 30°C (Heating)*1.
3.0 3.0 *1 Depending on the type of remote controller.
2.5 2.5
4 HP 5 HP 6 HP 8 HP 10 HP 4 HP 5 HP 6 HP 8 HP 10 HP
LE 2 LE 1 LE 2 LE 1

Blue fin condenser LE1 LE2

The anti-corrosion Blue Fin treatment of the heat


Energy savings design LE1 LE2 exchanger provides greater resistance against corrosion.
All models are equipped with Blue Fin condenser.

1
Panasonic A large-capacity inverter compressor has been adopted. The inverter
6 2 Inverter Compressor compressor is superior in performance with improved partial-load capacity.

2 Printed Circuit Board The number of PCB is 2 pieces for making maintenance easier.
4
A large accumulator has been adopted to maintain compressor reliability
3 Accumulator because of the increased refrigerant quantity, which allows an extended
max piping length. Heat exchanger
Checking load and outside temperature, the DC motor is controlled for ( blue fin condenser ) [ Rear view ]
4 DC Fan Motor optimum air volume.
7
The newly designed fan blades have been developed to inhibit air turbulence
5 Newly Designed Fan and to increase efficiency. As fan diameter has been increased its size, the air

3
volume has been increased whilst maintaining a same sound level. High durability outdoor unit LE1 LE2

6
Heat Exchanger & The heat exchanger size and the copper tube sizes in the heat exchanger have
Copper Tubes been redesigned to increase efficiency. Corrosion-resistance treated for high
5 1 A centrifugal separator has been adopted to improve oil separation efficiency and resistance to rust and salty air to assure Outer body
7 Oil Separator
reduce refrigerant pressure loss.
long-lasting performance. Screws
PC board

Metal part in
Note: Selecting this unit does not completely eliminate
air flow route
the possibility of rust developing. For details
concerning unit installation and maintenance,
Flexible demand response with the optional terminal block LE1 LE2 please consult an authorised dealer.
* Specific model with suffix “E” has this treatment.

Demand Response Flexible Demand Response with the CZ-CAPDC2*1


Featuring inverter control technology, all Panasonic Mini FSV Setting is possible as 0% or in the range from 40 to 100% (in
systems are Demand Response Management (DRM) ready. steps of 5%). At the time of shipping, setting has been done
With this control, power consumption at times of peak load to the three steps of 0%, 70% and 100%.
can be set in three steps to deliver optimum performance. *1 An outdoor Seri-Para l/O unit (CZ-CAPDC2) is required for demand input signal.
This helps to reduce annual power consumption with minimal * Demand timer setting for high spec remote controller is available. Quiet operation mode LE1 LE2
loss in comfort.
*Terminal block parts to be supplied separately. Please ask your dealer. • Quiet operation mode reduces outdoor unit operating sound down to 7dB than rating.
Power input
Set point Normal operation • 3-step set point is available.
• External input signal is also available.
DRED
Outdoor unit (Demand controller)
* Timer setting of quiet operation mode is available in High-spec Remote Controller.
Relay contact Time
point:No voltage
relay Power input
Current input is
DC 24 V 10 mA Level 1 100% (Preset)
DRM1 DRM2 DRM3 C Possible to change 40-100%
Terminal block Level 2 70% (Preset)
Level 3 0% (Always in stop condition)

46 47

180730_FSV_ASIA_D_2.indd 46-47 2018/10/12 14:39:10


Mini-FSV LE Series Mini-FSV LE Series

2-WAY Mini-FSV LE2 Series 2-WAY Mini-FSV LE1 Series


HP 4 4 5 5 6 6 HP 8 10
Model name U-8LE1H7 U-10LE1H7
Model name U-4LE2H4 U-4LE2H7 U-5LE2H4 U-5LE2H7 U-6LE2H4 U-6LE2H7
Power supply 380/400/415V/3-phase/50Hz 380/400V/3-phase/60Hz 380/400/415V/3-phase/50Hz 380/400V/3-phase/60Hz
220/230/240V/ 380/400/415V/ 220/230/240V/ 380/400/415V/ 220/230/240V/ 380/400/415V/ Voltage 380V 400V 415V 380V 400V 415V
Power supply 1-phase/50Hz 3-phase/50Hz 1-phase/50Hz 3-phase/50Hz 1-phase/50Hz 3-phase/50Hz
220/230V/1-phase/60Hz 380/400V/3-phase/60Hz 220/230V/1-phase/60Hz 380/400V/3-phase/60Hz 220/230V/1-phase/60Hz 380/400V/3-phase/60Hz kW 22.4 28.0
Cooling
Voltage 220V 230V 240V 380V 400V 415V 220V 230V 240V 380V 400V 415V 220V 230V 240V 380V 400V 415V BTU/h 76,500 95,600
Capacity
kW 12.1 12.1 14.0 14.0 15.5 15.5 kW 25.0 28.0
Cooling Heating
BTU/h 41,300 41,300 47,800 47,800 52,900 52,900 BTU/h 85,300 95,600
Capacity Cooling W/W 4.20 3.59
kW 12.5 12.5 16.0 16.0 16.5 16.5
Heating EER/COP
BTU/h 42,700 42,700 54,600 54,600 56,300 56,300 Heating W/W 4.52 4.55

Cooling W/W 5.08 5.08 4.61 4.61 4.27 4.27 Dimensions (H/W/D) mm 1,500 x 980 x 370 1,500 x 980 x 370
EER/COP Net weight kg 132 133
Heating W/W 5.95 5.95 5.25 5.25 5.08 5.08
Dimensions HxWxD mm 996 x 980 x 370 996 x 980 x 370 996 x 980 x 370 996 x 980 x 370 996 x 980 x 370 996 x 980 x 370 Running current A 8.70 8.25 7.95 12.7 12.1 11.7
Cooling
Net weight kg 106 106 106 106 106 106 Electrical Power input kW 5.33 5.33 5.33 7.8 7.80 7.80

Running current A 11.90 11.40 10.90 3.89 3.69 3.56 15.20 14.50 13.90 4.91 4.67 4.50 18.10 17.30 16.60 5.87 5.57 5.37
ratings Running current A 9.05 8.60 8.25 10.0 9.55 9.20
Cooling Heating
Power input kW 2.38 2.38 2.38 2.38 2.38 2.38 3.04 3.04 3.04 3.04 3.04 3.04 3.63 3.63 3.63 3.63 3.63 3.63 Power input kW 5.53 5.53 5.53 6.15 6.15 6.15
Electrical
ratings Running current A 10.60 10.10 9.70 3.47 3.29 3.18 15.20 14.60 14.0 4.93 4.68 4.51 16.20 15.50 14.90 5.25 4.99 4.81 Starting current A 1 1
Heating m3 / min 150 160
Power input kW 2.10 2.10 2.10 2.10 2.10 2.10 3.05 3.05 3.05 3.05 3.05 3.05 3.25 3.25 3.25 3.25 3.25 3.25
Air flow rate
Starting current A 1 1 1 1 1 1 L/s 2,500 2,666

m3 / min 69 69 72 72 74 74 Refrigerant amount at shipment kg R410A 6.30 R410A 6.60


Air flow rate Piping Gas pipe mm (inches) Ø19.05 (Ø3/4) Ø22.22 (Ø7/8)
L/s 1,150 1,150 1,200 1,200 1,233 1,233
connection Liquid pipe mm (inches) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8)
Refrigerant amount
kg R410A 6.70 R410A 6.70 R410A 6.70 R410A 6.70 R410A 6.70 R410A 6.70
at shipment
Cooling:-10˚CDB~+46˚CDB, Cooling:-10˚CDB~+46˚CDB,
Piping Gas pipe mm (inches) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ambient temperature operating range
Heating:-20˚CWB~+18˚CWB Heating:-20˚CWB~+18˚CWB
connection Liquid pipe mm (inches) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8)
Sound Normal mode dB(A) 59.0 62.0
Cooling: Cooling: Cooling: Cooling: Cooling: Cooling: pressure level
Ambient temperature -10˚CDB~+46˚CDB, -10˚CDB~+46˚CDB, -10˚CDB~+46˚CDB, -10˚CDB~+46˚CDB, -10˚CDB~+46˚CDB, -10˚CDB~+46˚CDB, (Cooling) Silent mode dB(A) 52.0 55.0
operating range Heating: Heating: Heating: Heating: Heating: Heating: Sound power
-20˚CWB~+18˚CWB -20˚CWB~+18˚CWB -20˚CWB~+18˚CWB -20˚CWB~+18˚CWB -20˚CWB~+18˚CWB -20˚CWB~+18˚CWB level (Cooling) Normal mode dB(A) 80.0 83.0
Sound Normal mode dB(A) 52.0 52.0 53.0 53.0 54.0 54.0
pressure level
(Cooling) Silent mode (3) dB(A) 45.0 45.0 46.0 46.0 47.0 47.0 * As a foot print.
Rated conditions: Cooling Heating
Sound power Normal mode ** High durable model (with suffix “E”) has same specifications.
dB 69.0 69.0 71.0 71.0 73.0 73.0 Global Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
level (Cooling)
remarks
* As a foot print. Outdoor air temperature 35˚C DB 7˚C DB / 6˚C WB
Rated conditions: Cooling Heating
** High durable model (with suffix “E”) has same specifications.
Global Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
remarks
Outdoor air temperature 35˚C DB 7˚C DB / 6˚C WB

Dimensions Dimensions
U-4LE2H4 / U-4LE2H7 U-8LE1H7 / U-10LE1H7
U-5LE2H4 / U-5LE2H7
U-6LE2H4 / U-6LE2H7
Dimensions : U-8LE1H7 / U-10LE1H7
Mounting hole (4-R6.5),
1 anchor bolt : M10
Air intake Air intake
Refrigerant tubing (liquid tube),
(10) 160 660 160 2 flared connection (ø9.52) for 8-10 HP finally.
(10) 160 660 160
230 200 160 350 Refrigerant tubing (gas tube),
Mounting hole (4-R6.5), 3
230 200 160 350 flared connection (ø19.05)
anchor bolt : M10 4 Refrigerant tubing port
(56) 5 Electrical wiring port (ø13)
Refrigerant tubing (liquid tube),
flared connection (Ø9.52) 6 Electrical wiring port (ø22)
(24.5) 18

Air intake A

412.5
(24)

370
330
412.5

7 Electrical wiring port (ø27)


450

Refrigerant tubing (gas tube),


370
330

170
flared connection (Ø15.88) 8 Electrical wiring port (ø35)

20
170

Refrigerant tubing port For U-10LE1H7


61

The tubing of the gas main has a diameter of ø22.22,

16
13

36
Electrical wiring port (Ø13)
61 Air discharge but the connection to the service valve of the outdoor
1
36

20

13 Electrical wiring port (Ø22) 49 980 unit has a diameter of ø19.05, so a flare has to be used.
Air discharge Consequently, be sure to use the enclosed joint tube B
Electrical wiring port (Ø27) 23° 4×ø 32 holes (holes for drain)
980 A VIEW and joint tube A in making connections (braze).
47.5 50

75.5
Electrical wiring port (Ø35) When using a drain pipe, install the drain socket
1 (field supply) onto the drain port. Seal the other
drain port with the rubber cap. 62.5
4×Ø32 holes (holes for drain)
A VIEW 370
When using a drain pipe, install the drain socket 980
(field supply) on to the drain port.Seal the other
drain port with the rubber cap. A VIEW

980
370 6 5
8 47 Air discharge Air intake 8 47
6 5 7
35

7 2

35
2 3
51

Air discharge Air intake

51
16

1500
Air intake
3
5

16
173
996

43

173
120

120
4 6
19

35 5
35 35 35
5 7 42 74
4
39

42 74
39

48 6
320

Z VIEW 100
100 8

39

469

39
29

48

48
121

7
121

82

Z VIEW Z VIEW
Z VIEW

121

121
29
60

82

48
82
6 7 8 8
82

36 60 4 89 60 36 60 60
4 6 7 8
30 4 4
30 Unit: mm 89 60 Unit: mm

48 49

180730_FSV_ASIA_D_2.indd 48-49 2018/10/12 14:39:14


Mini-FSV LE Series Mini-FSV LE Series

Distribution Joint Kits Piping design

CZ-P160BK2 Select the installation location so that the


Use: For indoor unit (Capacity after distribution joint is 22.4 kW or less.) length and size of refrigerant piping are
L1
within the allowable range shown in the LA L2
LB LC LD n
GAS TUBING LIQUID TUBING figure below. Less than
110 110 110 110 Main tube 400 mm
97 97 97 97 of unit H1
For
C C extension
B
B
B
C
C
C D EC D E
AB D D

72
72

72
A

72
1st branch 1 2 3 n-1
B Distribution B A A Insulation Distribution C C L3 H2
Insulation Joint Joint
D D Unit distribution tube
C C E E
Unit: mm
Distribution joint (CZ-P160BK2)
Ball valve (field supply)

Size of connection point on each part (Shown are inside diameters of tubing)
Size Part A Part B Part C Part D Part E
(mm) Ø19.05 Ø15.88 Ø12.70 Ø9.52 Ø6.35
Ranges that Apply to Refrigerant Piping Lengths
Dimension
(inches) Ø3/4 Ø5/8 Ø1/2 Ø3/8 Ø1/4
and to Differences in Installation Heights
Items Marks Contents Length (m)
Actual length 120
L1 Max. tubing length
Equivalent length 140
Wiring System Diagrams ∆L (L2 – L3)
Difference between max. length and min. length
40
Allowable tubing length from the No.1 distribution joint
3-3. Wiring System Diagrams
Indoor unit
1, 2... n Max. length of each distribution tube 30
(No. 1) Outdoor unit : single-phase model Power supply Total max. tubing length including length of
Power supply L 1, 2... n-1+L1 150
220 – 240V ~50Hz N
L
N
220 – 240V, Single-phase, ~ 50Hz each distribution tube (only narrow tubing)
220 – 230V ~60Hz 220 – 230V, Single-phase, ~ 60Hz
Ground B
C When outdoor unit is installed higher than indoor unit 50
Remote U1 U1
Ground Allowable elevation H1
controller
U2 U2 When outdoor unit is installed lower than indoor unit 40
D difference
WHT 1 1 R1 Ground
BLK 2 2 R2 H2 Max. difference between indoor units 15

Ground L = Length, H = Height


C In case of 3-phase power supply
Indoor unit Outdoor unit : 3-phase model
(No. 2) A
Power supply L L1
L Ground L1 Power supply
N U1
L2 L2
220 – 240V ~50Hz N 380 – 415V, 3-phase, ~50Hz
U2
L3 L3
220 – 230V ~60Hz N 380 – 400V, 3-phase, ~60Hz
Ground N
B U1
Remote U2
controller D Ground
WHT 1 1 R1
BLK 2 2 R2
Ground Tubing Size
C
Indoor unit Outdoor unit : single-phase model Outdoor unit : 3-phase model
Power supply
Group control:
L
(No. 3) Main Tubing Size (LA) Main Tubing Size After Distribution (LB, LC...)
L
220 – 240V ~50Hz N 2P terminal board 4P terminal board
220 – 230V ~60Hz
N
12.1 kW 14.0 kW 15.5 kW Total Below kW 7.1 12.1 14.0 15.5
Ground B Ground capacity after
E U1 System kilowatts 12.1 14.0 15.5 distribution Over kW – 7.1
U2

Gas tubing mm (inches) ø15.88 (ø5/8) ø19.05 (ø3/4) (mm) ø12.7 ø15.88 ø19.05
U1 U2 U1 U2
R1
R2 Gas tubing
Liquid tubing mm (inches) ø9.52 (ø3/8) (inches) ø1/2 ø5/8 ø3/4
Ground L N U1 U2 L1 L2 L3 N U1 U2 Tubing size
C Power supply Inter-unit (mm) ø9.52
Power supply Inter-unit Note :If the system consists of only one indoor unit with an outdoor 6HP, the Liquid tubing
control wiring control wiring
main tube of the unit (LA) should be ø19.05. Convert ø19.05 to ø15.88 using (inches) ø3/8
Indoor unit
a reducer (field supply) close to the indoor unit and then make the
(No. n) kW = kilowatts
Power supply L connection.
Note :In case the total capacity of connected indoor units exceeds the total
L
N
220 – 240V ~50Hz N Indoor unit
220 – 230V ~60Hz Ground capacity of the outdoor units, select the main tubing size for the total
Ground B capacity of the outdoor units.
Remote
controller D
U1
U2
7P terminal board
Indoor Unit Tubing Connection ( 1, 2... n–1)
WHT 1 1 R1
BLK 2 2 R2 Indoor unite type 22 28 36 45 56 73 90 106 140 160
Gas tubing mm (inches) ø12.7 (ø1/2) ø15.88 (ø5/8)
Liquid tubing mm (inches) ø6.35 (ø1/4) ø9.52 (ø3/8)
L N U1 U2 R1 R2
Power Unit Remote
supply control controller
wiring line
T1, F1, E1, D1, L1 Types
6P terminal board 5P terminal board System Limitations
Outdoor units 12.1 kW 14.0 kW 15.5 kW

Number of max.
L N U1 U2 R1 R2 6 8 9
L N U1 U2 connectable indoor units
Power Unit Remote
supply control control Power Unit
Max. allowable indoor/
line line supply control 50 – 130%
line outdoor capacity ratio
U1, Y1, M1, P1, R1 Types K1 Type
kW = kilowatts
Fig. 2-1

50 51

180730_FSV_ASIA_D_2.indd 50-51 2018/10/12 14:39:15


Indoor Unit

Indoor Units Key Indoor Units Equipped DC motors DC


motor

Wide choice of models depending on


the indoor requirements

ECONAVI sensor All Ducted Series / F2,M1,Z1,E2,E1,H1, type

Discharge air temperature control


Smart sensors control discharge air temperature
Providing outstanding energy-saving for precise room temperature control. Air intake
sensor
performance, Panasonic’s inverter Possible to reduce cold drafts during heating
VRF System can be connected to operation. E3 sensor

ECONAVI to detect when energy is E1 sensor


being wasted. ECONAVI senses the
presence or absence of people and ECONAVI Sensor Air discharge sensor

the level of activity in each area of an Detection of the level of activity CZ-CENSC1
enables optimum power saving
office. When unnecessary heating or Wall Mounted / K2 (22~36), K2 (45~106) type
Activity or absence of people at their desks and the level of activity in the office
cooling is detected, indoor units are are detected in real time. Cooling or heating is automatically adjusted for
individually controlled to match office optimum operation required to lower power consumption.
Noise reducing external valve kit
conditions for energy-saving
Sensor is remotely located to maximize To reduce noise level of expansion valve.
operation.
the energy saving effect (Optional accessory)
Pillars, walls, cabinets and other fittings obstruct the sensors, reducing the area
of detection and lowering the energy-saving effect. Taking into consideration
blind spots, Panasonic enables the optimum layout for sensors in any office.
Compact design with flat surface
enables seamless match with any
High-spec Wired Remote Controller type of room interior
CZ-P56SVK2 (for 22 - 56 type)
CZ-P160SVK2 (for 73 - 106 type)

Large 3.5" full-dot LCD with white LED backlight


Characters and icons are clearly displayed for
improved visibility. The display is also large enough to Remote Temperature Sensor
provide a wide range of information for easy
confirmation of operation conditions. • This is a remote sensor which can be used with indoor
units. Use it to detect the room temperature when no
Stylish, easy-to-use touch key design remote controller sensor or body sensor is used (connection
The elegant, flat design features large touch keys in a to a system without a remote controller is possible).
simple layout enabling easy, intuitive operation. • For joint use with a remote control switch, use the remote
control switch as main remote controller.

CZ-RTC5B CZ-CSRC3

52 53

180730_FSV_ASIA_D_2.indd 52-53 2018/10/12 14:39:22


Indoor Unit Indoor Unit

FSV Indoor Units Range


Wide choice of models depending on the indoor requirements
Class 22 28 36 45 56 60 73 90 106 140 160 180 224 280 Wireless remote control
Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating
Type with
Capacity Type with
separately
kW 2.2/2.5 2.8/3.2 3.6/4.2 4.5/5.0 5.6/6.3 6.0/7.1 7.3/8.0 9.0/10.0 10.6/11.4 14.0/16.0 16.0/18.0 18.0/20.0 22.4/25.0 28.0/31.5 built-in
installed
Functions
sensor
Type BTU/h 7,500/8,500 9,600/11,000 12,000/14,000 15,000/17,000 19,000/21,000 20,400/24,200 25,000/27,000 30,000/34,000 36,000/39,000 47,800/54,600 54,600/61,500 61,400/68,200 76,400/85,300 95,500/107,500 sensor


F2 type self-diagnosing Auto fan Mild dry

Mid Static Ducted DC


motor
S-22MF2E5A S-28MF2E5A S-36MF2E5A S-45MF2E5A S-56MF2E5A S-60MF2E5A S-73MF2E5A S-90MF2E5A S-106MF2E5A S-140MF2E5A S-160MF2E5A Auto restart Drain pump DC motor

M1 type


self-diagnosing Auto fan Mild dry
Slim Low Static
Ducted DC
motor
S-22MM1E5A S-28MM1E5A S-36MM1E5A S-45MM1E5A S-56MM1E5A Auto restart Drain pump DC motor

Z1 type


self-diagnosing Auto fan Mild dry
Slim Low Static (High Static Ducted)

Ducted Twenty Series DC


motor
S-22MZ1H4A S-28MZ1H4A S-36MZ1H4A S-45MZ1H4A S-56MZ1H4A S-60MZ1H4A S-73MZ1H4A Auto restart DC motor

E2 type High Fresh Air High Fresh Air


High Static Ducted / self-diagnosing Auto fan Mild dry

Energy Saving High- DC


Fresh Air Ducted
motor

S-180ME2E5 * S-224ME2E5 S-280ME2E5 Auto restart DC motor


E1 type
High Static Ducted self-diagnosing Auto fan Mild dry Auto restart
S-73ME1E5 S-106ME1E5 S-140ME1E5 S-224ME1E5 S-280ME1E5

High Fresh Air High Fresh Air High Fresh Air


H1 type
High Fresh Air
self-diagnosing Auto fan Auto restart
Ducted
S-140MH1H5 S-224MH1H5 S-280MH1H5

(Class of 45 - 106)
K2 type
Wall Mounted
S-22MK2E5A S-28MK2E5A S-36MK2E5A S-45MK2E5A S-56MK2E5A S-73MK2E5A S-106MK2E5A
• • self-diagnosing Auto fan Mild dry

DC
motor
Auto flap

Auto restart Air swing DC motor

U2 type **
4-Way Cassette
Panel No. CZ-KPU3
Panel No. CZ-KPU3A
• • self-diagnosing Auto fan Mild dry Auto flap

DC
motor

S-22MU2E5A S-28MU2E5A S-36MU2E5A S-45MU2E5A S-56MU2E5A S-60MU2E5A S-73MU2E5A S-90MU2E5A S-106MU2E5A S-140MU2E5A S-160MU2E5A Auto restart Air swing Drain pump DC motor

Y2 type
4-Way Mini Cassette
Panel No. CZ-KPY3AW
• • self-diagnosing Auto fan Mild dry Auto flap

DC
motor
S-22MY2E5A S-28MY2E5A S-36MY2E5A S-45MY2E5A S-56MY2E5A Auto restart Air swing Drain pump DC motor

L1 type
2-Way Cassette
Panel No. CZ-02KPL2
Panel No. CZ-03KPL2 S-22ML1E5 S-28ML1E5 S-36ML1E5 S-45ML1E5 S-56ML1E5 S-73ML1E5
• • self-diagnosing Auto fan Mild dry Auto flap

(Only for S-73ML1E5) Auto restart Air swing Drain pump

D1 type
1-Way Cassette
Panel No. CZ-KPD2 S-28MD1E5 S-36MD1E5 S-45MD1E5 S-56MD1E5 S-73MD1E5
• • self-diagnosing Auto fan Mild dry Auto flap

DC
motor

Auto restart Air swing Drain pump DC motor

• •
T2 type self-diagnosing Auto fan Mild dry Auto flap
Ceiling DC
motor

S-36MT2E5A S-45MT2E5A S-56MT2E5A S-73MT2E5A S-106MT2E5A S-140MT2E5A Auto restart Air swing DC motor


P1 type
Floor Standing self-diagnosing Auto fan Mild dry Auto restart

S-22MP1E5 S-28MP1E5 S-36MP1E5 S-45MP1E5 S-56MP1E5 S-71MP1E5

R1 type
Concealed Floor
Standing
• self-diagnosing Auto fan Mild dry Auto restart

S-22MR1E5 S-28MR1E5 S-36MR1E5 S-45MR1E5 S-56MR1E5 S-71MR1E5


* Only for High Static Ducted
** Only for CZ-KPU3A Self-diagnosing Automatic fan Intelligent auto Automatic restart function DC
Mild dry Air swing Built-in drain pump DC motor
function operation flap control for power failure motor

54 55

180730_FSV_ASIA_D_2.indd 54-55 2018/10/12 14:39:36


Indoor Unit / F2 Type Indoor Unit / F2 Type

F2 TYPE Mid Static Ducted DC


motor

ECONAVI ready
S-60MF2E5A / S-73MF2E5A / S-90MF2E5A
The new F2 type is designed specifically for applications requiring fixed
square ducting. An anti-mould filter is equipped as standard.
S-22MF2E5A / S-28MF2E5A / S-36MF2E5A / For all indoor units
S-45MF2E5A / S-56MF2E5A CZ-RWSK2 +
CZ-CENSC1 CZ-RTC5B CZ-RWSC3
S-106MF2E5A / S-140MF2E5A / S-160MF2E5A

Built-in Drain External electrical equipment


Self-diagnosing Automatic Mild dry Automatic Built-in Drain pump (DC motor box makes maintenance easy
Function Fan Restart Pump
Operation Function pump)

Technical focus Standardised height of


290 mm for all models
• Variable external static pressure control • Air off sensor avoids cold air drafts during heating
Height standardisation enables easy
• Industry-leading low sound levels from 25 dB(A) operation
and uniform installation for models
• Built-in drain pump provides 702 mm lift • Configurable air temperature control with different capacities.
• Easy to install and maintain • Anti-mould washable filters included

• Built-in filter
• Side removable filter
Variable external static pressure control
Optimal airflow set-up is possible depending on ducting design and conditions.

