Automatic Transfer Switch Controller

DTSC-200A

Product Training
Last update: Dec’22

©
W
O
O
D
W
What is an ATS system?
ATS Engine start command
Controller
S1 voltage sensing DTSC-200A S2 voltage sensing

Switch control signals

ATS
S1 S2

2 | © WOODWARD, INC.
Woodward ATS Control Offer

http://wwdmanuals.com/ http://wwdmanuals.com
dtsc-200 /dtsc-200a

DTSC-200 DTSC-200A

Rated CT Part Number Configuration


Model Description
secondary (P/N) Software

.../1 A 8440 -1867 DTSC-200-51B ToolKit


DTSC-200
.../5 A 8440 -1868 DTSC-200-55B ToolKit
DTSC-200A …/5A 8440 - 2297 DTSC-200A-352-P1 ToolKit

DTSC-200A is available on short production lead time


3 | © WOODWARD, INC.
DTSC-200A Expansion Modules
USB Serial interface CAN interface
RS - 485 Modbus RTU Slave CANopen protocol

Netbiter
EC350

PLC

ToolKit (ServLink)
ESENET / ESEPRO

IKD 1
IO module
IKD-IN-16

Phoenix IKD-OUT-16
IO module

4 | © WOODWARD, INC.
DTSC-200A Applications

Utility Utility Generator


– – –
Utility Generator Generator

SUPPORTED TRANSITION TYPE: OPEN, DELAYED, OR CLOSED (SHORT/EXTENDED)

5 | © WOODWARD, INC.
DTSC-200A Applications

Transfer Delay (Utility –Utility) External Permit Closed Transition Gen-Gen

6 | © WOODWARD, INC.
DTSC-200A Features (1/3)
FlexRangeTM Allows to operate on a wide range of PT voltage inputs and CT
configurations
- True RMS 3-phase voltage measuring inputs
- True RMS 3-phase load-current

LogicsManagerTM Configurations, and operating modes can be modified by using logical


operators, timers

FlexAppTM Technology for Mains-Gen., Gen.-Gen. or also Mains-Mains applications

DynamicsLCDTM Flexible, multifunctional display

7 | © WOODWARD, INC.
DTSC-200A Features (2/3)
• Open, delayed or closed transition transfer
• Make-before-break overlap time < 100 ms
• In-phase monitoring (synch check)
• Extended parallel
• Preferred source selection by LogicsManager
• Transfer and/or retransfer inhibit
• Elevator pre-signal
• Load Shed and Motor Load Disconnect signal
• Supported transfer switches: 2/3/4 position switches and standard circuit breakers
8 | © WOODWARD, INC.
DTSC-200A Features (3/3)

• Engine exerciser (load / no-load test)


• Configurable via PC (ToolKit) and front panel
• Multi-Level password protection
• Multi-language capability (English, German, Spanish, Polish, Russian)
• Modem connectivity and remote control via RS-485 / CAN / discrete input signals

9 | © WOODWARD, INC.
Voltage and current (load) sensing
3Ph-4W (3phase, 4wire) 3Ph-3W (3phase, 3wire)
1-, 2- and 3-phase CT arrangement possible

FlexRangeTM

1Ph-3W (1phase, 3wire) 1Ph-2W (1phase, 2wire)


1-, 2- and 3-phase CT arrangement possible only 1-phase CT possible

B5 C2 B1 C6

B6 C1 B2 C5

C
A L3
A1 A2 N A5 A6
N
L1

10 | © WOODWARD, INC.
DynamicsLCD
The 480 x 272 pixel adaptive and interactive TFT LC display has tactile buttons and a clear menu structure to
ensure intuitive user operation and navigation.

New button arrangement in


„diamond“ shape.
Button function shown in upper right
corner

11 | © WOODWARD, INC.
DynamicsLCD
Dedicated tactile buttons at the bottom of the screen for bypassing the counters, enter settings menu,
conduct load test, engine test and for alarm acknowledgement.

12 | © WOODWARD, INC.
DynamicsLCD
• Alarm messaging on the display
• Active / not active visible
• 16 entries with date and time stamp

• Event history list


• Incoming and outgoing events (+ / -)
• 300 entries with date and time stamp
• FIFO logging, user cannot erase
• Password required to view
13 | © WOODWARD, INC.
Measurement Functions
• Voltage – True RMS sensing for both sources
• Frequency
• Phase Rotation
• Current – True RMS sensing for load
• Power– True RMS sensing at load, calculated from active supply source(s) [real
(kW) and re-active (kvar)]
• Power factor (cosφ)
• Energy counters: Real (kWh), Reactive (kvarh)
• Operating hours, maintenance call, no of engine starts
14 | © WOODWARD, INC.
Monitoring (1/2)
• Source monitoring
• Over- / undervoltage

• Over-/ underfrequency

• Voltage imbalance

• Phase rotation (CW or CCW)

• Load monitoring
• Overcurrent (3 levels configurable)

• Overload (2 levels configurable)

15 | © WOODWARD, INC.
Monitoring (2/2)
• Switch monitoring
• Breaker position feedback / plausibility

