DTSC-200A
Product Training
Last update: Dec’22
©
W
O
O
D
W
What is an ATS system?
ATS Engine start command
Controller
S1 voltage sensing DTSC-200A S2 voltage sensing
ATS
S1 S2
2 | © WOODWARD, INC.
Woodward ATS Control Offer
http://wwdmanuals.com/ http://wwdmanuals.com
dtsc-200 /dtsc-200a
DTSC-200 DTSC-200A
Netbiter
EC350
PLC
ToolKit (ServLink)
ESENET / ESEPRO
IKD 1
IO module
IKD-IN-16
Phoenix IKD-OUT-16
IO module
4 | © WOODWARD, INC.
DTSC-200A Applications
5 | © WOODWARD, INC.
DTSC-200A Applications
6 | © WOODWARD, INC.
DTSC-200A Features (1/3)
FlexRangeTM Allows to operate on a wide range of PT voltage inputs and CT
configurations
- True RMS 3-phase voltage measuring inputs
- True RMS 3-phase load-current
7 | © WOODWARD, INC.
DTSC-200A Features (2/3)
• Open, delayed or closed transition transfer
• Make-before-break overlap time < 100 ms
• In-phase monitoring (synch check)
• Extended parallel
• Preferred source selection by LogicsManager
• Transfer and/or retransfer inhibit
• Elevator pre-signal
• Load Shed and Motor Load Disconnect signal
• Supported transfer switches: 2/3/4 position switches and standard circuit breakers
8 | © WOODWARD, INC.
DTSC-200A Features (3/3)
9 | © WOODWARD, INC.
Voltage and current (load) sensing
3Ph-4W (3phase, 4wire) 3Ph-3W (3phase, 3wire)
1-, 2- and 3-phase CT arrangement possible
FlexRangeTM
B5 C2 B1 C6
B6 C1 B2 C5
C
A L3
A1 A2 N A5 A6
N
L1
10 | © WOODWARD, INC.
DynamicsLCD
The 480 x 272 pixel adaptive and interactive TFT LC display has tactile buttons and a clear menu structure to
ensure intuitive user operation and navigation.
11 | © WOODWARD, INC.
DynamicsLCD
Dedicated tactile buttons at the bottom of the screen for bypassing the counters, enter settings menu,
conduct load test, engine test and for alarm acknowledgement.
12 | © WOODWARD, INC.
DynamicsLCD
• Alarm messaging on the display
• Active / not active visible
• 16 entries with date and time stamp
• Over-/ underfrequency
• Voltage imbalance
• Load monitoring
• Overcurrent (3 levels configurable)
15 | © WOODWARD, INC.
Monitoring (2/2)
• Switch monitoring
• Breaker position feedback / plausibility
• Transfer failure
16 | © WOODWARD, INC.
Discrete I/O
8 x Relay Outputs
Discrete I/O Status Display
• Alarm and control • Indicates when input / output is active
• 6 single-pole contacts
• 2 two-pole contacts
• Relay 2 – 4: max. 7 Adc
• Relay 5 : max. 7 Aac
• Relay 6 - 7: max. 10 Adc
• Relay 8 – 9: max. 7 Aac Expansion with external DI/DO boards
• Max. 2x Woodward IKD 1 • IKD-IN-16
12 x Discrete Inputs (16 DI/16 DO)
• Control (isolated) functions • Phoenix modules
• Input 1 – 5: fixed functionality (max. 16 DI/DO)
• IKD-OUT-16
• Input 6 – 12: freely configurable
17 | © WOODWARD, INC.
Configuration via Toolkit
USB
USB
18 | © WOODWARD, INC.
DTSC-200 Functions Controlled By Inputs
• Test Switch • Auto/Manual Selector
• Disconnect Switch • Transfer Mode Selector
• Remote Peak Shave • Transfer Commit
• Remote Inhibit Transfer to Normal or • Source Priority Selector Switch
Emergency
• Reply From Bypass Isolation Switch Normal or
• Remote Load Shed Emergency
• Interruptible Power Rate Provisions • Logics Manager Configuration
19 | © WOODWARD, INC.
DTSC-200 Functions Controlled By Outputs
• Motor Load Disconnect • Shunt Trip Enable
• Normal Position Indication • Elevator Pre-Signal
• Emergency Position Indication • Status Message “Not In Automatic”
• Neutral Position Indication • Status Message “EPS Supplying Load”
• Normal Source Available • Status Message “Bypassed Normal Source”
• Emergency Source Available • Status Message “Bypassed Emergency Source”
• Load Shed • Centralized Alarm
• Logicsmanager
relays
20 | © WOODWARD, INC.
DTSC-200 Transfer Timers
• Transfer commit • Emergency Source Start Time Delay 0-300 Sec.
• S2 Start Delay • Emergency Source Cool Down Timer
• Preferred source Delay • Motor Load Disconnect Timer: Pre, Post or Both
• S1 source stable timer • Elevator pre-signal duration 0-300 Seconds
• S2 source stable timer • Time Delay From Neutral To Source 1 0-10 Minutes
• S1 outage delay
• S2 outage delay
• External Timer Bypass
21 | © WOODWARD, INC.
ATS Inhibit
• Security feature
• Locks out all transfer operations
• Emergency source will be started, but no transfer takes place
• Configurable via LogicsManager
• In cabinets used in combination with an “Inhibit switch”
22 | © WOODWARD, INC.
Limit switch Monitoring (plausibility check)
• Limit switch monitoring evaluates the ATS limit switch replies and checks them
after limit switch failure delay time for plausibility
• If the replies are not plausible, the "Actual" and "Expected" replies are displayed
• Meanwhile, the status of the breaker replies cannot be reset with the Reset
button and all further transfers are inhibited
23 | © WOODWARD, INC.