Optimal Control by DC Motor Discharge air temperature control


• Possible to control discharge air temperature for accurate room
For short For long ducting or Air intake
sensor
temperature control.
ducting such 10Pa 150Pa for usage with high • Possible to reduce cold drafts during heating operation. E3 sensor
as hotels efficiency filter
Before spec-in, please consult with an authorised Panasonic dealer.
E1 sensor
* Please refer to technical databook for detail.
Air discharge sensor

V-shaped heat exchanger


System example To improve heat exchange efficiency, an original V-shaped heat exchanger was
Rectangle duct Canvas duct developed incorporating a conventional high-efficiency slit fan and high-efficiency
An inspection port (450 mm x 450 mm or larger) is grooved heat transfer tubes. This increases the heat exchange surface area by
required at the lower side of the indoor unit body. about 80%.
Increases surface area
by about 30 to 80%

Inspection port Intake grille


(450 x 450 mm or more)

More powerful drain pump


Up to 300 mm
Using a high-lift drain pump, drain piping can be
Up to 500 mm
elevated up to 702 mm from the base of the unit.
202 mm

56 57

180730_FSV_ASIA_D_2.indd 56-57 2018/10/12 14:39:41


Indoor Unit / F2 Type Indoor Unit / F2 Type

F2 TYPE Mid Static Ducted

Model Name S-22MF2E5A S-28MF2E5A S-36MF2E5A S-45MF2E5A S-56MF2E5A S-60MF2E5A S-73MF2E5A S-90MF2E5A S-106MF2E5A S-140MF2E5A S-160MF2E5A
Power source 220/230/240V, 1 phase - 50/60Hz 220/230/240V, 1 phase - 50/60Hz
kW 2.2 2.8 3.6 4.5 5.6 6.0 7.3 9.0 10.6 14.0 16.0
Cooling capacity
BTU/h 7,500 9,600 12,000 15,000 19,000 20,400 25,000 30,000 36,000 47,800 54,600
kW 2.5 3.2 4.2 5.0 6.3 7.1 8.0 10.0 11.4 16.0 18.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 24,200 27,000 34,000 39,000 54,600 61,500
Cooling kW 0.070/0.070/0.070 0.070/0.070/0.070 0.070/0.070/0.070 0.070/0.070/0.070 0.100/0.100/0.100 0.120/0.120/0.120 0.120/0.120/0.120 0.135/0.135/0.135 0.195/0.195/0.195 0.215/0.215/0.215 0.225/0.225/0.225
Power input
Heating kW 0.070/0.070/0.070 0.070/0.070/0.070 0.070/0.070/0.070 0.070/0.070/0.070 0.100/0.100/0.100 0.120/0.120/0.120 0.120/0.120/0.120 0.135/0.135/0.135 0.200/0.200/0.200 0.210/0.210/0.210 0.225/0.225/0.225
Running Cooling A 0.60/0.57/0.56 0.60/0.57/0.56 0.60/0.57/0.56 0.60/0.57/0.56 0.77/0.74/0.71 0.91/0.89/0.87 0.91/0.89/0.87 0.99/0.97/0.95 1.35/1.30/1.27 1.48/1.44/1.39 1.55/1.50/1.47
amperes Heating A 0.60/0.57/0.56 0.60/0.57/0.56 0.60/0.57/0.56 0.60/0.57/0.56 0.77/0.74/0.71 0.91/0.89/0.87 0.91/0.89/0.87 0.99/0.97/0.95 1.37/1.34/1.29 1.46/1.42/1.38 1.55/1.50/1.46
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan
m³/h 840/780/600 840/780/600 840/780/600 840/780/600 960/900/720 1,260/1,140/900 1,260/1,140/900 1,500/1,380/1,140 1,920/1,620/1,320 2,040/1,740/1,380 2,160/1,860/1,500
Air flow rate (H/M/L)
Fan motor L/s 233/217/167 233/217/167 233/217/167 267/250/220 267/250/220 350/317/250 350/317/250 417/383/317 533/450/367 567/483/383 600/517/417
Output kW 0.119 0.119 0.119 0.119 0.119 0.124 0.124 0.124 0.235 0.235 0.235
External static pressure Pa 70(10-150) 70(10-150) 70(10-150) 70(10-150) 70(10-150) 70(10-150) 70(10-150) 70(10-150) 100(10-150) 100(10-150) 100(10-150)
Power sound level (H/M/L) dB(A) 55/51/47 55/51/47 55/51/47 56/54/50 56/54/50 57/54/48 57/54/48 59/56/50 60/56/53 61/57/54 62/58/55
Sound pressure sound (H/M/L) dB(A) 33/29/25 33/29/25 33/29/25 34/32/28 34/32/28 35/32/26 35/32/26 37/34/28 38/34/31 39/35/32 40/36/33
Dimensions HxWxD mm 290x800x700 290x800x700 290x800x700 290x800x700 290x800x700 290x1,000x700 290x1,000x700 290x1,000x700 290x1,400x700 290x1,400x700 290x1,400x700
Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8)
Pipe
Gas mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8)
connections
Drain piping VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25
Net weight kg 29 29 29 29 29 34 34 34 46 46 46

Specifications are subject to change without notice.


Rated conditions: Cooling Heating
GLOBAL
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB
SIZE 60-90 MF2E5A Filter

1 Refrigerant piping joint (liquid tube) Ø9.52 Flare


2 Refrigerant piping joint (gas tube) Ø15.88 Flare
3 Upper drain port VP25 (O.D. Ø32 mm) 172 35
6

200 flexible hose supplied

28

32
4 Bottom drain port VP25 (O.D. Ø32 mm)
5 Suspension lug (4-12 × 30 mm)
9

280
6 Power supply outlet Inspection
3
26
7 Fresh air intake port (Ø150 mm) access
450 x 450 4
8 Flange for flexible air outlet duct

700
700

636
758
(Field supply)

9 Electrical component box


7
89

300
113 65
256
1

130 70

32
30
16-ø3holes
150

30
20
8
23 140 23
21 150 x 5 = 750 21 2
1000 33 27 186
5
1067(Suspension bolt pitch) (150) 290
(75)
54 792(Flange O.D.) 154

27
F2 TYPE MID STATIC DUCTED Dimensions

186
unit: mm

77
SIZE 22-56 MF2E5A
Filter

SIZE 106-160 MF2E5A Filter


1 Refrigerant piping joint (liquid tube) Ø6.35 Flare
2 Refrigerant piping joint (gas tube) Ø12.7 Flare
3 Upper drain port VP25 (O.D. Ø32 mm) 6 1 Refrigerant piping joint (liquid tube) Ø9.52 Flare
200 flexible hose supplied
172 35 2 Refrigerant piping joint (gas tube) Ø15.88 Flare
28

32

4 Bottom drain port VP25 (O.D. Ø32 mm) 3 Upper drain port VP25 (O.D. Ø32 mm)
5 Suspension lug (4-12 × 30 mm) 200 flexible hose supplied 6
4 Bottom drain port VP25 (O.D. Ø32 mm) 172 35

28
6 Power supply outlet
9
280

32
7 Fresh air intake port (Ø150 mm) 3 5 Suspension lug (4-12 × 30 mm)
Inspection
8 Flange for flexible air outlet duct access
26
6 Power supply outlet 9

280
9 Electrical component box
450 x 450 4
7 Fresh air intake port (Ø150 mm)
700

636
758

700

(Field supply) Inspection 3


26
7 8 Flange for flexible air outlet duct access
4
450 x 450
9 Electrical component box

700

636
758

700
89 (Field supply)
7
300
65
256

89
1

300
113 65
113

256
1
32

130 70
12-ø3holes
30

32
130 70
8 20-ø3holes

30
30
20

8 150

30
20
71 150 x 3 = 450 71 23 140 23 150 x 7 = 1050 23 140 23
2 71 71 2
800 33 27 186 1400 33 27 186
5 867(Suspension bolt pitch) (150) 5 1467(Suspension bolt pitch) (150) 290
290
(75)
(75)
54 592(Flange O.D.) 154 1192(Flange O.D.)
54 154
23

27
186

186
77

Dimensions: mm unit: mm

77
58 59

180730_FSV_ASIA_D_2.indd 58-59 2018/10/12 14:39:45


Indoor Unit / M1 Type Indoor Unit / M1 Type

M1TYPE Slim Low Static Ducted DC


motor
ECONAVI ready

Concealed duct
The ultra slim M1 type is one of the leading products of its type in the industry.
For all indoor units
With a height of only 200 mm, it provides greater flexibility and adaptability for various applications.
CZ-RWSK2 +
In addition, high efficiency and extreme low noise level make it highly suitable for hotels and small offices.
CZ-CENSC1 CZ-RTC5B CZ-RWSC3
S-22MM1E5A / S-28MM1E5A / S-36MM1E5A
S-45MM1E5A / S-56MM1E5A

Model Name S-22MM1E5A S-28MM1E5A S-36MM1E5A S-45MM1E5A S-56MM1E5A


Power source 220/230/240 V, 1 phase - 50 / 60 Hz
kW 2.2 2.8 3.6 4.5 5.6
Self-diagnosing Automatic Mild dry Automatic Built-in Drain Cooling capacity
Function Fan Restart Pump BTU/h 7,500 9,600 12,000 15,000 19,000
Operation Function
kW 2.5 3.2 4.2 5.0 6.3
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000
Cooling kW 0.036/0.036/0.036 0.040/0.040/0.040 0.042/0.042/0.042 0.049/0.049/0.049 0.064/0.064/0.064
Technical focus Power input
Heating kW 0.026/0.026/0.026 0.030/0.030/0.030 0.032/0.032/0.032 0.039/0.039/0.039 0.054/0.054/0.054

Running Cooling A 0.26/0.26/0.26 0.30/0.30/0.30 0.31/0.31/0.31 0.37/0.37/0.37 0.48/0.48/0.48


• Ultra-slim profile: 200 mm for all models current Heating A 0.23/0.23/0.23 0.27/0.27/0.27 0.28/0.28/0.28 0.34/0.34/0.34 0.45/0.45/0.45
• DC fan motor greatly reduces power consumption Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan
• Ideal for hotel application with very narrow false ceilings m³/h 480/420/360 510/450/390 540/480/420 630/570/480 750/690/600
Air flow rate (H/M/L)
• Anti-mould washable filters included Fan L/s 133/117/100 142/125/108 150/133/117 175/158/133 208/192/167
• Easy maintenance and service by external electrical box Motor output kW 0.05 0.05 0.05 0.05 0.05
• 40 Pa static pressure enables ductwork to be fitted. External static pressure Pa 10 (30) 15 (30) 15 (40) 15 (40) 15 (40)
• Includes drain pump Sound power level (H/M/L) dB 43/42/40 45/44/42 47/45/43 49/47/45 52/50/48
Sound pressure level (H/M/L) dB(A) 28/27/25 (30/29/27)* 30/29/27 (32/31/29)* 32/30/28 (34/32/30)* 34/32/30 (36/34/32)* 35/33/31 (37/35/32)*
Dimensions HxWxD mm 200 x 750 x 640 200 x 750 x 640 200 x 750 x 640 200 x 750 x 640 200 x 750 x 640
Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4)
Pipe
Ultra-slim profile for all models connections
Gas mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2)
Drain piping VP-20 VP-20 VP-20 VP-20 VP-20

200mm height for all models allows installation in Net weight kg 19 19 19 19 19

very narrow ceilings. Rated conditions: Cooling Heating


Specifications are subject to change without notice. * With booster cable.
200 GLOBAL
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
mm REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB

M1 TYPE SLIM LOW


STATIC DUCTED
Drain pump with increased power! Up to 300 mm Dimensions
Using the built-in high-lift drain pump, the drain Inspection access
piping rise height can be increased to 653 mm from Up to 500 mm
the lower surface of the body.
153 mm

(suspension bolt pitch)


Inspection access
(450 x 450)
Field supply

Hole

Hole

(suspension bolt pitch) Inspection access panel


Ceiling
1 Refrigerant piping joint (narrow tube)
Hole

(air discharge space)


2 Refrigerant piping joint (wide tube)
3 Upper and bottom drain port (O.D. 26 mm)
4 Suspension lug
5 Power supply outlet (2- Ø30)
6 Flange for air intake duct
7 Pl cover
8 Electrical component box
9 Frame filter (air discharge space)
View A. Frame Filter Uninstalled
unit: mm

60 61

180730_FSV_ASIA_D_2.indd 60-61 2018/10/12 14:39:48


Indoor Unit / Z1 Type Indoor Unit / Z1 Type

Z1 TYPE Slim
Concealed duct
Low Static Ducted Twenty Series ECONAVI ready

The ultra slim Z1 type is one of the leading products of its type in the industry.
With a height of only 200 mm, it provides greater flexibility and adaptability for various applications.
DC
motor
For all indoor units
In addition, high efficiency and extreme low noise level make it highly suitable for hotels and small offices. CZ-RWSK2 +
S-22MZ1H4A/ S-28MZ1H4A/ S-36MZ1H4A/ S-73MZ1H4A CZ-CENSC1 CZ-RTC5B CZ-RWSC3
S-45MZ1H4A/ S-56MZ1H4A/ S-60MZ1H4A

Model Name S-22MZ1H4A S-28MZ1H4A S-36MZ1H4A S-45MZ1H4A S-56MZ1H4A S-60MZ1H4A S-73MZ1H4A


Power source 220/230/240 V, 1 phase - 50 / 60 Hz
kW 2.2 2.8 3.6 4.5 5.6 6.0 7.3
Self-diagnosing Automatic Mild dry Automatic Cooling capacity
Function Fan Restart BTU/h 7,500 9,500 12,200 15,300 19,100 20,500 24,900
Operation Function
kW 2.5 3.2 4.2 5.1 6.4 7.1 8.0
Heating capacity
BTU/h 8,500 10,900 14,300 17,400 21,800 24,200 27,300
Cooling kW 0.075/0.075/0.075 0.080/0.080/0.080 0.085/0.085/0.085 0.095/0.095/0.095 0.100/0.100/0.100 0.100/0.100/0.100 0.125/0.125/0.125
Technical focus Power input
Heating kW 0.075/0.075/0.075 0.080/0.080/0.080 0.085/0.085/0.085 0.095/0.095/0.095 0.100/0.100/0.100 0.100/0.100/0.100 0.125/0.125/0.125

Running Cooling A 0.50/0.47/0.45 0.55/0.52/0.50 0.60/0.57/0.55 0.70/0.68/0.65 0.75/0.72/0.70 0.75/0.72/0.70 0.80/0.78/0.75


• Ultra-slim profile: 200 mm for all models current Heating A 0.50/0.47/0.45 0.55/0.52/0.50 0.60/0.57/0.55 0.70/0.68/0.65 0.75/0.72/0.70 0.75/0.72/0.70 0.80/0.78/0.75
• DC fan motor greatly reduces power consumption Type Sirroco fan Sirroco fan Sirroco fan Sirroco fan Sirroco fan Sirroco fan Sirroco fan
• Ideal for hotel application with very narrow false ceilings m³/h 480/420/360 600/540/420 600/540/420 690/630/510 720/660/540 870/750/630 1,080/840/660
Air flow rate (H/M/L)
• Easy maintenance and service by external electrical box Fan L/s 133/117/100 167/150/117 167/150/117 192/175/142 200/183/150 242/208/175 300/233/183
• 29 Pa static pressure enables ductwork to be fitted. Motor output W 60 60 60 60 60 60 60
• Drain pump (optional) External static pressure Pa 10-30 10-30 10-30 10-30 10-30 10-30 10-30
Sound power level (H/M/L) dB 50/49/47 52/51/49 54/52/50 56/54/52 57/55/53 60/57/55 62/60/58
Sound pressure level (H/M/L) dB(A) 28/27/25 30/29/27 32/30/28 34/32/30 35/33/31 38/35/33 40/38/36
Dimensions HxWxD mm 200×830×500 200×830×500 200×830×500 200×830×500 200×830×500 200×830×500 200x1,050×550
Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8)
Pipe
Ultra-slim profile for all models connections
Gas mm (inches)
O.D. Ø20.5 mm /
Ø12.7 (Ø1/2) Ø12.7 (Ø1/2)
O.D. Ø20.5 mm /
Ø12.7 (Ø1/2)
O.D. Ø20.5 mm /
Ø12.7 (Ø1/2)
O.D. Ø20.5 mm /
Ø12.7 (Ø1/2)
O.D. Ø20.5 mm /
Ø15.88 (Ø5/8)
O.D. Ø20.5 mm /
Ø15.88 (Ø5/8)
O.D. Ø20.5 mm /
Drain piping
I.D. Ø15.5mm I.D. Ø15.5mm I.D. Ø15.5mm I.D. Ø15.5mm I.D. Ø15.5mm I.D. Ø15.5mm I.D. Ø15.5mm
200mm height for all models allows installation in Net weight kg 17 17 18 18 18 18 24
very narrow ceilings.
Specifications are subject to change without notice.
Rated conditions: Cooling Heating
GLOBAL
200 REMARKS
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
mm Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB

Z1 TYPE SLIM LOW


STATIC DUCTED
Drain pump with increased power! (optional) TWENTY SERIES SIZE 22-60MZ1H4A SIZE 73MZ1H4A
Using the optional high-lift drain pump, the drain Dimensions d d

piping rise height can be increased to 700 mm from


the drain pipe port.

Air outlet duct side


Air outlet duct side

797.6(Flange)

1,050
1,085

962 (Flange)
845
780
715
867.6
830

926.6

65
40
69

19
19.3

41.3
CZ-73DMZ1

200
102 55

150

66.5
117.4 55.4 185
185 e e 200 38 453
62 400.9 9.5
200
30 b a 550
b a

16
a) Refrigerant tubing joint (liquid tube) 27 500

131
b) Refrigerant tubing joint (gas tube)

30
154
130.6
c) Bottom drain port O.D.Ø20.5 mm /

55
f

153.9
123.5
I.D. Ø15.5mm c g

14
d) Suspension lug (4 – 12 × 30 mm) 411

37.8

21.9
54.8
e) Power supply outlet g
f c
f ) Flange for flexible air outlet duct 89.6

g) Electrical component box unit: mm

62 63

180730_FSV_ASIA_D_2.indd 62-63 2018/10/12 14:39:51


Indoor Unit / E2 Type Indoor Unit / E2 Type

E2 TYPE High Static Ducted DC


motor

Concealed duct / Air conditioning mode


High static and large airflow ducted for exceptional installation flexibility.
For all indoor units
CZ-RWSK2 +
CZ-RTC5B CZ-RWSC3
S-180ME2E5 / S-224ME2E5 / S-280ME2E5

Model Name S-180ME2E5 S-224ME2E5 S-280ME2E5


Power source 220/230/240 V, 1 phase - 50/60Hz
kW 18.0 22.4 28.0
Self-diagnosing Automatic Mild dry Automatic Cooling capacity
Function Fan Restart BTU/h 61,400 76,400 95,500
Operation Function
kW 20.0 25.0 31.5
Heating capacity
BTU/h 68,200 85,300 107,500
Cooling kW 0.400 0.440 0.715
Technical focus Power input
Heating kW 0.400 0.440 0.715

Running Cooling A 2.40 / 2.30 / 2.20 2.55 / 2.45 / 2.35 3.95 / 3.85 / 3.70
• Design flexibility thanks to high static pressure • Discharge air temperature control to reduce cold current Heating A 2.40 / 2.30 / 2.20 2.55 / 2.45 / 2.35 3.95 / 3.85 / 3.70
and large air volume drafts during heating operation Type Sirocco fan Sirocco fan Sirocco fan
• DC motor equipped • Configurable air temperature control m³/h 2,940 / 2,640 / 2,340 3,360 / 3,060 / 2,640 4,320 / 3,780 / 3,180
Fan Air flow rate (H/M/L)
• Power input 45% less (compared to E1 type) • Available Fresh Air Intake mode (See page 80-81) L/s 816 / 733 / 650 933 / 850 / 733 1,200 / 1,050 / 883
External static pressure Pa 140 (60/270) 140 (60/270) 140 (72/270)
Sound power level (H/M/L) dB 76 / 74 / 72 77 / 75 / 73 81 / 79 / 75
3-step static pressure set up
Sound pressure level (H/M/L) dB(A) 44 / 42 / 40 45 / 43 / 41 49 / 47 / 43
Dimensions HxWxD mm 479 x 1,453 x 1,205 479 x 1,453 x 1,205 479 x 1,453 x 1,205
You can select between the three Static Pressure modes of 60(72*) 140Pa 270Pa Liquid inches (mm) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
270 Pa/140 Pa/60(72*) Pa for extra installation flexibility. Pa Factory
Setting
Pipe
connections Gas inches (mm) Ø19.05 (3/4)* Ø19.05 (3/4)* Ø22.22 (7/8)*

* 28 kW model Drain piping VP-25 VP-25 VP-25


Net weight kg 102 102 106

Max. 270 Pa static pressure setting *Connection tubing which is included with the unit as an accessory is required.