• Transfer failure

• Sync-check (in-phase monitoring)


• External sync permission configurable

• Battery over-/undervoltage (2 Levels)

• Engine Start Failure S1 & S2

• Engine unintended stop failure S1 & S2

• Discrete input configurable to acknowledge alarms

• Event Logger with 300 entries

• CAN interface monitoring

16 | © WOODWARD, INC.
Discrete I/O
8 x Relay Outputs
Discrete I/O Status Display
• Alarm and control • Indicates when input / output is active
• 6 single-pole contacts
• 2 two-pole contacts
• Relay 2 – 4: max. 7 Adc
• Relay 5 : max. 7 Aac
• Relay 6 - 7: max. 10 Adc
• Relay 8 – 9: max. 7 Aac Expansion with external DI/DO boards
• Max. 2x Woodward IKD 1 • IKD-IN-16
12 x Discrete Inputs (16 DI/16 DO)
• Control (isolated) functions • Phoenix modules
• Input 1 – 5: fixed functionality (max. 16 DI/DO)
• IKD-OUT-16
• Input 6 – 12: freely configurable

17 | © WOODWARD, INC.
Configuration via Toolkit

USB

USB

Note: DTSC-200A accepts


ToolKit settings files
created for DTSC-200.

18 | © WOODWARD, INC.
DTSC-200 Functions Controlled By Inputs
• Test Switch • Auto/Manual Selector
• Disconnect Switch • Transfer Mode Selector
• Remote Peak Shave • Transfer Commit
• Remote Inhibit Transfer to Normal or • Source Priority Selector Switch
Emergency
• Reply From Bypass Isolation Switch Normal or
• Remote Load Shed Emergency
• Interruptible Power Rate Provisions • Logics Manager Configuration

19 | © WOODWARD, INC.
DTSC-200 Functions Controlled By Outputs
• Motor Load Disconnect • Shunt Trip Enable
• Normal Position Indication • Elevator Pre-Signal
• Emergency Position Indication • Status Message “Not In Automatic”
• Neutral Position Indication • Status Message “EPS Supplying Load”
• Normal Source Available • Status Message “Bypassed Normal Source”
• Emergency Source Available • Status Message “Bypassed Emergency Source”
• Load Shed • Centralized Alarm
• Logicsmanager

relays

20 | © WOODWARD, INC.
DTSC-200 Transfer Timers
• Transfer commit • Emergency Source Start Time Delay 0-300 Sec.
• S2 Start Delay • Emergency Source Cool Down Timer
• Preferred source Delay • Motor Load Disconnect Timer: Pre, Post or Both
• S1 source stable timer • Elevator pre-signal duration 0-300 Seconds
• S2 source stable timer • Time Delay From Neutral To Source 1 0-10 Minutes
• S1 outage delay
• S2 outage delay
• External Timer Bypass

21 | © WOODWARD, INC.
ATS Inhibit
• Security feature
• Locks out all transfer operations
• Emergency source will be started, but no transfer takes place
• Configurable via LogicsManager
• In cabinets used in combination with an “Inhibit switch”

22 | © WOODWARD, INC.
Limit switch Monitoring (plausibility check)

• Limit switch monitoring evaluates the ATS limit switch replies and checks them
after limit switch failure delay time for plausibility
• If the replies are not plausible, the "Actual" and "Expected" replies are displayed
• Meanwhile, the status of the breaker replies cannot be reset with the Reset
button and all further transfers are inhibited

23 | © WOODWARD, INC.
In-phase monitoring (sync check)

• Available for all transfer switch types


• Checks phase angle and Voltage/Frequency difference to ensure a transfer into
the other source occurs within a phase angle difference of 7° or less.
• User programmable outcome conditions if In-Phase monitoring fails.
• User programmable setpoint windows for voltage and frequency difference.
• Transfer switch reaction time is adjustable

24 | © WOODWARD, INC.
Max parallel time <100ms
• Tests showed that smallest max.
parallel time is between 40 and
50ms

• With breaker closing time 50ms a


max. parallel time of 92ms has
been verified

• For this reason, to reach max.


parallel time of 100ms, the
breaker closing time needs to be
max. 50ms

25 | © WOODWARD, INC.
Extended parallel time for softloading application
• Only available for Closed transition operation

• Transfer switch can stay parallel as long the customer wishes it to do.
ATS
S1 Gen

Switch control Bias

Extended
Parallel time req.

