Professional Documents
Culture Documents
DOI 10.1007/s40313-013-0014-5
Received: 10 March 2011 / Revised: 22 July 2011 / Accepted: 14 August 2012 / Published online: 2 April 2013
© Brazilian Society for Automatics–SBA 2013
123
340 J Control Autom Electr Syst (2013) 24:339–348
frequencies according to the time domain characteristic of Under certain conditions, for example, an unsuccessful
the transient voltage, which is also sensitive to the CCVT reclosing of a transmission line, or after clearing out a short-
load. A third method estimates the value of the measured circuit in the CCVT secondary terminals, ferroresonance may
voltage based on the source impedance ratio (SIR), in which take place. This phenomenon is basically the resonance of the
the equivalent impedance seen from the CCVT bus is needed. circuit capacitance with the iron-core nonlinear inductance.
Also, the value of SIR is difficult to obtain. In order to damp out ferroresonance oscillations, a ferrores-
A fast and reliable method to correct the CCVT secondary onance suppression circuit (FSC) is used across the SDT
voltage waveform in real time is still needed. In this direc- winding.
tion, this study presents the steps to design a hardware device The diagram shown in Fig. 1 is valid only near power
capable of performing the correction of the CCVT secondary frequency. A CCVT model applicable for electromagnetic
voltage. The device is basically a recursive digital filter whose transient studies must take into account stray capacitances
parameters are obtained from the CCVT frequency response between the windings and stray capacitances between each
assuming a predefined topology. The error evaluation is car- winding and ground (Kezunovic et al. 1992; Kojovic et al.
ried out through real time simulations with the device con- 1994). A model suitable for a frequency range from 10 Hz
nected to the Real Time Digital Simulator (RTDSTM ). With to 10 kHz is shown in Fig. 2, for a particular FSC (Fer-
the strategy used here the errors do not depend on the load nandes Jr. 2003). It basically consists on six main com-
connected to the CCVT secondary terminal, as opposed to ponents: capacitor stack (C1 e C2 ), compensating inductor
design methods reported in the literature. (Rc , L c e Cc ), SDT (Rp , L p , Cp , Cps , Rs , L s , Cs , Rm e L m ),
Evaluation of the operation of the proposed device is given FSC (Rf , L f e Cf ), and drain coil (L d );. However, this
for a 230 kV CCVT from Companhia Hidro Elétrica do São detailed representation requires data which are not easily pro-
Francisco (CHESF). Two important situations are addressed: vided by manufacturers.
harmonic distortion and short-circuit in a 230 kV system. Aiming to reduce the complexity of the model, Kezunovic
Real time simulations show that the dynamic compensation et al. (1992) and Fernandes (1999) performed sensitivity
of the CCVT secondary voltage may enhance the perfor- analysis in a frequency range from 10 Hz to 10 kHz to detect
mance and reliability of the measuring, control, and protec- which parameters are relevant in this frequency range. They
tion systems. concluded that L d , Cps , Rs , L s e Cs do not cause significant
changes in CCVT frequency response curves, i.e., they can
be neglected without affecting the results. The equivalent
circuit of the CCVT with the most important parameters is
2 Coupling Capacitor Voltage Transformer Model shown in Fig. 3. This topology has been successfully used in
electromagnetic transient studies (Fernandes Jr. 2003; Neves
A typical CCVT consists of two capacitive stacks connected et al. 2007).
in series (C1 and C2 ), with an intermediate derivation b whose The circuit shown in Fig. 3 is appropriate to reproduce
rated voltage is typically in between 10 and 20 kV, which in the behavior of an actual CCVT in the frequency range of a
turn feeds the primary winding of a step down transformer few kHz and will be used here to represent the CCVT in real
(SDT), providing the secondary voltage Vo to measure and time simulations. However, since there are some situations
protect the instruments. The compensating inductor (L c ) is in which the CCVT secondary voltage is not a replica of
designed to correct the voltage lag produced by the capacitive its primary voltage, a compensating device must be used to
divider. A basic circuit diagram for a typical CCVT at 60 Hz overcome those difficulties. In the next section, the steps to
is shown in Fig. 1. design a programmable compensating device to be attached
to the CCVT secondary terminal is presented. The behavior
Fig. 1 Electrical basic diagram for a typical CCVT Fig. 2 CCVT general model for electromagnetic transient studies
123
J Control Autom Electr Syst (2013) 24:339–348 341
-5
Gain (dB)
-10
-15
-20
-25
1 2 3 4
10 10 10 10
Frequency (Hz)
Fig. 3 CCVT model used for linear parameters estimation
Fig. 5 Magnitude curve of the 230 kV CCVT voltage ratio (Fernandes
Jr. 2003)
100
50
Phase (º)
Fig. 4 Block diagram to perform the correction of the CCVT sec- -50
ondary voltage
-100
-150
of the CCVT and the device altogether must reproduce the -200
ideal voltage divider response as close as possible. 10
1
10
2
10
3
10
4
Frequency (Hz)
Fig. 6 Phase curve of the 230 kV CCVT voltage ratio (Fernandes Jr.