Rated conditions: Cooling Heating


A maximum static pressure setting of a high 270 Pa enables the use of long ducts for installation in a wide range GLOBAL
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
of spaces. Ideal for large-scale offices, restaurants and other facilities. REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB

Sensible cooling 5-10% improved


New heat exchanger with φ7mm pipe that increases the heat transfer surface to improve sensible cooling E2 TYPE HIGH STATIC DUCTED Dimensions
(5-10% improvement) 5 27
4

1 Refrigerant piping (liquid pipes) Ø9.52

65

467
2 Refrigerant piping (gas pipes)

479
264
180 & 224 type: Ø19.05, 280 type: Ø22.22
No Rap Valve Kit required 3 Power supply outlet (Ø25 grommet, rubber)
4 Power supply outlet (spare) (Ø30 knock-out) 77
479 3

Thanks to improved performance, a Rap Valve Kit (CZ-P160RVK2) 5 Optional outlet for piping 300 40 800 or more 1310 600 or more
100 100 50 (service space) 132 1070 (service space) 467
6 Drain port 25 A, male thread 23
45 10×10 pitch=1000 7

60
156

is no longer required.

43
7 Duct connection for suction 6
8 Duct connection for discharge

207
45
1
28- 3.2 holes

131
2

(suspension bolt pitch)


4-37×12 holes
(for suspension bolts)

(service space)

1100
1170
1100 or more
1205

1220

1138
Discharge air temperature control

• Equipped with 4 sensors (Intake/ Discharge)


• Able to control discharge air temperature for

60
100 100 60 Approx.200 9×100 pitch=900
accurate room temperature control. 8 422
320 41 964 Inspection port 600
434 Inspection port 600 67 1200 67

• Possible to reduce cold drafts during heating


(suspension bolt pitch)
26- 3.2 holes (entire circumference)

1310

operation.

(service space)
610 or more
Ceiling Surface

1334
1453 unit: mm

64 65

180730_FSV_ASIA_D_2.indd 64-65 2018/10/12 14:39:54


Indoor Unit / E2 Type Indoor Unit / E2 Type

E2 TYPE Energy Saving


High Fresh Air Ducted DC
motor

Concealed duct high-static pressure For all indoor units


CZ-RWSK2 +
High static and large airflow ducted for exceptional installation flexibility. S-224ME2E5 / CZ-RTC5B CZ-RWSC3
S-280ME2E5

Model Name S-224ME2E5 S-280ME2E5


Power source 220/230/240 V, 1 phase - 50/60Hz

Self-diagnosing Automatic Automatic kW 22.4 28.0


Cooling capacity
Function Fan Restart BTU/h 76,400 95,500
Operation Function
kW 21.2 26.5
Heating capacity
BTU/h 72,200 90,400

Technical focus Power input


Cooling kW 0.290 0.350
Heating kW 0.290 0.350
Cooling A 1.80 2.10
• 100% fresh air intake for ventilation purpose • Power input 45% less (compared to H1 type) Running
current Heating A 1.80 2.10
• Design flexibility with high static pressure • Discharge air temperature control to reduce cold
Type Sirocco fan Sirocco fan
and large air volume drafts during heating operation
m³/h 1,700 2,100
• DC motor equipped • Configurable air temperature control Air flow rate
Fan L/s 472 583
Motor output W 560 560
High Fresh System FSV Outdoor unit External static pressure Pa 200 200
Sound power level dB 75 76
High Fresh System enables delivery of fresh outside air at Outside
High
to another room
Sound pressure level dB(A) 43 44
fresh air
almost the same temperature and humidity as indoor air Fresh Air
Ducted unit Indoor unit Indoor unit Dimensions HxWxD mm 479 x 1,453 x 1,205 479 x 1,453 x 1,205
without putting a burden on air conditioning. Liquid inches (mm) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8)
* Capable of treating outdoor air only. Indoor air conditioner SA SA Corridor Pantry /
Exhaust
air
Pipe
connections
Gas inches (mm) Ø19.05 (Ø3/4)* Ø22.22 (Ø7/8)*
units are required to adjust indoor air temperature.
W.C.
Drain piping VP-25 VP-25
Room
Net weight kg 102 106
*Connection tubing which is included with the unit as an accessory is required.
1st Area 2nd Area Last Area
→ Ducted
Air
unit → → → → Forced exhaust
Outside
fresh air office Hallway,Hall Pantry,W.C. GLOBAL Rated conditions: Cooling Heating
Meeting room Warehouse
REMARKS Outdoor air temperature 33˚C DB / 28˚C WB 0˚C DB / -2.9˚C WB
Specifications are subject to change without notice.

Mix operation unit with standard indoor units


Possible to combine High Fresh Air ducted indoor unit and standard air ducted indoor units.
When other indoor units are connected in same circuit, keep following capacity ratio. E2 TYPE HIGH STATIC DUCTED Dimensions
E2 type/Outdoor unit < 30%, and Total of indoors(incl. E2)/outdoor <100%
4
5 27

1 Refrigerant piping (liquid pipes) Ø9.52

65

467
2 Refrigerant piping (gas pipes)

479
264
224 type: Ø19.05, 280 type: Ø22.22
Discharge air temperature control 3 Power supply outlet (Ø25 grommet, rubber)
4 Power supply outlet (spare) (Ø30 knock-out) 77
479 3

• Equipped with 4 sensors (Intake/ Discharge) 5 Optional outlet for piping


6 Drain port 25 A, male thread 23
300
100 100
40
50
800 or more
(service space) 132
45
1310
1070
10×10 pitch=1000
600 or more
(service space)
7
467

60
156

• Able to control discharge air temperature for accurate

43
7 Duct connection for suction 6
8 Duct connection for discharge

207
room temperature control.

45
1
28- 3.2 holes

131
• Possible to reduce cold drafts during heating operation. 2

(suspension bolt pitch)


4-37×12 holes
(for suspension bolts)

(service space)

1100
1170
1100 or more
1205

1220

1138
Remark For High Static Ducted Series
Model Operation Rap valve kit 3way control PCB 3way valve kit Distribution Joint kit Distribution Joint kit
CZ-P160RVK2 CZ-CAPE2 CZ-P160HR3 <2pipes> <3pipes>

60
100 100 60 Approx.200 9×100 pitch=900
8 422
Inspection port 600
CZ-P160BK2
964
CZ-P224BH2
320 41
434 Inspection port 600 67 1200 67
for 22.4kW unit or less for 22.4kW unit (suspension bolt pitch)
26- 3.2 holes (entire circumference)

CZ-P680BK2 CZ-P680BH2 1310

for more than 22.4kW for 28.0kW unit

(service space)
610 or more
E2 Type Cooling Only - - - - -
Energy Saving
Cool or Heat 2pcs 2pcs - 2pcs -
High-Fresh Air Ceiling Surface

Ducted Heat Recovery - 2pcs 2pcs 1pc 1pc 1334


1453 unit: mm

66 67

180730_FSV_ASIA_D_2.indd 66-67 2018/10/12 14:39:56


Indoor Unit / E1 Type Indoor Unit / E1 Type

E1 TYPE High Static Ducted


Concealed duct high-static pressure
The E1 range of ducted units offers improved design flexibility for extended duct
layouts as a result of their increased external static pressures. For all indoor units
S-73ME1E5/ CZ-RWSK2 +
S106ME1E5/ S-224ME1E5 / CZ-RTC5B CZ-RWSC3
S-140MH1H5 S-280ME1E5

Model Name S-73ME1E5 S-106ME1E5 S-140ME1E5 S-224ME1E5 S-280ME1E5

220/230/240 V, 1
Power source 220/230/240 V, 1 phase - 50 / 60 Hz
phase - 50 Hz
Self-diagnosing Automatic Mild dry Automatic
Function Fan Restart kW 7.3 10.6 14.0 22.4 28.0
Cooling capacity
Operation Function BTU/h 25,000 36,000 47,800 76,400 95,500
kW 8.0 11.4 16.0 25.0 31.5
Heating capacity
BTU/h 27,000 39,000 54,600 85,300 107,500
Technical focus Cooling kW 0.480/0.505/0.530 0.520/0.545/0.570 0.600/0.660/0.710 0.870/0.900/0.930 1.270/1.330/1.390
Power input
Heating kW 0.480/0.505/0.530 0.520/0.545/0.570 0.600/0.660/0.710 0.870/0.900/0.930 1.270/1.330/1.390
• Complete flexibility for ductwork design • Discharge air temperature control to reduce cold Cooling A 2.29/2.30/2.31 2.46/2.46/2.47 2.80/2.90/3.00 4.05/4.06/4.07 6.04/6.06/6.07
Running
• Can be located into a weatherproof housing for drafts during heating operation current Heating A 2.29/2.30/2.31 2.46/2.46/2.47 2.80/2.90/3.00 4.05/4.06/4.07 6.04/6.06/6.07
external installation • Configurable air temperature control Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan
Air flow rate (H/M/L) m³/h 1,380/1,320/1,260 1,800/1,680/1,500 2,160/2,100/1,980 3,360/3,190/2,980 4,320/4,200/3,960
Fan L/s 383/367/350 500/467/417 600/583/550 933/886/828 1,200/1,167/1,100
Motor output kW 0.2 0.2 0.35 0.2 0.4
System example External static pressure Pa 186 176 167 176 216 (235)*
Sound power level (H/M/L) dB 55/54/53 56/55/53 58/57/55 59/58/57 62/61/60
An inspection port (450 x 450 mm or more) is Sound pressure level (H/M/L) dB(A) 44/43/42 45/44/42 47/46/44 48/47/46 51/50/49 (52/51/50)*
required at the lower side of the indoor unit body Dimensions HxWxD mm 420 x 1,065 x 620 420 x 1,065 x 620 450 x 1,065 x 620 479 x 1,428 x 1,230 479 x 1,428 x 1,230
(field supply). Inspection port (450 x Liquid mm (inches) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8)
450 mm or more) Pipe
Gas mm (inches) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø19.05 (Ø3/4) Ø22.22 (Ø7/8)
connections
Drain piping VP-25 VP-25 VP-25 VP-25 VP-25
Net weight kg 47 50 54 110 120
Discharge air temperature control
Specifications are subject to be changed without notice.
Rated conditions: Cooling Heating
• Equipped with 4 sensors (Intake/ Discharge) GLOBAL
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
* Via Jumper setting.
REMARKS
• Able to control discharge air temperature for Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB

accurate room temperature control.


• Possible to reduce cold drafts during heating
operation. E1 TYPE HIGH STATIC DUCTED Dimensions
SIZE 73-140 SIZE 224-280
1 Refrigerant liquid line (ø9.52) 1 Refrigerant piping (liquid pipes) Ø9.52
2 Refrigerant gas line (ø15.88) 2 Refrigerant piping (gas pipes)
3 Power supply entry 224 type: Ø19.05, 280 type: Ø22.22
4 Drain connection (20A / VP25) 940
793
3 Power supply outlet (Ø25 grommet, rubber)
5 Duct connection for suction 7 × 100 = 700 4 Power supply outlet (spare) (Ø30 knock-out)
6 Duct connection for discharge 55 20
5 Drain port 25 A, male thread
(Hole for full circumference)
22 - ø3.2
40 90 6 Duct connection for suction
60 7 Duct connection for discharge
48

(Suspension bolt pitch)


130

Remark For High Static Ducted Series 290

Model Operation Distribution Joint kit Distribution Joint kit


Electric box
View in direction of arrow X
Rap valve kit 3way control PCB 3way valve kit or more
80
CZ-P160RVK2 CZ-CAPE2 CZ-P160HR3 <2pipes> <3pipes> (service space) holes
4-ø20 (entire circumference)
CZ-P160BK2 CZ-P224BH2 46 (Hole for suspension bolt)
unit: mm
for 22.4kW unit or less for 22.4kW unit 16 - ø3.2
A B C (Hole for full circumference)
CZ-P680BK2 CZ-P680BH2

(service space)
73 / 106 420 395 68 4 × 100 = 400

or more
for more than 22.4kW for 28.0kW unit 140 450 425 98 15 500
980 (Suspension bolt pitch)
15

Cooling Only - - - - - 620 holes


E1 Type 25 55 500 70 50 55 35 1010 35 (for suspension bolts)

High Static Ducted Cool or Heat 2pcs - - 2pcs - 10 940


pitch holes
100
(Only for S-224,S-280) (entire circumference)

(274)
Inspection port
- - 2pcs 1pc 1pc
100
Heat Recovery 81 (suspension bolt pitch)
310

300

100 B
A 100 100
55
55 C

23
Drain pan unit: mm

68 69

180730_FSV_ASIA_D_2.indd 68-69 2018/10/12 14:40:02


Indoor Unit / H1 Type Indoor Unit / H1 Type

H1TYPE High-Fresh Air Ducted


Concealed duct
High static and large airflow ducted for exceptional installation flexibility.
For all indoor units
CZ-RWSK2 +
S-140MH1H5 S-224MH1H5 CZ-RTC5B CZ-RWSC3
S-280MH1H5

Model Name S-140MH1H5 S-224MH1H5 S-280MH1H5


Power source 220/230/240 V, 1 phase - 50Hz

Self-diagnosing Automatic Automatic kW 14.0 22.4 28.0


Cooling capacity
Function Fan Restart BTU/h 47,800 76,400 95,500
Operation Function
kW 13.2 21.2 26.5
Heating capacity
BTU/h 45,000 72,300 90,400
Cooling kW 0.430/0.430/0.430 0.670/0.670/0.670 0.730/0.730/0.730
Technical focus Power input
Heating kW 0.430/0.430/0.430 0.670/0.670/0.670 0.730/0.730/0.730
Cooling A 2.0/1.9/1.9 3.2/3.1/3.0 3.6/3.4/3.3
• 100% fresh Air intake for ventilation purpose • Discharge air temperature control to reduce cold Running
current Heating A 2.0/1.9/1.9 3.2/3.1/3.0 3.6/3.4/3.3
• Design flexibility thanks to high static pressure drafts during heating operation
Type Sirocco fan Sirocco fan Sirocco fan
and large air volume • Configurable air temperature control
m³/h 1,560 1,800 2,100
Fan Air flow rate
L/s 433 500 583
Motor output kW 0.2 0.4 0.4
High Fresh System Sound power level (H/M/L) dB 75/76/76 78/79/79 79/80/80
FSV Outdoor unit
Sound pressure level (H/M/L) dB(A) 43/44/44 46/47/47 47/48/48
High Fresh system enables delivery of
Dimensions HxWxD mm 420 x 1,065 x 620 479 x 1,428 x 1,230 479 x 1,428 x 1,230
fresh outside air at almost the same Outside to another room
High Liquid mm (inches) Ø9.52 (Ø3/8) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2)
temperature and humidity as indoor air fresh air
Fresh Air Pipe
Ducted unit Indoor unit Indoor unit Gas mm (inches) Ø15.88 (Ø5/8) Ø25.4 (Ø1) Ø25.4 (Ø1)
without putting a burden on air connections
Drain piping VP-25 VP-25 VP-25
conditioning.
Net weight kg 50 110 110
* Capable of treating outdoor air only. SA SA Corridor Pantry /
Exhaust
air
Indoor air conditioner units are required W.C.
Rated conditions: Cooling Heating Specifications are subject to change without notice.
GLOBAL
to adjust indoor air temperature. Room
REMARKS Outdoor air temperature 33˚C DB / 28˚C WB 0˚C DB / -2.9˚C WB

1st Area 2nd Area Last Area


→ Ducted
Air
unit → → → → Forced exhaust
Outside
fresh air office Hallway,Hall Pantry,W.C.
Meeting room Warehouse

H1TYPE HIGH-FRESH AIR DUCTED Dimensions


1 Refrigerant liquid line 4 Drain connection
2 Refrigerant gas line 5 Duct connection for suction
Mix operation unit with standard indoor units 3 Power supply entry 6 Duct connection for discharge

Possible to combine High Fresh Air ducted indoor unit and standard air ducted indoor units.
S-140MH1H5 S-224MH1H5/S-280MH1H5

When other indoor units are connected in same circuit, keep following capacity ratio.

479

467
H1 type/Outdoor unit < 30%, and Total of indoors(incl. H1)/outdoor <100% 5 Duct connection
Over 600 Over 700 for suction
Service space Service space
Over 600
479 Over 800 Service space
793 300 Service space 1070 467
Drain

Suspension bolt pitch


Electric box
2 Refrigerant
Remark For High Static Ducted Series 1 Refrigerant

290
gas line

Service space
liquid line

Over 1100

1170
1230
Model Operation Rap valve kit 3way control PCB 3way valve kit Distribution Joint kit Distribution Joint kit 500
<2pipes> <3pipes> 15 15
CZ-P160RVK2 CZ-CAPE2 CZ-P160HR3
980 5 Duct connection
CZ-P160BK2 CZ-P224BH2 Suspension bolt pitch
for 22.4kW unit or less for 22.4kW unit for suction
250 334
CZ-P680BK2 CZ-P680BH2 6 Duct connection 423
for 28.0kW unit 620 1065 for discharge 435 67 1200 67
for more than 22.4kW 6 Duct connection
500 940 1 Refrigerant 1310 for discharge
Cooling Only - - - - - liquid line
H1 Type
Service space
Over 580
450
310

300

Service space
High-Fresh Air Cool or Heat 2pcs - - 2pcs -

Over 610
Over 130
Ducted
Heat Recovery - - 2pcs 1pc 1pc 4 Drain 2 Refrigerant
Drain pan connection gas line
1428
unit: mm

70 71

180730_FSV_ASIA_D_2.indd 70-71 2018/10/12 14:40:05


Indoor Unit /K2 Type Indoor Unit /K2 Type

K2 TYPE Wall Mounted DC


motor
ECONAVI ready

The K2 type wall mounted unit has a stylish smooth design with a washable front panel.
Small, lightweight and low noise level makes it ideal for small offices and other commercial applications.

S-22MK2E5A / S-28MK2E5A / S-45MK2E5A / S-56MK2E5A /


S-36MK2E5A S-73MK2E5A / S-106MK2E5A CZ-CENSC1 CZ-RTC5B CZ-RWSK2

Quiet operation
Self-diagnosing Automatic Mild dry Intelligent Auto Automatic Auto Swing
Low operating noise level makes these units ideal for hotels and hospital applications.
Function Fan Swing Restart (Auto Flap Control)
Operation Function

Technical focus
Smooth and durable design
• Closed discharge port when not in use • Washable front panel The smooth cover means these units match most modern interiors.
• Lighter and smaller units make installation easy • Air distribution is automatically altered depending Their compact size enables them to blend in, even in small spaces.
• Quiet operation on the operational mode of the unit
• Smooth and durable design • Anti-mould washable filters are included
• Piping outlet in six directions

Piping outlet in six directions


Piping outlet is possible in the six directions of right, right rear, right
Noise reducing external valve kit
bottom, left, left rear, left bottom, making installation easier.
To reduce noise level of expansion valve.
(Optional accessory)

Washable front panel


The indoor unit’s front panel can be easily removed and washed for trouble-
CZ-P56SVK2 (for 22 - 56 type) free maintenance.
CZ-P160SVK2 (for 73 - 106 type)

Closed discharge port


Air distribution is automatically adjusted depending
When the unit is turned off, the flap closes completely to prevent entry of dust into the unit on the operational mode of the unit
and to keep the equipment clean. F1
Air outlet angle is automatically adjusted for cooling and heating operation.
F2 90¡

F3
Compact indoor units make the installation easy F4
F5
Heating: F1 to F5
K2 (22-36) TYPE K2 (45-106) TYPE
Cooling: F1 to F3

290 mm 302 mm

870 mm
1120 mm

72 73

180730_FSV_ASIA_D_2.indd 72-73 2018/10/12 14:40:08


Indoor Unit /K2 Type Indoor Unit /K2 Type

K2 TYPE Wall Mounted

Model Name S-22MK2E5A S-28MK2E5A S-36MK2E5A S-45MK2E5A S-56MK2E5A S-73MK2E5A S-106MK2E5A


Power source 220/230/240 V, 1 phase - 50 / 60 Hz 220/230/240 V, 1 phase - 50 / 60 Hz
kW 2.20 2.80 3.60 4.5 5.6 7.3 10.6
Cooling capacity
BTU/h 7,500 9,600 12,000 15,400 19,100 24,900 36,200
kW 2.50 3.20 4.20 5.0 6.3 8.0 11.4
Heating capacity
BTU/h 8,500 11,000 14,000 17,100 21,500 27,300 38,900
Cooling kW 0.025/0.025/0.025 0.025/0.025/0.025 0.030/0.030/0.030 0.030/0.030/0.030 0.035/0.035/0.035 0.055/0.055/0.055 0.080/0.080/0.080
Power input
Heating kW 0.025/0.025/0.025 0.025/0.025/0.025 0.030/0.030/0.030 0.030/0.030/0.030 0.035/0.035/0.035 0.055/0.055/0.055 0.080/0.080/0.080

Running Cooling A 0.21 0.23 0.25 0.33/0.32/0.31 0.36/0.35/0.34 0.52/0.51/0.50 0.72/0.70/0.68


current Heating A 0.21 0.23 0.25 0.33/0.32/0.31 0.36/0.35/0.34 0.52/0.51/0.50 0.72/0.70/0.68
Type Cross-flow fan Cross-flow fan Cross-flow fan Cross-flow fan Cross-flow fan Cross-flow fan Cross-flow fan
m³/h 540/450/390 570/500/390 655/540/390 870/750/600 960/840/720 1,170/1,020/840 1,290/1,110/900
Fan Air flow rate (H/M/L)
L/s 150/125/108 158/139/108 182/150/108 242/209/167 267/234/200 236/284/234 359/309/251
Motor output kW 0.03 0.03 0.03 0.054 0.054 0.054 0.054
Sound power level (H/M/L) dB 51/48/44 52/49/44 55/51/44 53/50/48 55/52/50 62/59/55 64/61/57
Sound pressure level (H/M/L) dB(A) 36/33/29 37/34/29 40/36/29 38/35/33 40/37/35 47/44/40 49/46/42
Dimensions HxWxD mm 290 x 870 x 214 290 x 870 x 214 290 x 870 x 214 302 x 1,120 x 236 302 x 1,120 x 236 302 x 1,120 x 236 302 x 1,120 x 236
Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8)
Pipe
Gas mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8)
connections
Drain piping mm Ø18 Ø18 Ø18 Ø18 Ø18 Ø18 Ø18
Net weight kg 9 9 9 13 13 14 14

Rated conditions: Cooling Heating Specifications are subject to change without notice.
GLOBAL
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB

K2 (22-36) TYPE WALL MOUNTED Dimensions K2 (45-106) TYPE WALL MOUNTED Dimensions

S-22MK2E5A / S-28MK2E5A / S-36MK2E5A S-45MK2E5A / S-56MK2E5A / S-73MK2E5A / S-106MK2E5A


1 Refrigerant tubing (liquid tube) ø6.35(flared) 1 Refrigerant tubing (liquid tube) Type 45-56 Ø6.35 (flared) Type 73-106 Ø9.52 (flared)
870 2 Refrigerant tubing (gas tube) ø12.7(flared) 2 Refrigerant tubing (gas tube) Type 45-56 Ø12.7 (flared) Type 73-106 Ø15.88 (flared)
3 Drain hose (outer dia. ø16) 3 Drain hose
4 Rear panel (PL BACK) 4 Rear panel
5 Rear panel fixing holes (ø5 holes or 5X13 oval holes) 5 Rear panel fixing holes (Ø5.3 holes or as shown in figure “C”)
6 Tubing and wiring holes (ø70) 6 Tubing and wiring holes (Ø80)

236 2 VIEW A

A
290

302
61
61

49
15

183 2 Gas tube 190 911 (415) (50) B


51

15
214 128.5 (570)
1 Liquid tube 3 Drain Hose 1120
Symmetry 3
2 1

557.5 562.5
350 350 le
ho

47.5
Exterior view of .3

30
5 Ø5

62
5 4 5
main unit 4-
5 5 5
45

47

47
95 60 60 85 183.5 188.5

243
114 60 60 114 132.5 128 128 137.5

235
or more
65mm

C
290

59
Ø29-1
+2

+0.3
Ø16.2 -0.2
75

4.5 (223.5) 5 663 233.5 6

.5
57

57

(R
10
6 Liquid connecting tube (400)

le)

Ø8 side
igh
5

ho

0 tu
Gas connecting tube (450)

t
10.5
100mm 50mm Cutting position

ing
Ø7

6 Tubing and
0

128 128

18
Ø7

tub
or more or more when tubing from left side
0

wiring holes 241.5 241.5

bin
18.5

e
50 50

sid
(L 80

gh
438.5 438.5

Ø
eft

ole
)
Minimum space requirements for installation Detailed view B Detailed view C
Front view unit: mm
5 4 5

unit: mm

74 75

180730_FSV_ASIA_D_2.indd 74-75 2018/10/12 14:40:13


Indoor Unit / U2 Type Indoor Unit / U2 Type

U2 TYPE 4-WAY Cassette DC


motor
[Optional]
ECONAVI ready
Semi concealed cassette NEW PANEL DESIGN
Required Kit

AIR INTAKE CHAMBER Flat design, well-matched with interior, building.


