You are on page 1of 27

Instrument Transformers

B3-Chapter 3

1
Introduction
 Power system transducers extract information from the
power system
 Current transformer (CT)
 Voltage / potential transformer (PT)
 CTs and PTs are the eyes and ears of the protective
system.
 Provide current and voltage signals to the relays (and meters)
which are faithful reproductions of the corresponding primary
quantities.
 Important roles
 Electrically isolate the protective relays from the high-voltage
power system for, the purpose of safety of the operating personnel.
 Step down the current and voltage to standard values such that 1 A,
5 A, 110 V so that the design of relays can be standardized
irrespective of the actual primary voltage and current.
2
CT Construction

 Two winding transformers with independent primary


and secondary windings.
 Single or fewer primary turns of heavy duty wire on primary.
 Large number of secondary turns wound on a laminated core
of low-loss magnetic material.
 One-turn primary winding, known as bar-primary, is
used when the magnitude of the primary current is
sufficiently high.
 Also known as series transformer.
3
Equivalent Circuit of CT

 Primary winding of a CT is connected in series with


the power network.
 Primary leakage impedance (R1 , L1) is insignificant.

4
Secondary referred equivalent circuit
 CT has to reproduce the primary
quantities at secondary.
 Secondary referred circuit is
better for analyse CT efficiency

 I1 Primary current referred to secondary


 Zm Mutual impedance seen from secondary
 Em Voltage across magnetizing reactance seen from
secondary
 Zb Burden impedance
 Eb Voltage across burden

5
CT Errors ..
 Ideally, CT should faithfully transform the current
without any errors.
𝐼1 = 𝐼2 + 𝐼𝑚
𝐸𝑚
𝐼𝑚 =
𝑍𝑚
𝐸𝑚 = 𝐸𝑏 + 𝐼2 𝑍2
 Ratio error in reproduced current
𝐸𝑟𝑟𝑜𝑟 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 𝐼1 − 𝐼2 𝐼𝑚
𝜀= = =
𝑇𝑜𝑡𝑎𝑙 𝑐𝑢𝑟𝑟𝑒𝑡𝑛𝑡 𝐼1 𝐼1
 Zb↓, I2↑, Im↓
 CTs work at their best when they are connected to very low
impedance burdens.
 CT error is zero percent in an ideal case of zero burden
6
CT Errors ..
 Phase angle error
 Angular difference between the secondary current phasor
and the primary current phasor referred to secondary.
 Simplification
 Rm part of Zm can be neglected
 Tanθ ≈ θ for small θ
𝐼𝑚
𝜃≈
𝐼1
 Zb↓, I2↑, Im↓
 Phase angle error will be smaller for smaller burden

7
Ratio Correction Factor
 The CT error is usually presented in terms of a ratio
correction factor (RCF)
 Defined as the constant by which the name plate turns ratio n
of a current transformer must be multiplied to obtain the
effective turns ratio.
1
𝑅𝐶𝐹 =
1− 𝜀 RCF
𝑛𝑒𝑓𝑓 = 𝑅𝐶𝐹 × 𝑛
 Although ε and R are complex numbers, sometime
only magnitudes are used for approximation.

8
Practice Problem

𝑍2 + 𝑍𝑏
𝐼𝑚 = 𝐼
𝑍2 + 𝑍𝑏 + 𝑍𝑚 1

𝐸𝑚 = 𝐼𝑚 𝑍𝑚

9
Saturation Characteristics
 Zm is not constant due to non-linearity of magnetizing
branch
 The actual excitation characteristic of the transformer
must be taken into account.
 CT saturation
 Core is no more able to handle further flux with increase in
primary current
 No flux change when the primary current changes.
 No further rise in secondary current with the rise in primary
current.
 All of the ratio current is used as magnetizing current and
none flows in to the load connected to the CT.

10
Saturation Characteristics
 Linear Region AB
 Excitation current is virtually
proportional to primary current.
 Ideally, transformer must operate
in linear region.
 Knee point K
 10% rise in the open-circuit
voltage results in an increase of
50% in the excitation current.
 Saturated zone
 Curve becomes virtually
horizontal
 High error in transformation ratio
 Secondary current is highly
distorted.
11
Multi Ratio CT
 CT may be provided with several taps to obtain multiple
options of turn ratio.
 Turns ratios for CTs have also been standardized
 Secondary current is standardized to 5A

12
Multi Ratio CT ..

13
Standard class design
 The equivalent circuit method of calculating the
performance of a CT depends upon the availability of
the magnetizing characteristic.
 Approximate assessment of the CT performance may
be made through its standard class designation.
 Defined by ANSI and IEEE
 Example: 10C400 or 10T300
 Standard is defined for 20 times loading
 First integer is error.
 Second integer is voltage at which above error exists.
 T signifies some uncertainties in the transformer design

14
Practice Problem
Calculate the maximum burden for 600:5 turn ratio CT for
class 10C400 to measure maximum current of 5kA.
 10% error for Is=100A at 400 V secondary
 Im = 10% Is = 0.1 × 20 10 = 10A
Vm 400
 Xm = = = 40Ω
Im 10 41.66A
37.5A
 At actual current of Ip=5kA 4.17A
5
 Is = × 5000 = 41.66A 167V
4.45Ω
600
40Ω
 At 10% error
 Im = 4.17A
 Vm = 4.17 × 40 = 167V
 Maximum allowable voltage at 5000A is 167V. It corresponds
to maximum allowable burden
167
 𝑍𝑏 = = 4.45Ω
37.5
15
CT Polarity Markings
 The terminals identified by solid marks indicate the
starting ends of the two windings.
 Both windings will go around the core in the same
sense (i.e. counter-clockwise or clockwise) starting
from marked terminal.