3 Compensator Design 2003)
123
342 J Control Autom Electr Syst (2013) 24:339–348
1.01
Gain (dB)
0.99
0.98
0.97
1 2 3 4
10 10 10 10
Frequency (Hz)
123
J Control Autom Electr Syst (2013) 24:339–348 343
2.5
1. Write the transfer function of the analog filter in the form
2
of poles and zeroes in the s plane (Eq. 10);
2. Rearrange poles and zeroes in increasing or decreasing
order of their real parts;
Phase (º)
1.5
3. Split the transfer function into four sections of second-
1
order filters (Eq. 11), each section comprising the ratio
0.5
of a pair of zeroes to a pair of poles (Eqs. 12–15).
The transfer function of the compensator can be written as
0
10
1
10
2
10
3
10
4 the product of second-order filters in the s plane:
Frequency (Hz)
G Com (s) = G 1 (s) .G 2 (s) .G 3 (s) .G 4 (s) , (11)
Fig. 10 Phase of the transfer function for the compensated CCVT
where each of them is expressed as:
s + z 1′′ . s + z 2′′
and pm , m = 1, . . . , 8 are the zeroes and poles of CCVT G 1 (s) = ; (12)
s + p1′′ . s + p2′′
rational function, respectively.
For convenience, the function φ(s)−1 was forced to have
s + z 3′′ . s + z 4′′
double zeroes at the origin to cancel out the existing double G 2 (s) = ; (13)
s + p3′′ . s + p4′′
zeroes in CCVT transfer function, HCCVT (s). Thus, the trans-
s + z 5′′ . s + z 6′′
fer function of the compensated CCVT can be represented G 3 (s) = ; (14)
s + p5′′ . s + p6′′
by Eq. 10. Where z n′′ , n = 1, . . . , 8 and pn′′ , m = 1, . . . , 8
are the zeroes and poles of the compensator transfer function, s + z 7′′ . s + z 8′′
respectively. The poles and zeroes of the compensator trans- G 4 (s) = . (15)
s + p7′′ . s + p8′′
fer function are shown in Table 3. Since all poles and zeroes
are located on the left hand side of the s plane, the compen- The Laplace Transform is very useful in stability analysis
sator has a stable behavior. The next step is to implement the of continuous systems. For discrete systems, the z-transform
compensator in the time domain. has a similar role. The implementation of the compensation
technique in digital signal processor was done by applying
A7 s 7 + A6 s 6 + · · · + A2 s 2
G CCVT (s) = (1) the bilinear transformation:
B8 s 8 + B7 s 7 + · · · + B0
2 1 − z −1
(s + z 1 ) . (s + z 2 ) . · · · . (s + z 7 )
HCCVT (s) = (2) s= , (16)
(s + p1 ) . (s + p2 ) . · · · . (s + p8 )
Td 1 + z −1
HCCVT (s) .G Com (s) = 1 (3)
HCCVT (s) .G Com (s) .ϕ (s) = 1 (4) where Td = 50 µs is the sampling time used. Thus, the trans-
G Com (s) = [HCCVT (s) .ϕ (s)]−1 (5) fer function of the compensator in the z plane is given by:
ϕ (s)−1 = 1 (6) 4
VCom (z) ki1 + ki2 .z −1 + ki3 .z −2
s2 G Com (z) = = k0
ϕ (s)−1 = (7) Vo (z) 1 + ki4 .z −1 + ki5 .z −2
D3 s 3 + D2 s 2 + D1 s + D0 i=1
s2
(17)
ϕ (s)−1 =
4.85 × 10−10 × s 3 + 1.00 × s 2 + 2.44 × s + 2.98 where, ko and ki j , with i = 1, . . . , 4 e j = 1, . . . , 5, are
(8) respectively, the scaling constant of the filter sections and
1
G Com (s) = .ϕ (s)−1 (9) the coefficients of second-order recursive digital filter. ki j
HCCVT (s)
coefficients depend on the sampling time (Td ) and on the
s + z 1′′ . s + z 2′′ . · · · . s + z 8′′
G Com (s) = (10) poles and zeroes of the compensator transfer function. In
s + p1′′ . s + p2′′ . · · · . s + p8′′
Table 4, ki j coefficients are shown for the 230 kV CCVT of
Fig. 3.