1
Provides a neat fit in the ceiling to match 1 [1] Air intake flange (Ø100)
modern décor, and uniform cooling through (field supply)
out the room, and easy installation. 2 2 Air intake box CZ-ATU2 *
For cassette only
3 Air intake plenum CZ-FDU3
CZ-RTC5B CZ-CNEXU1 CZ-RWSU3
3 * When using Air intake box (CZ-ATU2), Nomal Panel : CZ-KPU3
Air intake plenum (CZ-FDU3) is required. ECONAVI Panel : CZ-KPU3A [CZ-RTC5B   is
CZ-FDU3 required]

High Ceiling (Factory settings)


High-ceiling installation (Up to 5 m for 10.6
kW and higher capacity models)
Self-diagnosing Automatic Fan Mild dry Intelligent Auto Automatic Auto Swing Built-in Drain New 2.7m 3.0m 3.6m
Function Operation Swing Restart (Auto Flap Control) Pump
model
Function The units can be installed in
rooms with high ceilings, where
Capacity 2.2-5.6kW 6.0-9.0kW 10.6-16.0kW
Technical focus they provide ample floor-level
heating in the winter. (See Industry’s
top-class
• New high performance turbo fan, new path system for • Econavi: Floor temperature and humidity sensor added. ceiling height guidelines below.)
heat exchanger Activity amount detection and new circulator 10.6- 4.5m 4.7m 5m

• Lower noise in slow fan operation • nanoeTM: The first 10x for CAC (10 times more nanoeTM 16.0kW
• Industry top light weight, easy piping particle for wide commercial space). Inside cleaning by
• Easy installation structure of the panel 10x nanoeTM + dry control Capacity 4-way discharge
high ceiling setting 2
3-way discharge
with the optional air-
2-way discharge
with the optional air-
blocking materials blocking materials

Ceiling height guidelines


Flat Horizontal Design Low-Profile
*1 settings 4-way discharge
*1 When using the unit in a configuration

The horizontal design of 4-way cassette achieves an


33.5 mm Panel Factory High ceiling High ceiling
3-way discharge
(optional air-blocking
2-way discharge
(optional air-blocking
other than the factory settings, it is
necessary to make settings on site to
setting 1 setting 1 setting 2 materials) materials) *2 increase airflow.
Indoor unit
elegant designed panel. Its slim design allow to protrude *2 Use air-blocking materials (CZ-CFU3)
2.2-5.6kW 2.7 3.2 3.5 3.8 4.2 to completely block two discharge
33.5mm from the ceiling. outlets for 2-way airflow.
6.0-9.0kW 3.0 3.3 3.6 3.8 4.2
10.6-16.0kW 3.6 4.3 5.0 4.7 5.0

Drain pump of up to 850 mm from the ceiling surface Up to 300 mm


Econavi panel is added into the line up
Built in drain pump allows flexible install and design options with Continue Conventional function (Energy saving & comfort) • New circulate function that improves comfort
up to 850mm lift. Long horizontal piping is also possible. Up to 850 mm
and following are newly added. • Movement detection is improved improving comfort
• Energy saving function: comfortable energy saving
based on temperature and humidity
Easy to clean suction grille
Suction grille is able to make 90-degree turns. Econavi energy saving function
Newly put humidity sensor on air suction part, • Energy saving operation in case of high humidity during
and achieve more comfort and energy saving operation. heating operation
• Energy saving operation in case of low humidity during Energy saving operation based on activity amount and
cooling operation comfort and energy saving based on temperature and
humidity.

360˚ Wide & Comfortable Airflow Panels & Panel parts


Ample airflow: 36 m3/min
Comfort air flow control and proper energy use. Flexible Air Flow Industry’s leading in the 140PU class.
Normal panel: CZ-KPU3
direction control by individual flap control:
Econavi panel: CZ-KPU3A
-4 Flaps can be controlled individually (by standard wired remote Wireless receiver (option) Econavi panel
controller*)
-Versatile air flow control to cover a wide variety of demands.
[Optional]

360° Wide Temperature distribution by nanoe X with 10 Times the Concentration


TM

thermograph
(cooling operation) nanoeTM X contains plenty of
OH radicals that inhibits bacteria
1m and viruses, deodorizes
Simulation conditions:
140M 4-way ceiling-mounted cassette
unpleasant odours and keeps
type in cooling mode room air clean and fresh.
/ Floor area of 225 m2
/ Ceiling height of 3 m
*Pre-setting is required for this function at System Test-run procedure
*CZ-CNEXU1 is required to use nanoeTM X function. Invisible Air Contaminants are Suppressed
76 77

180730_FSV_ASIA_D_2.indd 76-77 2018/10/12 14:40:25


Indoor Unit / U2 Type Indoor Unit / U2 Type

U2 TYPE 4-WAY Cassette

Model Name S-22MU2E5A S-28MU2E5A S-36MU2E5A S-45MU2E5A S-56MU2E5A S-60MU2E5A S-73MU2E5A S-90MU2E5A S-106MU2E5A S-140MU2E5A S-160MU2E5A
Power source 220/230/240 V, 1 phase - 50Hz/60Hz 220/230/240 V, 1 phase - 50Hz/60Hz
kW 2.2 2.8 3.6 4.5 5.6 6.0 7.3 9.0 10.6 14.0 16.0
Cooling capacity
BTU/h 7,500 9,600 12,300 15,400 19,100 20,500 24,900 30,700 36,200 47,800 54,600
kW 2.5 3.2 4.2 5.0 6.3 7.1 8.0 10.0 11.4 16.0 18.0
Heating capacity
BTU/h 8,500 10,900 14,300 17,100 21,500 24,200 27,300 34,100 38,900 54,600 61,400
Cooling kW 0.020/0.020/0.020 0.020/0.020/0.020 0.020/0.020/0.020 0.020/0.020/0.020 0.025/0.025/0.025 0.035/0.035/0.035 0.040/0.040/0.040 0.040/0.040/0.040 0.090/0.090/0.090 0.095/0.095/0.095 0.105/0.105/0.105
Power input
Heating kW 0.020/0.020/0.020 0.020/0.020/0.020 0.020/0.020/0.020 0.020/0.020/0.020 0.025/0.025/0.025 0.035/0.035/0.035 0.040/0.040/0.040 0.040/0.040/0.040 0.085/0.085/0.085 0.090/0.090/0.090 0.100/0.100/0.100

Running Cooling A 0.21/0.21/0.20 0.21/0.21/0.20 0.21/0.21/0.20 0.21/0.21/0.20 0.24/0.23/0.22 0.34/0.33/0.32 0.37/0.36/0.35 0.39/0.38/0.37 0.74/0.71/0.68 0.77/0.74/0.71 0.85/0.82/0.79
current Heating A 0.20/0.20/0.19 0.20/0.20/0.19 0.20/0.20/0.19 0.20/0.20/0.19 0.23/0.22/0.21 0.33/0.32/0.31 0.36/0.35/0.34 0.38/0.37/0.36 0.72/0.69/0.66 0.75/0.72/0.69 0.83/0.80/0.77
Type Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan
m³/h 870/780/690 870/780/690 870/780/690 930/780/690 990/810/690 1,260/960/780 1,350/960/780 1,380/1,110/840 2,040/1,500/1,140 2,160/1,560/1,200 2,220/1,680/1,440
Fan Air flow rate (H/M/L)
L/s 233/200/183 233/200/183 233/200/183 250/217/200 267/250/200 350/283/233 367/283/233 383/317/250 550/450/350 583/467/367 600/483/383
Motor output kW 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.09 0.09 0.09
Sound power level (H/M/L) dB 45/44/43 45/44/43 45/44/43 46/44/43 47/45/43 51/47/44 52/47/44 53/50/47 59/53/49 60/54/50 61/55/53
Sound pressure level (H/M/L) dB(A) 30/29/28 30/29/28 30/29/28 31/29/28 32/30/28 36/32/29 37/32/29 38/35/32 44/38/34 45/39/35 46/40/38
Dimensions HxWxD mm 256+(33.5) x 840 (950) x 840 (950) 319+(33.5) x 840 (950) x 840 (950)
Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8)
Pipe
Gas mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8)
connections
Drain piping VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25
Net weight (Panel) kg 19 (+5) 19 (+5) 19 (+5) 19 (+5) 19 (+5) 20 (+5) 20 (+5) 20 (+5) 25 (+5) 25 (+5) 25 (+5)

Rated conditions: Cooling Heating


GLOBAL
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB
Specifications are subject to change without notice.
U2 TYPE 4-WAY CASSETTE Dimensions

1 Air intake
2 Discharge outlet
3 Refrigerant tubing (liquid tube) 22-56 type ø6.35 (flared), 60-90 type ø9.52 (flared)
4 Refrigerant tubing (gas tube) 22-56 type ø12.7 (flared), 60-90 type ø15.88 (flared)
Test report for odours and mould suppression performance 5 Drain tube connection port VP25 (outer dia. ø32)
6 Power supply port
No. Target Substance Effectiveness Testing Institute Test Report No. Method Result 7 Discharge duct connection port (ø150)
8 Suspension bolt hole (4-12×30 elongated hole)
nanoe X was operated in a test
TM
9 Fresh air intake duct connection port (ø100) *
space (55m2) and the deodorisation 10 ECONAVI sensor (Only CZ-KPU3A)
Decrease by 0.7 Gunma Research Test Report effect on a piece of cloth impregnated Decrease in odour
1 Odours level Center No. 27055 with odour components of cigarette intensity by 0.7 level after
smoke was evaluated using 6 level 2 hour of operation
odor intensity indication method.
*1: Necessary to attach duct connecting flange (field supplied).
Mould sensor was attached at indoor Filter size: 520 x 520 x 15
Inhibit Mould Institute of Test Report unit inside. In a test space (95m2) at
No Mould Growth after 9
2 Mould Growth
Environmental No.150901, 25 degree and 75% humidity, AC
days.
Biology 150904 cooling with nanoeTMX was operated
during 2 hour per day for 9 days.

unit: mm

The length of the suspension bolts should be selected so that there is a gap of 30 mm or more
below the lower surface of the ceiling (18 mm or more below the lower surface of the main
unit), as shown in the figure at right. If the suspension bolt is too long, it will contact the ceiling
panel and the unit cannot be installed.

78 79

180730_FSV_ASIA_D_2.indd 78-79 2018/10/12 14:40:27


Indoor Unit / Y2 Type Indoor Unit / Y2 Type

Y2 TYPE 4-WAY Mini Cassette DC


motor

ECONAVI ready
Mini semi concealed cassette PANEL

Designed to fit perfectly into a 60 x 60 cm ceiling grid without the need to alter the bar configuration,
the Y2 is ideal for small commercial and retrofit applications. In addition, improvements to the Y2’s
efficiency make this model one of the most advanced units in the industry. 51 x 700 x 700 mm
(HxWxD) CZ-CENSC1 CZ-RTC5B CZ-RWSK2
CZ-KPY3AW

Model Name S-22MY2E5A S-28MY2E5A S-36MY2E5A S-45MY2E5A S-56MY2E5A


Power source 220/230/240 V, 1 phase - 50, 60 Hz
kW 2.2 2.8 3.6 4.5 5.6
Self-diagnosing Automatic Mild dry Intelligent Auto Automatic Auto Swing Built-in Drain Cooling capacity
BTU/h 7,500 9,600 12,300 15,400 19,100
Function Fan Swing Restart (Auto Flap Control) Pump
Operation Function kW 2.5 3.2 4.2 5.0 6.3
Heating capacity
BTU/h 8,500 10,900 14,300 17,100 21,500
Cooling kW 0.035 0.035 0.040 0.040 0.045
Power input
Technical focus Heating
Cooling
kW
A
0.030
0.30
0.030
0.30
0.035
0.30
0.035
0.32
0.040
0.35
Running
amperes Heating A 0.25 0.30 0.30 0.30 0.35
• Mini cassette fits into a 60 x 60 cm ceiling grid
Type Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan
• Anti-mould and anti-bacteria washable filters m³/h 547/493/335 558/504/335 583/522/360 601/558/493 622/587/511
• Powerful drain pump gives 750 mm lift Fan motor Airflow rate (H/M/L)
L/s 152/137/93 155/140/93 162/145/100 167/155/137 173/163/142
• DC fan motor with variable speed and a new heat exchanger ensures efficient power consumption Output kW 0.04 0.04 0.04 0.04 0.04

• Fresh air knock out Power sound Cooling dB 50/48/46 50/48/46 51/49/47 53/51/48 55/52/49
level (H/M/L) Heating dB 50/48/44 50/48/44 51/49/45 53/51/47 55/52/49
• Multi directional air flow
Sound pressure Cooling dB(A) 35/33/31 35/33/31 36/34/32 38/36/33 40/37/34
level (H/M/L) Heating dB(A) 35/33/29 35/33/29 36/34/30 38/36/32 40/37/34
Dimensions* HxWxD mm 288 (+31) x 575 (700) x 575 (700) 288 (+31) x 575 (700) x 575 (700) 288 (+31) x 575 (700) x 575 (700) 288 (+31) x 575 (700) x 575 (700) 288 (+31) x 575 (700) x 575 (700)
Compact design Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4)
Pipe
Gas mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2)
connections
The panel is a compact (70×70 cm) so it can be Drain piping VP-25 VP-25 VP-25 VP-25 VP-25
installed even in a small room where space is limited. Net weight* kg 18 (+2.4) 18 (+2.4) 18 (+2.4) 18 (+2.4) 18 (+2.4)

* The values in ( ) for external dimensions and Net weight are the values for the
Rated conditions: Cooling Heating
700 mm GLOBAL optional ceiling panel.
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB Specifications are subject to change without notice.
REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB
700 mm

Lighter and slimmer, easier installation Y2 TYPE 4-WAY CASSETTE Dimensions


When only 260mm of indoor body height, it can easily fit in A
288mm 1 Air intake grill
limited spaces and tight spots. Indoor Unit 2 Air outlet
650 (ceiling opening dimension)

3 Refrigerant piping (liquid pipe) ø6.35 (flared) 530(suspension bolt pitch)


(Required 288mm from bottom of panel to top of the unit) 4 Refrigerant piping (gas pipe) ø12.7 (flared)
5 Drain tube connection port VP25 (outer ø32)

(ceiling opening dimension)


6 Power supply entry

(suspension bolt pitch)

212
7 Suspension bolt hole (4-11 x 26 slot) 7 Panel center
8 Fresh air intake duct connection port (ø80)

530

650
A drain height of up to 148

316
301
8

320
750 mm from the ceiling surface 750
mm VIEW A
Indoor Unit
The internal pump allows the drain pipe to be (583) (583)
575 575
elevated up to 750mm above the base of the unit. 200 44 170 146
5

25

(288)
260
283
179
123
112
Anti-Mould Long-Life Air Filter

31
4 3 6

31
(23)
Anti-mould and anti-bacteria washable filter ensures ing
hole
700
336
arr
3B
clean, healthy air. 4-ø 2
ø80

71

45
1

336
700
71
unit: mm
Dimension of Fresh air intake duct (field supply) Adjust the suspension bolt length so that the gap from the
connection port lower ceiling surface becomes 45mm or more,
as shown in the figure at right.
If the suspension bolts is too long, it will contact the ceiling
panel and the unit cannot be installed.
2

80 81

180730_FSV_ASIA_D_2.indd 80-81 2018/10/12 14:40:33


Indoor Unit / L1 Type Indoor Unit / L1 Type

L1 TYPE 2-WAY Cassette PANEL

The L1 is very thin, compact and light, allowing flexible install options.
A redesigned fan has been used to achieve this size and weight reduction. CZ-02KPL2
Big size panel (for S-73ML1E5)
CZ-03KPL2
CZ-RTC5B CZ-RWSL2N

Model Name S-22ML1E5 S-28ML1E5 S-36ML1E5 S-45ML1E5 S-56ML1E5 S-73ML1E5


Power source 220/230/240V, 1 phase - 50 / 60Hz
kW 2.2 2.8 3.6 4.5 5.6 7.3
Self-diagnosing Automatic Mild dry Intelligent Auto Automatic Auto Swing Built-in Drain Cooling capacity
Function Fan Swing Restart (Auto Flap Control) Pump BTU/h 7,500 9,600 12,000 15,000 19,000 25,000
Operation Function
kW 2.5 3.2 4.2 5.0 6.3 8.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 27,000
Cooling kW 0.086/0.090/0.095 0.086/0.092/0.097 0.088/0.093/0.099 0.091/0.097/0.103 0.091/0.097/0.103 0.135/0.145/0.154
Technical focus Power input
Heating kW 0.055/0.058/0.062 0.055/0.060/0.064 0.057/0.061/0.066 0.060/0.065/0.070 0.060/0.065/0.070 0.100/0.109/0.117

• Airflow and distribution is automatically altered depending on the operational mode of the unit Running current
Cooling A 0.45/0.45/0.45 0.44/0.45/0.45 0.44/0.45/0.45 0.45/0.45/0.45 0.45/0.45/0.45 0.64/0.65/0.66

• Drain up is possible up to 500 mm via the built-in drain pump Heating A 0.29/0.29/0.30 0.28/0.29/0.30 0.28/0.29/0.30 0.29/0.29/0.30 0.29/0.29/0.30 0.46/0.48/0.49

• Simple maintenance Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan
m³/h 480/420/360 540/480/420 580/520/460 660/540/480 660/540/480 1,140/960/840
Fan Air flow rate (H/M/L)
L/s 133/117/100 150/133/117 161/144/128 183/150/133 183/150/133 317/267/233
Auto flap control Motor output kW 0.03 0.03 0.03 0.03 0.03 0.05
auto flap section
Sound power level (H/M/L) dB 40/38/35 44/40/37 45/42/39 46/44/40 46/44/40 49/46/44
Airflow and distribution is automatically altered
Sound pressure level (H/M/L) dB(A) 30/27/24 33/29/26 34/31/28 35/33/29 35/33/29 38/35/33
depending on the operational mode (cooling or 20
Dimensions * HxWxD mm 350+(8)x840 (1,060) x600 (680) 350+(8)x840 (1,060) x600 (680) 350+(8)x840 (1,060) x600 (680) 350+(8)x840 (1,060) x600 (680) 350+(8)x840 (1,060) x600 (680) 350+(8)x 1,140 (1,360) x600 (680)
heating) of the unit.
2.7 m

Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø9.52 (Ø3/8)
Pipe connections Gas mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø15.88 (Ø5/8)
40¡ Drain piping VP-25 VP-25 VP-25 VP-25 VP-25 VP-25
Cool/Dry/Fan Heating/(H/M/L)
Net weight * kg 23 (+5.5) 23 (+5.5) 23 (+5.5) 23 (+5.5) 23 (+5.5) 30 (+9)

* The values in ( ) for external dimensions and Net weight are the values for the
Rated conditions: Cooling Heating
Drain up is possible up to 500 mm GLOBAL
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
optional ceiling panel.
Specifications are subject to change without notice.
REMARKS
via the built-in drain pump. Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB

300 mm or less
Maintenance of the drain pump is possible from
both sides, from the left side (piping side) and
from the inside of the unit. 500 mm or less L1 TYPE 2-WAY CASSETTE Dimensions
310 mm 1 Air intake
2 Air outlet 22 56 type 73 type
3 Ceiling opening dimensions
Inspection lid A 840 1,140
4 Suspension fitting (notch: 12 mm) 450 B 440 590
5 Refrigerant piping (liquid pipes)
C 480 630
6 Refrigerant piping (gas pipes)

20
7 Drain connection VP25 (outer diameter ø 32) D 1,020 1,320

300
8 Inlet for option cord between power supply and unit E 1,060 1,360
9 Drain pan, drain pump inspection lid Ceiling opening
1,020x640 1,320x640
Simple maintenance 10 Drain pump inspection lid
11 Round flange (field supply) mounting part Ceiling panel and ceiling
dimensions

530
600
640
680
(fresh air inlet ø 125) opening center Refrigerant piping
ø6.35 ø9.52
(liquid pipes)
12 Discharge duct (field supply) mounting part
The drain pan is equipped with site wiring and can be removed. The fan case has a split construction, and the (installation possible only on the right side) Refrigerant piping
fan motor can be removed easily when the lower case is removed. 13 Wireless remote controller (option) signal receiver (gas pipes)
ø12.7 ø15.88
installation part 40 A
70 B C Duct connection port
x 1 pc. x 2 pc.
20 D
(only on the right side)
(230)
E
110
80
30 70 70

