Professional Documents
Culture Documents
MECCOCT18-12509
Swaraj Dubli
Saudi Aramco
Yanbu Refinery
P.O. Box 30028 Royal Commission of Yanbu
Saudi Arabia
ABSTRACT
Crude tower overhead corrosion has been one of the most researched subject in the field of refinery
corrosion. Even though extensive study and work has been done in the industry, it has been still a concern
in most refineries around the world. Each overhead system has its own unique problem and hence
requires similarly unique set of solutions to effectively manage the corrosion.
In current times, it is believed and well understood that a continuous water wash system is required to
effectively manage and mitigate the overhead corrosion risk posed due to dew point acid corrosion and
ammonium chloride corrosion. But the challenge lies in managing and mitigating the corrosion risk in
overhead systems where continuous water wash is not possible.
In the current study a systematic approach has been adopted to understand the main root causes for the
corrosion (under the available intermittent water wash) and possible solution were recommended to
overcome the challenge of mitigating and managing the overhead corrosion risk and reduce the number
of leaks in the Crude Distillation Unit (CDU) overhead system. In the current study various tools and
methods were deployed to optimize the water wash and ensure its effectiveness.
Keywords: Overhead corrosion, dew point acid corrosion, ammonium chloride corrosion, intermittent
water wash, Integrity Operating Windows (IOWs)
INTRODUCTION
Corrosion in crude unit overhead has been a problem since the beginning of the petroleum refining
process. Various solutions have been adopted to overcome these challenges ranging from addition of
various chemicals to the process stream to incorporation of complex water wash system and use of
modelling tools to predict corrosion.1, 2, 3 Despite all the complex research at disposal for the industry to
combat crude unit overhead corrosion, it remains one of the most challenging issue for the refining
industry at large.
Major corrosion challenges for the crude unit overhead system are dew point corrosion, ammonium or
amine salt corrosion, under-deposit corrosion and fouling due to salt deposit, erosion-corrosion especially
at overhead piping bends and inlet of overhead condensers tubes. Industry adopted varied solutions to
overcome each specific challenge such as use of neutralizing amines or ammonia to control the pH (in
the range of 5.5 – 6.5) and corrosion inhibitors to create a protective film on the metal surface prone to
corrosion activity. Further caustic is also added to the desalted crude to lower the salt hydrolysis rate
which in turn reduces the amount of inorganic acid in the overhead. Also, one of the objective of water
wash is to enforce the water condensation before the salting point and the condensed water may wash
away the salts thereby reducing its corrosivity.4,5,6,7
Despite all the technological advancements and practices available at our disposal, there remain
challenges to overcome which are inherent in the system due to design limitations, increased processing
capacity, unit operating conditions and cost constraints.
The unit initially designed for 175,000 bpd has undergone several revamps and de-bottlenecking to
process 250,000 bpd of crude. After the revamps, the desalter vessels were under-sized for the new
processing capacity and therefore lead to more salt out of the desalter than the established limit of 1 ptb.
To overcome this challenge of high salt out due to under-sized desalters, caustic is injected downstream
of the desalters and preheat train in the hot crude stream. To control any damage due to caustic injection,
its concentration is maintained at the least in the range of 4-6 Be⁰ and injected at the center-line of the
pipe to ensure good mixing with the crude. Figure 1 below shows the trend for desalter salt out against
the acceptable threshold limit.
Figure 2: Tube failure history for the overhead fin fan coolers
To effectively manage the corrosion and to define a strategy for intermittent water washing in crude unit
overhead system, following are analyzed:
8.00
7.50
7.00
6.50
6.00
5.50
5.00
4.50
4.00
There have been number of fin fan condensers leak reported with multiple tube failures. To understand
about the exact damage mechanism for frequent failures of these tubes, detailed investigation was
carried out for the failed tube sample.
The failed tube was found severely thinned and found with deposits. These deposits were analyzed for
composition and pH. The pH of the 1% solution of the deposit in deionized water was found to 5.28.