3.3 Recursive Digital Filter Implementation The scaling constant of the filter is found adjusting the
ratio between any non-zero value of the secondary voltage
The compensator is implemented as an 8th order recursive Vo and the compensated secondary voltage VCom at point n
digital filter—four second-order cascaded sections. A sim- defined by:
ple method to cascade second-order filters is presented by
Oppenheim and Schafer (1989) and adapted here in the form Vo (n)
k0 ≡ , (18)
of an algorithm: VCom (n)
123
344 J Control Autom Electr Syst (2013) 24:339–348
1 −2062291087.4731565 −0.744497659727
2 14144.602140705099 300342.107079962380
3 −564.938044020341 −898.562006472482 − j4385.708773829852
4 −203.477585444023 −898.562006472482 + j4385.708773829852
5 −905.900621118066 − j4344.234016373835 −503.410022344792 − j852.036648385486
6 −905.900621118066 + j4344.234016373835 −503.410022344792 + j852.036648385486
7 −1.219717000724 − j1.220039934453 −60.390407860040 − j119.503111095392
8 −1.219717000724 + j1.220039934453 −60.390407860040 + j119.503111095392
Table 4 Coefficients of
second-order filter sections for Coefficients Section
the 230 kV CCVT 1 2 3 4
123
J Control Autom Electr Syst (2013) 24:339–348 345
The block diagram representing the signal-conditioning Table 5 CHESF transmission line data
circuit with the respective waveforms in the output of each Sequence R (/km) ω. L(/km) ω. C(µ S/km)
stage is shown in Fig. 13.
Zero 0.4309 1.5659 2.3301
Positive 0.0888 0.5249 3.1210
3.5 Validation of the Technique Through Real Time
Simulations
The validation of the technique for correction of the CCVT voltage. It comprises three voltage harmonic sources and two
secondary voltage will be made through real time simula- 230 kV transmission lines (200 km long) whose data were
tions using the RTDSTM . The simulator operates in real time, obtained from the electrical system of CHESF (Companhia
therefore not only allowing the simulation of the power sys- Hidro Elétrica do São Francisco), the most important North-
tem but also making it possible to test physical protection and east Brazilian utility. The line resistance, reactance, and sus-
control equipment (Forsyth et al. 2004). The benefits of the ceptance values (zero and positive sequences) are shown in
compensator will be addressed for two situations: harmon- Table 5.
ics and single-phase short-circuit. For clarity, the simulation The voltage sources for phase a at buses 1, 2, and 3, in kV,
results are presented in Sect. 4. are represented by expressions 19, 20 and 21. Although the
voltage sources are not realistic, i.e., their harmonic contents
3.5.1 Harmonics in the 230 kV System are much higher than expected, they are suitable to analyze
the behavior of the compensator device under extreme situ-
The fictitious electric system shown in Fig. 14 is used here ations.
to validate the technique for correcting the CCVT secondary √ √
230 2 230 2
va(Bus 1) = √ sin(ωt) + √ sin(3ωt)
3 3 3
√ √
230 2 230 2
+ √ sin(5ωt) + √ sin(7ωt)
5 3 7 3
√
230 2
+ √ sin(9ωt) (19)
9 3
√
230 2
va(Bus 2) = √ sin(ωt − 5◦ )
3
√
Fig. 14 Electrical system used for measurement of harmonics in 230 2
230 kV transmission system + √ sin(11ωt − 55◦ )
11 3
123
346 J Control Autom Electr Syst (2013) 24:339–348
√
230 2 to control the angle of the fault and fault impedance, was
+ √ sin(13ωt − 65◦ )
13 3 implemented in real time.