290
350
310
220
195

165
102 (55) 23

60
(105)

8
75
680

unit: mm

82 83

180730_FSV_ASIA_D_2.indd 82-83 2018/10/12 14:40:35


Indoor Unit / D1 Type Indoor Unit / D1 Type

D1TYPE 1-WAY Cassette DC


motor
PANEL
Semi concealed slim cassette
Designed for installation within the ceiling void, the D1 range of slimline 1 way cassettes
feature a quiet yet powerful fan that can reach the floor up 4.2 m from ceiling height.
CZ-KPD2

CZ-RTC5B CZ-RWSD2

Model Name S-28MD1E5 S-36MD1E5 S-45MD1E5 S-56MD1E5 S-73MD1E5


Power source 220/230/240 V, 1 phase - 50 / 60 Hz
kW 2.8 3.6 4.5 5.6 7.3
Self-diagnosing Automatic Mild dry Intelligent Auto Automatic Auto Swing Built-in Drain Cooling capacity
Function Fan Swing Restart (Auto Flap Control) Pump BTU/h 9,600 12,000 15,000 19,000 25,000
Operation Function
kW 3.2 4.2 5.0 6.3 8.0
Heating capacity
BTU/h 11,000 14,000 17,000 21,000 27,000
Cooling kW 0.050/0.051/0.052 0.050/0.051/0.052 0.050/0.051/0.052 0.058/0.060/0.061 0.086/0.087/0.089
Technical focus Power input
Heating kW 0.039/0.040/0.042 0.039/0.040/0.042 0.039/0.040/0.042 0.046/0.048/0.049 0.075/0.076/0.077

• Ultra-Slim profile Running Cooling A 0.40/0.39/0.39 0.40/0.39/0.39 0.40/0.39/0.39 0.46/0.46/0.46 0.71/0.70/0.69


current
• Suitable for standard and high ceilings Heating A 0.36/0.35/0.35 0.36/0.35/0.35 0.36/0.35/0.35 0.42/0.41/0.41 0.66/0.65/0.63
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan
• Built-in drain pump provides 590 mm lift from ceiling
m³/h 720/600/540 720/600/540 720/660/600 780/690/600 1,080/900/780
• Easy to install and maintain Fan
Air flow rate
(H/M/L) L/s 200/167/150 200/167/150 200/183/167 217/192/167 300/250/217
• Hanging height can be easily adjusted
Motor output kW 0.05 0.05 0.05 0.05 0.05
• Uses a DC fan motor to improve energy-efficiency
Sound power level (H/M/L) dB 47/45/44 47/45/44 47/46/45 49/47/45 56/51/47
Sound pressure level (H/M/L) dB(A) 36/34/33 36/34/33 36/35/34 38/36/34 45/40/36
Drain height Dimensions * HxWxD mm 200+(20) x 1,000 (1,230) x 710 (800) 200+(20) x 1,000 (1,230) x 710 (800) 200+(20) x 1,000 (1,230) x 710 (800) 200+(20) x 1,000 (1,230) x 710 (800) 200+(20) x 1,000 (1,230) x 710 (800)

300 mm or less Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø9.52 (Ø3/8)
A built-in drain pump provides up to 590mm lift from Pipe
Gas mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø15.88 (Ø5/8)
connections
ceiling height for flexible install options. Drain piping VP-25 VP-25 VP-25 VP-25 VP-25
590 mm or less
Net weight * kg 21 (+5.5) 21 (+5.5) 21 (+5.5) 21 (+5.5) 22 (+5.5)

* The values in ( ) for external dimensions and Net weight are the values for the
Rated conditions: Cooling Heating
GLOBAL optional ceiling panel.
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB Specifications are subject to change without notice.
REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB

With 3 types of air-blow systems, the units can be used in various ways.
D1 TYPE 1-WAY CASSETTE Dimensions
(1) One-direction “down-blow” system
1 Air intake grille
Powerful one-direction “down-blow” system reaches the floor even 2 Air outlet
3 Refrigerant piping (liquid pipes) (suspension bolt pitch)
from high ceilings (up to 4.2 m). Size 28 to 56: Ø6.35 (flared)
Size 73: Ø9.52 (flared)

(ceiling opening dimension)


4 Refrigerant piping (gas pipes)

(suspension bolt pitch)


Size 28 to 56: Ø12.7 (flared)
Size 73: Ø15.88 (flared)
5 Drain connection VP25 (outer Ø32)
(2) Two-direction ceiling-mounted system 6 Power supply entry
7 Discharge duct connection port (for descending ceiling)
8 Wireless remote control receiver (option)
“Down-blow” and “front-blow” systems are combined in a ceiling- 9 Suspension mounting (4-12 x 30 slot)
10 Fresh air intake (Ø100)
mounted unit to blow air over a wide area.
(ceiling opening dimension)

(3) One-direction ceiling-mounted system


This powerful ceiling-mounted “front-blow” system efficiently air-
conditions the space in front of the unit.
(Additional accessories required)

unit: mm

84 85

180730_FSV_ASIA_D_2.indd 84-85 2018/10/12 14:40:38


Indoor Unit / T2 Type Indoor Unit / T2 Type

T2 TYPE Ceiling
S-73MT2E5A
DC
motor
S-106MT2E5A
S-140MT2E5A ECONAVI ready
Ceiling mounted
S-36MT2E5A
S-451MT2E5A
Providing outstanding energy-saving performance and comfortable, S-56MT2E5A
long-distance air flow distribution, it’s recommended for stores and schools.

CZ-CENSC1 CZ-RTC5B CZ-RWST3N

Model Name S-36MT2E5A S-45MT2E5A S-56MT2E5A S-73MT2E5A S-106MT2E5A S-140MT2E5A


Power source 220 / 230 / 240 V, 1 phase - 50 / 60 Hz

Self-diagnosing Automatic Mild dry Intelligent Auto Automatic Auto Swing kW 3.6 4.5 5.6 7.3 10.6 14.0
Cooling capacity
Function Fan Swing Restart (Auto Flap Control) BTU/h 12,300 15,400 19,100 24,900 36,200 47,800
Operation Function
kW 4.2 5.0 6.3 8.0 11.4 16.0
Heating capacity
BTU/h 14,300 17,100 21,500 27,300 38,900 54,600
Cooling kW 0.035/0.035/0.035 0.040/0.040/0.040 0.040/0.040/0.040 0.055/0.055/0.055 0.080/0.080/0.080 0.100/0.100/0.100
Technical focus Power input
Heating kW 0.035/0.035/0.035 0.040/0.040/0.040 0.040/0.040/0.040 0.055/0.055/0.055 0.080/0.080/0.080 0.100/0.100/0.100
Cooling A 0.37/0.36/0.35 0.39/0.38/0.37 0.39/0.38/0.37 0.45/0.44/0.43 0.69/0.67/0.65 0.82/0.79/0.77
• Lower sound levels Running
current Heating A 0.37/0.36/0.35 0.39/0.38/0.37 0.39/0.38/0.37 0.45/0.44/0.43 0.69/0.67/0.65 0.82/0.79/0.77
• Standardised height and depth for all models
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan
• Long and wide air distribution
m³/h 840/720/630 900/750/630 900/750/630 1,260/1,080/930 1,800/1,500/1,380 1,920/1,680/1,440
• Easy to install and maintain Fan Air flow rate (H/M/L)
L/s 233/200/175 250/208/175 250/208/175 350/300/258 500/417/383 533/467/400
• Fresh air knockout
Motor output kW 0.043 0.043 0.043 0.074 0.111 0.111
Sound power level (H/M/L) dB 54/50/48 55/51/48 55/51/48 57/53/51 60/55/54 62/58/55
Compact Looking, Stylish, One-Motion Design Sound pressure level (H/M/L) dB(A) 36/32/30 37/33/30 37/33/30 39/35/33 42/37/36 44/40/37
Dimensions HxWxD mm 235 x 960 x 690 235 x 960 x 690 235 x 960 x 690 235 x 1,275 x 690 235 x 1,590 x 690 235 x 1,590 x 690
With its streamlined, one-motion form, the unit looks slim and compact Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8) Ø9.52 (Ø3/8)
when installed for a neat appearance in any room. When not operating, Pipe
connections
Gas mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8) Ø15.88 (Ø5/8)
the louver closes to provide an elegant look while keeping the unit clean. Drain piping VP-20 VP-20 VP-20 VP-20 7
123
VP-20
61
VP-20

73
Net weight kg 27 27 27 33 40 40

190
(suspension
Specifications are subject to change without notice.

bolt pitch)

114
265
Energy-Saving Technology Top Class Energy Saving GLOBAL
Rated conditions: Cooling Heating
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
Delivering Top-Class Efficiency REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB
Large Diagonal 1226 (suspension bolt pitch)

Optimization of the shape of the casing and fan assures bigger Air Flow Fan 1269
690
216 1 8

15

4
air flow and higher efficiency.

131
Approx. 2°

193
235
Energy-saving performance is top class in the industry. DC Fan diameter T2 TYPE CEILING Dimensions Over Over
motor f147.5 5 Air discharge 250 1275 250 80 186

Minimum
50cm
Air intake Service space Service space

DC monitor S-36MT2E5A // S-45MT2E5A // S-56MT2E5A S-73MT2E5A // S-106MT2E5A // S-140MT2E5A Tubing hole position on wall surface
(Figure shows view from front)

1 Drain port VP20 Inside diameter ø26mm, drain hose supplied A B C D E

176
2 Left drain position 106-140 type 1.590 235 690 1.584 1.541
Comfortable, Long-Distance 3
4
Refrigerant liquid tubing
Refrigerant gas tubing
Ø6.35mm for 36~56type, Ø9.52mm for 73~140type
Ø12.77mm for 36~56type, Ø15.88mm for 73~140type
73 type 1.275 235 690 1.269 1.226 9

216
6 96

Air Flow Distribution 5 Left side drain hose outlet port (cutout) 2

6 Tubing hole on wall surface Ø100mm 90


3 4 86 (Gas tubing)
Ceiling height 7 Upper side tubing port (Closed with rubber stopper at
70 (Liquid tubing)
90 (Right drain position)
8 Right side drain hose outlet port (cutout) time of shipment.) (Left drain position)

The shape of the outlet has been optimized to provide long-


distance air flow distribution. Even in deep spaces, air flow
4.3m * 9 Wireless remote controller receiver installation location

7
123 61
7
123 61

73
73
reaches every corner for exceptionally comfortable air conditioning.

190
190

(suspension
(suspension

bolt pitch)

114
bolt pitch)

265
114
265
Air flow distance Air flow distance

13m*
High Ceiling Setting
*Setting by remote control
112 140 160 1226 (suspension bolt pitch)
E (suspension bolt pitch)

C
4.3m 12m 13m 13m *Results are based on specific testing conditions. 1269
690
1 8
D 216 1 8

15
216

4
15

131
Approx. 2°

193
B
131
Approx. 2°

193
235
Over Over
5 Air discharge 80 186
250 A 250
Over Over

Minimum
5 Air discharge 250 250 80 186
1275
Minimum

Air intake

Multiple Piping Directions For Flexible


Service space Service space

50cm
50cm

Air intake Tubing hole position on wall surface


Top
Service space Service space
(Figure shows view from front)
Tubing hole position on wall surface

Installation (Figure shows view from front)

176
9

176
The 5-directional drain pipe and 3-directional refrigerant pipe make

216
Left side
9 96
6
2

216
6 96 90

installation much easier. And the neat fit with walls and ceilings
86 (Gas tubing)
Left back
2 3 4
(Closed with rubber stopper at 70 (Liquid tubing)
Right side Right back
90
3 4 86 (Gas tubing) time of shipment.) (Left drain position) 90 (Right drain position)

assures more installation flexibility.


70 (Liquid tubing)
(Closed with rubber stopper at
time of shipment.) (Left drain position)
90 (Right drain position)

Refringerant pipe Drainpipe


unit: mm unit: mm
123 61
7
73

86 87
190
(suspension
bolt pitch)

114
265

E (suspension bolt pitch)

C
1 8
180730_FSV_ASIA_D_2.indd 86-87 D 216
2018/10/12 14:40:42
15

4
Indoor Unit / P1 Type Indoor Unit / P1 Type

P1 TYPE Floor Standing


The compact floor standing P1 units are the ideal solution for providing perimeter air conditioning.
A standard wired controller can be incorporated into the body of the unit.
CZ-RWSK2 +
CZ-RTC5B CZ-RWSC3

Model Name S-22MP1E5 S-28MP1E5 S-36MP1E5 S-45MP1E5 S-56MP1E5 S-71MP1E5


Power source 220/230/240 V, 1 phase - 50 / 60 Hz

Self-diagnosing Automatic Mild dry Automatic kW 2.2 2.8 3.6 4.5 5.6 7.1
Cooling capacity
Function Fan Restart BTU/h 7,500 9,600 12,000 15,000 19,000 24,000
Operation Function
kW 2.5 3.2 4.2 5.0 6.3 8.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 27,000
Cooling kW 0.051/0.056/0.061 0.051/0.056/0.061 0.079/0.085/0.091 0.116/0.126/0.136 0.116/0.126/0.136 0.150/0.160/0.170
Technical focus Power input
Heating kW 0.036/0.040/0.045 0.036/0.040/0.045 0.064/0.070/0.076 0.079/0.091/0.101 0.079/0.091/0.101 0.110/0.120/0.130
Cooling A 0.24/0.25/0.26 0.24/0.25/0.26 0.37/0.38/0.39 0.54/0.56/0.58 0.54/0.56/0.58 0.70/0.72/0.73
• Pipes can be connected to either side of the unit from the bottom or rear Running
current Heating A 0.17/0.18/0.19 0.17/0.18/0.19 0.30/0.31/0.32 0.37/0.41/0.43 0.37/0.41/0.43 0.52/0.54/0.56
• Easy to install
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan
• Front panel opens fully for easy maintenance
m³/h 420/360/300 420/360/300 540/420/360 720/540/480 900/780/660 1,020/840/720
• Removable air discharge grille gives flexible air flow Fan Air flow rate (H/M/L)
L/s 117/100/83 117/100/83 150/117/100 200/150/133 250/217/183 283/233/200
Motor output kW 0.01 0.01 0.02 0.02 0.03 0.06
Sound power level (H/M/L) dB 44/41/39 44/41/39 50/46/40 49/46/42 50/47/42 52/49/46
Effective perimeter air conditioning Sound pressure level (H/M/L) dB(A) 33/30/28 33/30/28 39/35/29 38/35/31 39/36/31 41/38/35
Dimensions HxWxD mm 615 x 1,065 x 230 615 x 1,065 x 230 615 x 1,065 x 230 615 x 1,380 x 230 615 x 1,380 x 230 615 x 1,380 x 230
Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø9.52 (Ø3/8)
Pipe
Gas mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø15.88 (Ø5/8)
connections
Drain piping VP-20 VP-20 VP-20 VP-20 VP-20 VP-20
Net weight kg 29 29 29 39 39 39

Specifications are subject to change without notice.


Rated conditions: Cooling Heating
GLOBAL
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB

A standard wired remote control P1 TYPE FLOOR STANDING


can be installed in the body Dimensions
1 4 x Ø12 holes (for floor fixing)
2 Power supply outlet
3 Air filter
4 Refrigerant piping (liquid pipes)
5 Refrigerant piping (gas pipes)
6 Level adjustment bolt
7 Drain outlet VP20 (with vinyl hose)
8 Refrigerant piping connection port (bottom or rear)
9 Operation switch (remote controller RCS-SH80AG) mounting part
10 Electric equipment box
11 Accessory copper pipe for gas pipe connection

Indoor unit A B C Liquid pipes Gas pipes


22 to 36 type 1,065 665 632
45 type Ø6.35 Ø12.7
56 type 1,380 980 947
71 type Ø9.52 Ø15.88

Knock-out hole

unit: mm

88 89

180730_FSV_ASIA_D_2.indd 88-89 2018/10/12 14:40:45


Indoor Unit / R1 Type Indoor Unit / R1 Type

R1 TYPE Concealed Floor Standing


At just 229 mm deep, the R1 unit can be easily concealed in perimeter
areas to provide powerful and effective air conditioning.

CZ-RWSK2+
CZ-RTC5B CZ-RWSC3

Model Name S-22MR1E5 S-28MR1E5 S-36MR1E5 S-45MR1E5 S-56MR1E5 S-71MR1E5


Power source 220/230/240 V. 1 phase - 50. 60 Hz

Self-diagnosing Automatic Mild dry Automatic kW 2.2 2.8 3.6 4.5 5.6 7.1
Cooling capacity
Function Fan Restart BTU/h 7,500 9,600 12,000 15,000 19,000 24,000
Operation Function
kW 2.5 3.2 4.2 5.0 6.3 8.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 27,000
Cooling kW 0.051/0.056/0.061 0.051/0.056/0.061 0.079/0.085/0.091 0.116/0.126/0.136 0.116/0.126/0.136 0.150/0.160/0.170
Technical focus Power input
Heating kW 0.036/0.040/0.045 0.036/0.040/0.045 0.064/0.070/0.076 0.079/0.091/0.101 0.079/0.091/0.101 0.110/0.120/0.130
Cooling A 0.24/0.25/0.26 0.24/0.25/0.26 0.37/0.38/0.39 0.54/0.56/0.58 0.54/0.56/0.58 0.70/0.72/0.73
• Chassis unit for discrete customisable installation Running
current Heating A 0.17/0.18/0.19 0.17/0.18/0.19 0.30/0.31/0.32 0.37/0.41/0.43 0.37/0.41/0.43 0.52/0.54/0.56
• Complete with removable filters
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan
• Pipes can be connected to the unit either from the bottom or rear
m³/h 420/360/300 420/360/300 540/420/360 720/540/480 900/780/660 1,020/840/720
• Easy to install Fan Air flow rate (H/M/L)
L/s 117/100/183 117/100/183 150/117/100 200/150/133 250/217/183 283/233/200
Motor output kW 0.01 0.01 0.02 0.02 0.03 0.06
Sound power level (H/M/L) dB 44/41/39 44/41/39 50/46/40 49/46/42 49/46/42 52/49/46
Sound pressure level (H/M/L) dB(A) 33/30/28 33/30/28 39/35/29 38/35/31 39/36/31 41/38/35
Dimensions HxWxD mm 616 x 904 x 229 616 x 904 x 229 616 x 904 x 229 616 x 1,219 x 229 616 x 1,219 x 229 616 x 1,219 x 229

Perimeter air conditioning with high interior quality Pipe


Liquid mm (inches) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø6.35 (Ø1/4) Ø9.52 (Ø3/8)
Gas 410 A mm (inches) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø12.7 (Ø1/2) Ø15.88 (Ø5/8)
connections
Drain piping VP-20 VP-20 VP-20 VP-20 VP-20 VP-20
Net weight kg 21 21 21 28 28 28

Specifications are subject to change without notice.


Rated conditions: Cooling Heating
GLOBAL
Indoor air temperature 27˚C DB / 19˚C WB 20˚C DB
REMARKS
Outdoor air temperature 35˚C DB / 24˚C WB 7˚C DB / 6˚C WB

R1 TYPE CONCEALED
FLOOR STANDING
Dimensions
1 4 x Ø12 holes (for floor fixing)
2 Electric equipment box
3 Power supply outlet (inner dimension)
4 Air filter (inner dimension)
5 Discharge duct connection flange (hole pitch=100)
6 Refrigerant connection outlet (liquid pipes)
7 Refrigerant connection outlet (gas pipes)
8 Drain filter
9 Drain pan
10 Level adjustment bolt
11 Drain outlet VP20 (with vinyl hose)

unit: mm
Indoor unit A B C D E F Liquid pipes Gas pipes
22 to 36 type 904 692 672 665 500 86
45 type Ø6.35 Ø12.7
56 type 1,219 1,007 1,002 980 900 51
71 type Ø9.52 Ø15.88

90 91

180730_FSV_ASIA_D_2.indd 90-91 2018/10/12 14:40:47


Indoor Unit Indoor Unit

Remark For High Static Ducted Series

E2 type E2 type E1 type


High Static Ducted Energy Saving High Static Ducted
High-Fresh Air Ducted

H1 type
High-Fresh Air Ducted

Model Operation Rap valve kit 3-way control PCB 3-way valve kit 3-way valve kit Distribution Joint kit Distribution Joint kit
multiple connection <2pipes> <3pipes>
CZ-P160RVK2 CZ-CAPE2 CZ-P160HR3
port type 4 port CZ-P160BK2 CZ-P224BH2
CZ-P4160HR3 for 22.4kW unit or less for 22.4kW unit
(160 type) CZ-P680BK2 CZ-P680BH2
for more than 22.4kW for 28.0kW unit

X 4pcs

Cooling Only - - - - - -
E2 Type
High Static Cool or Heat - - - - - -
Ducted
Heat Recovery - 2pcs 2pcs use 2ports 1pc 1pc

Cooling Only - - - - - -
E2 Type
Energy Saving
Cool or Heat 2pcs 2pcs - - 2pcs -
High-Fresh Air
Ducted
Heat Recovery - 2pcs 2pcs use 2ports 1pc 1pc

Cooling Only - - - - - -
E1 Type
High Static
Ducted Cool or Heat 2pcs - - - 2pcs -
(Only for
S-224,S-280)
Heat Recovery - - 2pcs use 2ports 1pc 1pc

Cooling Only - - - - - -
H1 Type
High-Fresh Air Cool or Heat 2pcs - - - 2pcs -
Ducted
Heat Recovery - - 2pcs use 2ports 1pc 1pc

92 93

180730_FSV_ASIA_D_2.indd 92-93 2018/10/12 14:40:50


VRF Smart Connectivity+ VRF Smart Connectivity+

VRF Smart Connectivity+


NEW

Through thorough energy management, Panasonic’s VRF


Smart Connectivity is a completely new, state-of-the-art
solution providing energy saving and comfort as well as
simple installation, operation and running.

VRF Smart Connectivity+


~New SE8000~
VRF Smart Connectivity+ 1. Quality Air Control
VRF Smart Connectivity+ offers efficient energy management and a new air conditioning control
Optimum IAQ is realized using the CO2 & humidity sensors. The
solution with high IAQ (Indoor Air Quality).
interior remains comfortable, while heating and cooling costs are
minimized.
Each room is monitored by high-precision sensors,
Energy Management making it possible to make every room’s
The CO2 sensor controls ventilation systems which contributes to
System for Rooms temperature comfortable without wasting energy.
improving the room’s air quality.