Further analysis of the deposit revealed the main constituents were chlorides, sulphates, ammonia and
iron. This clearly indicates that ammonium chloride salts are being deposited inside the fin fan cooler
tubes and leading to under deposit corrosion.
Figure 6: Sliced section of failed fin fan tube
Corrosion Risk Monitor (CRM)†, an ionic modelling program was used to calculate the corrosion risk of
the crude tower and the overhead piping including the condensing system. The program calculates the
dew point, velocities, and salt formation temperature of ammonia and other amines in the system at the
tower, overhead and at the dew point. The corrosion risk due to salt is measured by ΔT (temperature
difference between system and salt formation temperature) and should be more than 5.5⁰C to be in risk
free zone as industry thumb rule.
The modelling showed that salt formation temperature was reached in the fin fan bundles close to inlet.
Therefore water wash injection was required before the inlet of the bundles and it was possible to operate
without continuous water wash at the tower top as no salt was formed in the overhead piping.
It further elaborated that in absence of any condensed phase in the overhead piping, it was out of
corrosion risk zone despite velocities being in erosional ranges. This was also confirmed by ultrasonic
thickness measurements taken in the overhead piping from time to time.
With understanding of the operations history, ionic modelling simulation of the overhead system and
investigation analysis of the failed tube sample clearly indicated the need of improvement of water wash
for effective removal of salts from the fin fan coolers. To identify the effective water wash duration, a set
of experiments were undertaken.
Corrosion coupon was placed inside the tube of the fin fan cooler with the help of an in-house designed
coupon holder. The first set of experiment was conducted with 24 hour water wash frequency. A particular
bundle was selected for the experiment and chloride profiling of the water from the bundle was performed
for 2 hours duration. The coupons were placed inside the tube for a period of 120 days. Same experiment
was repeated with identified bundle but with a 4 hour wash water frequency. Figure 7 shows the
comparison of chloride profiling test conducted with different water wash frequencies.
___________________________________________________
†
Corrosion Risk Monitor (CRM) – A Baker Hughes Program
Figure 7: Comparison of chloride profiling with 4 and 24 hour water wash cycles
Deposit was found on coupon which was installed in the initial phase of the experiment i.e. during 24
hours of water wash cycle however the amount of deposit was reduced to minimal with 4 hours of water
wash cycle. The salt collected in the initial phase was tested and found high with chlorides, ammonia and
iron as in case of failed tube sample.
From the above figure it is evident that the water wash is most effective for the initial 60-70 minutes from
the start of water washing. Most of the salt is removed as the water wash is started and then attain a
stable chloride levels which cannot be further reduced with the existing wash water system. It is clear
from the plots above that more salt is deposited in the tube bundles with large dry out periods.
With the implementation of increased frequency of 4-hour water wash helps in effectively removing the
deposited salts from the tube bundle. Minimum amount of salt are deposited with low dry out time which
can be easily removed with the amount of wash water available for removal thereby reducing the
corrosion rate in the fin fan cooler. This was also confirmed by measurement of corrosion rate of the
coupons placed inside the fin fan cooler.
As the initial one hour is been most effective period for salt removal from the bundle, there is scope of
further increasing the frequency of the water wash to 1 or 2 hours and reduce the dry out period to 2.5
days but this is practically difficult to implement as all the valves are manually controlled.
As an outcome of ionic modelling, it was also found that providing wash water injection in sub headers
after the main overhead piping can provide effective scrubbing of the contaminant in the short residence
time provided water is injected at the location and in correct quantity. Some paper have also suggested
the use stronger base amines in conjunction with existing neutralizing amine to reduce the corrosivity of
the salts thereby increasing the life of the fin fan coolers. (8)
ACKNOWLEDGEMENT
I would like to thank Toney K Joy for his rough draft and final review of the paper. I would also like to
express my gratitude towards Saudi Aramco Yanbu Refinery Management for their support and
encouragement for undertaking this task.
REFERENCES
8. J. Lack, B. Harrell, “Reducing Salt Corrosion Rates with Stronger Base Amines,”
CORROSION/2013, paper no. 2037 (Houston, TX: NACE, 2013).