√
230 2
+ √ sin(15ωt − 75◦ )
15 3
√ 4 Case Studies: Real Time Simulations
230 2
+ √ sin(17ωt − 85◦ ) (20)
17 3 The validation of the method will be done in two stages: first,
√
230 2 the compensator is used to monitor voltage signals with high
va(Bus 3) = √ sin(ωt − 10◦ ) harmonic content; second, the behavior of the compensator
3
√ is analyzed when faults occur in the system.
230 2
+ √ sin(19ωt − 190◦ ) In both cases, the voltage waveforms obtained with the
19 3 compensator will be compared to the CCVT primary voltage.
√
230 2 The diagram used to perform the simulations in real time is
+ √ sin(21ωt − 210◦ )
21 3 shown in Fig. 16. There are connections among the computer,
√ RTDSTM , oscilloscope, DSP, and signal-conditioning circuit.
230 2
+ √ sin(23ωt − 230◦ ) When performing the simulations, it was necessary to use
23 3
√ an oscilloscope with four channels due to the number of sig-
230 2 nals to be monitored, specifically:
+ √ sin(25ωt − 250◦ )
25 3
(21) 1. Channel 1 (CH1) was used to get the signal from the
For the source voltages at phases b and c, the RTDSTM com- CCVT secondary voltage;
putes the magnitude and phase angles automatically. In fact, 2. Channel 2 (CH2) was used to get the reference signal to
the magnitude of each harmonic component in each bus is trigger the oscilloscope;
the same as its corresponding harmonic source at phase a, 3. Channel 3 (CH3) was used to display the corrected volt-
but their phase angles changes according to their harmonic age signal, i.e., the output of the compensator;
sequence. For instance, in phase b and c positive-sequence 4. Channel 4 (CH4) was used to display the CCVT primary
harmonics introduce a −120◦ and +120◦ shift, respectively, voltage waveform. This signal was used as reference in
whereas negative-sequence harmonics introduce a +120◦ valuation of the compensator behavior.
and −120◦ shift, respectively.
Since the ADC input of the DSP works only for voltages
between 0 and +3 V, a circuit to condition the signal coming
3.5.2 Single-Phase Short-Circuit in the 230 kV System
from RTDSTM was assembled as shown in Fig. 17. An oscil-
loscope was used to check the signal conditioning circuit. A 6
In order to evaluate the compensator behavior in the protec-
tion system, the model of a simplified power system with
three buses, as shown in Fig. 15, was implemented. Table 6 Data of the 230 kV equivalent system
The electrical system consists on three buses, two voltage
Source Voltage (kV) R0 () X 0 () R1 () X 1 ()
sources with their respective impedances and transmission
lines (200 km long). The lines are the same lines of Fig. 14. A 187.8/0◦ 0.2856 5.5610 2.0205 7.2720
The data sources are shown in Table 6, where voltages cor- B 187.8/− 10◦ 0.8644 12.2484 12.8150 31.7268
respond to phase to ground peak values.
For this study, a logic to perform all kinds of faults (phase-
ground, between phases or between phases and ground) and
123
J Control Autom Electr Syst (2013) 24:339–348 347
V peak-to-peak sinusoidal signal was applied to the input of Figure 19 shows per unit CCVT primary and secondary
the signal-conditioning circuit and a 2 V peak-to-peak output voltage waveforms during the monitoring of harmonic dis-
voltage signal with +1.5 V DC biased was obtained as shown tortion without using the compensator.
in Fig. 18. One can see that the signal-conditioning circuit Note that the voltage waveform at the CCVT secondary
works fairly well. side is very different from the primary side voltage. The com-
pensator enables greater accuracy for the measurements of
4.1 Compensator Effects: Harmonics signals with harmonic contents, as shown in Fig. 20. There-
fore, measurements of signals with harmonic distortion may
With the real time implementation of the electrical sys- present significant errors when the CCVT is not compen-
tem shown in Fig. 14, several simulations were performed. sated.
4
Input Voltage
3 Output Voltage 1.5
CCVT Primary Voltage
2 CCVT Secondary Voltage Corrected
1
Voltage (V)
1
Voltage (p.u.)