A Building Energy Management System (BEMS) can


Management System for also be connected for Plug & Play centralised 2. Room Key Card or Key Cardless Solutions for Hotels
the Entire Building control of the building’s entire energy consumption.
Solutions are provided that meet the needs of various regions and hotel grades.
Whilst the previous model’s automatic detection function offered optimal air conditioning with
Advantages or without a hotel room key card, the latest model enables conventional key cards to control
air conditioners and other devices coordinately.The increase in the types of devices that can
Dramatic Reduction of OpEx with Ultimate Customisation. be connected enables customized control of any hotel room.
Outstanding IAQ. · Background colour customisable
· 3 Built-in sensors: Temperature, RH and · Custom display/icons, messages
Occupancy · Programmable logic (also stand alone)
· ZigBee wireless sensors: CO2/Temperature/ · Various controls and various external 3. Other Equipment Control
RH%, window/door, ceiling/wall connection devices
One room controller manages various devices including lighting and the blinds.
User-/Owner-friendly. Easy Design and Plug and Play to A ventilation system and other external connection devices (dry contact input)
· Colour touch screen Reduce CapEx. can be connected so that various control is possible with this controller alone,
· Ease and simply of use · Simple Plug & Play VRF connection to even without BEMS.
· 22 Languages Building Energy Management System
· Easy-to-understand error description (BEMS)
· Stand alone or BEMS connected
· Easy Installation of ZigBee Sensors

94 95

180730_FSV_ASIA_D_2.indd 94-95 2018/10/12 14:40:53


VRF Smart Connectivity+ VRF Smart Connectivity+

Energy Management System for Rooms Management System for the Entire Building
By installing a ceiling motion sensor, wall motion temperature sensor, window/door sensor,
The smarter solution to simplify energy management,
and CO2 sensor in the room, ideal, waste-free air conditioning is achieved.
optimise building efficiency and drive savings.

VRF
Plug and Play BEMS connection.
With the SE8000, connection to BEMS is extremely easy. Better still, a remote controller is all that’s needed to
OR enable use as a stand-alone system. In addition to dramatically reducing the burden on system integrators, this
cuts costs.
Wired Connection

PAC

SE8000
Panasonic AHU
VRF (VRF Operated)
ZigBee · VRF
· GHP

Wall/Ceiling motion/ Door/Window CO2 Sensor Water Leakage Hotel Room Controller
temperature/ Sensor Sensor (HRC)
humidity Sensor
Relay Pack
(TE2)
A
Wall/Ceiling motion/
temperature/
humidity Sensor
ZigBee

Sensing & Control technology


Using sensors from Schneider Electric, high-quality Room
Door/Window Sensor controller
occupancy control and automatic IAQ control were
Ceiling motion
realised. The sensors detect the presence or absence Window sensor
ZigBee
sensor (option)
(option)
of occupants, and the opening and closing of doors Door sensor
(Option)
and windows to achieve the most efficient energy Room CO2 Sensor
management for exceptional air-conditioned comfort. controller

Flexible installation is possible to match different CO2 sensor


(option)

applications and building features such as walls, Built in PIR,


Humidity
ceilings and proximity to doors and windows. No Water
Water Leakage Sensor

wiring means extra installation versatility. leakage sensor


(Option)

Batteries last for up to five years (10-year battery for CO2 sensor), and are easy to BEMS Hotel Room
install and replace.
Gateway Controller Relay Pack
(MPM) (HRC) (TE2)
B

With VRF dedicated GUI

A SE8000 smart controller with


Door/Window Sensor Wall/Ceiling motion/ CO2 Sensor direct hub to ZigBee® Pro
Door and window contact detection temperature/humidity Sensor Monitor indoor air quality, review data on sensors. C
sensor to monitor opening and closing. Wall and ceiling sensor to detect the interfacing devices, and control fresh air
presence or absence of occupants. inside customizable zones.
Great Occupancy and IAQ BEMS Widget
control. (Exclusive)
Ex: Hotel room occupancy
check by PIR sensor, IAQ by
CO2 sensor, Door / Window
contacts.

B BACnet IP connection would


be prefferable (BACnet MS/TP
or Modbus RTU could be
selectable as an option).
Water PackTE2
Relay Leakage Relay
RelayPackTE2
Pack Hotel Room Controller
Sensor
TE2 ( TE2 ) ( HRC) C For Schneider Electric BEMS BEMS Gateway
Two sensing pads under the Wireless programmable terminal The Hotel Room Controller controls connection, Panasonic VRF ( MPM)
body activate when water is equipment controllers for HVAC connected guest room devices and widgets enable easy Plug and Multi-Purpose Management devices
present between the two pads. equipment and pulse counting. aggregates data, making it visible to enable the control, monitoring, and
Detecting the water, the sensor Includes local memory to store guest room and property management Play.
management of entire sites via Schneider * Graphic shows combination of products from Panasonic,
reports the event to the controller. fail safe control sequence. systems. Better understanding for VRF Electric’s BMS system. Schneider Electric and others. Please consult authorised
as a chiller system. dealer for more details.

* Specifications are subject to change.

96 97

180730_FSV_ASIA_D_2.indd 96-97 2018/10/12 14:41:03


VRF Smart Connectivity+ VRF Smart Connectivity+

Smart Management Solutions 2 Small and Medium Offices 3 Super Markets

1 Hotels
Room Key Card or Key Cardless
Solutions for Hotels
The SE8000 and ZigBee Sensor automatic detection
function offer optimal air conditioning regardless of
whether there is a hotel room key or not. Sensors
detect the presence or absence of occupants and
the opening and closing of doors and windows for
the optimum air-conditioned environment guests
expect. Automatic control ensures the most efficient CO2 sensors (option) and Humidity sensors Humidity sensors
operation when guests are away or when windows CO2 sensors (option) take measurements in units of Humidity sensors enable automatic dehumidification
are open. This contributes to an appreciable ppm, and humidity sensors enable fine air quality for the optimum IAQ regardless of climatic
reduction in operation costs. control. This creates the most comfortable space for conditions. This creates an even more comfortable
occupants while contributing to improved employee environment for customers, employees, and
satisfaction. products themselves.
1. Remote sensing & IAQ contorol 2. BEMS Connectivity * Except for products for small sized project (Ultra Slim Ducted, Bulkhead Ducted, 4-PIPE Mini Cassette)

In addition to detecting a room’s temperature, humidity and With MPM as the BEMS gateway and by setting HRC as the
CO2 concentration, ZigBee remote sensors detect the guestroom controller, sensing, control and BEMS connection Innovative and Unrivalled Advantages
opening/closing of windows and doors, and the presence/ can be realized in coordination with SE8000!
Colour and Design to Match Office Interiors Customisation in Approx. 22 Languages Possible
absence of people in a room.
Colour combinations The display can be customised to match the native
Various IAQ controls and detailed energy savings are
and design can be languages of guests to
possible by using TE2 (Relay Pack) based on this detected
set to match different enable smooth, stress-free
information.
facilities. communication for
MPM BACnet
BEMS hospitality at its finest.

ERV
R1/R2 Ceiling
Motion
R1/R2 Easy-to-Understand Error Description Programmable Logic
Window
Sensor*
Sensor
BACnet Error description during an Full customisation of remote
Door
Sensor*
emergency is easy to control logic possible, and
understand, enabling staff updating to match conditions.
Room Room
controller CO2/ controller to respond quickly.
Temp.+RH% HRC
Sensor
ZigBee ZigBee
Modbus
TE2 *In electrical
22 languages Wall motion 22 languages distribution panel
Sensor (field supply)
*In electrical Water
distribution panel leakage sensor
(field supply) (Option)

Smart Connectivity Devices


3. Key Cardless control 4. Other control
The introduction of TE2 and HRC enables conventional wired The introduction of TE2, HRC and MPM enables the on/off
keycards to be connected to the system so that it is possible control of devices having dry contact input, such as
to meet the specific requirements of various hotel and room ventilation, lighting and blinds.
types. MPM HRC Door/Window Sensor Wall/Ceiling motion/temperature/
SED-WDC-G-5045 humidity Sensor ZigBee Communication Card
VCM
*With optional VCM communication card

ERV ERV
R1/R2 R1/R2
Light on/off Light
Control Control
Modbus
Modbus
Key Card
(Wired) Schneider Electric
Room Room CO2 Sensor Water Leakage Sensor brand - SE8000
controller controller HRC SED-CO2-G-5045 SED-WLS-G-5045
HRC

BACnet
TE2
ZigBee
*In electrical
TE2
ZigBee
*In electrical
Features · Up to 5-year battery life (10-year battery for CO2 sensor), batteries included
Key Card
(Wired)
22 languages distribution panel 22 languages distribution panel · Battery level is a point
(field supply) (field supply)
· Sensor points visible when SE8000 is integrated via BACnet MS/TP
*In electrical *In electrical
distribution panel distribution panel · Sensor status and battery level visible when SE8150 is integrated via ZigBee® Pro
(field supply) (field supply)
· Integration to BMS only recommended when each MPM is connected to Ethernet and set as a ZigBee®
Coordinator node

98 99

180730_FSV_ASIA_D_2.indd 98-99 2018/10/12 14:41:14


VRF Smart Connectivity+ VRF Smart Connectivity+

Reference Description Reference Description


SER8150R0B1194 Pana Net Con, RH, No PIR, SE Brand, R1R2 Relay Pack TE2
HRC
SER8150R5B1194 Pana Net Con, RH, PIR, SE Brand, R1R2 HRCEP14R Hotel Room Expansion Module 14IO Dimensions
VCM8000V5094P Wireless ZigBee Pro communication card
HRCPBG28R Hotel Room Controller 28IO
TE2 HRCPDG42R Hotel Room Controller w/Display 42IO
ZigBee Pro 108mm Specifications
Smart Terminal Controller ZigBee Pro High Power, External Antenna, 4UI/4AO/5DO,
SEC-TEA-R-230-5045 ZigBee Sensors (optional pink striped *Al3 can be used for pulse counting (4.25 in) Dimensions 6.93in x 4.25in
220-240VAC antenna for 2.4GHz) when ZigBee is paired directly to MPM 176mm x 108mm
Smart Terminal Controller ZigBee Pro High Power, External Antenna, 4UI/4AO/5DO, SED-CO2-G-5045 Sensor with Room CO2, Temperature and Humidity Voltage 24VAC; ± 15%; 50/60HZ; Class 2.
SEC-TEA-R-24-5045 SED-TRH-G-5045 Sensor with Room Temperature and Humidity 24VDC ± 10%
24VAC GND R5A
SED-WDC-G-5045 Door/Window Sensor 115VAC/230VAC
Typical Consumption 10VA (115/230 VAC)
MPM SED-MTH-G-5045 Wall/Ceiling motion/temperature/humidity Sensor AI1 R5B
5VA (24V)
MPM-UN-0I4-5045 Universal network controller with Building Expert and StruXureWare integration, Inputs Pulse input: Support for one

176mm (6.93 in)


SED-WLS-G-5045 Water Leakage Sensor AI2 R4A
fast pulse input counting
High Power, 6 I /6O, Modbus AI3* R4B (up to 1000Hz / 1ms) – AI3
MPM-RAEC-5045 Universal network controller Cable extension Outputs Analog (x4): 0-12V, nominal 50 mA max each,
AI4 R3B 12-bit resolution
Relay (x5) (optional): Maximum 230VAC, 5A per relay.
GND Live First three relays (R1, R2 and R3) or based on
AO1 R2B input power voltage (24V, 115VAC or 230VAC).
Two relays (R4 and R5) are independent of
VRF Smart Connectivity controller external dimensions AO2
AO3
Live
R1B
the input power voltage
Analog (x1): 24VAC, 2VA (115 VAC and 230 VAC Voltage
only models, one additional output)
(*20VAC if used with 110V 50Hz)
AO4 Live ZigBee Pro Frequency: 2400 to 2483.5MHz, 16RF channels
Room Controller for SE8000 Wall/Ceiling Wireless Sensor SED-MTH-G-5045 NC Neutral
Range Non line of sight to MPM: 50ft/17m
Line of sight to MPM: 100ft/30m
Dimensions Dimensions Specifications NC Neutral Certification
Dimensions 70mm diam..x26.6mm 24VAC Neutral Check with your local government for
Colour White instruction on disposal of these products.
Weight 59g GND Neutral
Communication ZigBee 3.0 HA 56mm for DIN rail mount
Detection Range Ceiling: (2.20 in)
Ø4m (installation height 2.5m)
Wall:
R5m (installation height 1.2m)
Battery Voltage 3V
120mm (4.72”)

Battery Cell LR03 AAA (2pcs)


Battery Life Up to 5 years Hotel Room Controller HRC
Ambient Temperature -10° - +50°C
Dimensions
Certification
144mm/5.6in
Check with your local government for Specifications
instruction on disposal of these products.
Dimensions 5.6in x 4.3in x 2.4in
144m x 110mm x 60.5mm
USB

Digital Inputs 12
Door/Window Wireless Sensor SED-WDC-G-5045 High Voltage Relay 10 x 3 A SPST +250 VAC relays
86mm (3.37”) Digital Outputs
Dimensions mini
Analog Inputs 12 x configurable analog inputs
25mm (0.99”)

USB

DI: voltage free DI, 10 kΩ input impedance


0-20mA: range 0..1000, < 150 Ω impedance

110mm/4.3in
HRC
0-10V: range 0..1000 > 10 kΩ impedance
Analog Outputs 6 x 0-10 V outputs. Load impedance > 700 Ω
Supply Voltage 24 VAC + 10% NOT ISOLATED
Master part +20...38 Vdc NOT ISOLATED
OK
Supply Frequency 50/60 Hz
Power Cycle 35 VA / 15 W
Operating -20 to 60 °C (-4 to 140 °F) conforming to UL 60730-1
Temperature
Storage Temperature -30 to 70 °C (-22 to 158 °F)

R1R2 Certification
Slave part Check with your local government for
instruction on disposal of these products.
Specifications
Dimensions Master part: 50mmx33mmx16.3mm Slave part: 50mmx9mmx9mm
Colour White/transp.
Weight 30g
Communication ZigBee 3.0 HA
Detection Range Trigger 'close': wood 30mm, metal 18mm
13 14 15
Tigger 'open': wood 32mm, metal 20mm BEMS Gateway MPM
Battery Voltage 3V
RS-485 REF

Battery Cell CR2450 Dimensions


RS-485 +
RS-485 -

Battery Life Up to 5 years


Ambient Temperature -10° - +50°C EnOcean (optional)

15VDC
OP 1A
OP 1B
OP 2A
OP 2B
BACnet MS/TP or Modbus
Certification (Gray striped antenna for 868MHz)
126mm

GND

GND

GND
Output port

AO1

AO2

AO3

AO4
Check with your local government for (Yellow striped antenna for 902MHz)
instruction on disposal of these products. (4.96 in)
Specifications
Dimensions Humidity Sensor and Calibration CO2 Sensor SED-CO2-G-5045
Height: 12cm/4.72in Single point calibrated bulk polymer type
Width: 8.6cm/3.39in sensor
ZigBee Pro (optional)
Dimensions
Depth: 2.7cm/1.06in Humidity Sensor Precision (Pink striped antenna for 2.4GHz)

132mm (5.20 in)


Power Requirements Reading range from 10 to 90 % R.H. non-
16 Vdc from Panasonic R-R IDU condensing 10 to 20% precision: 10%
connectors 20% to 80% precision: 5% 24V AC/DC 24V AC/DC
50/60 Hz, 4VA, Class 2 Supply 80% to 90% precision: 10% CAN H
Range from Indoor Unit Humidity Sensor Stability CAN H
Recommended 500ft (150 m) Less than 1.0 % yearly (typical drift) CAN L CAN L
Operating Conditions Wiring GND
0 °C to 50°C (32°F to122°F) Maximum wire length between last indoor GND
0% to 95% R.H. non-condensing unit to SER8150RxB1194 equals 490ft
Storage Conditions (150m) with AWG #18 wire (0.82 mm2).
-30°C to 50°C (-22°F to 122°F) Refer to Panasonic VRF guidelines “Wiring
Ethernet 100B/T
0% to 95% R.H. non-condensing System Diagram for Remote Controller” for
Temperature Sensor this limitation.
Local 10 K NTC type 2 thermistor Approximate Shipping Weight
Temperature Sensor Resolution 0.34 kg (0.75 lb)
± 0.1°C (± 0.2°F)
for DIN rail mount

GND

GND

GND

GND

GND

GND
Temperature Sensor Accuracy Input port

AI6

AI5

AI4

AI3

AI2

AI1
± 0.5°C (± 0.9°F ) @ 21°C (70°F) typical 34mm

B
A
calibrated Specifications (1.34 in)
Dimensions 3.26in x 2.85in x 0.72in
Check with your local government for 82.9 mm x 72.4 mm x 18.4 mm
Operating Temperature 0°C to 50°C (32°F to 122°F)
RS 485 connectors for
instruction on disposal of these products. Specifications
Temperature Accuracy ±0.3°C (0.54 °F) typical within operating range Modbus (optional)
Humidity Range 0% to 100% Dimensions 5.20in x 4.96in
THIS PRODUCT FOR COMMERCIAL USE ONLY Humidity Accuracy ± 3% RH (typical within 0% to 80% RH) 132mm x 126mm
Measurement Range 0 to 5000 ppm Voltage 24VAC; ± 15%; 50/60HZ
Measurement/ 24VDC ± 10%
Transmission Intervals 2.5 minutes (day), 10 minutes (evening) Typical Consumption 5 VA + Output (VAC), 1.6 W + Output (VDC)
Note: Battery life will be reduced should interval Communication ZigBee Pro, EnOcean, BACnet
be shortened (i.e. using remote CANbus (125-500 Kbps)
temperature/humidity functions) Ethernet (10/100 Mbps)
CO2 Accuracy at NTP ±60ppm +3% of reading (400 - 2,000ppm range) Analog Inputs Current: 4-20mA with 249 external resistor
Communication Zigbee 3.0 Green Power (encrypted, bi-directional) Voltage: 0-10V
Battery Voltage 3.6 V Outputs Analog (x4): 0-12V,nominal 50mAmax each,
Battery Cell AA Lithium ion 12-bit resolution
Battery Life 10+ years (non-replaceable) Relay (x2): 24V, 1.1 Amp per relay
Note: Battery life can be reduced when sensor is operated at RS485 (optional) Supported protocols: Modbus
temperatures approaching the operating limits. ZigBee Pro (Optional) Frequency: 868MHz, 902MHz
Ambient Temperature -30°C to 70°C
Certification
Certification
Check with your local government for
Check with your local government for instruction on disposal of these products.
instruction on disposal of these products.
* Except for products for small sized project (Ultra Slim Ducted, Bulkhead Ducted, 4-PIPE Mini Cassette)
100 101

180730_FSV_ASIA_D_2.indd 100-101 2018/10/12 14:41:16


FSV Controllers

FSV Controllers
ECONAVI Sensor
CZ-CENSC1

Utilises ECONAVI Sensor


and Control Program
technologies to detect
where energy is normally
A wide variety of control options to meet the wasted and self-adjusts
cooling power to reduce
requirements of different applications. energy waste.

• Activity detection
• Absence detection

OPERATION
INDIVIDUAL CONTROL SYSTEMS TIMER OPERATION CENTRALISED CONTROL SYSTEMS
SYSTEM
Simplified load distribution ratio BMS System Connection with
Operation from anywhere in the Operation with various functions Only ON/OFF operation from (LDR) for each tenant PC Base 3rd Party Controller
Requirements High-spec operation Normal operation Quick and easy operation Daily and weekly program
room from a central location a central location
10.4 in. touch screen panel color LCD
P-AIMS Software Seri-Para I/O unit
Up to 1024 units for outdoor unit

External appearance

CZ-CAPDC2
CZ-CSWKC2

High-spec Wired Timer Remote Controller


Wireless Remote Controller Simplified Remote Controller Schedule Timer System Controller ON/OFF Controller Intelligent Controller
Remote Controller (Wired)
Optional software Interface Adaptor
Type, model name
CZ-RWSU3 CZ-RWSD2
CZ-256ESMC3
CZ-RTC5B CZ-RTC4 CZ-RWSL2N CZ-RWST3N CZ-RE2C2 CZ-ESWC2 CZ-64ESMC3 CZ-ANC3
(CZ-CFUNC2)
CZ-RWSC3 CZ-RWSK2
CZ-CAPC3
Built-in thermostat l l l l — — — —
ECONAVI Seri-Para I/O unit
ON/OFF control l l — — — l — l CZ-CSWAC2
for Load distribution for each indoor unit
Number of indoor CZ-CSWWC2
units which can be 1 group, 8 units 1 group, 8 units 1 group, 8 units 1 group, 8 units 64 groups, max. 64 units 64 groups, max. 64 units 16 groups, max. 64 units 64 units x 16 systems, max. 256 units for Web application
controlled CZ-CSWGC2
for Object layout display
·R
 equired power supply CZ-CSWBC2 CZ-CAPBC2
·U
 p to 2 controllers can ·U
 p to 2 controllers can · Up to 10 controllers, can be
from the ·U
 p to 8 controllers (4 main units + for BACnet software
be connected per group be connected per group connected to one system.
system controller 4 sub units) · A communication adaptor interface
(When using ECONAVI (When using ECONAVI ·U
 p to 2 controllers can be ·U
 p to 2 controllers can be · Main unit/sub unit (1 main unit + 1
Use limitations
sensor, only one remote sensor, only one remote connected per group. connected per group.
·W
 hen there is no system
sub unit) connection is possible.
can be connected to one system. (CZ-CFUNC2) must be installed
*PC required (field supply) Communication
controller, connection is ·U
 se without remote controller is for three or more links.
controller is possible to controller is possible to
possible to the T10
· Use without remote controller is
impossible.
Adaptor
connect at indoor unit) connect at indoor unit) possible.
terminal of an indoor unit.

Function ON/OFF l l l l — l l l CZ-CFUNC2


Mode setting l l l l — l — l
Fan speed setting l l l l — l — l LonWorks Interface
Temperature setting l l l l — l — l
Air flow direction l l l l — l — l
Permit/Prohibit
switching — — — — — l l l CZ-CLNC2

Weekly program l l — — l l — l
All specifications are subject to change without notice.

102 103

180730_FSV_ASIA_D_2.indd 102-103 2018/10/12 14:41:20


FSV Controllers FSV Controllers

Individual Control Systems High-spec wired remote controller (CZ-RTC5B)

Control contents Part name, model No. Quantity Basic Operation


• Individual Louver Control (Lock individual flap only
Standard Control Timer remote controller 1 unit each
• Control of the various operations of the indoor unit by wired or CZ-RTC4 / CZ-RTC5B for 4-way cassette U1 type)
wireless remote controller. Simplified remote controller • ON/ OFF timer
• Cooling or heating mode of the outdoor unit is decided by the CZ-RE2C2
first priority of the remote controller. Wireless remote controller • Weekly Timer
• Switching between remote controller sensor and body sensor CZ-RWSU3 / CZ-RWSL2N / CZ-RWSC3 / CZ-RWSK2 / • Filter information*
is possible. CZ-RWST3N / CZ-RWSD2
• Outing function
• Quiet operation mode*
(1) Group control Timer remote controller 1 unit • Energy saving
• Batch remote control on all indoor units. CZ-RTC4 / CZ-RTC5A
• Initial settings
• Operation of all indoor units in the same mode. Simplified remote controller
• Up to 8 units can be connected. CZ-RE2C2 • Ventilation
• The sensor is the body sensor, and thermostat ON/OFF Wireless remote controller
setting in regard to the temperature set by the remote CZ-RWSU3 / CZ-RWSL2N / CZ-RWSC3 / CZ-RWSK2 / Dimensions
controller is possible for each indoor unit. CZ-RWST3N / CZ-RWSD2 H 120 x W 120 x Maintenance Function
D 16 mm
• Outdoor unit error data
• Service Contact address
(2) Main/sub remote control Main or sub As required
• Max 2 remote controllers per indoor unit. (Main remote Timer remote controller
• RC setting mode
controller can be connected) CZ-RTC4 / CZ-RTC5A Energy Saving • Test Run
• The button pressed last has priority. Simplified remote controller • ECONAVI on/ off* • Sensor Information
• Timer setting is possible even with the sub remote controller. CZ-RE2C2
(When using ECONAVI sensor, only one remote controller is Wireless remote controller • Temperature Auto Return • Service check
possible to connect at indoor unit) CZ-RWSU3 / CZ-RWSL2N / CZ-RWSC3 / CZ-RWSK2 / • Temperature Setting Range • Simple/ Detailed Settings
CZ-RWST3N / CZ-RWSD2
• Auto Shutoff • Auto address
• Schedule peak cut * Depending on the model, some menus cannot be used.
• Repeat off timer
SYSTEM EXAMPLE FSV

Timer remote controller (CZ-RTC4)

Weekly Programme Function


• A maximum of 6 settings/day and 42 settings/week
can be programmed.

