You are on page 1of 17

Siemens Energy

system | Zhabhiz.Ramini@siemens.com
Item Value
Year of Reporting 2019
System system
Terminal 1 Name terminal
Energy Transmitted Terminal 1 1
Terminal 2 Name terminal2
Energy Transmitted Terminal 2 2
NORMAL RATING 4
PERIOD HOURS 8784

Addition Data
Start of commerial Operation: 05-09-2020
DC System Voltage [kV] 500
System Configuration Bipole System
asymetrical Monopole System
Symmetrical Monopole System
Bipole System
2 or 3 line DC Transmission Overhead line
Type of Semiconductor Thyristor
Transformer Type One phase
Number of transformers per Converter 4
Voltage Rating 4
Equipment Manufacturer 4
HVDC Availabilty App

Reference to CIGRE TB590


Table 1
DC SYSTEM PERFORMANCE
System system
Year 2019
SYSTEM DC VOLTAGE 500kv
TERMINAL 1 NAME terminal
TERMINAL 2 NAME terminal2

1. ENERGY TRANSMITTED GWh


1.1 From terminal
1.2 From terminal2
1.3 Total

2. ENERGY UTILIZATION %
NORMAL RATING Pm =
Period Hours PH=

3. ENERGY Availability %
EA

4.ENERGY UNAVAILABILITY % due to


Scheduled Outages
4.11 Deferred
4.1 4.12 Planned
Forced Outages
4.21 Substations
4.2 4.22 DC Transmission Line

5.FORCED OUTAGES due to

Substations
AC Switchyard Equipment
Valve
Control and Protection
DC Switching Equipment
Other
DC Transmission Line
External AC System

6.COMMUTATION FAILURE STARTS


CFS(A)
CFS(B)
RECORDABLE AC FAULTS
7.FORCED OUTAGE SEVERITY
Pole Bipole
Number Of Events Forced Energy Unavail. Number Of Forced Energy Unavail.
Events
7 0.32 3 0.
to terminal2 1
to terminal 2
3

MW 4
hours 8784
U %= 8.54

SEU 0.00
SEUD 0.00
SEUP 0.00
FEU 1.17
FEUSS 0.00
FEUTL 1.17

Number of Events Equivalent Outage Hours


SS 0 0
AC-E 0 0
V 0 0
C-P 0 0
DC-E 0 0
O 0 0
TL 18 102.48
EXT 0 0

0
0
0
Bipole Total
Forced Energy Unavail. Number Of Forced Energy Unavail.
Events
0.64 18 0.00
System system
Year 2019

Table 2FS Replaced by


Outage Code Event or Equipment Failure Description Severity Code Spare (S) or
AC-E AC Switchyard Equipment Total Outages= 0 BP R Manually
V Valve Total Outages= 0 BP R
C-P Control and Protection Total Outages= 0 BP R
DC-E DC Switching Equipment Total Outages= 0 BP R
O Other Total Outages= 0 BP R
AC-E AC Switchyard Equipment Total Outages= 0 P R
V Valve Total Outages= 0 P R
C-P Control and Protection Total Outages= 0 P R
DC-E DC Switching Equipment Total Outages= 0 P R
O Other Total Outages= 0 P R

OUTAGE SUMMARY
Total AOD HRS
Bipole 0 0
Pole 0 0
Forced Unavailability %
Actual Outage
n in
Duration AOD
Capacity
0 hr 100
0 100
0 100
0 100
0 100
0 50
0 50
0 50
0 50
0 50

EQH HRS FEU %


0 0.00
0.00 0.00
0.00 0.00
System system
Year 2019

Table 2SSReplaced by Actual Outage


Outage Code Event or Equipment Failure Description Severity Code Spare (S) or Duration AOD
Manually hr
AC-E AC Switchyard Equipment 0 BP R 0
V Valve 0 BP R 0
C-P Control and Protection 0 BP R 0
DC-E DC Switching Equipment 0 BP R 0
O Other 0 BP R 0
AC-E AC Switchyard Equipment 0 P R 0
V Valve 0 P R 0
C-P Control and Protection 0 P R 0
DC-E DC Switching Equipment 0 P R 0
O Other 0 P R 0

TOTAL EOH PM EOH DEF


TOTAL PLANNED null SEUP 0 0
TOTAL DEFERRED null SEUD 0 0
Equiv
n in Outage
Outage
Capacity Hours
Hours PM
100 0
100 0
100 0
100 0
100 0
50 0
50 0
50 0
50 0
50 0

% UA
0.00
0.00
System system
Year 2019

Table 3
HVDC OVERHEAD LINE PROTECTION OPERATION

Number of Final Restart


Event Time of Pole Voltage &
Date Attempted Successful / DC Protection
No. Day Polarity
Restarts Unsuccessful

1 03-09-2020 20:57 56kv 56 Successful Yes


Table 3
NE PROTECTION OPERATIONS

Actual Outage
Duration if Unsucc Note
Hrs

56 Abv
System system
Year 2019

Table 4
COMMUTATION FAILURE STARTS
System system
Year 2019

Table 5

Number of Number of
Converter Type
Converter Unit Hours Available Semiconductor Semiconductor Devices
6 or 12 Pulse Devices Failed In Operation
System system
Year 2019

Table 6
Capacity Reduction
FORCED OUTAGE due to Outage Code Number of Actual Equiv Outage
Events Outage Hours Hours
AC Filter and Shunt Bank AC-E.F 0 0 0
AC Switchyard Equipment AC-E.SW 0 0 0
AC Control & Protection AC-E.CP 0 0 0
Converter Transformer AC-E.TX 0 0 0
Synchronous Compensator AC-E.SC 0 0 0
AC and Auxiliary Equipment AC-E.AX 0 0 0
Total AC and Auxiliary Equip AC-E 0 0 0
Valve Electrical V.E 0 0 0
Valve Cooling V.VC 0 0 0
Total Valve V 0 0 0
Local HVDC cont & prot C-P.L 0 0 0
Master HVDC cont & prot C-P.M 0 0 0
Telecommunication C-P.T 0 0 0
Total HVDC cont & prot C-P 0 0 0
DC Filters DC-E.F 0 0 0
DC Smoothing Reactor DC-E.SR 0 0 0
DC Switching Equipment DC-E.SW 0 0 0
DC Ground Electrode DC-E.GE 0 0 0
DC Ground Electrode Line DC-E.EL 0 0 0
Other DC Yard & Valve Hall Equip DC-E.O 0 0 0
Total Other Primary DC Equip DC-E 0 0 0
Other O 0 0 0
TOTAL SUBSTATIONS SS 0 0 0
DC Transmission Line TL 8 56 18.48
External AC System EXT 0 0 0

TOTAL 8 56 18.48
Forced Unavailability % 0 0 0.21
Table 6
Pole Bipole Total
Number of Actual Equiv Outage Number of Actual Equiv Outage Number of
Events Outage Hours Hours Events Outage Hours Hours Events
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 0 0 0 0 0
7 56 28 3 56 56 18
0 0 0 0 0 0 0

7 56 28 3 56 56 18
0 0 0.32 0 0 0.64 0
FEUSS% =
FEUTL% =
Total
Equiv Outage
Hours
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
102.48
0

102.48
102.48
0.00
1.17