0.5
0
-1 0
-2
-0.5
-3
-1
-4
0 10 20 30 40 50 60 70 80 90 100
-1.5
Time (ms) 0 5 10 15 20 25 30 35 40 45 50
Time (ms)
Fig. 18 Oscilloscope waveforms of input and output voltage of the
signal conditioning circuit Fig. 20 CCVT with the compensator: Primary voltage with harmonic
1.5 distortion
CCVT Primary Voltage
CCVT Secundary Voltage
1
1.5
CCVT Primary Voltage
Voltage (p.u.)
0.5
CCVT Secondary Voltage
1
0
Voltage (p.u.)
0.5
-0.5
0
-1
-0.5
-1.5
0 5 10 15 20 25 30 35 40 45 50 -1
Time (ms)
-1.5
0 50 100 150
Fig. 19 CCVT without the compensator: Primary voltage with har-
monic distortion Time (ms)
1.5
CCVT Primary Voltage Acknowledgments The authors are grateful to capes (coordenação de
1
CCVT Secondary Voltage Corrected aperfeiçoamento de pessoal de nível superior) and fpti (fundação parque
tecnológico itaipu) for financial support. The authors would also like to
thank the reviewers for their invaluable suggestions.
Voltage (p.u.)
0.5
-0.5 References
-1
Arrillaga, J., & Watson, N. (2003). Power system harmonics (2nd ed.).
-1.5
Wiley. 399 pp
0 50 100 150 Fernandes, D., Jr. (1999). Parameter estimation for coupling capaci-
Time (ms) tor voltage transformers (In Portuguese). Master’s thesis, Federal
University of Paraíba, Campina Grande, Brazil
Fig. 22 CCVT with the compensator: Fault occurrence Fernandes, D, Jr. (2003). Coupling capacitor voltage transformers
model for electromagnetic transient studies (In Portuguese). Ph.D
Dissertation, Federal University of Campina Grande, Campina
5 Conclusion Grande, Brazil
Forsyth, P., Maguire, T., & Kuffel, R. (2004). Real time digital simu-
lation for control and protection system testing. IEEE 35th annual
In this paper, a compensator device capable of performing power electronics specialists conference, 2004. PESC 04. Vol. 1, pp.
the correction of the CCVT secondary voltage in real time, 329–335
was presented. The compensator was designed from the lin- He, B., Li, Y., & Bo, Z. Q. (2006). An adaptive distance relay based
on transient error estimation of CVT. IEEE Transactions on Power
ear parameters of the CCVT and from the ideal frequency
Delivery, 21(4), 1856–1861.
response of the compensated CCVT, for a frequency range Kezunovic, M., Kojovic, L., Skendzic, V., Fromen, C. W., Sevcik, D. R.,
from 10 Hz to 10 kHz. & Nilsson, S. L. (1992). Digital models of coupling capacitor volt-
Two time domain studies were carried out to evaluate the age transformers for protective relay transient studies. IEEE Trans-
actions on Power Delivery, 7(4), 1927–1935.
voltage at the secondary side of a 230 kV CCVT when a
Kojovic, L. J., Kezunovic, M., Skendzic, V., Fromen, C. W., & Sevcik,
disturbance occurred at its primary side: a harmonic source D. R. (1994). A new method for the CCVT performance analysis
applied to the CCVT primary side; a fault at the CCVT pri- using field measurements, signal processing and EMTP modeling.
mary side. In both cases, the compensator acted to bring the IEEE Transactions on Power Delivery, 9(4), 1907–1915.
Neves, W. L. A., Souza, B. A., Fernandes, D., Jr., Costa, E. G., Almeida,
secondary voltage waveform close to the primary voltage
G. J. C., Lira, G. R. S., et al. (2007). Representation of coupling
signal. In other words, the compensated CCVT secondary capacitor voltage transformers in electromagnetic transient studies
voltage is a replica of the primary voltage. (In Portuguese). Technical Report. Federal University of Campina
The coefficients of the compensator were calculated tak- Grande, Campina Grande, Brazil
Oppenheim, A. V., & Schafer, R. W. (1989). Discrete-time signal
ing as reference the CCVT frequency response. With the
processing. Prentice Hall. 1120 pp.
strategy used here the coefficients of the compensator do not Press, W. H., Teukolsky, S. A., Vetterling, W. T., & Flannery, B. P.
depend on the load connected to the CCVT secondary termi- (1992). Numerical recipes in Fortran—The art of scientific comput-
nal, as opposed to design methods reported in the literature. ing (2nd ed.). New York: Cambridge University Press. 963 pp
123