Outing Function
• This function can prevent the room temperature
Remote controller Main Sub Main Sub from dropping or rising when the occupants are out
for a long time.
Standard control (2) Main/sub (1) Group control
remote control Sleeping Function
• This function controls the room temperature for
Dimensions
comfortable sleeping.
H 120 x W 120 x
D 20 mm
Max. 8 indoor units can be controlled from
one remote controller
Basic remote controller ON/OFF
• Operation mode changeover Remote control by main remote controller
(Cooling, Heating, Dry, Auto, Fan). and sub controller is possible
• Temperature setting
(Cooling/Dry: 18-30 deg Heating: 16-30 deg). Max. 2 remote controllers (main remote controller and
• Fan speed setting H/ M/ L and Auto. sub controller) can be installed for one indoor unit.
• Air flow direction adjustment. * Depending on the model, some menus cannot be used.
• ECONAVI on/ off*

Time Function 24 hours real time clock


• Day of the week indicator.

104 105

180730_FSV_ASIA_D_2.indd 104-105 2018/10/12 14:41:21


FSV Controllers FSV Controllers

Wireless remote controller Timer Operation


Remote control by main remote controller
and sub controller is possible Schedule timer (CZ-ESWC2)
• Max. 2 remote controllers (main remote controller
and sub controller) can be installed for one indoor • A function for pausing the timer in case of
unit. national holidays has been added, and
timer operation also can be stopped for a
When CZ-RWSC3 is used, wireless control long time
L1 type U2 type
CZ-RWSL2N CZ-RWSU3 becomes possible for all indoor units
• When a separate receiver is set up in a different · By setting holidays or operation stop within one
room, control from that room also becomes week, the timer can be paused just for that week.
possible. · All timer settings can be stopped with the timer
•A utomatic operation by means of the emergency “ON/OFF effective” button. (Return to timer
Dimensions
operation button is possible even when the remote H 120 x W 120 x D 16 mm operation is made by pressing the button again.)
controller has been lost or the batteries have been
T2 type exhausted. Up to 64 groups (max 64 indoor units) can
CZ-RWST3N The power supply for the schedule timer is taken from one of the
D1 type K1, K2, Y2 type be controlled divided into 8 timer groups
CZ-RWSD2 CZ-RWSK2 In addition, there are other functions such following.
1. C ontrol circuit board (T10) of a nearby indoor unit (power
as temperature setting, operation • Six program operations (Operation/Stop/ supply wiring length: within 200m from the indoor unit).
switching, airflow direction/fan speed Local permission/ Local prohibition) per 2. S ystem controller (power supply wiring length: within 100 m
setting, etc from the indoor unit).
day can be set in a program for one week When the power supply for the schedule timer is taken from the
control circuit board of the indoor unit, that indoor unit cannot be
Ventilation independent operation is · Only operation or stop, remote controller local used with other control devices using the T10 terminal.
possible As operation mode and temperature settings are not possible
permission or remote controller local prohibition, with the schedule timer, it must be used together with a remote
When commercial ventilation fans or heat-exchange and their respective combinations are possible. controller, a system controller, an intelligent controller, etc. Also,
For all indoor units
CZ-RWSK2 + ventilation fans have been installed, they can be (Operation + local permission, stop + local as it does not have an address setting function, the control
CZ-RWSC3 function of a system controller etc. must be used for address
operated with this remote control (interlocked prohibition, only local permission, etc.) setting.
operation with the indoor unit or independent · Local prohibition and the combination of the three
ventilation ON/OFF). items of temperature setting, mode change, and
operation/stop can be set at the time of
installation.

Simplified remote controller (CZ-RE2C2)


Connection example 1 (POWER SUPPLY FROM THE INDOOR UNIT)

A remote controller with simple functions and basic operation


• Suitable for open rooms or hotels where detailed functions are not required.
• ON/OFF, operation mode switching, temperature setting, airflow velocity switching,
airflow direction setting, alarm display, and remote controller self-diagnosis can be
performed.
• Batch group control for up to 8 indoor units. Remote Schedule
controller timer
• Remote control by main remote controller and sub controller is possible with a
simplified remote controller or a wired remote controller (up to two units).
• Built-in temperature sensor
Dimensions
H 120 x W 70 x D 17 mm Connection example 2 (POWER SUPPLY FROM THE SYSTEM CONTROLLER AND ON/OFF CONTROLLER)

Indoor/outdoor
operation wire Zone 1
Centralised Timer group 1: Timer group 2:
addresses Centralised Centralised
1 to 16 addresses addresses
Schedule System 1 to 8 9 to 16
timer controller

Zone 2 Timer group 3: Timer group 4:


Centralised
addresses 17 Centralised Centralised
to 32 addresses addresses
17 to 24 25 to 32

Zone 3
Centralised Timer group 5: Timer group 6:
addresses 33 Centralised Centralised
to 48 addresses addresses
33 to 40 41 to 48

Zone 4
Centralised Timer group 7: Timer group 8:
addresses 49 Centralised Centralised
to 64 addresses addresses
49 to 56 57 to 64

106 107

180730_FSV_ASIA_D_2.indd 106-107 2018/10/12 14:41:23


FSV Controllers FSV Controllers

Centralised Control Systems • A control mode corresponding to the use condition can be selected from 10 patterns

A : Operation mode: Central control mode or remote control mode Connection example
can be selected
A Operation mode
System controller (CZ-64ESMC3) Central control mode: The system controller is used as centralised
control device. (Setting from a remote controller can be prohibited Central control mode Remote control mode
by prohibiting local operation from the system controller.) All central control
All mode All remote control
Dimensions Remote control mode: The system controller is used as a remote Example 1
H 120 x W 120 x D 16 + 52 controller. (Setting from the system controller can be prohibited by
Zone 1 Zone 1 central control
(embedding dimension mm) prohibiting local operation from another central control unit.) Zone 1 remote control
B mode Example 2
Controlled
Zone 2 Zone 2 remote control
Power supply: AC 100 to 240 V B : Controlled unit number mode: All mode or zone 1, 2, 3, 4 unit Zone 2 central control
mode Example 3
I/O part: mode can be selected number
Remote input part (effective mode Zone 3 Zone 3 central control
All mode: All, zone, or group unit can be selected. Zone 3 remote control
voltage:DC24V) All operation,All mode Example 4
Zone 1, 2, 3, 4 mode: Setting is possible only for the indoor units
stop,Demand 1,Demand 2
of zone 1, 2, 3, or 4. Zone 4 Zone 4 remote control
Remote output part (non Zone 4 central control
mode Example 5
voltage contact) Operation,
Alarm (external power supply
within DC 30V, max 0.5A)
Total wiring length : 1 km

System
controller

Individual remote controller


Control mode example 2: Central control for zone 1

System controller
Group control

Individual control is possible for max 64 groups, 64 indoor units. Control mode example 3: Remote control for zone 2

• Control of 64 indoor units divided into 4 zones. (One zone can have up to 16 groups, and
one group can have up to 8 units.)
System controller
Individual remote controller
• Control is possible for ON/OFF, operation mode, fan speed, air flow direction, operation Control mode example 4: Central control for zone 3

monitoring, alarm monitoring, ventilation, remote controller local operation prohibition, etc.
Prohibition setting for Remote controller operation
Setting mode ON/OFF Mode Temperature Fan speed Flap System controller System without a
Control of a group
remote controller
without remote controller
Permit l l l l l
Control mode example 5: Remote control for zone 4
Prohibit 1 — l l l l
Prohibit 2 — — — l l System controller
Control mode example 1: All central control
Prohibit 3 l — — l l
Prohibit 4 l — l l l
In case of joint use with a wireless remote controller, there are limitations for the control mode. Please use only with setting “Permit” and “Prohibit1
(prohibition for ON/OFF)”. ON/OFF controller (CZ-ANC3)
*Contents for Prohibit 1~4 can be modified.
l : Operation from the remote controller is possible.
— : Operation from the remote controller is prohibited.
Dimensions
H 121 x W 122 x D 14 + 52
(embedding dimension mm)

• Joint use with a remote controller, an intelligent controller, etc. is possible


Power supply: AC 100 to 240 V
(The maximum number of connectable system controllers is 10, including other central controllers on the same circuit.) I/O part:
(In case of joint use with a wireless remote controller, there are limitations for the control mode. Please use only with setting “Permit” Remote input (effective
voltage: within DC 24 V): All ON/OFF
and “Prohibit1 (prohibition for ON/OFF)”.) Remote output (allowable
voltage: within DC 30 V): All ON, All alarm
• Control of systems without a remote controller and of main/sub systems
(a total of up to 2 units) is possible

• Weekly timer function


• 8 programs per day (with ON/OFF/Mode/Temperature/Central control setting items) for 1week (7days) can be set.
• Special holiday setting can ignore the timer operation temporary by keeping original timer setting. (Special holiday setting can be removed • 16 groups of indoor units can be controlled.
by same setting display.) • Collective control and individual group (unit) control can also be performed.
• Up to 8 ON/OFF controller (4 main, 4 sub) can be installed in one link system.
• 5 types of Energy saving function
Set temperature automatic return / Set temperature range limitation / Off remind / Off timer operation / Demand control timer
• The operation status can be determined immediately.

108 109

180730_FSV_ASIA_D_2.indd 108-109 2018/10/12 14:41:24


FSV Controllers FSV Controllers

Intelligent controller (CZ-256ESMC3)

• Outdoor unit quiet operation ON/OFF System configuration


The following is an example of a system configuration.
• Energy-saving Functions
Intelligent Controller Area group
• Event control [such as equipment linkage] Distribution group
Inter-unit control wiring (no polarity)

• Limitation contents for prohibited Linked systems #1

operation
Inter-unit control
Prohibition means limitation of the operation contents Pulse meter x 3 wiring (no polarity)
from the remote controller. It is also possible to Signal input x 3
change the prohibition items. Signal output x 2

Limitation contents
(Limitations can be user defined)
Communication adaptor
Individual There is no limitation for the operation of the remote control wiring (RS-485
controller. However, the contents will be changed to (polarity present)) Linked systems #2
the contents of the controller operated last. (Last-
Touch panel pressed priority.)
Prohibition 1 The remote controller cannot be used for ON/OFF. (All
Dimensions other operations are possible from the remote
H 240 x W 280 x D 85 mm controller.)
Power supply AC 100 to 240 V (50/60 Hz)
Prohibition 2 The remote controller cannot be used for ON/OFF,
LCD: 10.4 in. TFT, XGA(1024 x 768), LED backlight
operation mode change and temperature setting. (All
other operations are possible from the remote
controller.)
Communication
Prohibition 3 The remote controller cannot be used for operation adaptor Inter-unit control wiring (no polarity)
mode change and temperature setting. (All other
Product Features operations are possible from the remote controller.) Linked systems #3
Prohibition 4 The remote controller cannot be used for operation
• 10.4 in., Large, easy-to-use color LCD mode change. (All other operations are possible from Inter-unit
the remote controller.) control
wiring (no
• With smartphone like operations, such as swiping Pulse meter x 3
polarity)
and flicking • Remote Control

• Enhanced energy-saving control functions The LAN terminal on this unit enables you to
Signal input x 3
connect it to a network. Connecting to internet Signal output x 2
Communication adaptor
• Packed with demand functions will enable you to operate the unit and check the control wiring (RS-485
(polarity present)) Linked systems #4
• Set temperature auto return settings, Auto status using a PC from remote location.
shutoff, Set temperature range limit settings

• Energy Visualization
• Displays electricity & gas usage distribution

• Supports energy-saving plans with graph display


function Indoor units: 256 units (64 units x 16 systems)
Outdoor units: 120 units (30 units x 16 systems)
Communication adaptor: 7 units

New Features
• Max 256 indoor unit [16 systems x 64
units] can be controlled. In case of three or
more systems [more than 128 units],
a communication adaptor CZ-CFUNC2 Communication adaptor
must be installed for three or more links. Display image on the remote PC is same design as the controller unit. (CZ-CFUNC2)
• Operation is possible as batch, in zone
units, and in group units.
• ON/OFF, operation mode setting,
temperature setting, for fan speed setting,
air flow direction setting (when used
without a remote controller) and remote
controller local operation prohibition
[prohibition 1,2,3,4] can be done
• Graph display [trends, comparisons]
• ECONAVI ON/OFF * Required when more than 129 indoor units are connected.

110 111

180730_FSV_ASIA_D_2.indd 110-111 2018/10/12 14:41:25


FSV Controllers FSV Controllers

Panasonic total air conditioning management system


P-AIMS

P-AIMS Basic software / CZ-CSWKC2 P-AIMS optional software


Up to 1024 indoor units can be controlled by one PC
CZ-CSWAC2 for Load distribution

Load distribution calculation for each tenant


Functions of basic software
• Air-conditioner load distribution ratio is calculated for each unit
• Standard remote control for all indoor units (tenant) with used energy consumption data (m3, kWh).
• Many timer schedule programs can be set on the calender • Calculated data is stored with CSV type file.
• Detailed information display for alarms • Data of last 365 days is stored
• CSV file output with alarm history, operating status.
• Automatic data backup to HDD

P-AIMS optional software


CZ-CSWWC2 for Web application
Web access & control from remote station
With 4 upgrade packages the
basic software can be upgraded to • Accessing P-AIMS software from remote PC.
suit individual requirements
CZ-CFUNC2 • You can monitor/operate FSV systems by using Web
browser (Internet Explorer).

The P-AIMS is ideal for large areas/buildings such as shopping centers, universities and office
buildings.
Each line can have max.8C/A units, and control max.512 units.
In total, 1024 indoor units can be controlled by 1 “P-AIMS” PC. P-AIMS optional software
CZ-CSWGC2 for Object layout display
Converter for each line (MAX 8 lines)
Whole system can be controlled visually
(Field supply)
RS485 (Polarised)
• Operating status monitor is available on the layout display.
User PC USB line Building A • Object’s layout and indoor unit’s location can be checked at once.
• Each unit can be controlled by virtual remote controller on the display.
• Max 4 layout screens are shown at once.
Communication
Adaptor

Personal computer specs


Operating system: Windows 7 on 32bit /
64bit or Windows 8.1 on 32bit / 64bit. Building B

CPU: Intel CoreTM i3-2100 or more


Memory: 2 GB or more
CPU clock: Core2 Duo E7500 2.93 GHz
P-AIMS optional software
or faster
(However, a PC for factory automation is
CZ-CSWBC2 for BACnet software interface
recommended for BACnet.)
CRT: 1280 x 1024 SXGA Speaker Connectable to BMS system
incorporated CRT is recommended.
External HDD: 100 GB or larger
(An external power supply type is preferable
Building D • Can communicate with other equipment by BACnet protocol.
because the HDD will be used for backing • FSV systems can be controlled by both BMS and P-AIMS.
up data.)
UPS : Select a UPS with a sine output wave • Max 255 indoor units can be connected to 1 PC (that has
form.
P-AIMS basic & BACnet software).

112 113

180730_FSV_ASIA_D_2.indd 112-113 2018/10/12 14:41:34


FSV Controllers FSV Controllers

T10 Terminal for External Control Interfaces for External Control


(Digital Connection) (Digital Connection)

Seri-Para I/O unit for each indoor


Connecting an FSV indoor unit to an
unit (CZ-CAPBC2) System example
external device is easy.
The T10 Terminal featured in the
electronic circuit board of all indoor
units enables digital connection to
external devices. Remote
station

CZ-CAPBC2

Central control panel

• Control and status monitoring is possible for individual indoor unit (1 group).
• In addition to operation and stop, there is a digital input function for air speed and operation mode.
• Temperature setting and measuring of the indoor suction temperature can be performed from central
monitoring.
• The analog input for temperature setting is 0 to 10 V, or 0 to 140 Ohm.
• Power is supplied from the T10 terminal of the indoor units.
• Separate power supply also is possible (in case of suction temperature measuring).

1. T10 Terminal Specification (T10:CN061 at indoor unit PCB) Interface adaptor (CZ-CAPC3)

• Control items:1 1. Start/stop input (eg hotel key • Example of wiring


System example
COM 2 card, push button operation)
CZ-CAPC3
3 2. Remote controller prohibit input 1
4
3. Operation status output (eg fresh
+12V
COM 2
COM 5
T10 air fan) 3
6
(yellow) 4
4. Fault status output +12V
COM 5
300msec. T10
or more 6
(yellow)
1-2 (pulse input)
• Control and status monitoring is possible for
ON/OFF
individual indoor unit (or any external electrical controller For example: fan coil unit etc.
+12
Condition 300msec.
or more device up to 250 V AC, 10 A) by contact signal. Total heat exchanger unit.
4-5 (output)
1.1-2
1-2(pulse
(Pulse input)
input): Unit ON/OFF condition switching with a pulse signal. (1
pulse signal: shortage status more than 300msec.or more)
Unit condition ON OFF ON 2. 2-3 (Static input): Open/ Operation with Remote is permitted.(Normal
condition) Close/ Remote controller+12
4-5 (output)
is prohibited.
3. 4-5 (Static output): 12V output during the unit ON. / No output at OFF.
Seri-Para I/O unit for outdoor unit (CZ-CAPDC2)
NOTE: The wire length from indoor unit to the Relay must be within 2.0m. 4. 5-6 (Static output): 12V output when some errors occur / No output at
Pulse signal changeable to static with JP cutting. (Refer to JP001) normal.
Unit condition ON OFF ON System example

2. Usage Example Seri-para I/O

Forced OFF control Operation ON/OFF signal output


• Condition • Condition

Central Control Device


1-2 (Static input): Close/ Operation with Remote is permitted. (Normal 4-5 (Static output): 12V output during the unit ON / No output at OFF
condition) Open/ Unit is forcibly OFF and Remote controller operation is
prohibited. • Example of wiring
• Example of wiring Relay (Field supply)
T10
Relay (Field supply) (YEL)
T10 Dimensions H 80 x W 290 x D 260 mm
(YEL) The contact in the Central control Power supply Single phase 110-120/220-240 V (50/60 Hz), 18 W
figure is a state
where the card is Input Batch operation/Batch stop (non-voltage contact/DC 24 V,
pulled out. pulse signal). Cooling/Heating (non-voltage contact/static • This unit can control up to 4 outdoor units.
2m
signal). Demand 1/2 (non-voltage contact/static signal) (Local • From the centre control device, mode changing
POWER Indoor unit control stop by switching)
Indoor unit
control PCB
External contact
(Card switch box, etc.: PCB Output Operation output (non-voltage contact). Alarm output and batch operation/batch stop are possible.
field supply)
(non-voltage contact) • Required for demand control.
NOTE: The wire length from indoor unit to the Relay must be within 2.0m Wiring length Indoor/Outdoor operation lines: Total length 1 km.
NOTE: The wire length from indoor unit to the Relay must be within 2.0m Pulse signal changeable to static with JP cutting. (Refer to JP001) Digital signal: 100 m or shorter

114 115

180730_FSV_ASIA_D_2.indd 114-115 2018/10/12 14:41:37


FSV Controllers FSV Controllers

Serial Interface for 3rd Party Serial Interface for LonWorks


External Controller Network

Example of 3rd party BMS connection with CZ-CFUNC2 LonWorks Interface (CZ-CLNC2)
(For the detail please consult to authorized dealer)

RS485/ BMS • This interface is a communications converter for


RS232C Manufacturer
Adaptor adaptor Communication connecting LonWorks to the control network of
(Field supply) (Field supply) adaptor
FSV.
• From the host connected to LonWorks, basic
(RS-485) Max. 64 I/D
settings and status monitoring is possible for up to
(RS-232C)
16 groups of indoor units.
Outdoor unit
Group control Remote controller

System example

Outdoor unit
Remote Group control
controller

Max. 64 I/D

Indoor/outdoor unit
control line LonWorks Interface
Outdoor unit
Remote controller Group control
LON LON

• System Controller LonWorks Center Control


communication line Device
(field supply)

Functions
Outdoor unit Start/stop
Max. 16 system Remote controller
Connectable I/D units: Max. Temp. setting
512 A/C unit settings from Settings for each
Operation mode
the LonWorks group of indoor units
communicator Option 1 settings
Option 2 settings
Functions via communication adaptor [CZ-CFUNC2] Settings for all units Emergency stop
Unit ON/OFF Communication Adaptor Start/stop
Mode-change (CZ-CFUNC2) Temp setting
Room temperature setting Operation mode
Fan speed setting Option 1 settings
A/C unit settings
Flap setting A/C unit status notifications made to
Option 2 settings
the LonWorks communicator
Central control setting Alarm status
Filter-sign clear Indoor units with active alarms
Alarm reset Room temp.
Unit ON/OFF status A/C unit status
Operation mode Transmission intervals settings
Configuration properties
Setting temperature Minimum time secured for transmission
Fan speed status
A/C unit status Flap status
Central control setting Up to 128 indoor units can be connected
Filter-sign situation to one Communication Adaptor.
Correct/incorrect status
Alarm code

116 117

180730_FSV_ASIA_D_2.indd 116-117 2018/10/12 14:41:38


FSV Controllers FSV Controllers

FSV Controller External Dimensions

HIGH-SPEC TIMER REMOTE CONTROLLER COMMUNICATION ADAPTOR INTELLIGENT CONTROLLER


WIRED REMOTE (CZ-RTC4) (CZ-CFUNC2) (CZ-256ESMC3)
CONTROLLER 290
270 80 280 85
(CZ-RTC5)

38
20

120

256

240
180
120

167

38

22
120 R 2.5
16

79
8
20 24.75
120 R5
ø22.2
(mm)

WIRELESS REMOTE SEPARATE RECEIVER FOR ON/OFF CONTROLLER SERI-PARA I/O UNIT FOR EACH INDOOR UNIT
CONTROLLER WIRELESS REMOTE (CZ-ANC3) 116 (CZ-CAPBC2)

20
CONTROLLER 70
(CZ-RWSC3)

160
6 148 (6) 14 52

6
120

115
121
160
148
Unit: mm

(6)
122

SIMPLIFIED REMOTE SYSTEM CONTROLLER


CONTROLLER (CZ-64ESMC3)
66.8 LONWORKS INTERFACE SERI-PARA I /O UNIT FOR OUTDOOR UNIT
(CZ-RE2C2) 17 70 10 (CZ-CLNC2) (CZ-CAPDC2)
120 16 51.9 15 90 15
16.7

4.4

24.7

9.4
70.6
70.6

83.5
120

116.8
83.5
120

9.4
24.7

2.0 - R2.5 46
8
33.5

4.4
16.6

5.4

13 4 - Ø 5 hole
33.4 Potbellied hole (4 locations) 3 - Ø 30 hole

Magnified view
Detail of the
ECONAVI SENSOR REMOTE SENSOR potbellied hole
70
(CZ-CENSC1) 12.3 20 (CZ-CSRC3)
66.8
17
70 10
16.7

4.4

9 .4
120

11.3
116.8
83.5

9.4
120

8
33.5

4.4
1 6 .6

5.4
13
33.4 (mm)
32.3

118 119

180730_FSV_ASIA_D_2.indd 118-119 2018/10/12 14:41:39


VRF Renewal

VRF Renewal
An important drive to further reduce the potential
damage to our ozone

R22 is a HCFC and classified as an ozone depleting substance banned under


the Montreal Protocol.
Many existing R22 VRF Systems will need to be replaced over the coming years
by more modern and efficient R410A VRF Systems.

