You are on page 1of 22

PACiS Network Architectures

PACiS Technical Training


CS&P – Support Team

PCL
1) PACiS RTU

1.1) C264 Stand-Alone


1.2) Cascade of Stand-alone
1.3) Remote Stand alone
1.4) Multi-Rack
1.1) Basic Stand-alone

- MODBUS (Modicon) - UCA2


SCADA Serial - DNP3
- T101
SCADA IP - T104
- DNP3

A0W A-Wired A0L A-LBUS IED A0S A-SBUS IED


SWU
C264C C264C

C264C
LBUS IED
I/Os - Vdew T103 Switch SWU
- MODBUS (Areva)
- DNP3
- T101
SBUS IED
- UCA2
- IEC 61850

SWR
Redundant Ethernet
possible

Schneider Electric - CS&P – System Architecture – F01 3


1.1) Basic Stand-alone naming?
A0T A-Wired

GPS C264C

I/Os

A0W A-Wired A0L A-LBUS IED A0S A-SBUS IED


C264C C264C C264C

LBUS IED
I/Os - Vdew T103 Switch SWU SBUS IED
- MODBUS (Areva) - UCA2
- DNP3 - IEC 61850
- T101

Schneider Electric - CS&P – System Architecture – F01 4


1.2) Cascade Stand-alone
SCADA

C264C LBUS IED


- Vdew T103
- MODBUS (Areva)
- DNP3
- T101

SCADA

C264C C264 Slave T101 DNP3 Modbus

I/Os
C264C

I/Os

Schneider Electric - CS&P – System Architecture – F01 5


1.3) Remote Stand-alone

SMT Automatic Disturbance


S1 Agency Tunneling

SCADA IP
Ethernet :
- modem
SCADA - redundancy
Serial
C264C

I/Os LBUS IED


- Vdew T103
- MODBUS (Areva)
- DNP3
- T101

Schneider Electric - CS&P – System Architecture – F01 6


1.4) Multi-Rack Stand-alone
SCADA

SCADA
Serial
SWU
1 to 8 Extension Racks
C264C No LHMI
MAIN
C264C 4 LBUS
C264 full rack (no TMU)
I/Os
Private Ethernet

Multi-Rack Redundant Ring


SWR

SWR SWR SWR

Schneider Electric - CS&P – System Architecture – F01 7


2) Single PACiS

2.1) Start/Tree Topology


2.1) Start/Tree Single topology

PACiS Gateway

Standard Ethernet
Stars topology (H63x)
Tree topology (SWU)
H63x

SWU SWU SWU SWU


GPS

Cubicle
Schneider Electric - CS&P – System Architecture – F01 9
3) Redundant Ethernet Ring

3.1) PACiS Redundant Ring


3.2) Two Separate Redundant Ring
3.3) Redundant Computer and Ethernet
3.4) Multi-Station Ring
3.1) PACiS Redundant Ring Ethernet
Redundant Ring

PACiS Gateway

H35 H35

SWR SWR SWR SWR


GPS

Full Bay
SWU on SBUS

Cubicle
Other
Subnet
Schneider Electric - CS&P – System Architecture – F01 11
3.2) Redundant Rings OI Clients &
Station
2 Redundant Ring

PACiS OI Clients

H35 H35 H35

H35 H35

PACiS OI Servers
2 IP Address no loop

H35 H35

SWR SWR SWR SWR


GPS

Schneider Electric - CS&P – System Architecture – F01 12


3.3) Redundant Ring & Computers
Redundant Ring
Redundant Computers

H35 H35

SWR SWR

SWR SWR

SWR
SWR

Computers Main Computers Back-up


Power supply Main Power supply Back-up

Schneider Electric - CS&P – System Architecture – F01 13


3.4) Multi Station Rings

NO LOOP H35 H35 H35

Each Ring seen by other


No redundancy of H35
H35

H35 H35 H35

SWR SWR SWR SWR SWR SWR SWR SWR SWR

Schneider Electric - CS&P – System Architecture – F01 14


4) Dual Homing

4.1) PACiS Redundant Homing Ethernet


4.2) PACIS Dual Redundancy
Homing/Ring
4.1) PACiS Redundant Homing
Ethernet PACiS Gateway

Standard Ethernet
H36 H36
2 separated Ethernet Stars
(based here on H63x)

H63x H63x

SWD SWD SWD SWD


GPS

Cubicle
Schneider Electric - CS&P – System Architecture – F01 16
4.2) PACiS Dual Redundant Homing
Ring PACiS Gateway

H6xx
between H35x and H36x
H36
need for conversion
copper optical H63x H63x

H35
H35

2 redundant rings
H35 H35 H35
for each H35 H35 H35

Dual Homing link H63x H63x H63x H63x H63x H63x

SWD SWD SWD


GPS

Schneider Electric - CS&P – System Architecture – F01 17


5) RSTP

5.1) RSTP - Sepam


5.2) PACIS – RSTP attachment
RSTP- Sepam : Multi master scheme,
daisy chain
Station
RTU computer

20 A I A DI

Maintenance
Control Center
Ethernet switch
Ethernet
switch
IEC61850 protocol 100 Mbit/s Ethernet
Fiber Optical Ring
with ring management
Ethernet switch RSTP

Lev 2 Lev 2
ACE850 ACE850 ACE850 ACE850 ACE850 ACE850

Sepam Sepam Sepam Sepam Sepam Sepam


series 80 series 80 series 40 series 80 series 80 series 40

Schneider Electric - CS&P – System Architecture – F01 19


PACIS - RSTP 20
12

HMI WARNING WITH :


Or SCADA - PERFORMANCES
w
Ne PACiS GATEWAYS H17x - AUTOMATION
- GOOSES

Ethernet – RSTP backbone Backup link

RSTP
compatible
Switch
(Teaming)

RSTP Switch

C264+ Px4x
SWS
Px3x C264

32 ieds Max/ subring


Schneider Electric - CS&P – System Architecture – F01 20
6) MULTI-PACIS

6.1) Multi Rings with Gateway IEC/IEC


6.1) Multi-PACiS Rings

H35

PACiS Top SS1_1


H35

H35 H35 H35 H35 H35

PACiS Bottom SS0_1 PACiS Bottom SS0_2 PACiS Bottom SS0_3

SWR SWR SWR SWR SWR SWR SWR SWR SWR

Schneider Electric - CS&P – System Architecture – F01 22

You might also like