26 | © WOODWARD, INC.
Transfer inhibit features

• Function “Inhibit transfer to Source 1” available


• Function “Inhibit transfer to Source 2” available
• Blocks the transfer into the desired direction completely
• Configurable via LogicsManager

27 | © WOODWARD, INC.
Elevator Pre –Signal + Timer
• This Signal is set before a transfer is carried out
• Signal is reset after transfer has been accomplished
• Signal & Timer only active if both sources are available
• Configurable to Relay output via LogicsManager

Elevator
Control

28 | © WOODWARD, INC.
Motor Load Disconnect Signal + Timer
• This Signal is set before a transfer is carried out
• Signal is reset after transfer has been accomplished
• Signal & Timer always active
• Configurable to Relay output via LogicsManager

Motor Loads

29 | © WOODWARD, INC.
Daisy chaining of MLD Signals
• This function is used as a method to initiate load shedding
• For extra load shedding points, the IKD’s are supported

MLD Relay 1

MLD 1
MLD Relay 2
expired

MLD 2
MLD Relay 3
expired

30 | © WOODWARD, INC.
Load sequencing with MLD

Motor Load 1

Motor Load 2
CAN
Motor Loads 1- 8

Motor Loads 9 - 16

31 | © WOODWARD, INC.
Source priority selection
• User selectable which source has priority
• Non-Prioritized Source always acts as an emergency source if the prioritized
source fails.
• Configurable via LogicsManager

Utility-2-Utility Utility-2-Gen Gen-2-Gen

32 | © WOODWARD, INC.
Load shed
• Capability for initiate a load circuit disconnection form the
non-preferred source.
• A re-transfer to the prioritized source is performed if
preferred source is available.
• If preferred source is not available, a transfer to
the neutral position will be initiated
• Once transferred to the preferred source and this source
fails, a transfer to the emergency source is blocked. Only a
transfer to the neutral position takes place.
• Configurable via LogicsManager

33 | © WOODWARD, INC.
Load Test
• Initiates an engine start and performs a transfer to the
• non-preferred source.
• Can be initiated via the tactile keys on the frontfoil
• Can also be initiated by using a discrete input.
• Load test timer configurable
• Configurable via LogicsManager

34 | © WOODWARD, INC.
Engine Test

• Initiates a engine start on the non-prioritized source


• Can be initiated via the tactile keys on the frontfoil
• Can also be initiated by using a discrete input.
• Engine test timer available
• Configurable via LogicsManager

35 | © WOODWARD, INC.
In-Phase monitoring
• Available for all transfer switch types
• Checks phase angle and Voltage/Frequency difference to ensure a
transfer into the other source occurs within a phase angle difference
of 7° or less.
• User programmable outcome conditions if In-Phase monitoring fails.
• User programmable setpoint windows for voltage and frequency
difference.
• Transfer switch reaction time is adjustable

36 | © WOODWARD, INC.
Extended parallel time

• Only available for Closed transition operation


• Transfer switch can stay parallel as long the customer wishes it
to do.
• For softloading applications

37 | © WOODWARD, INC.
Extended parallel time

ATS
S1 Gen

Bias
Switch control

Extended
Parallel time
req.

38 | © WOODWARD, INC.
Vector group adjustment
• For usage, if transformers are used in the ATS System
• Adjustable in the range +/- 180 °
+30 °

0° +30 ° ATS
S1 S2

S1 Volt. S2 Volt.
measurement measurement

39 | © WOODWARD, INC.
Shunt Trip enable
• Capability to shunt trip a circuit breaker
• Trips, if both sources have been paralleled for more than configured time
• Signal stays tripped, until it gets acknowledged

CB
S1 S2

Shunt trip
enable
Signal

40 | © WOODWARD, INC.
Transfer Timers
• Transfer commit • Emergency Source Start Time Delay 0-300 Sec.
• S2 Start Delay • Emergency Source Start Time Delay For Test 0-
300 Seconds
• Preferred source Delay
• Emergency Source Stable Timer
• S1 source stable timer
• Normal Source Stable Timer
• S2 source stable timer
• Emergency Source Cool Down Timer
• S1 outage delay
• Motor Load Disconnect Timer: Pre, Post or Both
• S2 outage delay
• Elevator pre-signal duration
• External Timer Bypass
• Elevator Pre-Signal 0-300 Seconds
• Time Delay From Neutral To Source 1 0-10
Minutes

41 | © WOODWARD, INC.
Remote I/O - IKD
Features per input:
• Assign a name
• Define a alarm class
• NO/NC configuration
• Configure a time delay Can bus

The relay outputs are controlled and configured over Outputs


Inputs
the CAN bus connection from the main controller.

Outputs
Inputs Outputs
Inputs

IKD-OUT-16
IKD-IN-16

IKD 1

42 | © WOODWARD, INC.
DTSC-200A is DTSC-200! But…
• Short Lead Time • I/O
• Proven and available hardware • Overall, one relay less (Ready-for-operation).

• DI‘s activated by B-
• Dimensions
• Slightly bigger cut-out • Interfaces
• CAN (Termination in-build),
• Voltage Measurement
• RS-485 (only Half-Duplex)
• Only restriction in UL market (may require PT)
• Service Port (USB)
• Current Measurement
• Only 5A CT input supported. Same accuracy. • Others
• Ethernet, RS-232, SD card slot available on HW
but currently not supported (evtl. in rev. B)

43 | © WOODWARD, INC.
Resources
Manual, Software, Config. Files, CAD models, etc.
• http://wwdmanuals.com/DTSC-200A

Product Page
• https://easygen.org/ats/

Videos
• https://www.youtube.com/playlist?list=PLW55kmXY0fHCoZptLxzCvzmB5POGRbfYK

Webinar recording
• https://wss.woodward.com/manuals/Support/Webinar_Recordings/DTSC-200A