Panasonic takes proactive action to switch to R410A refrigerant VRF Renewal Kit (CZ-SLK2) and Sight Glass
Recognising consumers’ anxiety and financial difficulties to adapt to the new R22 regulations, Panasonic The following shows an overview of the VRF Renewal Kit: CZ-SLK2

developed a new cost-effective and simple solution to switch to R410A refrigerant. VRF Renewal Kit (CZ-SLK2) that is Filter Drier Charge Port

required when existing tubing is reused. If Outdoor unit Indoor unit side

What is Panasonic VRF Renewal? the exact tube length and tube size of the B A A B

Panasonic VRF Renewal enables reuse of good quality existing R22 pipe work to be installed with a new high existing tubing are uncertain, attach a
efficiency R410A system. sight glass in accordance with the figure
below. It will be used for checking the 445 (12, 14, 16 HP)
What’s so unique about Panasonic’s solution? amount of additional refrigerant charge
535 (4,5,6,8, 10 HP)
By enabling reuse of existing R22 piping, consumers get to save substantially from reduced installation cost, and (calculating the amount in Judgment 4
without any sacrifices to warranty or performance. see page 122). Unit: mm

Ozone Depletion Potential


R22 HCFCs 0.055 Before renewing piping, be sure to contact an
authorised Panasonic dealer for advice. Attaching the Renewal Kit and sight glass
R410A HFC 0
R407C HFC 0 • To adjust the limited pressure level into 3.3 MPa, special setting is necessary on site.
• A filter drier shall be attached to the liquid tubing of each outdoor unit.
R22 - The reduction of Chlorine critical for a cleaner future
• Do not need to remove Renewal Kit after a test run is performed as it can be retained for normal operation.
• When attaching Renewal Kit, be extra careful with regards to installation location and orientation of the filter drier and ball valve. Any mistakes
will complicate maintenance work.
• Thermal insulation material (field supply: heat resistance of 80˚C or higher and thickness of 10 mm or greater) shall be applied to the Renewall Kit.
• The filter drier of the Renewal Kit may need to be replaced depending on the condition of the existing unit. Use a Danfoss DMB 164 as the
replacement filter drier (field supply).
VRF Renewal
Panasonic’s Renewal system allows a completely new VRF system, indoor and outdoor units, to be installed
Sight glass (field supply).
using the existing systems pipe work. Panasonic’s advanced technology enables the system to work with Connecting tube dimensions (Inch mm) If the exact tube length and tube size
previously installed pipe work by managing the working pressure within the system down to R22 (3.3 bar) levels. A Ø 1/2 (12.7) (12,14,16 HP) of the existing tubing are uncertain,
attach a sight glass to the liquid tubing,
This ensures the system works safely and efficiently without loss of capacity. B Ø 3/8 (9.52) (8,10 HP) and use it to check whether there is an
appropriate amount of additional
The new equipment has potential to increase COP/EER by using state of the art inverter compressor and heat Note: If the tube size does not match that of the existing tubing, use refrigerant charge.
exchanger technology. a reducer (field supply) to adjust the tube diameter.

Having contacted your Panasonic supplier regarding pipe work restrictions and gained approval to use the Gas tubing
Panasonic Renewal System there are three main tests that have to be carried out to ensure that the system can Sight glass (field supply) Balance
tubing
be used effectively. If the exact tube length and tube size of the
Firstly a thorough inspection of the pipe work must be carried out and any damage must be repaired. existing tubing are uncertain, attach a sight Liquid tubing
Secondly an oil test has to be carried out to ensure that the system has not been subject to a compressor glass to the liquid tubing, and use it to check
burnout during its lifetime. whether there is an appropriate amount of
Lastly a VRF Renewal Kit (CZ-SLK2) has to be installed within the pipe work to ensure that the system is cleaned additional refrigerant charge.
of any oil residue. VRF Renewal Kit (CZ-SLK2)

120 121

180730_FSV_ASIA_D_2.indd 120-121 2018/10/12 14:41:41


VRF renewal VRF renewal

Procedure for VRF Renewal

Is the existing pipe work


Judgment 1
reusable? Renewal flow

Is the pipe work length and the


installation height difference of
Judgment 2 the existing pipe work within
the tolerance ranges of the No
new system? Can the existing pipe New pipe work needs
work be reused? to be installed.
Is the existing pipe work within
Judgment 3 the ranges of reusable tube
size? when judgments 1~4
are all OK Yes
Is the additional refrigerant
Judgment 4 charge at or below the upper
limit? No Recover the refrigerant
Can the existing unit perform
using a refrigerant
cooling operation?
recovery device.

Yes

Perform cooling operation for at


least 15 minutes, and then perform
a pump down to recover refrigerant
in the existing unit.

Should not use Remove the existing indoor and


existing piping outdoor units

Is there a problem with dirt inside Yes


the existing pipe work?

No

Install the new indoor and outdoor units, and attach the VRF Renewal Kit (CZ-SLK2).
If the exact length of the pipe work is uncertain, attach a sight glass to aid charging.
If the gas pipe size of the main piping is three sizes larger, add oil. (Judgment 3 item)

Perform a pipe work tightness test and refrigeration charge test


If the existing pipe length and pipe size are uncertain, charge with the minimum amount of additional refrigerant
based on calculation in Judgment 4. Next, determine if the additional refrigerant charged is sufficiently charged and
proportionate to the total refrigerant system by checking the system sight glass and system pressures during a
cooling test run.

Is there any history of compressor Yes


Recheck failure in the existing unit? Perform a heating test run.
(1) Operate in heating test run mode for 30 minutes.
(2) Replace the filter driers (inside of Renewal Kit)
No
of all outdoor units.

Could the existing unit perform the No *Obtain replacement filter driers separately.
Recheck cooling operation?

Yes

Perform a cooling test run.


If the minimum amount of additional refrigerant was added when the exact existing pipe lengths were uncertain,
check the condition of flowing refrigerant through the sight glass attached to the liquid piping - add as required.
However, the amount of additional refrigerant charge should not exceed the maximum level.

122 123

180730_FSV_ASIA_D_2.indd 122-123 2018/10/12 14:41:43


A Globally Trusted
Air Conditioning Brand
With roots going back 60 years, the Panasonic Air Conditioning Business Division has grown to become a
multinational company recognised around the world. Driven by a never-ending quest for product innovation,
the group has evolved from manufacturing compressors to providing comprehensive air conditioning solutions.
Panasonic has become a brand that people trust to deliver products with superior quality and reliability. Releases the world’s first
large-capacity modular
combination VRF system with
simultaneous heating/cooling

Panasonic’s
persistent innovation Releases the world’s first
large-capacity modular
spurs the evolution of combination VRF system

air conditioning
Starts production of
absorption chillers
solutions.
Introduces the world’s first
simultaneous 3-pipe
heating/cooling VRF system

Introduces first
GHP (gas heat pump)
VRF air conditioner

1957 1972 1985 2003 2006 • Panasonic HA Air-Conditioning Europe


(PHAAE) strengthens company’s
• Start of the Home Cooler business • MAICO, the Division’s first overseas • Begins development of scroll • Launches automatic filter-cleaning • Cumulative global production of commercial air conditioning business

1958 manufacturing base, established in


Malaysia
compressors
• Scroll compressors bring high
function for air conditioners (AC robot) Panasonic compressors reaches
200 million units 2010
• Panasonic (using • Starts export from MAICO to Japan, efficiency, low noise, and low • Begins collaboration with SANYO
the National brand)
introduces its first
Indonesia, Australia, and other
markets
vibration in comparison to rotary
compressors
2008 air conditioner business
• Through share exchange, SANYO
• Debuts quiet, lightweight, compact • Starts air-to-water heat pump business
Home Cooler, a • Begins operating twin-based system and Panasonic Electric Works
EcoCute systems with improved in Europe
window-type air out of Japan and Malaysia become wholly owned subsidiaries
energy-saving technology • Hot water heating considered an eco-
conditioner model • EcoCute adopts highly efficient, friendly alternative to conventional fuel- 2011
1990
• Electrical Appliance Business Group accumulator-less CO2 scroll type heating systems
compressor • Launches FSV series of large-capacity
(Kadoma) starts manufacture of Home • At the Energy Conservation
• CO2 heat-pump hot water VRF air conditioners
Coolers • Launches world’s first air
2012
Grand Prize awards,
• Sales of Home Coolers begin conditioner equipped with heater (EcoCute) uses non-toxic,
Panasonic air conditioners
non-combustible natural refrigerant
1961 compact scroll compressor
(CO2) instead of Freon, to reduce
win Chairman’s Award,
whilst EcoCute wins
• New Panasonic Group inaugurated

• Starts exports of Home Coolers to


1983
environmental impact
• Begins production of new
Director General Prize
(prizes presented by Energy
2013
South Vietnam
energy-saving mini-VRF series • Expands VRF operation in Malaysia
1965
Conservation Center of
• Launches inverter air conditioners
• Starts sale of Panasonic’s first inverter 1993 multi-split packaged air
conditioners for
Japan)
• nanoe technology installed
• Launches Room air conditioners • Establishes Matsushita-Wanbao residential use
on room air conditioners
Coolers • Inverters grow to (Guangzhou) Air Conditioner
2005
1968 become a core
technology in the
(MWAC)
• Establishes Matsushita-Wanbao • Panasonic products become extremely
• Begins development of rotary compressors air conditioner (Guangzhou) Compressor successful in Japan’s air conditioner
2009
• The high efficiency and quality of these
compressors draw interest from domestic
industry
• Starts shipment of
(MWCC)
• Establishes Matsushita
market
• Innovations such as airstream • Establishes sales company in Europe 2016
and overseas air conditioner manufacturers air conditioners to Air Conditioner Engineering robots and motion sensors help grow (PHAAE) dedicated to selling air • Partnership started with Schneider
• External sales begin Panasonic America (Matsushita ACE) Panasonic’s market share conditioners Electric

124 125

180730_FSV_ASIA_D_2.indd 124-125 2018/10/12 14:41:45


Reliability and Durability

At Panasonic, we believe that the best air conditioner is one that works
quietly and effectively in the background whilst minimising its impact on the
environment. People who use our products can look forward to long years of
high-quality performance without the need for constant maintenance.
As part of our rigorous design and development process, Panasonic air
conditioners undergo a variety of stringent tests to ensure their effectiveness
and long-term reliability. Tests for durability, waterproofing, shock resistance,
and noise are conducted on component parts or on the finished products
themselves.
As a result of all of these painstaking efforts, Panasonic air conditioners
meet even the most demanding industrial standards and regulations in every
country where they are sold.

Applying advanced technologies that truly make life


better, we live by an unparalleled commitment to product
quality. Our approach to product development originates
in the DNA of Japanese craftsmanship.
Panasonic is building on the Japanese tradition of
uncompromising quality control worldwide, developing
and manufacturing fine products and delivering them to
customers everywhere.

Testing laboratory Panasonic Gunma, Japan (PAPARS)

Durability International Standard Quality


At Panasonic we know the importance of a long service life with minimal maintenance. To uphold the company’s reputation around the world, Panasonic strives continuously to offer the highest
That’s why we subject our air conditioners to a wide range of stringent durability tests. quality with the lowest possible environment impact.

A resin-potted
circuit board
The strength of the
resin material used
in a propeller fan is
confirmed by
a tension test

Long-Term Durability Test Compressor Reliability Test Waterproofing Test Reliable Parts That Meet or RoHS / REACH Sophisticated
To ensure durability and stable operation After the continuous operation test, we The outdoor unit, which is subject Exceed Industrial Standards Compliant Parts Production Process
for many years, we conduct a long- remove the compressor from a selected to rain and wind, complies with IPX4 In every country where they are sold, All Panasonic parts and materials comply Panasonic’s air conditioner production
term continuous operation test under outdoor unit, disassemble it, and examine waterproof specifications. Contact Panasonic air conditioners comply with Europe’s strict RoHS/REACH lines employ state-of-the-art factory
conditions that are much more severe the internal mechanisms and parts for sections on printed circuit boards are with all required industrial standards environmental regulations. During the automation technologies to ensure
than actual operating conditions. potential failure. This helps ensure reliable resin-potted to prevent adverse effects and regulations. In addition, Panasonic development and production of parts, products are manufactured efficiently and
long-term performance under harsh caused by exposure to water (an unlikely conducts stringent testing to ensure the stringent inspections are conducted with uniformly high levels of quality and
conditions. occurrence). reliability of parts and materials. on over 100 materials to ensure that no reliability.
hazardous substances are included.

126 127

180730_FSV_ASIA_D_2.indd 126-127 2018/10/12 14:41:48


Global Networking of
Air Conditioning Solutions
In any indoor environment, eco-friendly air conditioning plays a vital role in Quality Assurance from Japan to the World PACT Headquarters and Bases
maintaining our health, comfort, and productivity. Whether it’s an office, a hotel, With a diverse network of production and R&D facilities, Panasonic delivers
EUROPE
or a shopping mall, every building matters. That’s why Panasonic has developed innovative products incorporating cutting-edge technologies that set the
standard for air conditioners worldwide. As our business expands globally,
energy-efficient large-scale air conditioning solutions to suit a variety of business Germany Wiesbaden
we strive to transcend borders with our superior-quality products.
applications.
As one of the pillars of Panasonic’s BtoB operations, our air conditioning sector
provides comprehensive solutions to businesses around the world. Harnessing our Japan
advanced technology and extensive on-site expertise, we serve clients in a diverse
range of environments throughout the world.
Panasonic air conditioning solutions are designed from the ground up to meet the
specific needs of each location, whilst placing a premium on efficiency and reliability.
Nordic Stockholm Hungary Budapest
At every stage, we seek to make optimal use of resources and energy to create Air Conditioning Division PAPARS
(Appliances Company) (Shiga, Japan) Panasonic Appliances Air
solutions that benefit the environment. Conditioning & Refrigeration
Established April 1972 System (Gunma, Japan)
• Appliances Company HQ
• Home Appliances Business Group Established July 1959
• Corporate Engineering Division • Air conditioners
• Cold-chain/refrigeration Russia (CIS) Moscow Spain Barcelona
products

Malaysia

Spain Madrid France Paris


Stockholm, Nordic Wiesbaden, Germany
Moscow, Russia
Budapest, Hungary
Bracknell, UK
Prague, Czech Rep.
Paris, France
Lyon, France Milan, Italy PAPAMY PAPARADMY PAPAMY Compressor PAPAMY Compressor R&D
Dalian
Madrid, Spain Panasonic Appliances Panasonic Appliances
Barcelona, Spain Japan Atlanta, USA Air Conditioning Malaysia Air Conditioning R&D Established January 1987 Established September 1997
Sdn Bhd. Malaysia Sdn. Bhd. • Rotary compressors for • R&D for rotary Italy Milan France Lyon
New Delhi, India Hanoi, China Taiwan air conditioners compressors Czech Rep. Prague UK Bracknell
Vietnam Zhonghe, Taiwan Established April 1972 Established June 1991
Mumbai, India
Hong Kong
Chennai, Philippines Panama, Latin America
• Air conditioners
• Air-to-water heat pumps
• R&D for air conditioners
• Air-to-water heat pumps ASIA
India
Bangkok,Thailand
Malaysia Shah Alam
Malaysia
Shah Alam, Malaysia China
Indonesia
Jakarta, Indonesia
Sydney, Australia
Auckland, New Zealand
Productions and R&D facilities
PACT headquarters
PACT bases
PAPAGZ PWAPCGZ PRDCS PAPARDL
Panasonic Appliances Air Panasonic Wanbao Panasonic R&D Center Panasonic Appliances Vietnam Hanoi India New Delhi
Conditioning (Guangzhou) Appliances Compressor Suzhou Co., Ltd. Air-Conditioning and
Co., Ltd. (Guangzhou) Co., Ltd. Refrigeration (Dalian) Co.,
Established April 2002 Ltd.
Established June 1993 Established June 1993 • Air conditioners
Air conditioners • Rotary compressors for • R&D for home appliance Established September 1992
PACT Training Facilities air conditioners products • Air conditioners
• Compressors for
Thailand Bangkok China
The 24 Panasonic Air Conditioning Training Centers (PACTs) automotive air
Taiwan Zhonghe Hong Kong
conditioners
around the world provide a wide range of support for Panasonic’s Indonesia Jakarta India Mumbai
business-use air conditioning systems. PACT represents Taiwan Indonesia Philippines India
Panasonic’s unwavering commitment to our sales partners, OCEANIA
distributors, and service teams in Europe, Asia, Oceania, and the Australia Sydney New Zealand Auckland
Americas.
AMERICAS
Latin America Panama USA Atlanta
PTW PMI PMPC PI
Panasonic Taiwan Co., Ltd. Panasonic Manufacturing Panasonic Manufacturing Panasonic India Pvt. Ltd.
Indonesia Philippines Corporation
Established October 1962 Established December 2012
• Air conditioners Established September 1965 Established September 1967 • Room Air conditioners
• Automotive air conditioners • Air conditioners • Air conditioners
• Home appliance products • Home appliance products • Home appliance products

128 129

180730_FSV_ASIA_D_2.indd 128-129 2018/10/12 14:41:57


Panasonic VRF Global
Project References
Panasonic air conditioning systems provides comprehensive solutions to businesses around the world.
Harnessing our advanced technology and extensive on-site expertise, we serve clients in a diverse range of
environments throughout the world. RETAIL SCHOOL
Italy Le Centurie CENTRO COMMERCIALE India Sai Aarav Motors, Mehsana Russia Sun City Mall United States Shippensburg University
HOTEL
Australia Travelodge Hobart Indonesia Patra Jasa Hotel Spain Hotel Claris 5 GL Spain Monument Hotel

Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System:
VRF 3-way MF1 series VRF 2-way FSV ME1 series 3 systems VRF 2-way ME1 series VRF 3-Way MF1 series
18 systems Indoor Units: 19 units 47 systems, 55 systems
Indoor Units: 57units Cooling Capacity: 156 kW / 44 USRT VRF 3-way 12 systems Indoor Units: 530 units
Cooling Capacity: Indoor Units: 283 units Cooling Capacity:
Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System: 656 kW / 186 USRT Cooling Capacity: 1,498 kW / 426 USRT
VRF 3-way FSV MF2 VRF 2-way FSV ME1 series VRF 2-way ME1&LE1 series VRF 2-way ME1 series 4 systems, 1,605 kW / 456 USRT
series 8 systems 14 systems 11 systems VRF 3-way 12 systems
Indoor Units: 132 units VRF 3-way MF1 series 14 systems Indoor Units: 171 units

SCHOOL HOSPITAL
Indoor Units: 116 units
Cooling Capacity: Cooling Capacity: Indoor Units: 233 units Cooling Capacity:
302 kW / 86 USRT 677 kW / 193 USRT Cooling Capacity: 769 kW / 218 USRT 592 kW / 168.33 USRT

Russia River Park Hotel Germany The LEGOLAND Castle Hotel Malaysia Xiamen University Russia Technopark of Nobosibirsk Academgorodok Indonesia Bekasi Hospital Indonesia Persada Hospital

Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System:
VRF 2-way ME1 series 47 systems VRF 3-way MF2 VRF FSV Systems 110 systems VRF 2-way ME1 series 38 systems, VRF 2-way FSV ME1 series VRF 2-way FSV ME1 series
Indoor Units: 96 units 12 systems Indoor Units: 1,349 units VRF 3-way 12 systems 42 systems 21 systems
Cooling Capacity: 788 kW / 224 USRT Indoor Units: 144 units Cloud adapter: CZ-CFUSCC1 17pcs Indoor Units: 234 units Indoor Units: 283 units Indoor Units:116 units
Cooling Capacity: Cooling Capacity: Cooling Capacity: Cooling Capacity:
592 kW / 168.33 USRT 1,487 kW / 422 USRT 1,834 kW / 524 USRT 989 kW / 281 USRT

OFFICE RESIDENTIAL
Malaysia Gapruna project Malaysia Plaza 33 Office Block A Thailand Areeya HongKong King Yip Road China Star River Group Luxury Condominium Singapore Punggol Eco-Town Hong Kong Gloucester Road Project Hong Kong The Green Project

Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System:
VRF 2-way FSV ME1 series VRF 2-way FSV ME1 series VRF 2-way FSV ME1 series 19 systems VRF FSM LA1 series VRF Master series 966 systems Inverter multi-split VRF FSM LA1 series 67 systems VRF FSM LA1 series 239 systems
109 systems 99 systems Single split system 67 systems 136 systems Indoor Units: 3,948 systems room air conditioner Twenty series 105 systems Twenty series 538 systems
Indoor Units: 537 units Indoor Units: 153 units Indoor Units: 85 units Indoor Units: 294 units Cooling Capacity: Indoor Units: Indoor Units: 255 units Indoor Units: 999 units
Cooling Capacity: Cooling Capacity: Cooling Capacity: Cooling Capacity: 16,737 kW / 4,755 USRT Wall mounted S series (with ECOVAVI) Cooling Capacity: 1,391 kW / 395 USRT Cooling Capacity:
5,370 kW / 1,526 USRT 3,667 kW / 1,042 USRT 1,519 kW / 432 USRT 2,108 kW / 599 USRT Control System: Panasonic HEMS 6,425 kW / 1,825 USRT

England Soapworks Spain PTA Malaga Russia Russian Government Building India Royal Orchids Eco-Green Homz India Heera Windfaire Panama Mosaic Building PANAMA PACIFICO

Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System: Air Conditioning System:
VRF 3-way MF2 VRF 2-way ME1 series VRF 2-way ME1 series 42 systems VRF 2-way FSV ME1 series VRF 2-way FSV ME1 series 96 systems, VRF 2-way FSV LE1 series 156 systems
77 systems 20 systems Indoor Units: 277 units 22 systems, VRF 3-way 12 systems Indoor Units: 357 units
with ERV 167 systems Indoor Units: 74 units Cooling Capacity: Indoor Units: 139 units Indoor Units: 479 units Cooling Capacity: 2,338 kW / 664 USRT
Cooling Capacity: 2,045 kW / 581 USRT Cooling Capacity: Cooling Capacity: 2,184kW / 620 USRT
908 kW / 258 USRT 802 kW / 228 USRT

130 131