You are on page 1of 3

Inspection and Test Plans (ITP) – MUM-10

AHU/FCU Installation Checklist

Client: Project Name: Project No:

Area: Drawing No’s: Date: Sheet: 1 of 3

Check Conducted By: Signature: Check Approved By: Signature:

INSPECTION CHECKLIST FOR: AIR HANDLING UNITS + FAN COIL UNITS


The below checks are to be completed by the Mechanical Contractor prior to start up and unit commissioning

INSPECTION HISTORY
NO: DESCRIPTION: INSPECTION:
ACCEPTABLE: DATE: COMMENTS:

Quality Control
Units type, model number and manufacturer approved
1 Yes No Yes No
for use
Units not being used are correctly stored
2 Yes No Yes No

Installation
Drawings on site are the latest issue
3 Yes No Yes No
AHU/FCU are not damaged in anyway
4 Yes No Yes No
AHU/FCUs are installed in correct location as per
5 Yes No Yes No
approved drawings and equipment schedule
AHU/FCUs are installed with approved vibration isolation
6 from the structure on which they are mounted and with Yes No Yes No
approved isolation from the duct work connected to it
AHU/FCUs are clearly labelled including number,
7 Yes No Yes No
manufacturer model number and duty
Confirm safety tray and/or condensate drainage provided
8 Yes No Yes No
to the units and is piped to adjacent waste point
Confirm AHU/FCU filters are fitted (construction filters
9 Yes No Yes No
during construction final filters at commissioning)

1
INSPECTION HISTORY
NO: DESCRIPTION: INSPECTION:
ACCEPTABLE: DATE: COMMENTS:
Confirm AHU/FCU is mounted so that adequate access is
10 provided for routine maintenance, removal of filters and Yes No Yes No
removal of coils and motors
Confirm correct installation of any motorised dampers on
11 Yes No Yes No
the units and that they are accessible for maintenance
12 Confirm correct electrical connection to unit Yes No Yes No
Confirm all interlocks are in accordance with unit wiring
13 Yes No Yes No
schematic
Confirm VSD installed and commissioned (if applicable)
14 Yes No Yes No
Confirm motor bearings lubricated, fan is free to rotate,
15 Yes No Yes No
drive is aligned and transport bolts are removed
Confirm correct CHW/HHW pipe work installed as per the
approved drawings complete with isolation valves, flow
16 Yes No Yes No
and water measuring valves, binder points, air vents and
drainage points
Confirm all ductwork and supply air/return air grilles
17 installed as per the approved drawings complete with Yes No Yes No
isolation from the AHU/FCU
Commissioning
Confirm CHW/HHW pipe work has been flushed to >110%
18 of the design flow rate prior to connecting the unit to the Yes No Yes No
pipe work
Confirm CHW/HHW flow achieves design flow rates prior
19 Yes No Yes No
to starting the unit
Confirm air flow achieves design flow rates prior to
20 Yes No Yes No
starting the unit
Confirm all associated controls are operating correctly
21 Yes No Yes No
including BMCS interface/monitoring as specified
Confirm unit operates to provide cooling or heating (as
22 Yes No Yes No
applicable) when cooling/heating signal provided

2
INSPECTION HISTORY
NO: DESCRIPTION: INSPECTION:
ACCEPTABLE: DATE: COMMENTS:
Mark alterations, sizes + final location on As Built
23 Yes No Yes No
drawings for record purposes

ADDITIONAL COMMENTS:

You might also like