16
Measurement CT
 Used for measurement purposes under normal
operation.
 High accuracy requirements – error should be 0.5% to
1%.
 Designed to protect the instruments from possible
damage under fault condition
 Must not faithfully transform the fault current.
 Designed to saturate at currents more than around
1.2pu.
 By suitable design, the operating point of the
measurement CT is kept near the knee of the
excitation characteristic.
17
Protective CT
 Faithful reproductions of high fault currents is
required
 Increased requirements of quality and quantity of core
material.
 No requirements on high accuracy and errors up to
10% are tolerable.
 It is rarely necessary to determine phase-angle error of
a CT used for relaying purposes.
 Most relaying applications can tolerate phase-angle
error which for metering purposes would be
unacceptable.
18
19
Voltage Transformers (VT)
 Also known as potential transformers (PT).
 Normal transformers with the primary winding
connected directly to the high-voltage apparatus.
 One or more secondary windings rated at the standard
voltage of 69.3 V for phase-to-neutral voltages or 120
V for phase-to-phase voltages.
 Transformation error is negligible for all practical
purposes in its entire operating range (0 to 1.1pu).
 Two main types
 Conventional two-winding, electromagnetic type
 Capacitive voltage divider type, known as capacitive voltage
transformer, preferred for extra high voltages (>345kV).
20
CCVT
 One of the most common voltage sources for high voltage
relaying is coupling capacitor voltage transformer
(CCVT).
 A capacitor stack is usually connected to high-voltage
transmission lines for the purpose of feeding the carrier
signal as a pilot channel for transmission line relaying.
 The same string of capacitors is used as a potential divider
 Tap provides a reduced voltage of about 1 to 4 kV,
depending upon the particular choice made by the
designer.
 The tap point is connected to a transformer through an
inductance.
 The turns ratio of the transformer is such that the
secondary voltage is the standard voltage (69.3 or 120 V)
required for relaying.
21
CCVT ..

Inductive and capacitive elements can cause significant


phase angle error at secondary
𝐶1
𝐸𝑡ℎ = 𝑉𝑙𝑖𝑛𝑒 ×
𝐶1 + 𝐶2
1
𝐸2 = 𝐸𝑡ℎ − 𝐼1 𝑗𝜔𝐿 +
𝑗𝜔 𝐶1 + 𝐶2
22
CCVT ..
 In order to supress phase angle error, inductance L should
be selected such that resonance occurs with (C1+C2) at
power frequency ω.
1 1
𝐿= 2
𝜔 𝐶1 + 𝐶2
 By careful design of the transformer, its leakage
inductance can be designed to provide such compensation.
 To avoid the impact of undesired frequencies due to
ferroresonance, extra filtration circuit (Zf) is also used at
transformer secondary.
 Ferroresonance is caused by the nonlinearity of the iron cores.
 Saturation also impact the leakage reactance of transformer.
 Terminal markings of VT are similar to CT
23
Practice Problem
 Secondary referred values: V1
 C1= 0.0018μF
 C2= 0.018μF V2
 V2=6.6kV
 Tuning reactance L=?
 If VX1:VH1 = 0.5, V1=?
1 Calculate C1 to get
𝐿= 2 = 512𝐻 V2=3.8kV, if
𝜔 𝐶1 + 𝐶2  V1=380kV
𝑉1 𝐶1 + 𝐶2  C2=0.018μF
= = 11
𝑉2 𝐶1 𝐶1 + 𝐶2 = 100𝐶1
Primary referred value:
99𝐶1 = 0.018𝜇𝐹
𝑉1𝑝 = 2𝑉1 =…
24
Electronic Instrument Transformers
 Now, several techniques are available to transform the
measured quantity using optical and state methods.
 Such transformers are also suitable for DC measurements.
 Optical Sensing – Certain optical sensing media (glass,
crystals, plastics) show a sensitivity to electric and
magnetic fields and
 Such magneto-optic sensing material can be immersed in a varying
magnetic field.
 Intensity of light passing through sensing material will very with
the varying magnetic field.
 Varying light intensity can be transformed into electronic signal
using light sensors.

25
Electronic Instrument Transformers ..
 In the case of a current measuring device the sensitive
element is either
 free in the magnetic field
 immersed in a field-shaping magnetic core
 In the case of a voltage-sensing device the same
alternatives exist, but such elements are used that are
sensitive to electric fields.

26
Electronic Instrument Transformers ..
 Hall effect sensing is more
powerful technique
 Hall Sensor: Charge carriers are
deflected by perpendicular magnetic
field, producing a potential
difference between two ends of strip
 In its simplest shape, the Hall
effect voltage is directly
proportional to the magnetising
current to be measured.
 Need external power source for
sensing material
 For more sensitive applications,
sensing current can be fed
through the secondary of
ordinary transformers.

27

You might also like