In-phase monitoring (sync check)
24 | © WOODWARD, INC.
Max parallel time <100ms
• Tests showed that smallest max.
parallel time is between 40 and
50ms
25 | © WOODWARD, INC.
Extended parallel time for softloading application
• Only available for Closed transition operation
• Transfer switch can stay parallel as long the customer wishes it to do.
ATS
S1 Gen
Extended
Parallel time req.
26 | © WOODWARD, INC.
Transfer inhibit features
27 | © WOODWARD, INC.
Elevator Pre –Signal + Timer
• This Signal is set before a transfer is carried out
• Signal is reset after transfer has been accomplished
• Signal & Timer only active if both sources are available
• Configurable to Relay output via LogicsManager
Elevator
Control
28 | © WOODWARD, INC.
Motor Load Disconnect Signal + Timer
• This Signal is set before a transfer is carried out
• Signal is reset after transfer has been accomplished
• Signal & Timer always active
• Configurable to Relay output via LogicsManager
Motor Loads
29 | © WOODWARD, INC.
Daisy chaining of MLD Signals
• This function is used as a method to initiate load shedding
• For extra load shedding points, the IKD’s are supported
MLD Relay 1
MLD 1
MLD Relay 2
expired
MLD 2
MLD Relay 3
expired
30 | © WOODWARD, INC.
Load sequencing with MLD
Motor Load 1
Motor Load 2
CAN
Motor Loads 1- 8
Motor Loads 9 - 16
31 | © WOODWARD, INC.
Source priority selection
• User selectable which source has priority
• Non-Prioritized Source always acts as an emergency source if the prioritized
source fails.
• Configurable via LogicsManager
32 | © WOODWARD, INC.
Load shed
• Capability for initiate a load circuit disconnection form the
non-preferred source.
• A re-transfer to the prioritized source is performed if
preferred source is available.
• If preferred source is not available, a transfer to
the neutral position will be initiated
• Once transferred to the preferred source and this source
fails, a transfer to the emergency source is blocked. Only a
transfer to the neutral position takes place.
• Configurable via LogicsManager
33 | © WOODWARD, INC.
Load Test
• Initiates an engine start and performs a transfer to the
• non-preferred source.
• Can be initiated via the tactile keys on the frontfoil
• Can also be initiated by using a discrete input.
• Load test timer configurable
• Configurable via LogicsManager
34 | © WOODWARD, INC.
Engine Test
35 | © WOODWARD, INC.
In-Phase monitoring
• Available for all transfer switch types
• Checks phase angle and Voltage/Frequency difference to ensure a
transfer into the other source occurs within a phase angle difference
of 7° or less.
• User programmable outcome conditions if In-Phase monitoring fails.
• User programmable setpoint windows for voltage and frequency
difference.
• Transfer switch reaction time is adjustable
36 | © WOODWARD, INC.
Extended parallel time
37 | © WOODWARD, INC.
Extended parallel time
ATS
S1 Gen
Bias
Switch control
Extended
Parallel time
req.
38 | © WOODWARD, INC.
Vector group adjustment
• For usage, if transformers are used in the ATS System
• Adjustable in the range +/- 180 °
+30 °
0° +30 ° ATS
S1 S2
S1 Volt. S2 Volt.
measurement measurement
39 | © WOODWARD, INC.
Shunt Trip enable
• Capability to shunt trip a circuit breaker
• Trips, if both sources have been paralleled for more than configured time
• Signal stays tripped, until it gets acknowledged
CB
S1 S2
Shunt trip
enable
Signal
40 | © WOODWARD, INC.
Transfer Timers
• Transfer commit • Emergency Source Start Time Delay 0-300 Sec.
• S2 Start Delay • Emergency Source Start Time Delay For Test 0-
300 Seconds
• Preferred source Delay
• Emergency Source Stable Timer
• S1 source stable timer
• Normal Source Stable Timer
• S2 source stable timer
• Emergency Source Cool Down Timer
• S1 outage delay
• Motor Load Disconnect Timer: Pre, Post or Both
• S2 outage delay
• Elevator pre-signal duration
• External Timer Bypass
• Elevator Pre-Signal 0-300 Seconds
• Time Delay From Neutral To Source 1 0-10
Minutes
41 | © WOODWARD, INC.
Remote I/O - IKD
Features per input:
• Assign a name
• Define a alarm class
• NO/NC configuration
• Configure a time delay Can bus
Outputs
Inputs Outputs
Inputs
IKD-OUT-16
IKD-IN-16
IKD 1
42 | © WOODWARD, INC.
DTSC-200A is DTSC-200! But…
• Short Lead Time • I/O
• Proven and available hardware • Overall, one relay less (Ready-for-operation).
• DI‘s activated by B-
• Dimensions
• Slightly bigger cut-out • Interfaces
• CAN (Termination in-build),
• Voltage Measurement
• RS-485 (only Half-Duplex)
• Only restriction in UL market (may require PT)
• Service Port (USB)
• Current Measurement
• Only 5A CT input supported. Same accuracy. • Others
• Ethernet, RS-232, SD card slot available on HW
but currently not supported (evtl. in rev. B)
43 | © WOODWARD, INC.
Resources
Manual, Software, Config. Files, CAD models, etc.
• http://wwdmanuals.com/DTSC-200A
Product Page
• https://easygen.org/ats/
Videos
• https://www.youtube.com/playlist?list=PLW55kmXY0fHCoZptLxzCvzmB5POGRbfYK
Webinar recording
• https://wss.woodward.com/manuals/Support/Webinar_Recordings/DTSC-200A
44 | © WOODWARD, INC.